™® The followi ng are trad emarks or regist ered trademar ks of their respective companies: BA
LonTalk, L
granted by Echelon Corporation; Compliant Scroll from Copeland Corporation; Modbus from Schneider Electric;, MicroTech
II, Open Choices from Daikin Applied.
ONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a license
Cnet from ASHRAE ;
LONMARK,
2 OMM 1130-2
Introduction
Water-Cooled
Global Design
Scroll Compressor
Nominal Capacity (Tons)
W = Water-Cooled Cond.
Design Vintage
General Description
Daikin Type WGZ water chillers are designed for indoor installations Equipment room temperature for
operating and standby conditions is 40°F to 122°F (4.4°C to 50°C). They are available with water-cooled
condensers (Model DW), or arranged for use with remote air-cooled or evaporative condensers (Model
DA). Each water-cooled unit is completely assembled and factory wired before evacuation, charging and
testing. They consist of hermetic scroll compressors, brazed-plate evaporator, water-cooled condenser (WGZDW), and complete refrigerant piping.
Uni
ts manufactured for use with remote condensers (Models WGZ-DA) have all refrigerant specialties factory-
mounted and connection points for refrigerant discharge and liquid lines.
Liquid line components that are included are manual liquid line shutoff valves, charging valves, filter-driers,
liquid line solenoid valves, sight glass/moisture indicators, and thermal expansion valves. Other features
include compressor crankcase heaters, and a MicroTech II microprocessor controller.
The electrical control center includes all equipment protection and operating controls necessary for dependable
automatic operation.
NOTE: This manual contains information on the chiller unit control software operating with various
refrigerants as follows:
• R-410A, used with the current “D” vintage of the WGZ chiller.
• R-134a, used with only with Model TGZ Templifiers. The operating manual devoted exclusively to
Templifiers is OMM 1136.
BOOT & BIOS
BOOT Version: 3.0F BIOS Version 3.56
Manuals: Information in unit initial installation and routine maintenance is contained in Installation and
Maintenance Manual IM 1131.
Nomenclature
W G Z 100 - D W
A = Unit Less Cond.
Water Pressure Drop
Water flow rates should be maintained as closely as possible to job design values. The vessel flow rates must
fall between the minimum and maximum values shown on the appropriate evaporator and condenser curves.
Measure the water pressure drop through the vessels at field-installed pressure taps and check the flow rate
using the following tables. Do not include valves or strainers in these readings.
The evaporator flow rates and pressure drops shown on the following page are for full load design purposes.
The maximum flow rate and pressure drop are based on a 6-degree temperature drop. Avoid higher flow rates
with resulting lower temperature drops to prevent potential control problems resulting from very small control
bands and limited start up/shut off temperature changes.
The minimum flow and pressure drop is based on a full load evaporator temperature drop of 16-degrees.
The chiller units have two ref rigerant cir cuits, Models WGZ 030 to WGZ 130 have two tandem scroll
compressors (total of four), a single two-circuited brazed plate evaporator, a single two-circuited watercooled condenser, interconnecting refrigerant piping and a control panel with associated sensors and
transducers.
Models WGZ 150 to WGZ 200 have two refrigerant circuits, two trio scroll compressors (total of six), a
single two-circuited shell-and-tube evaporator, a single two-circuited water-cooled condenser,
interconnecting refrigerant piping and a control panel with associated sensors and transducers.
Figure 4, Schematic Piping Diagram (One of Two Circuits for WGZ030D – 130D)
NOTE: W
electronic expansion valves.
GZ 150 to WGZ 200 have a shell-and-tube evaporator, three compressors per circuit, and
OMM 1130-27
Field Wiring Diagrams
Figure 5, WGZ030DW – WGZ200DW Field Wiring Diagram (Packaged Unit)
8 WGZ030D through WGZ200D OMM 1130-2
Figure 6, WGZ030DA – WGZ200DA Field Wiring Diagram (Remote Condenser)
OMM 1130-29
Control Panel Layout
Warning
!
(3) 120V/24V
LineV/120V
Control
Control
Optional
Switch
Microtech
(2) Circuit
(4) Compressor
(4) Compressor
Grounding
Location for
Table 1, Typical Control Panel, 4-Compressor Unit
Controller
Mechanical
Hi-Pressure
Switch Relays
Circuit Breakers
Contactors
Optional External
Overloads
Transformers
Control
Transformer
Transformer
Fuses, Primary
Transformer Fuse,
Secondary
Disconnect
Lug
NOTES:
1. Additional space provided in the upper right section for optional multiple point power connection and
optional circuit breakers.
2. Front door has a slot opening at the top for access to the MicroTech II controller for viewing display
and making keypad entries without opening the panel door.
