Danfoss 176F6489 Installation Instructions Manual

Description
The bus bar kit is designed for the specic VLT® HVAC Drive FC
102, VLT
®
AQUA Drive FC 202, and VLT® AutomationDrive FC
®
Parallel Drive Modules mounted in a Rittal TS8 enclosure. The bus bars in this kit link 2 drive modules in parallel.
Kit Part Number
Part number Kit description
176F6489
Bus bar kit for the VLT
®
Parallel Drive Modules
(12-pulse, 2-drive system)
Table 1.1 Part Number for the VLT® Parallel Drive Modules
Bus Bar Kit
Items Supplied
The kit contains the following parts:
Bus bar assembly
Nut with integrated washer, M5 (10)
Nut with integrated washer, M8 (10)
Nut with integrated washer, M10 (6)
Screw, M5 x 12 mm (40)
Screw with integrated washer, M10 x 30 (6)
Stand-o, M5 x 25 (15)
Ground bus bar, 800 mm (1)
Ground plate (1)
Ground jumper plate (2)
Ground jumper bus bar (2)
Ground clamp (1)
EMI/EMC bracket, left (2)
EMI/EMC bracket, right (2)
EMI/EMC bracket, front (2)
EMI/EMC shield, lower (1)
DC bus assembly
L-brackets (2)
DC-link jumper bus bar (-) (2)
Jumper bus bar (+) (2)
DC bus support plate (1)
DC-link bus bar (2)
AC bus bar assembly
Brake terminal, left (2)
Brake terminal, right (2)
Brake terminal bracket (2)
Solid AC bus bar, (6)
AC bus bar assembly bracket (1)
S-bracket (1)
Flexible AC bus bars (6)
AC support bracket (1)
Side support (2)
Safety
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the unit is o. High voltage can be present even when the warning indicator lights are o. Failure to wait 20 minutes after power has been removed before performing service or repair work, could result in death or serious injury.
Stop the motor.
Disconnect the AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
Wait 20 minutes for the capacitors to discharge fully, before performing any service or repair work.
Measure the voltage level to verify full discharge.
Installation
NOTICE
If both a bus bar kit and a back-channel cooling kit are being installed in the cabinet, install the back-channel cooling kit rst.
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
Danfoss A/S © 04/2016 All rights reserved. MI92O102
NOTICE
APPROVALS AND CERTIFICATIONS
This VLT® Parallel Drive Modules bus bar kit is UL 508C compliant. These installation instructions describe how to install Danfoss-supplied bus bars which, if followed, meet specic agency approvals and certications. Seek agency approvals or
certications
apart from Danfoss if designing
and building other congurations.
Installing DC-link Bus Bars
1. Install 1 L-bracket inside the top of the enclosure on each side. Secure each bracket with 3 M5 nuts and torque to 2.3 N · m (20 in-lb). See Illustration 1.1.
1 L-brackets 2 DC fuse with microswitch
Illustration 1.1 Installation of DC Bus Bar L-brackets above the
DC Fuses
2. Install the 6 stand-os onto the support plate. Torque to 2.3 N · m (20 in-lb). Refer to Illustration 1.2.
3. Install the 2 DC-link bus bars onto the support plate using 3 M5 nuts per bus bar. Torque to 2.3 N · m (20 in-lb).
1 Support plate 3 DC-link bus bars
2 Stand-os 4 M5 nut
Illustration 1.2 Installing DC-link Bus Bars onto Support Plate
4. With the DC-link bus bars facing downward, slide the support plate onto the L-brackets. Secure the support plate with 6 M5 screws and torque to 2.3 N · m (20 in-lb). Refer to Illustration 1.3.
5. Install the DC+ and DC- jumper bus bars between the DC fuses and the DC bus bars. Refer to Illustration 1.4.
1L-brackets
2 DC-link bus bar assembly (support plate and bus bars)
Illustration 1.3 Installation of DC Bus Bars onto L-brackets
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
2
Danfoss A/S © 04/2016 All rights reserved. MI92O102
1 DC-link jumper bus bars (+/- indicated in drawing) 3 Microswitch
2 DC-link bus bar 4 DC fuse
Illustration 1.4 Installation of DC Jumper Bus Bars
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
MI92O102 Danfoss A/S © 04/2016 All rights reserved.
