Danfoss 176F6609 Installation Instructions Manual

Description
The ground bar kit ts the following drives in E1h and E2h enclosures:
VLT® HVAC Drive FC 102
VLT® Refrigeration Drive FC 103
VLT® AQUA Drive FC 202
VLT® AutomationDrive FC 302
The kit includes a pair of ground bars for installation inside E1h/E2h enclosures.
Kit Part Numbers
Use these instructions with the following kits.
Kit number Kit description
176F6609 Ground bar kit for E1h/E2h drives
Tab le 1. 1 Par t Nu mbe rs fo r K it s
Items Supplied
The ground bar kit contains the following items.
Item Quantity
Ground bar 2
Angle bracket 2
M5x18 mm screw 4
M6 hex nut 4
Table 1.2 Items Supplied in Ground Bar Kit
Safety Information
WARNING
ELECTRICAL SHOCK HAZARD
VLT® FC series drives contain dangerous voltages when connected to mains voltage. Improper installation, and installing or servicing with power connected, can cause death, serious injury, or equipment failure.
To avoid death, serious injury, or equipment failure:
Only use
qualied
electricians for the installation.
Disconnect the drive from all power sources before installation or service.
Treat the drive as live whenever the mains voltage is connected.
Follow the guidelines in these instructions and local electrical safety codes.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning LED indicator lights are
o.
Failure to wait 40 minutes after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC­link connections to other drives.
Disconnect or lock PM motor.
Wait 40 minutes for capacitors to discharge fully.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
Installation Instructions
Ground Bar Kit for E1h/E2h Drives VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
Danfoss A/S © 10/2017 All rights reserved. MI35K102
Installation Instructions
Installing the Ground Bar Kit
The ground bar kit includes 2 ground bars, 1 for the mains side and 1 for the motor side of the drive. To install the ground bars, use the following steps. Refer to Illustration 1.1 to Illustration 1.3.
Illustration 1.1 Location of Ground Bar Mounting Holes in Midplate
Installation Instructions
Ground Bar Kit for E1h/E2h Drives VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
2
Danfoss A/S © 10/2017 All rights reserved. MI35K102
1 M6 hex nut 5 Side view of assembled ground bar and bracket
2 Ground bar assembly for mains side 6 Front view of assembled ground bar and bracket
3 Angle bracket 7 Ground bar assembly for motor side
4 M5x18 mm screw 8 End view of assembled ground bar and bracket
Illustration 1.2 Assembly of Ground Bars and Angle Brackets
1. Attach the ground bars to the angle brackets:
1a Place 1 ground bar over the 2 threaded
posts on the angle bracket.
1b Fasten 2 M6 hex nuts (T30) to the bracket
posts, 1 on each post. See Illustration 1.2.
1c Tighten nuts to 3.9 Nm (35 in-lb).
1d Repeat for remaining ground bar and angle
bracket. Position ground bar with the long end oriented in the opposite direction on
Installation Instructions
Ground Bar Kit for E1h/E2h Drives VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
MI35K102 Danfoss A/S © 10/2017 All rights reser ved.
3
the bracket. When correctly assembled, the 2 grounhd bars mirror each other.
2. Remove 4 screws from the mounting holes in the midplate, 2 from each side of the drive. For the location of the mounting holes, see Illustration 1.1.
3. Position the 2 angle brackets with attached ground bars over the mounting holes in the midplate. See Illustration 1.3.
4. Fasten angle brackets to the midplate with 4 M5x18 mm screws (T25) from the kit, 2 in each angle bracket. Tighten to 2.3 Nm (20 in-lb).
1 Mains side ground bar installed 2 Motor side ground bar installed
Illustration 1.3 Ground Bars and Angle Brackets Installed
Installation Instructions
Ground Bar Kit for E1h/E2h Drives VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
4
Danfoss A/S © 10/2017 All rights reserved. MI35K102
Installation Instructions
Ground Bar Kit for E1h/E2h Drives VLT
®
FC Series FC 102, FC 103, FC 202, and FC 302
MI35K102 Danfoss A/S © 10/2017 All rights reser ved.
5
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this materi al are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com
*MI35K102*
MI35K102130R0763 10/2017