Motor Protection Module
The motor protection system consists of an external control module, located on each compressor, motor
terminal box, connected to a series of thermistors located in the motor windings and the compressor
discharge port. If the windings experience an over-temperature condition or the discharge temperature is
excessive, the module will trip and shut off the compressor.
Disconnect the compressor three-phase power before removing the terminal box cover Removal of the
terminal box cover will expose the three-phase power connections. Contact with them can cause serious
injury or death..
10 WGZ030D through WGZ200D OMM 1130-2
Start-Up and Shutdown
Pre Start-up
1. The chilled-water system should be flushed and cleaned. Proper water treatment is required to
prevent corrosion and organic growth.
2. With main disconnect open, check all electrical connections in control panel and starter to be sure
they are tight and provide good electrical contact. Although connections are tightened at the factory,
they can loosen enough in shipment to cause a malfunction.
3. Check and inspect all water piping. Make sure flow direction is correct and piping is made to correct
connection on evaporator and condenser.
4. Open all water flow valves to the condenser and evaporator.
5. Flush the cooling tower and system piping to be sure the system is clean. Start evaporator pump and
manually start condenser pump and cooling tower. Check all piping for leaks. Vent the air from the
evaporator and condenser water circuit, as well as from the entire water system. The cooler circuit
should contain clean, treated, non-corrosive water.
6. Check to see that the evaporator water thermostat sensor is securely installed.
7. Making sure control stop switch S1 is open (off) and pumpdown switches PS1 and PS2 are on
“manual pumpdown,” place the main power and control disconnect switches to “on.” This will
energize the crankcase heaters. Wait a minimum of 12 hours before starting the unit.
8. Check compressor oil level. Prior to start-up, the oil level should cover at least one-third of the oil
sight glass located in the equalizing line between the compressors or on the compressor.
9. Note the water pressure drop across evaporator and condenser on pages 4 and 5 and check that water
flow is correct per the system design flow rates.
10. Check the actual line voltage to the unit to make sure it is the same as called for on the compressor
nameplate, within + 10%, and that phase voltage unbalance does not exceed 3%. Verify that adequate
power supply and capacity is available to handle load.
11. Make sure all wiring and fuses are of the proper size. Also make sure that all interlock wiring is
completed per Daikin Applied diagrams.
12. Veri
13. Make sure all auxiliary load and control equipment is operative and that an adequate cooling load is
fy that all mechanical and electrical inspections by code authorities have been completed.
available for in it ia l st ar t-up.
Start-up
1. Open the compressor discharge shutoff valves until backseated. Always replace valve seal caps.
2. Open the two manual liquid line shutoff valves.
3. Check to see that the unit circuit breakers are in the “off” position.
4. Check to see that the pumpdown switches, PS1 and PS2, are in the “manual pumpdown” position and
the control system switch S1 is in the “off” position.
5. Put the main power and control circuit disconnects to the “on” position.
6. Verify crankcase heaters have operated for at least 12 hours prior to start-up. Crankcase should be
warm to the touch.
7. Check that the MicroTech II controller is set to the desired chilled water temperature.
8. Start the system auxiliary equipment for the installation by turning on the time clock, ambient
thermostat and/or remote on/off switch and water pumps.
9. Check resets of all equipment protection controls.
10. Switch on the unit circuit breakers.
11. Set pumpdown switches PS1 and PS2 to “auto” for restart and normal operation.
OMM 1130-211
12. Start the system by setting the system switch S1 to on.
13. After running the unit for a short time, check the oil level in each compressor crankcase, rotation of
condenser fans (if any), and check for flashing in the refrigerant sight glass.
14. After system performance has stabilized, it is necessary that the “Compressorized Equipment
Warranty Form” (Form No. 206036A) be completed to establish commencement of the warranty
period. Be sure to list the pressure drop across both vessels. This form is shipped with the unit and
after completion should be returned to Daikin Applied service department through your sales
representative.
Weekend or Temporary Shutdown
Move pumpdown switches PS1 and PS2 to the “manual pumpdown” position. After the compressors have
pumped down, turn off the chilled water pump. Note: With the unit in this condition, it will not restart
until these switches are turned back on. The unit has one-time pumpdown. It is important that the
compressors pump down before the water flow to the unit is interrupted to avoid freeze-up in the
evaporator.
Leave S1 on and power to the unit so that the crankcase heaters will remain energized.
Start-up after Temporary Shutdown
1. Start the water pumps.
2. With the control system switch S1 in the “on” position, move the pumpdown switches PS1 and PS2 to
the “auto pumpdown” position.
3. Observe the unit operation for a short time, noting unusual sounds or possible cycling of compressors.
4. Check compressor crankcase heaters.
Extended Shutdown
Close the manual liquid line shutoff valves.
After the compressors have pumped down, turn off the water pumps.
Turn off all power to the unit.
