Dairyland SSD Series Installation Instructions Manual

Page 1
ALWAYS RUGGED. ALWAYS RELIABLE.
Blocking Threshold
Terminal Arrangement
Solid-State Decoupler (SSD)
Installation Instructions
READ ENTIRE DOCUMENT BEFORE INSTALLING
INTRODUCTION
The Solid-State Decoupler (SSD) is a solid-state DC isolation/ AC grounding (i.e., coupling) device design ed for use in conjunction with cathodically protected equipment located
in Class I, Division 2 hazardous (classied) locations or
ordinary (non- hazardous) locations. The SSD is suitable for: (1) decoupling ground mats, (2) AC voltage mitigation, (3) over­voltage protection of insulated joints and similar structures and equipment, (4) DC isolation and AC grounding of cathodically protected structures and electrical equipment in cathodically protected structures.
The SSD can be used in a variety of different applications,
each of which requires specic installation guidelines.
These installation instructions cover the following common applications and arrangements.
• Over-voltage protection for insulated joints
• Decoupling gradient control mats
• Decoupling cathodically protected structures containing electrical equipment from grounding systems
• AC mitigation
Some applications listed may not apply in some countries due to different codes and practices. If your application is not covered by these installation instruc tions, contact Dairyland.
Technical information for applications is available on the
Dairyland website.
Model Number Chart
Choose: 2/2 (Standard)
3/1 (Optional)
AC Fault Current
Note: For EAC products see separate EAC installation manual available at www.dairyland.com
Choose: 1.2kA
2kA
3.7kA 5kA
Certications
The SSD has been tested by Nationally Recognized Testing Laboratories (NRTLs) for compliance to independent standards in its operation, ratings,
and construction. Visit our website for Complete Certications and Listings.
Safety Grounding
UL (United States) and C-UL (Canada) listing for: NFPA 70 (US National Electric Code - NEC), Article 250.2 and 250.4 (A) (5), and CSA C22.1-12, Section 10-500 and 10-806. Over-voltage protection from lightning per ANSI C62.11.
Blocking Cathodic Protection Current
NFPA 70, Article 250.6(E)
Hazardous Location Use
The SSD has been certied for use in Class I, Division 2, Groups A, B, C,
D hazardous locations to:
• NFPA 70 (U.S. National Electrical Code) sections 500-505
• ANSI/ISA 12.12.01-2011
• CSA C22.2 No.213-M1987 (R2008)
The SSD has been certied to ATEX Directive 94/9/EC and IECEx
requirements for use in Zone 2, Group IIC hazardous locations by UL/ DEMKO to: EN 60079-0:2012, EN 60079-15:2010, IEC 60079-0: 6th Ed, IEC 60079-15: 4th Ed
Add “-R” for standard terminal arrangement
Remove “-R” for alternate terminal arrangement*
Certification System
Add “-EAC” for EAC version for Zone Class 2 Group IIC
Lightning Surge Current
Choose 100 for 2kA, 3.7kA, 5kA models
Leave blank for standard certifications
Choose 75 for 1.2kA models
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Document ID: 4557 SSD Installation Instructions Published Date: 2019.08.20
Page 2
INSTALLATION INSTRUCTIONS
These general instructions apply to all applications.
WARNING:
During installation, the voltage on the structure may rise to an unsafe level (i.e., due to induced AC, AC fault or
lightning on the structure). Sparking and current ow may
occur when connecting or disconnecting decouplers or over-voltage protectors. Assure that this does not occur in hazardous locations where gases or vapors may be present. All necessary safety precautions must be taken by the user to avoid unsafe worker conditions, including arcing, in accordance with applicable industry and/or company-required practices. Dairyland provides suggested procedures for installing and operating this equipment (See the section on Worker Safety). But the user must be responsible for and approve the procedures to be used by its workers when installing the equipment because Dairyland cannot be familiar with each user’s safety guidelines.
CAUTION:
Note: Explosion Hazard - Substitution of any component
may impair suitability for Class I, Division 2.
Worker Safety
For worker safety during installation, it is recommended that the user obtain certain equipment; namely a pair of electrically
insulated gloves, a shorting cable approximately 3 ft (0.91 m)
long with insulated clamps on each end, and a multi-meter to measure AC voltage. (Of these items, Dairyland offers a suitable 3 ft long 1/0AWG shorting cable with insulated clamps, Model# BCL-1/0 for decouplers rated 10kA or higher or Model# BCL-2 for decouplers rated less than 10kA.) The following installation procedure assumes that these items are available. It is suggested that a grounding jumper be used as a safety precaution in the event the lead to the structure rises to an unsafe potential when it is disconnected during the installation process or if an electrical disturbance occurs while the decoupler is being installed. Be sure to remove the grounding jumper after the decoupler is completely installed. If the structure voltage is not at a safe touch potential (i.e.,>15VAC to ground per NACE SP0177), then insulating gloves should be used.
joint applications the SSD can, and should, be installed with less than 8” (200 mm) of conductor. Conductors can develop
1-3 kV/ft. (approx. 3-10 kV/meter) of length due to lightning;
hence, for this reason, leads should be kept as short as possible in lightning applications. Conductor length is not critical for limiting voltage due to 50 Hz or 60 Hz current.
