Installation Instructions
LOP Connection and Set-up
®
VLT
Items Supplied
•
•
•
DriveMotor FCP/FCM 106
Local operating panel (LOP), 175N0128 IP 65, see
Illustration 1.1.
Fixture for LOP, 175N2717 (included in 175N0128),
see Illustration 1.2.
LOP cable.
Illustration 1.1 Local Operation Panel (LOP) 175N0128 IP 65
Illustration 1.2 Fixture for LOP 175N2717 (included in 175N0128)
Danfoss A/S © 09/2015 All rights reserved. MI03L202

Installation Instructions
LOP Connection and Set-up
®
DriveMotor FCP/FCM 106
VLT
Safety Instructions
Refer to VLT® DriveMotor FCP 106 and FCM 106 Operating
Instructions for detailed information about safety precautions
for installation.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. High voltage can be present even when the
warning LED indicator lights are
specied time after power has been removed before
performing service or repair work can result in death or
serious injury.
1. Stop the motor.
2. Disconnect AC mains, permanent magnet type
motors, and remote DC-link supplies, including
battery back-ups, UPS, and DC-link connections to
other frequency converters.
3. Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration
of waiting time is
specied
Failure to wait the
o.
in Ta b l e 1 . 1 .
Connection to FCP 106 or FCM 106
1. Connect the LOP as shown in Ta b le 1 . 2 and
Illustration 1.3.
2. After completing connections, cut o or isolate
excess wire.
3. Connect terminal 27 V to +24 V or set
parameter 5-12 Terminal 27 Digital Input to [0] No
operation.
Terminal Dual-speed
operation
18 Purple Gray
19 –
27 Brown
29 Green
12 Red
50 Yellow
55 Blue
Table 1.2 Electrical Connections
Dual-mode
operation
Dual-direction
operation
Volt age
[V]
3x400 0.55–7.5 4
Table 1.1 Discharge Time
1) Power ratings relate to NO, see VLT
Operating Instructions.
Power Range
1)
[kW]
®
DriveMotor FCP 106 and FCM 106
Minimum waiting
time
(min)
Illustration 1.3 LOP Connections to FCP 106 or FCM 106
2
Danfoss A/S © 09/2015 All rights reserved. MI03L202

Installation Instructions
LOP Connection and Se t-up
®
DriveMotor FCP/FCM 106
VLT
Set-up
1. Perform set-up according to Table 1 . 3 .
2. Use the [+]/[-] keys to set reference.
3. At power-up, the unit is always in stop mode. The set reference is stored during power down. To set up permanent start
mode, connect terminal 12 to terminal 19 and do not connect purple/gray wire to terminal 12. Permanent start mode
disables the stop function on the LOP.
Function Settings Key I (Start) Key II (Start)
Key (Stop)
Default - Dual speed operation
(connect purple or orange wire)
Function 2 - Dual-mode
operation
(connect purple or orange wire)
Function 3 - Dual direction
operation (connect gray wire)
No changes to factory setting. Run on set
reference (+/-)
Select the modes of operation in set-ups 1 and 2.
Set parameter 0-10 Active Set-up to [9] Multi Set-up.
Run with
set-up 1
Set parameter 5-13 Terminal 29 Digital Input to [23] Set-up
select bit 0.
Set parameter 4-10 Motor Speed Direction to [2] Both
Run forward Run reverse
directions.
Set parameter 5-13 Terminal 29 Digital Input to [11] Start
reversing .
Run on 5 Hz
jog speed
Run with
set-up 2
1)
Stop (and reset
- if trip)
Stop (and reset
- if trip)
Stop (and reset
- if trip)
2)
2)
2)
Table 1.3 LOP Operation Mode
1) Set jog speed in parameter 3-11 Jog Speed [Hz]
2) When reset is required, set parameter 5-11 Terminal 19 Digital Input to [1] Reset.
MI03L202 Danfoss A/S © 09/2015 All rights reserved.
3

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on
order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss
and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
MI03L202130R0393 09/2015
*MI03L202*