Danaher Controls HG1 Data Sheet

EAGLE SIGNAL brand
Electric Timers
HG1 FLEXOPULSE
®
Repeat Cycle Timer
Repeat cycle timer features separate dial scales for ON and OFF time
The HG1 is an ON-OFF repeat cycle timer engineered with the same features as the rest of the plug-in CYCL-FLEX
6
Repeat cycle, two circuit timer housed in CYCL-FLEX
Separate dial scale for ON time and OFF time
E L
T
Individually adjustable ON and OFF time intervals via concentric
E
I
C T R
I
C
knobs on front of unit
M
Combination of ON and OFF time equals total time cycle of unit
E
R
S
®
family.
OPERATION
A cycle progress pointer oscillates between the ON and OFF time setpoints. As this pointer crosses the zero point on the dial, two internal 10 amp SPDT output switches transfer. The transfer point of the output switches is adjustable to allow a make before break (overlap) or a break before make (dwell) switch action. The overlap or dwell time interval is limited to 1.5% of the total (ON plus OFF) time cycle.
A synchronous unidirectional motor drives the unit through precision gearing. Instant reversing of the progress pointer is accomplished by positive mechanical action.
SPECIFICATIONS
Time Ranges:
Sym.
00 01 02 03 04 05 06 07 08 09 10
Dial
Range
30 Sec. 60 Sec.
150 Sec.
5 Min. 10 Min. 30 Min. 60 Min.
150 Min.
5 Hr. 10 Hr. 30 Hr.
Minimum
Setting
.5 Sec.
1 Sec, 2 Sec.
5 Sec. 10 Sec. 30 Sec.
1 Min.
2 Min.
5 Min. 10 Min. 30 Min.
Max. Dwell or Overlap
.5 Sec.
1 Sec. 2 Sec.
5 Sec. 10 Sec. 30 Sec.
1 Min.
2 Min.
5 Min. 10 Min. 30 Min.
®
plug-in case
®
RECOGNIZED
Voltage/Frequency: 120V, 60 Hz
240V, 60 Hz
Burden: 2.5 VA @ 120V AC Output Rating: 10 amp 120 VAC, 5 amp 240 VAC Resistive
Mechanical Life: 10,000,000 operations Switch Life: 250,000 under 10 amp, 120 VAC resistive load 1,000,000 under 5 amp, 120 VAC resistive load
Repeat Accuracy: 1/2 of 1% of dial Temperature Range: -20˚ to 140˚F Agency Approvals: UL Recognition E61735
CSA Certification LR26861
CERTIFIED
OPERATION
To Set
Move the black pointer to the desired OFF setting and the orange pointer to the desired ON setting (as shown in Figure 1). The sum of these ON and OFF intervals cannot exceed the total time of one scale. Switch contacts are tripped open or closed each time the indicator pointer passes 0. When the indicator pointer is in the OFF scale to the left of 0 contacts 4-3 and contacts 6-8 are closed and 4-5 and 6-7 are open. When the indicator pointer is in the ON scale to the right side of 0 contacts 4-5 and 6-7 are closed and 4-3 and 6-8 are open. The indicator pointer must travel to the preset limit and back to 0 to complete the total ON or OFF interval. The two switches can operate together or be set to allow a break before make (dwell) interval or make before break (overlap) between ON-OFF switching. Refer to the standard time range chart under specifications for the maximum dwell or overlap interval for each time range. Figure 2 illustrates the path of the indicator pointer and the switch action each time the zero point is passed. Figure 3 illustrates the terminal location on the rear of the unit case.
®
WIRING
BLACK
POINTER
MOUNTING
DRILL AND TAP FOUR HOLES FOR 8-32 SCREWS (INCLUDED W/UNIT)
1.406
(35.71)
1.406
(35.71)
15
20
10
1.406
(35.71)
5
60
55
50
45
40
25
+
3.187 .062 +
(80.95 1.57)
DIA. CUTOUT
N
O
35
30
Figure 1
1.406
(35.71)
O
30
35
F
F
60
5
25
55
10
50
15
20
45
40
MTG. HOLE USED FOR GROUNDING CASE
INDICATOR
POINTER
ORANGE POINTER
OFF
SETTING
3.812
(96.82)
ON
SETTING
6
7
8
9
5
4
3
7
6
8
Figure 2
5
4
3 7
6
8
10
TERMINAL ARRANGEMENT
Figure 3
5
M
11
12
CONTACTS SHOWN IN
"ON" POSITION
4
3
2
1
6
T O
4.250
(107.95)
3.062
(77.77)
4.125
(104.78)
5.750
(146.05)
1.625
(41.27)
E
T
L
T
E
A
I
C
L
M
T
E
I
R
R
Z
I
S
I
C
N G
ENCLOSURES
Model No. NEMA Class Description HN308 1 Surface Mtg. with terminal block
HN364 1 Surface Mtg. without terminal block HN370 1A Dual unit cabinet less unit cases and
ACCESSORIES
Model No. Description
H-5331 Mounting Brackets 2 req'd per timer HP50-31 One Hole Mounting Ring HP50-133 Surface Mounting Adapter to use in place of brackets
toggle switch, with 9 terminal block
ORDERING INFORMATION
Consult Customer Service for availability of other time ranges, voltages, and frequencies.
HG1 01 A6 05
TIME RANGE
See Specifications for
Time Range Catalog Symbol
VOLTAGE & FREQUENCY
Sym. Description
A5 A6 B5 B6
120V, 50 Hz 120V, 60 Hz 240V, 50 Hz 240V, 60 Hz
FEATURES
Sym.
Revised for Mounting in Explosion Proof
05
Description
Housing Enclosed in HN388 Explosion Proof Housing
92
DANAHER INDUSTRIAL CONTROLS 6.17