Mounting Accessories
Numerous mounting accessories are available from Dairyland to aid in the proper installation of the PCR. Full details and complete installation instructions are available on the Dairyland website here: Dairyland Accessories.
Specic Installation Guidance
The Dairyland website contains detailed information on
the installation methods specic to a given application.
For wiring diagrams and/or application guidance, see
Dairyland Applications.
Environmental Exposure
The SSD enclosure is rated IP68 and is suitable for indoor or outdoor use, in submersible and non-submersible applications. SSDs may be submersed in non-freezing conditions up to 6.5 ft. (2 m) depth for occasional prolonged periods, though not continuously.
The unit must be installed in environments with ambient temperatures of -49ºF to +149ºF (-45ºC to +65ºC).
Polarity
If the SSD purchased has asymmetrical blocking characteristics and it is being connected between a cathodically protected structure and ground, connect the negative terminal of the SSD to the cathodically protected structure and the positive terminal to ground. If being connected between two different cathodically protected systems, attach the negative terminal to the more negative structure and the positive terminal to the less negative structure. A label on the SSD housing shows the polarity of each terminal.
Enclosure
The standard enclosure is rated IP68 to 2 m depth (comparable to NEMA 6P). This enclosure is suitable for submersible applications.
Ambient Operating Temperature
-45ºC to +65ºC.
Mounting
Mount the SSD so that the total length of conductor to the connection points will be as short as possible if the SSD is going to be used to provide over-voltage protection from lightning.
All conductors have inductance which will cause a signicant
Field Testing
Before installation, the following measurements are suggested
to conrm that the steady-state conditions imposed on the
SSD will be within its ratings.
voltage per unit of conductor length when subject to lightning surge current. To minimize the voltage developed between the connection points, install the SSD as close as practical to the required connection points and cut the conductor to the shortest possible length during installation. For most insulated
1. Measure the open-circuit DC voltage between the SSD connection points with a multimeter. The open-circuit DC voltage measured should be within the DC blocking voltage rating of the model selected (i.e., normally -3.0 V/+1.0 V or +/-2.0 V, unless a custom version has been ordered).
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Document ID: 4557 SSD Installation Instructions Published Date: 2019.08.20
Page 3
2. Measure the steady-state short-circuit AC-RMS current between the SSD connection points with a clamp-on ammeter. The short-circuit AC-RMS steady-state current measured should be less than the steady-state AC current rating of the SSD model ordered.
3. After installation, the DC voltage across the SSD terminals
can be measured to conrm that the expected value of cathodic protection voltage exists, assuming the cathodic
protection system is ON. (The voltage measured with a voltmeter will be less than the actual cathodic protection voltage because it is not being measured with respect to a reference cell.)
4. After installation, the steady-state AC current through the
SSD conductors can again be measured. The current measured should be comparable to the value measured prior to installation since the AC impedance of the SSD is negligible (i.e., about 10 milliohms at 60 Hz).
5. To verify correct device operation while in service, measure
the pipe to soil voltage using a reference cell. An acceptable CP reading will indirectly indicate correct operation with DC isolation, as device conduction would bond the CP system to ground (or to the other connected structure) and affect the CP reading. While an indirect test, it has proven to be a good indicator of operation. An unacceptable reading may be due to other factors besides the Dairyland device, and if needed perform the following additional tests.
GENERAL COMMENTS
The SSD does not require routine maintenance, but if the cathodic protection voltage level near the SSD is below the
normal or expected value, it is suggested that the unit be eld
tested following procedures available from Dairyland.
If a problem is suspected, contact Dairyland for trouble­shooting assistance. If repairs are necessary the unit is to be returned to Dairyland for diagnosis and repair after requesting a Return Material Authorization (RMA).
The SSD is designed to fail as a short-circuit to assure safety
grounding at all times if the unit fails due to excessive AC fault
current or lightning current beyond rating.
ATEX AND IECEx COMMENTS
• The device shall be placed into service in accordance with the ratings and limitations stated in the installation and operating instructions.
• No ongoing maintenance is required, as the device is designed to be maintenance-free, and is of solid-state construction with no moving, wearing, or serviceable parts.
