Danfoss 176F6757, 176F6756, 176F6517 Installation Instructions Manual

Description
The current sensor cylinder busbar kits include all parts required to install the cylinder busbars in D1h–D8h drives. Each cylinder busbar is inserted through the center of a current sensor during installation. For more information, see the current sensor kit installation instructions listed in Tab l e 1.4 .
Kit number Kit description
176F6517 300 A D1 LEM BB kit
176F6757 300 A D2 LEM BB kit
176F6756 500 A D2 LEM BB kit
Table 1.1 Ordering Numbers for Current Sensor Cylinder Busbar Kits
Items Supplied
Item Quantity
Nomex sleeve 3
U, V, W cylinder busbars 1 set of 3
M6x90 screw 3
Cylinder busbar mounting frame 1
M6x16 screw 3
Table 1.2 Items Supplied with D1h/D3h/D5h/D6h Kit (176F6517)
Item Quantity
Nomex sleeve 3
U, V, W cyclinder busbars 1 set of 3
M8x70 screw 3
Table 1.3 Items Supplied with D2h/D4h/D7h/D8h Kit
(176F6756/176F6757)
Safety Information
Only qualied, Danfoss authorized personnel are allowed to install the parts described in these installation instructions. Handling of the drive and its parts must be done in accordance with the corresponding operating guide.
WARNING
ELECTRICAL SHOCK HAZARD
VLT® FC series drives contain dangerous voltages when connected to mains voltage. Improper installation, and installing or servicing with power connected, can cause death, serious injury, or equipment failure.
To avoid death, serious injury, or equipment failure:
Only use
qualied
electricians for the installation.
Disconnect the drive from all power sources before installation or service.
Treat the drive as live whenever the mains voltage is connected.
Follow the guidelines in these instructions and local electrical safety codes.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning LED indicator lights are o. Failure to wait the specied time after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC­link connections to other drives.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The minimum waiting time is 20 minutes.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Installation Instructions
Current Sensor Cylinder Busbar Kit (D1h–D8h) VLT
®
FC Series FC 102, FC 103, FC 202, FC 302
Danfoss A/S © 08/2018 All rights reserved. MI70Z202
Cylinder Busbar
Identication
Kit 176F6517 Kit 176F6757 Kit 176F6756
90/110/132 kW power rating 160 kW power rating 200/250 kW power rating
V-phase busbar: 64 mm x
Ø
16 mm
U/W-phase busbar: 71 mm x
Ø
16 mm
U/V/W-phase busbar:
49 mm x
Ø
19 mm
U/V/W-phase busbar:
49 mm x Ø25 mm
Illustration 1.1 Current Sensor Cylinder Busbars
Busbar kit Current sensor kit Kit description Installation instruction
176F6517 176F6516 300 A D1 retro t kit 300 A Current Sensor Kit for D1h/D3h/D5h/D6h Drives
176F6757 176F3752 300 A D2 retro t kit 300 A/500 A Current Sensor Kit for D2h/D4h/D7h/D8h Drives
176F6756 176F3737 500 A D2 retro t kit 300 A/500 A Current Sensor Kit for D2h/D4h/D7h/D8h Drives
Table 1.4 Comparison of Current Sensor Cylinder Busbar Kits
Installation Instructions
Current Sensor Cylinder Busbar Kit (D1h–D8h) VLT
®
FC Series FC 102, FC 103, FC 202, FC 302
2
Danfoss A/S © 08/2018 All rights reserved. MI70Z202