Move the control service switch S1 to the “off” position.
Close the discharge shutoff valves on the compressor(s) and the liquid outle t valv es at the condense r.
Tag all opened disconnect switches to warn against start-up before opening the compressor suction and
discharge valves.
Drain all water from the unit evaporator, condenser, and chilled water piping if the unit is to be shut down
during the winter and exposed to below freezing temperatures. Do not leave the vessels or piping open to
the atmosphere over the shutdown period.
Start-up after Extended Shutdown
1. Inspect all equipment to see that it is in satisfactory operating condition.
2. Remove all debris that has collected on the surface of the condenser coils (remote condenser models)
or check the cooling tower, if present.
3. Backseat the compressor discharge valves. Always replace valve seal caps.
4. Open the manual liquid line shutoff valves.
5. Check circuit breakers. They must be in the “off” position.
6. Check to see that the pumpdown switches PS1 and PS2 are in the “manual shutdown” position and
the control system switch S1 is in the “off” position.
7. Put the main power and control circuit disconnects to the “on” position.
8. Allow the crankcase heaters to operate for at least 12 hours prior to start-up.
9. Start the chilled water pump and purge the water piping as well as the evaporator in the unit.
10. Start the system auxiliary equipment for the installation by turning on the time clock, ambient
thermostat and/or remote on/off switch.
12 WGZ030D through WGZ200D OMM 1130-2
11. Check that the MicroTech II controller is set to the desired chilled water temperature.
CAUTION
!
12. Check resets of all equipment protection controls.
13. Switch the unit circuit breakers to “on.”
14. Start the system by setting the system switch S1 to “on.”
Most relays and terminals in the control center are powered when S1 is closed and the
control circuit disconnect is on. Therefore, do not close S1 until ready for start-up or
serious equipment damage can occur.
15. Set pumpdown switches PS1 and PS2 to the “auto pumpdown” position for restart and normal
operation.
16. After running the unit for a short time, check the oil level in the compressor oil sight glass or in the
compressor’s equalizing lines for flashing, indicating possible refrigerant in the oil.
Low Ambient Start
The low ambient start logic is for starting units with remote air-cooled condensers during periods of low
ambient air temperatures.
A low ambient start takes place if the saturated condenser temperature is less than 85.0°F when the first
compressor starts. The low ambient start is active for a time defined by the Low OAT Start Timer set
point. This set point is found on screen three in the alarm set points menus.
During the low ambient start, the freezestat logic for the low-pressure stop alarm and the low-pressure
events are disabled. The low-pressure stop alarm can still be triggered if the evaporator pressure drops
below 5.0 psi at any time while the circuit is in the ‘Run’ state. Also, during the low ambient start, the
second compressor is not allowed to start. The evaporator pressure is checked at the end of the low
ambient start time frame. If the pressure is less than the Low Pressure Unload set point, then the low
ambient start is not successful and the compressor will shut off. This will not be a manual reset alarm
until three consecutive attempts have failed. The circuit alarm triggered after the third failed attempt is a
Low OAT Restart fault. The Low OAT Restart faults are Circuit alarms so each circuit will attempt to start
either compressor three times before the Low OAT Restart fault is indicated.
Fan High Ambient Rapid Start
The following logic exists to get condenser fans started earlier than normal during unit starts with warm
ambient air temperatures.
•If the outside air temperature higher than 75.0°F the condenser fan staging logic changes to bring on
the first fan on when the condenser pressure is greater than 140 psi.
•The standard condenser fan staging logic would start the first condenser fan when the condenser
pressure is higher than 200.0 psi.
•The last condenser fan on each circuit will not shut down until the condenser pressure drops below
140.0 psi regardless of the outside air temperatu re
Sequence of Operation
The following sequence of operation is typical for WGZ water chiller models. The sequence can vary
slightly depending upon options.
Compressor Heaters
With the control circuit power on and the control stop switch S1 off, 115V power is applied through the
control circuit fuse Fl to the compressor crankcase heaters HTR1, HTR2, HTR3, and HTR4.
Start-up/Compressor Staging
When compressors start and stop.
Stage Up Temp is the LWT temperature at which the next compressor to start will stage up (start) after at
least one compressor on the unit has started and is running.
OMM 1130-213
41.5°
F
40.0°
F
38.5°
F
½DB
½DB
EWT
50.0°
F
10.0°
F
40.0°
F
EvapDelta-TSetLWT
S
e
t
StartDeltaT
46.5°F
36.5°F
Stop Delta T
t Up Temp is the LWT at which the first compressor starts. The start up temperature equals the stage
Star
up temperature plus the Start Delta temperature. A high Start Delta will keep the unit off longer and
reduce unit cycling at low loads. However, t his high Start Delta will cause a larger excursion from the
LWT setpoint before the unit starts.