• During installation the device should be handled and mounted in a location so that direct impact is minimized.
6. The denitive test is one performed with the device out of
circuit. If the device is in service, disconnect the CP structure attachment conductor (typically at the negative terminal) so
that the product is isolated, but rst addressing any safety
issues such as adding a current-rated bonding jumper between the two connection points, wearing insulating gloves, etc. Note that if the Dairyland device is performing mitigation of induced AC voltage, disconnecting the device will leave the structure as an open circuit, and the induced voltage on the pipeline may rise to high levels. Therefore, take appropriate safety measures before proceeding.
Next, momentarily short the device terminals to remove
any residual charge that may be on the internal capacitor. Connect a multi-meter, set to the lowest Ohms scale, across the terminals. If the product is functional, the resistance will start at zero ohms and then very slowly increase as the capacitor in the decoupler begins to charge from the multi-meter. The test may be discontinued at this point, as charging the capacitor can take up to 10 minutes, and it is
only necessary to observe this general response briey. If the product is failed, the reading will remain xed and at a
very low resistance value, typically a fraction of one Ohm.
If any measurements do not produce the expected results,
contact Dairyland.
• Regular testing of the device is not required. Users who desire to verify the operating condition of the device should refer to the section entitled “Field Testing.” Observe all safety precautions described, in addition to industry or company safety practices.
• WARNING: Potential electrostatic charging hazard – Plastic enclosures are to be cleaned or wiped only with a damp cloth.
• Products marked CE, Ex II 3 G are Equipment Group II,
Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and
construction of such equipment given in Annex II to the
Directive 94/9/EC.
• This equipment is intended for use in area in which explosive
atmospheres caused by gasses, vapors, mists, air or dust
mixtures are unlikely to occur, or are likely to occur only
infrequently and for short periods. Such locations correspond
to Zone 2 classication according to ATEX Directive 94/9/EC.
• This equipment complies with standards EN 60079-0:2012
and EN 60079-15:2010 per certicate number DEMKO 05 ATEX 0431689X and IEC 60079-0 Ed. 6 and IEC 60079­15 Ed. 4, per certicate number IECEx UL 14.0021X. The
Quality Assurance Report is based on ISO/IEC 80079-34: Edition 1 2011-04.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Document ID: 4557 SSD Installation Instructions Published Date: 2019.08.20
Page 4
1.00
25.4
3.97
100.8
.17
.33
8.3
.59
14.9
4.4
8.72
221.4
5/16"
HARDWARE
Negative Terminal
10.00 254
12.00
304.8
.5
13
NOTE: Applies to all SSD models with standard terminal arrangement (-R model numbers)
2.31
58.8
1.00
25.4
Positive Terminal
2.00
50.8
ANSI Y14.5M 1994 APPLIES
UNLESS NOTED UNITS: INCHES 3-PLACE: 2-PLACE: 1-PLACE / FRAC: ANGULAR:
.005
.015
63
.03
1
DAIRYLAND ELECTRICAL INDUSTRIES, INC.
P.O. BOX 187 STOUGHTON, WI 53589 608-877-9900 DAIRYLAND.COM
DESCRIPTION
SSD Outline Drawing - All Models with Standard Terminals
DOCUMENT #
100074
SCALE
1:2
REV
A
DRAWN:
DATE DRAWN
2015-04-08
JPW
SHEET:
DWG SIZE
1
OF
DATE APPROVAL
B
2015-04-10
1
DWG APPROVAL:
HNT
3.50
88.9
2.22
56.4
Page 5
1.00
25.4
3.97
100.8
.59
.33
8.3
14.9 .17
4.4
8.72
221.4
5/16"
HARDWARE
.5
13
2.00
50.8
Positive Terminal
10.00 254
12.00
304.8
NOTE: Applies to all SSD models with an optional terminal arrangement
2.31
1.00
25.4
(non -R model numbers)
58.8
3.50
88.9
Negative Terminal
ANSI Y14.5M 1994 APPLIES
UNLESS NOTED UNITS: INCHES 3-PLACE: 2-PLACE: 1-PLACE / FRAC: ANGULAR:
.005
.015
63
.03
1
DAIRYLAND ELECTRICAL INDUSTRIES, INC.
P.O. BOX 187 STOUGHTON, WI 53589 608-877-9900 DAIRYLAND.COM
DESCRIPTION
SSD Outline Drawing - All Models with Optional Terminals
DOCUMENT #
100075
SCALE
1:2
REV
A
DRAWN:
DATE DRAWN
2015-04-08
JPW
SHEET:
DWG SIZE
1
OF
DATE APPROVAL
B
2015-04-10
1
DWG APPROVAL:
HNT
Loading...