Danfoss 176F3737, 176F3752 Installation Instructions Manual

1.1 Description
The 300 A and 500 A current sensor kits are designed for D2h/D4h/D7h/D8hdrives in the power ranges shown in
Tab l e 1.1 and Tabl e 1.2 . To identify the power rating, see chapter 1.1.1 Identifying the Power Rating.
Product group and series Voltage rating
(V)
(hp)]
VLT
®
HVAC Drive FC 102,
VLT
®
Refrigeration Drive FC 103,
VLT
®
AQUA Drive FC 202
(T4) 380–480 110–200
(150–300)
(T7) 525–690 75–315
(75–350)
VLT
®
AutomationDrive FC 302
(T5) 380–500 90–160
(125–200)
(T7) 525–690 55–250
(75–350)
Table 1.1 Applicable Power Ranges for 300 A Current Sensor Kit
Product group and series Voltage rating
[V]
(hp)]
VLT
®
HVAC Drive FC 102,
VLT
®
Refrigeration Drive FC 103,
VLT
®
AQUA Drive FC 202
(T4) 380–480 200–315
(300–450)
(T7) 525–690 200–400
(250–400)
VLT
®
AutomationDrive FC 302
(T5) 380–500 200–250
(300–350)
(T7) 525–690 160–315
(200–350)
Table 1.2 Applicable Power Ranges for 500 A Current Sensor Kit
1.1.1 Identifying the Power Rating
To
nd
the drive power rating, use the following steps:
1. Obtain the following information from the nameplate, which is on the drive. Refer to Illustration 1.1.
Product group and drive series (characters 1–6)
Power rating (characters 7–10)
Voltage rating (phases and mains) (characters 11–12)
2. Determine if the power rating is in Ta ble 1. 1 and Tab l e 1.2 .
1 Product group and drive series
2Power rating
3 Voltage rating (phases and mains)
Illustration 1.1 Example Nameplate
1.1.2 Kit Ordering Numbers
Kit number Kit description
176F3752 300 A Current Sensor Conversion Kit
D2h/D4h/D7h/D8h
176F3737 500 A Current Sensor Conversion Kit
D2h/D4h/D7h/D8h
Table 1.3 Kit Numbers for 300 A and 500 A Current Sensor Kits
Installation Instructions
300 A/500 A Current Sensor Kit for D2h/D4h/D7h/D8h Drives
VLT
®
FC Series FC 102, FC 103, FC 202, FC 302
Danfoss A/S © 07/2018 All rights reser ved. MI70V202
1.1.3 Items Supplied
Tabl e 1.4 provides a list of items included in the 300 A and 500 A current sensor kits for D2h/D4h/D7h/D8h drives. Refer also to Illustration 1.4.
Description Quantity
R/S/T terminal label 1
M10x30 machine screw with captive washer 6
M10 nut 6
Mains input terminal block 1
M5x12 machine screw 12
U/V/W terminal label 1
Motor terminal block 1
Cable retaining clip 6
M10 nut with captive washer 4
Cable clamp adapter 2
Power terminal mounting plate (IP21/IP54) 1
Power terminal mounting plate (IP20/Chassis) 1
Mixing fan 1
Mixing fan housing 1
EMC shield 1
Plastic mounting button 3
Motor busbar (U) 1
Motor busbar (V) 1
Motor busbar (W) 1
Busbar insulator sleeve 1
M5x16 torx screw 3
M8x70 screw 3
Cylinder busbar 3
Nomex tube 3
300 A or 500 A current sensor 3
Wire harness (current sensor cables) 1
M4x10 thread-forming screw 6
M5 nut 2
Wire harness (current sensor cables) 1
Multiple wire guide, not shown 4
Wire routing clip, not shown 1
M5x11 thread-cutting screw, not shown 6
IGBT busbar (300 A kit only) 3
Table 1.4 Items Supplied in 300/500 A Current Sensor Kit
1.2 Safety Information
Only qualied, Danfoss-authorized personnel are allowed to install the parts described in these installation instructions. Handling of the drive and its parts must be done in accordance with the corresponding operating guide.