Stated another way, the Start Delta is the number of degrees above the Evap LWT setpoint, plus ½ the
Dead Band, that determines when the first compressor starts. The Start Delta is in effect for only the first
start after all compressors have been off. Additional compressor starts and stops are determined by the
LWT in respect to the dead band only. The dead band is automatically set at 30% of the EvapDeltaT
selected in menu 3. The following sequence would occur for the settings shown below:
EvapDelta T=10.0°F Dead Band=3.0°F StartDelta=5.0°F StopDelta=2.0°F LWT=40.0°F
Figure 7, Staging/Starting Temperatures
For a warm start-up (no compressors
running), the first compressor will start at any
temperature above 46.5°F. Each subsequent
compressor will start after the Stage Up
Timer has timed out and if the temperature is
above the dead band, 41.5°F in this case.
If the LWT stays above 41.5°F, all of three (or
5) remaining compressors will eventually
stage on after the Stage Up Timer times out
between each stage.
At some point, the chilled water temperature will be dropping and begin to approach the point when
compressors should begin staging off, which is the LWT setpoint minus ½ of the Dead Band, 38.5°F in
this case. If the LWT remains below LWT setpoint minus ½ Dead Band and the Stage Down Timer times
out, additional compressors will stage off. The last compressor will stage off when the LWT falls below
the LWT Setpoint minus ½ the Dead Band minus the Stop Delta T. The stop Delta T is in effect for only
the last compressor running.
If the temperature climbs above 38.5°F all running compressors will remain on. No compressor staging
occurs within the Dead Band. The next-on compressor will start when the chilled water temperature
reaches 41.5°F and the Stage Up Timer times out.
However, in some circumstances this methodology can cause the LWT to drop to dangerously low levels,
with the evaporating temperature below the freeze point, before stopping. In the example shown in
Figure 7, the Shutdown Temp (last compressor off) would be 36°F.
This would result in a refrigerant evaporating temperature approaching freezing, so the rule is amended to
read:
If the Cool Leaving Water Temperature (LWT) set point is less than half the Control Band
above 39.0° F the Stage Down temperature is calculated as:
Stage Down Temperature = Cool LWT – (Cool LWT - 39.0
Shutdown Temperature = Cool LWT – (Cool LWT - 39.0
This keeps the Stage Down Temp above 39°F and the Shutdown Temp above 36°F, as the maximum Stop
Delta T allowed is 3-degrees.
Which compressor starts and stops. One compressor per circuit will start before starting the second
compressor (or third) on any circuit. In other words, the compressor with the lowest number of starts will
start first. The compressor with the lowest number of starts on the other circuit will start next, so that one
compressor on each circuit will be running. The third compressor on will be the compressor on either
circuit with the fewest starts. The remaining compressor will be the last on. If a circuit is unavailable for
any reason, the second compressor on the operating circuit will stage on. Only two (or three)
compressors (on the one circuit) will be operating.
There is a 150 second delay after power-up before any compressor is allowed to start.
14 WGZ030D through WGZ200D OMM 1130-2
°
F), and the
°
F) – Stop Delta T
When staging down, one compressor on each circuit will be left on until each circuit has only one
Description
Occurs When:
Action Taken
Below)
After Stage Up Delay times out then, LVG
Evap T > Evap LWT SP + (DB/2)
Available compressor on the other
circuit with least starts, ON
Evap T > Evap LWT SP + (DB/2)
with least starts, ON
After Stage Up Delay times out then, LVG
Evap T < Evap LWT SP – (CB/2)
After Stage Down Delay times out then, LVG
Evap T < Evap LWT SP – (DB/2)
Compressor on the other circuit with
most run hours, OFF
After Stage Down Delay times out then, LVG
Evap T < Evap LWT SP – (DB/2)
Compressor on either circuit with most
run hours, OFF
After Stage Down Delay times out then, LVG
Evap T < Evap LWT SP – (DB/2)-StopDelta T
compressor running. In other words, the compressor, on either circuit, with the most run-hours will stop
first. The compressor with the most run-hours on the other circuit will stop next. One compressor on
each circuit will be running. The third compressor off will be the one, on either circuit, with the most
run-hours. The remaining compressor will be the last off. See the following description of pumpdown.
Table 2, Staging in Cool and Glycol Mode
Stage #1 ON
(See Notes
Stage #2 ON
Stage #3 ON
Stage #4 ON
Stage #4 OFF
Stage #3 OFF
Stage #2 OFF
Stage #1 OFF
Note 1: DB (Dead Band) = Evap Water Delta T x .3
Lvg Evap T > Evap LWT SP + (DB/2) +
Startup Delta T
After Stage Up Delay times out, then LVG
Evap T > Evap LWT SP + (DB/2)
After Stage Down Delay times out then, LVG
Available compressor with least starts,
ON
Available compressor on either circuit
Remaining compressor, ON
Compressor with most run hours, OFF
Remaining compressor, OFF
Manual Compressor Disable Logic
Logic is available that allows the operator to manually enable and disable compressors. When a
compressor is disabled, it is considered unavailable to start in the staging logic. This allows a damaged
compressor to be taken offline while the remaining compressor can still provide some cooling
•The Compressor Disable set points are found on Compressor Set Points screens three and four.