3
Assembling the AC Bus Bar Subassemblies
The AC bus bar assembly consists of the following 3 subassemblies, as shown in Illustration 1.5.
1 AC bus bar assembly bracket 3 AC support bracket with drive module 2 brake terminal assembly
2 Motor bus bar subassembly
Illustration 1.5 Exploded View of the AC Bus Bar Assembly
1. Install the left and right brake terminals onto the brake terminal bracket using 4 M5 nuts. Torque to 2.3 Nm (20 in-lb).
2. Secure the brake terminal assembly to the AC bus bar assembly bracket with 2 M8 nuts. Torque to 9.6 Nm (85 in-lb). Refer to Illustration 1.6.
3. Install the S-bracket to the AC bus bar assembly bracket using 2 M5 nuts. Torque to 2.3 Nm (20 in-lb).
1 AC bus bar assembly support bracket 4 M5 nut
2 Mounting point for lower EMI/EMC shield 5 S-bracket
3 Brake terminal assembly (terminals and bracket) 6 Studs that insert into the side support bracket
Illustration 1.6 Assembling the AC Bus Bar Assembly Bracket
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
4
Danfoss A/S © 04/2016 All rights reserved. MI92O102
4. Assemble the motor bus bar subassembly using 9 stand-os and 9 M5 nuts. Torque to 2.3 Nm (20 in-lb). Refer to Illustration 1.7.
1 Slotted opening for M10 screw 3 M5 nut
2 Stand-os (front and back side of bus bar), indicated by an S in
the drawing
4 Solid motor bus bars
Illustration 1.7 Assembling the Motor Bus Bar Subassembly
5. Install the left and right brake terminals onto the brake terminal bracket using 4 M5 nuts. Torque to 2.3 Nm (20 in-lb).
6. Secure the brake terminal assembly to the AC support bracket with 2 M8 nuts. Torque to 9.6 Nm (85 in-lb). Refer to Illustration 1.8.
1 AC support bracket 2 Brake terminal assembly (terminals and bracket)
Illustration 1.8 Assembling the AC Support Bracket with the Drive Module 2 Brake Terminal Assembly
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
MI92O102 Danfoss A/S © 04/2016 All rights reserved.
5
Installing the AC Bus Bar Assembly
1. Install 1 side support bracket inside the enclosure on each side. Secure each side support bracket with 4 M5 screws and torque to 2.3 Nm (20 in-lb). See Illustration 1.9.
2. Install ground plate assembly. See Illustration 1.9.
2a Attach the ground support bracket to the
inside of the enclosure. Secure with 4 M5 screws and torque to 2.3 Nm (20 in-lb).
2b Install the ground plate onto the 5 studs on
the ground support bar.
2c Secure the bottom of the ground plate to
the enclosure using 8 M5 screws. Torque to
2.3 Nm (20 in-lb).
2d Install the ground bus bar onto the ground
plate. Secure with 5 M8 nuts and torque to to 9.6 Nm (85 in-lb).
2e Install the 1 ground jumper plate per drive
module. Secure the bottom of the ground jumper plate to the top of the ground plate using 1 M5 nut. Torque to 2.3 Nm (20 in-lb).
2f Secure the top of the ground jumper plate
to the bottom of the drive module reusing the 2 existing M10 nuts. Torque to 19 Nm (169 in-lb).
3. Install the ground jumper bus bars. Perform this step for each drive module.
3a Secure the bottom of the ground jumper
bus bar to the ground bus bar using 1 M5 nut. Torque to 2.3 Nm (20 in-lb). See Illustration 1.9 for the mounting attachment points on the ground bus bar.
3b Secure the other end of the ground jumper
bus bar to the drive module ground terminal using 1 M5 nut. Torque to 2.3 Nm (20 in-lb).
