Danfoss 324166 Installation And Operation Manual

www.danfoss.com DKCD 5/2002
Temperature setting
Set room temperature on the thermostat dial. On the right-hand side of the thermostat is a func- tion switch with 3 possible settings:
Sun
: The room temperature will be as set on the
Clock
: Used only if the zone regulator is en­gaged. The temperature will be as set on the room thermostat, but in accordance with the consumption pattern entered. The consumption pattern in the zone regulator can be overridden by moving the switch to sun or moon.
Moon
: The room temperature will be as set on the thermostat - minus 5°C.
Limitation of the setting range
Behind the button for temperature setting are two lock-pins. These can be placed in the setting knob as shown in fig. 4 if the thermostat setting range is to be narrowed.
Putting into operation
Each room thermostat has a unique ID number preventing conflicts with other thermostats. A single room thermostat is capable of regulating several heating outputs, provided these outputs are assigned to the thermostat.
Assigning thermostats to output(s)
-The installation cable between room thermostat and CFM (fig. 2) must be connected in assigning each thermostat to the respective output(s).
-In the LED array the first available output will flash. The LED in the CFR will also flash. Out­puts already assigned will not be lit (fig. 2). By pressing OK the thermostat will be assigned to that output. If the room thermostat is to be as­signed under another lit output, scroll to the out­put by means of the +/- keys, then press OK.
-When the installation cable is removed, the red LED behind the front panel (fig. 4) will flash for at least 4 minutes. See “Test of room thermostat”
Removal of assigned thermostat
-It is not necessary to have the installation cable in place when removing an assigned ther­mostat. Once a thermostat has been removed, it may be reassigned to another output.
-Removal of room thermostat is done by pressing OK for 5 seconds, then the entire LED array will be lit. Scroll to the specific room thermostat to be removed with the +/- button,and press OK for 5 seconds. The thermostat has now been re­moved.
Test of room thermostat
If a defect in a room thermostat is suspected, the following test may be carried out:
- Set the thermostat to the highest temperature.
- Move the function switch on the side of the room thermostat to a new position.
- If the LED behind the front panel (fig. 4) flashes quickly for 4 minutes, the room thermo­stat is OK.
Battery change
If the battery is getting low, the LED will flash 6 times every 6 seconds. See fig. 4.
Master regulator CFM
This regulator governs the individual heat cir­cuits via wireless communication with the asso­ciated room thermostats. Connection of 8 heat circuits is enabled.
If more heat circuits are required, connect one or max. two slave regulators CFS, each with connection for 8 circuits. This allows max. 24 heat circuits to be governed.
The master/slave is to be fitted immediately above the distributor pipe on the wall or in a dis­tribution cabinet. Easy access to plugs and ter­minals should be ensured. See instruction draw­ing on the opposite page.
If two slave regulators are connected, move the jumper in “slave 2” to position 2. See instruction drawing. The connection cable for the slave regulator is 1 m. Cable lengths of up to 100 m are enabled (available from your electrical items wholesaler)
Alarm
There are 2 options with respect to alarms given by the master regulator:
-Integral acoustic signal can be selected by moving the jumper marked “buzzer” from OFF to ON. See installation drawing.
-External alarm generator can be connected to the output marked


 .
Technical data
Max. ambient temperature 60°C . Enclosure IP40
Zone regulator CFZ
The zone regulator governs a maximum of 6 heat zones. For each heat zone, individual tim­ing programmes can be connected. For reading and operating convenience, it is recommended to place the regulator at eye height.
The connection cable is 5 m. Cable lengths up to 100 m are permitted (available from your electrical items supplier).
Tr oubleshooting
Appearance Problem Reason/cause Solution Comments
CFM controller out­put array blinks specifically from a row and column(s)
Alarm symbol in zone controller, CFZ flashes
Acoustic alarm buzzes (provided jumper is set to “ON”)
Master or slave controller row(s) and entire columns lit on master output array
Constant light in LED array
LED on back of room thermostat does not blink dur­ing test mode
All output LEDs are unresponsive
CFM controller out­put array blinks rap­idly 3 times specifi­cally from a row and column(s)
Lack or ex­cessive heat to floor heat­ing system
Room tem­perature is below 6oC (43oF)
No heat
No heat
Lack or ex­cessive heat to floor heat­ing system
No heat
None
Distance between room and master is too far.
Degradation of signal due to reinforced concrete or foil faced insulation between floors.
External antenna mounted close to metal parts or wires.
Master control is placed in metal enclosure.
Interference from electronic equipment using the same frequency, 433.92Mhz (i.e. baby monitors, portable or wireless headphones)
Low battery Problem in heating system
or signal to thermostat
Blown fuse in master/slave Loose wire connection be-
tween master and slave con­troller
Defective zone actuator Lack of heated fluid to sys-
tem
Faulty battery Bad contacts between bat-
tery and thermostat Defective room thermostat
Improper wiring Master controller is defective
Normal operation during test of room thermostat
Reposition thermostat in room until signal is clear.
Reposition external an­tenna, however if signal is still unclear move external antenna to the same floor as thermostat(s)
Reposition room thermo­stat and run test mode
Mount external antenna if not already installed.
Eliminate interfering elec­tronic equipment
Replace battery and test thermostat
Check heating supply to the system and the circu­lator pump
Check master control, CFM, is properly wired.
First check actuators for proper wiring then re­place fuse in master/slave controller,
1.25A Check wire and connec-
tion between master and slave
Replace zone actuator Check heating supply to
the system and the circu­lator pump
Replace battery/ Adjust connection in ther­mostat to ensure better contact to battery
Replace room thermostat Check wiring of power to
CFM Replace master control-
ler.
If signal is continuosly poor contact Danfoss
Max. load for CFM 6W, max. Load for CFS 3W
Installation and operation Wireless floorheating controller and room thermostat, type CF
www.danfoss.com DKCD 5/2002
CFR CFZ
CFM
CFS
CFS 24 T 1.25A
+ T 0.5A
CFS 230 F 4A
+ T 0.5A
CFM 24 T 1.25A CFM 230 F 4A
1
2
3
4
5
Loading...
+ 1 hidden pages