•A running compressor cannot be disabled until it has been shutdown.
•If all of the compressors on a circuit are disabled, then the circuit will be disabled.
•If both circuits have all of their compressors disabled, then the Unit State will remain Off
Automatic Pumpdown
WGZ units are equipped with single pumpdown control. When the last compressor running on either
circuit is ready to shut off, the liquid line solenoid valve (LLSV) is closed first and the compressor
continues to run until the pumpdown pressure is reached, at which time the compressor shuts off. The
shut off pressure is set at 15 psi below the Low Evaporator pressure Unload setpoint.
When the first compressor on a circuit starts, the LLSV opens simultaneously.
Manual Pumpdown
When the Pumpdown Switch is in the pumpdown position, all compressors except #1 and #2 will shut off.
Then the Liquid Line and Hot Gas Bypass Valves will close. The operating compressor will pump out the
refrigerant. When the Suction Pressure is at 40 psig, the compressors will stop.
Chilled Water and Condenser Water Pumps
The chiller MicroTech II controller can be programmed to start and stop the system chilled water and
condenser water pumps. They may also be controlled by the BAS or manually. Programming directions
and the sequence of operation can be found beginning on page 38.
Cooling Tower Control
The cooling tower fans and/or the tower bypass valve can be controlled by the MicroTech II controller.
This provides a simple and direct method to control the unit’s discharge pressure. Programming
OMM 1130-215
directions and the sequence of operation can be found on page 65. Some means of discharge pressure
Stage #
Fan 1 Fan
3
Stage #
Fan 1 Fan 3 Fan
5
Stage #
Fan 1 Fan 3 Fan 5 Fan
7 1 ON 1 ON 1 ON
ON
ON 2 ON
ON
ON
ON
3 ON
ON
ON 3 ON
ON
ON
ON
ON
ON
ON
Stage #
5&7
Stage #
5&7
9
Stage #
5&7
9&11 1 ON 1 ON 1 ON
2
ON
ON 2 ON
ON 2 ON
ON
3
ON
ON 3 ON
ON
3
ON
ON
ON
ON
ON 4 ON
ON
ON
ON
ON
ON 5 ON
ON
ON
ON 5 ON
ON
ON 6 ON
ON
ON
ON
Stage #
Fan 2 Fan
4
Stage #
Fan 2 Fan 4 Fan
6
Stage #
Fan 2 Fan 4 Fan 6 Fan
8
ON 1 ON 1 ON
ON
ON 2 ON
ON
ON
ON
ON
ON
ON 3 ON
ON
ON
ON
ON
ON
ON
Stage #
Fan 2 Fan 4 Fan
6&8
Stage #
Fan 2 Fan 4 Fan
6&8
Fan
10
Stage #
Fan 2 Fan 4 Fan
6&8
Fan
10&12
1
ON 1 ON 1 ON
2
ON
ON 2 ON
ON 2 ON
ON
ON
ON 3 ON
ON
ON ON
4
ON
ON
ON 4 ON
ON
ON
4
ON
ON
ON
5
ON
ON
ON
ON 5 ON ON
ON
6
ON
ON
ON
ON
control must be installed if the condenser water temperature can fall below 60°F (16°C).
Condenser Fan Control
Model AC chillers equipped with air-cooled or evapora tive -cooled condensers usually require some form
of discharge pressure control. The MicroTech II controller can be programmed to provide this function
by cycling condenser fans based on the unit discharge pressure. Directions on the pressure settings can be
found on page 65. The following charts illustrate how four controller outputs can control six fan steps.
Circuit 1
Number of Fans = 4 Number of fans = 6 Number of fans = 8
2
4
Circuit 2
1
2
2
4
Number of fans = 8 (R410A)Number of fans = 10 (R410A)Number of fans = 12
Fan 1 Fan 3 Fan
Number of Fans = 4 Number of fans = 6 Number of fans = 8
3
Fan 1 Fan 3 Fan
Fan
2
4
Fan 1 Fan 3 Fan
4
Fan
Number of fans = 8 (R410A)Number of fans = 10 (R410A)Number of fans = 12
3
ICE
In ICE mode, the compressors stage to 100% load until the LWT is less than the ICE LWT SP. Then
Compressors #3 and #4 shut down. Following that, Compressors #1 and #2 shut down after going
through normal pumpdown on both circuits. There is a programmable, start-to-start, Ice Mode Start
Delay that limits the frequency of starts when in the ice mode. The timer can be manually cleared to
force a restart.