4. Secure the motor bus bar subassembly to the AC bus bar assembly bracket using 3 M5 nuts. Torque to
2.3 Nm (20 in-lb). Refer to Illustration 1.5.
5. Install the AC bus bar bracket/motor bus bar subassembly to the side support brackets. Secure each side with 2 M5 nuts and torque to 2.3 Nm (20 in-lb).
6. Shape the
exible
bus bars to
t.
7. Install the motor
exible
bus bars for each drive
module. Refer to Illustration 1.10.
7a Insert 1 M10 screw into each of the slotted
holes in the motor bus bar subassembly, with the screw shaft facing the front.
7b Install 3
exible
motor bus bars per drive module, securing 1 end to the screw and the other end to the drive module terminal. Secure with 2 M10 nuts per bus bar. Torque to 19 Nm (169 in-lb).
7c Verify that the proper U, V, W connections
are made. Refer to the Terminal Dimensions
section in the VLT
®
Parallel Drive Modules
Installation Guide.
8. Assemble the front EMI/EMC bracket assembly.
8a Attach the left EMI/EMC bracket to the front
EMI/EMC bracket using 3 M5 screws. Torque to 2.3 Nm (20 in-lb).
8b Attach the right EMI/EMC bracket to the
front EMI/EMC bracket using 3 M5 screws. Torque to 2.3 Nm (20 in-lb).
9. Install the front EMI/EMC bracket assembly over each set of
exible
motor bus bars. Secure with 4 M5 nuts and torque to 2.3 Nm (20 in-lb). Refer to Illustration 1.11.
10. Install the lower EMI/EMC shield to the AC bus bar subassembly bracket. Secure with 2 M5 nuts. Torque to 2.3 Nm (20 in-lb). See Illustration 1.12.
11. Run the mains cables up to the drive module mains terminals. Secure with the M10 nut that is already provided on the terminal, and torque to 19 Nm (169 in-lb).
12. Verify that the proper R, S, T connections are made.
Refer to the Terminal Dimensions section in the VLT
®
Parallel Drive Modules Installation Guide.
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
6
Danfoss A/S © 04/2016 All rights reserved. MI92O102
1 Screw at the bottom of the drive module that connects
to the top of the ground jumper plate
6 Ground bus bar
2 M10 nut 7 Ground jumper bus bar
3 Ground jumper plate 8 Side support bracket
4 M5 nut 9 Ground support bracket
5Ground plate ––
Illustration 1.9 Installation of Side Support Brackets and Ground Bus Bar Assembly
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
MI92O102 Danfoss A/S © 04/2016 All rights reserved.
7
1 Motor bus bar screws for drive module 1 4 M10 nuts
2 Motor bus bar subassembly 5 Flexible motor bus bars
3 Motor bus bar screws for drive module 2
Illustration 1.10 Installation of Flexible Motor Bus Bars
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
8
Danfoss A/S © 04/2016 All rights reserved. MI92O102
1 Left EMI/EMC bracket (shown on drive module 1) 4 Ground plate
2 Front EMI/EMC bracket (shown on drive module 1) 5 Right EMI/EMC bracket (shown on drive module 1)
3 Flexible motor bus bars
Illustration 1.11 Installation of Front EMI/EMC Bracket Assembly
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
MI92O102 Danfoss A/S © 04/2016 All rights reserved.
9
1 Mains cable for drive module 1 8 Front EMI/EMC bracket assembly for drive module 2
2 Flexible bus bars for drive module 1 motor terminals 9 Brake terminal assembly for drive module 2
3 Front EMI/EMC bracket assembly for drive module 1 10 Ground bar support bracket
4 AC support bracket 11 Ground bar
5 Brake terminal assembly for drive module 1 12 Ground plate
6 Side support bracket 13 Lower EMI/EMC shield
7 Drive module 2
Illustration 1.12 Installation of Mains Cables
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
10
Danfoss A/S © 04/2016 All rights reserved. MI92O102
Installation Instructions
Bus Bar Kit for 12-pulse, 2-drive System VLT
®
Series FC 102, FC 202, and FC 302
MI92O102 Danfoss A/S © 04/2016 All rights reserved.
11
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com
*MI92O102*
MI92O102130R0687 04/2016
Loading...