WARNING
ELECTRICAL SHOCK HAZARD
VLT® FC series drives contain dangerous voltages when connected to mains voltage. Improper installation, and installing or servicing with power connected, can cause death, serious injury, or equipment failure.
To avoid death, serious injury, or equipment failure:
Only use
qualied
electricians for the installation.
Disconnect the drive from all power sources before installation or service.
Treat the drive as live whenever the mains voltage is connected.
Follow the guidelines in these instructions and local electrical safety codes.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning LED indicator lights are
o.
Failure to wait the
specied
time after power has been removed before performing service or repair work can result in death or serious injury.
Stop the motor.
Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC­link connections to other drives.
Disconnect or lock PM motor.
Wait for the capacitors to discharge fully. The minimum waiting time is 20 minutes.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged.
NOTICE
ELECTROSTATIC DISCHARGE
Follow proper ESD precautions to prevent damage to sensitive components.
Installation Instructions
300 A/500 A Current Sensor Kit for D2h/D4h/D7h/D8h Drives VLT
®
FC Series FC 102, FC 103, FC 202, FC 302
2
Danfoss A/S © 07/2018 All rights reser ved. MI70V202
1.3 Disassembly Guidelines
NOTICE
To make the disassembly/reassembly process easier, use these general guidelines:
1. Follow the disassembly instructions for each component.
2. Place the component together with the removed fasteners.
3. Replace old component with the new component provided in the kit.
4. If any fasteners are stripped or lost, replace with similar fastener from the kit.
5. Follow the assembly instructions to replace and secure each component.
1.3.1 General Torque Tightening Values
Use a torque wrench to ensure that correct torque is applied. Incorrect torque can cause electrical connection problems. For fastening hardware described in this instruction, use the values listed in Tab le 1.5 to Tabl e 1.7 except where noted in the procedures.
Shaft
size
Tor x /h ex
drives size
Class A
Nm (in-lb)
Class B
Nm (in-lb)
M4 T20/7 mm 1.2 (10) 0.8 (7)
M5 T25/8 mm 2.3 (20) 1.2 (10)
M6 T30/10 mm 3.9 (35) 2.3 (20)
M8 T40/13 mm 9.6 (85) 3.9 (35)
M10 T50/17 mm 19.1 (169) 9.6 (85)
M12 –/18 mm or
19 mm
37.9 (335)
Table 1.5 Torque Values Standard Thread
Shaft
size
Tor x dri ve s
size
Class A
Nm (in-lb)
Class B
Nm (in-lb)
M4.8 T25 5.7 (50) 3.1 (27)
M5 T25 1.7 (15) 1.7 (15)
Table 1.6 Torque Values for Thread Cutting into Metal
Shaft
size
Tor x d riv es
size
Class A
Nm (in-lb)
Class B
Nm (in-lb)
M4 T20 2.8 (24) 2.8 (24)
M5 T25 5.1 (45) 4.0 (35)
Table 1.7 Torque Values for Thread Forming into Plastic
Class A: Clamping metal
Class B: Clamping PCA or plastic
1.3.2 Removing AC Input Busbars
To remove the AC input busbars, use the following steps. The AC input busbars can look
dierent
when the drive includes extra input options, such as RFI lter or mains fuses. Illustration 1.2 shows the AC input busbars congured to include mains fuses.
1. Remove the air bae by removing 4 screws (T25) and 2 nuts (13 mm).
2. Disconnect the customer input power wiring.
3. The next step
diers
based on the input options present in the drive. Select the appropriate procedure for the drive:
No options
Mains fuses only
RFI lter only
Mains fuses and RFI
lter
1 Top nut (13 mm) 6 Power terminal mounting plate
2 AC input busbar 7 Brake busbar (optional)
3 Bottom nut (13 mm) 8 U motor busbar
4 Fuse spacer 9 Brake terminal (optional)
5 Mains input terminal 10 Motor terminal block
Illustration 1.2 AC Input Busbars with Mains Fuse Conguration
(Shown with Fuses Removed)
Installation Instructions
300 A/500 A Current Sensor Kit for D2h/D4h/D7h/D8h Drives VLT
®
FC Series FC 102, FC 103, FC 202, FC 302
MI70V202 Danfoss A/S © 07/2018 All rights reser ved.
3