16 WGZ030D through WGZ200D OMM 1130-2
3
MicroTech II Controller
Controller Software Version
This manual is based on software version WGZD20102F. The “02F” is the version descriptor. The
version installed in a unit can be viewed by pressing the MENU and ENTER keys simultaneously, then
pressing MENU to return to the regular menu screen.
General Description
The MicroTech II controller’s state-of-the-art design will not only permit the chiller to run more
efficiently but will also simplify troubleshooting if a system failure occurs. Every MicroTech II controller
is programmed and tested prior to shipment to assist in a trouble-free start-up. The MicroTech II
controller can be used to cycle fans on remote air-cooled condensers for head pressure control when the
setpoint Water Cooled=N is selected in one of the setpoint menu screens. Water Cooled=Y sets the chiller
for operation with the water-cooled condenser.
Operator Friendly
The MicroTech II controller menu structure is separated into three distinct categories, which provide the
operator or service technician with a full description of
1. current unit status,
2. control parameters (setpoints)
3. alarms. Security protection prevents unauthorized changing of the setpoints and control parameters.
The MicroTech II controller continuously performs self-diagnostic checks, monitoring all system
temperatures, pressures and protection devices, and will automatically shutdown a compressor, a
refrigerant circuit or the entire unit should a fault occur. The cause of the shutdown and date stamp are
retained in memory and can be easily displayed in plain English for operator review, which is an
extremely useful feature for troubleshooting. In addition to displaying alarm diagnostics, the MicroTech
II chiller controller also provides the operator with a warning of pre-alarm conditions.
Staging
The four scroll (or six) compressors are staged on and off as a function of leaving chilled water
temperature, number of starts and run-hours. See Sequence of Operation.
Equipment Protection
The unit is protected by alarms that shut it down and require manual reset, and also by limit alarms that
limit unit operation in response to some out-of-limit condition. Shut down alarms activate an alarm signal
that can be wired to a remote device.
Unit Enable Selection
Enables unit operation from local keypad or digital input
Unit Mode Selection
Selects standard cooling, ice, glycol, or test operation mode
OMM 1130-217
Keypad/Display
#
Description
Type
Signal Source
Range
*1
Evaporator Refrigerant Pressure #1 (R134a,R22)
C1
0.1 to 0.9 VDC
0 to 132 psi
*1
(R410a)
C1
0.1 to 0.9 VDC
0 to 350 psi
*2
Evaporator Refrigerant Pressure #2 (R134a,R22)
C2
0.1 to 0.9 VDC
0 to 132 psi
*2
Evaporator Refrigerant Pressure #2 (R410a)
C2
0.1 to 0.9 VDC
0 to 350 psi
*3
Condenser Refrigerant Pressure #1 (R134a,R22)
C1
0.1 to 0.9 VDC
3.6 to 410 psi
*3
Condenser Refrigerant Pressure #1 (R410a)
C1
0.1 to 0.9 VDC
0 to 700 psi
(10k@25°C)
Condenser Entering Water Temperature or Outside Ambient
Temperature (See Note below)
(10k@25°C)
*6
Condenser Refrigerant Pressure #2 (R134a,R22)
C2
0.1 to 0.9 VDC
3.6 to 410 psi
*6
Condenser Refrigerant Pressure #2 (R410a)
C2
0.1 to 0.9 VDC
0 to 700 psi
7
Reset of Leaving Water Temperature
UT
4-20 mA Current
0-(10 to 80°F)
8
Demand Limit (R22, R410A)
UT
4-20 mA Current
0-100 % Load
(10k@25°C)
(10k@25°C)
AirConditioning
ALARM
VIEW
SET
<
<
<
Menu Key
Key to Screen Pathway
"Enter" Key
Arrow Keys
A 4-line by 20-character/line liquid crystal display and 6-key keypad is mounted on the unit controller. Its
layout is shown below.
Figure 8, Keypad and Display in MENU Mode
our arrow keys (UP, DOWN, LEFT, RIGHT) have three modes of use.
The f
Scroll between data screens as indicated by the arrows (default mode).
Select a specific data screen in a hierarchical fashion using dynamic labels on the right side of the display
(this mode is entered by pressing the MENU key).
Change field values in edit mode according to the following table:
LEFT Default RIGHT Cancel
UP Increment DOWN Decrement
These four edit functions are indicated by one-character abbreviation on the right side of the display (this
mode is entered by pressing the ENTER key).
Inputs/Outputs
Table 3, Analog Inputs
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, *n = Refrig. Dependent
Evaporator Refrigerant Pressure #1
4
Leaving Evaporator Water Temperature UT
5
9
Compressor Suction Temperature #1 C1
10
Compressor Suction Temperature #2 C2
UT
NTC Thermister
NTC Thermister
NTC Thermister
NTC Thermister
Notes:
1. If Water Cooled = Y, then Entering Condenser. If Water Cooled = N, then Outside Ambient.
2. Selection of R134a in unit setpoint screen will modify unit operation for Templifier application.
18WGZ030D through WGZ200D OMM 1130-2
-58 to 212°F
-58 to 212°F
-58 to 212°F
-58 to 212°F
Table 4, Analog Outputs
#
Description
Output Signal
Range
1
Cooling Tower Bypass Valve Position
0 to 10 VDC
0 to 100% Open
2
Cooling Tower VFD Speed
0 to 10 VDC
0 to 100%
4
Circuit #2 Electronic Expansion Valve
0 to 10 VDC
0 to 100%
#
Description
Type
Signal
Signal
1
Unit OFF Switch
UT
0 VAC (Stop)
24 VAC (Auto)
2
Pump Down Switch #1
C1
0 VAC (Stop)
24 VAC (Start)
3
Evaporator Water Flow Switch
UT
0 VAC (No Flow)
24 VAC (Flow)
*4
*4
Open
5
Open
6
Pump Down Switch #2
C2
0 VAC (Stop)
24 VAC (Start)
*7
Motor Protection #2
C2
0 VAC (Fault)
24 VAC (No Fault)
*7
Open
*8
*8
Condenser Water Flow Switch (R134a,R410a)
UT
0 VAC (No Flow)
24 VAC (Flow)
9
Phase Voltage Fault #1 (See Note 1 Below)
C1
0 VAC (Fault)
24 VAC (No Fault)
10
Phase Voltage Fault #2 (See Note 1 Below)
C2
0 VAC (Fault)
24 VAC (No Fault)
11
Ground Fault Prot. #1 (See Note 2 Below)
C1
0 VAC (Fault)
24 VAC (No Fault)
12
Ground Fault Prot. #2 (See Note 2 Below)
C2
0 VAC (Fault)
24 VAC (No Fault)
13
*14
Condenser Water Flow Switch
UT
0 VAC (No Flow)
24 VAC (Flow)
*14
(
*15
Open
*15
(R134a,R410a)
C1
0 VAC (Fault)
24 VAC (No Fault)
*16
Open
*16
(R134a,R410a)
17
Ice Mode Switch
UT
0 VAC (Normal)
24 VAC (Ice)
18
Heat Mode Switch
UT
0 VAC (Normal)
24 VAC (Heat)
#
Description
Type
Load
Output OFF
Output ON
1
Alarm
C1,C2,UT
Alarm Indicator
Alarm OFF
Alarm ON
2
Evaporator Water Pump
UT
Pump Contactor
Pump OFF
Pump ON
Condenser Water Pump – Water Cooled = Y
Pump Contactor
4
3 Circuit #1 Electroni c E xpansion V alve 0 to 10 VDC 0 to 100%
NOTE: Analog outputs 3 & 4 are for R410A and R134a units only.
Table 5, Digital Inputs
The following parameters are digital inpu ts to this contr oll er .
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, *n = Refrigerant Dependent
Motor Protection #1 C1 0 VAC (Fault) 24 VAC (No Fault)
Open
Remote Start/Stop UT 0 VAC (Stop) 24 VAC (Start)
Open
Motor Protection #1
Motor Protection #2
C2 0 VAC (Fault) 24 VAC (No Fault)
Notes:
1. See Safety Alarms Table for “Phase Voltage Protection”. Units with single point electrical connection will have one PVM with
Inputs 9 and 10 wired together. Units with multiple point connection will have two PVM’s with Input 9 for Electrical Circuit #1 and
Input 10 for Electrical Circuit #2.
2. See Safety Alarms Table for “Ground Fault Protection”. Units with single point electrical connection will have one GFP with
Inputs 11 and 12 wired together. Units with multiple point connection will have two GFP’s with Input 11 for Electrical Circuit #1
and Input 12 for Electrical Circuit #2.
Table 6, Digital Outputs
The following parameters are digital outputs from this controller.
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit, *n = Refrigerant Dependent
Condenser Fan #1 – Water Cooled = N /
3
C1 / UT
Fan Contactor/
Fan OFF Fan ON
Motor Control Relay #1 = Compr#1 C1 Starter Compressor OFF Compressor ON
Continued next page.
OMM 1130-219
Table 6, Continued
#
Description
Type
Load
Output OFF
Output ON
5
Motor Control Relay #3 = Compr#3
C1
Starter
Compressor OFF
Compressor ON
#2-Water Cooled=Y
UT
*6
(R134a,R410a)
7
Liquid Line #1
C1
Solenoid
Cooling OFF
Cooling ON
9
Motor Control Relay #2 = Compr#2
C2
Starter
Compressor OFF
Compressor ON
10
Motor Control Relay #4 = Compr#4
C2
Starter
Compressor OFF
Compressor ON
*11
Condenser Fan #4
C2
Fan Contactor
Fan OFF
Fan ON
*11
(R134a,R410a)
12
Liquid Line #2
C2
Solenoid
Cooling OFF
Cooling ON
13
14
Hot Gas Bypass #1
C1
Solenoid
Cooling OFF
Cooling ON
15
*16
Condenser Fan #6
C2
Fan Contactor
Fan OFF
Fan ON
*16
*17
Condenser Fan #7
C1
Fan Contactor
Fan OFF
Fan ON
*17
(R134a,R410a)
18
Condenser Fan #8
C2
Fan Contactor
Fan OFF
Fan ON
18
Condenser Fan #6&8
C2
Fan Contactor
Fan OFF
Fan ON
#
Description
Type
Output Off
Output On
1
2
Cond Water Pump Output #2
UT
Pump Off
Pump On
3
Condenser Fan #9
C1
Fan OFF
Fan ON
4
Condenser Fan #10
C2
Fan OFF
Fan ON
#
Description
Type
Output Off
Output On
(R134a)
(10k@25°C)
2
Demand Limit (R134a)
UT
4-20 mA Current
0-100 % Load
(10k@25°C)
Condenser Fan #3– Water Cooled =N /Tower Fan
*6
Motor Control Relay #5 = Compr#5
Condenser Fan #2 – Water Cooled =N /Tower Fan
8
#1-Water Cooled=Y
Motor Control Relay #6 = Compr#6
Condenser Fan #5C1 Fan Contactor Fan OFF Fan ON
Hot Gas Bypass #2C2 Solenoid Cooling OFF Cooling ON
Condenser Fan #4C2 Fan Contactor Fan OFF Fan ON
Condenser Fan #5&7
C1 /
Fan Contactor Fan OFF Fan ON
C1 Starter Compressor OFF Compressor ON
C2 /
Fan Contactor Fan OFF Fan ON
UT
C2 Starter Compressor OFF Compressor ON
C1 Fan Contactor Fan OFF Fan ON
Expansion I/O Controller
Digital Outputs
The following parameters are digital outputs from this controller.
Types: C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit
Evap Water Pump Output #2 UT Pump Off Pump On
Analog Inputs
The following parameters are digital outputs from this controller for Templifier operation only.
Types: C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, & UT = Unit
Entering Evaporator Water Temperature
1
3 Liquid Line Temperature #1 (R134a)
4 Liquid Line Temperature #2 (R134a)
UT
C1
C2
NTC Thermister
NTC Thermister
10k@25°C)
(
NTC Thermister
-58 to 212°F
-58 to 212°F
-58 to 212°F
20WGZ030D through WGZ200D OMM 1130-2
Setpoints
Unit Enable
Off
Off, On
O
Control source
Switches
Keypad, Network, Switches
O
Ice w/Glycol, Test
20.0 to 85.0°F (R134a)
40. 0 °F
15.0 to 40.0 °F
110.o°F
110 to 165°F
Evap Delta T
10.0 °F
6.0 to 16.0 °F
O
Startup Delta T
10.0 °F
1.0 to 15.0 °F
O
Max Pulldown Rate
1.0 °F
0.5 to 5.0 °F
M
Evap Recirculate Timer
30
15 to 300 seconds
M
20.0°F
5.0 to 40.0°F
(Water-cooled = Yes)
Demand Limit
Off
Off, On
M
* Water Cooled
Off
Off, On
M
Clear Ice Delay
No
No, Yes
M
Hot Gas Delay Time
30 sec.
30 to 180 seconds
M
BAS Protocol
Modbus
BACnet, LonWorks, Modbus
M
Ident number
001
000-200
M
Baud rate
9600
1200,2400,4800,9600,19200
M
Units
F/psi
F/psi (only)
Language
English
English (only)
* Refrigerant Select
None
R22, R407C, R410A, R134a
Cooling Reset Type
None
None, 4-20mA, [Return( Refrig = R134a only)]
O
Cooling Maximum Reset
10 ºF
0 to 16 ºF
O
Compressor
# of Compressors
(Refrig = R410A or R134a to select 6)
Clear Cycle Tmr
Off
On/Off
M
Stage Down Delay
30
20 to 60 sec
M
Start-Start
15 min
10 to 60 min
M
Stop-Start
5 min
3 to 20 min
M
The following parameters are remembered during power off, are factory set to the Default value, and can be
adjusted to any value in the Range column.
The PW (password) column indicates the password level that must be active in order to change the setpoint.
Passwords are as follows:
O = Operator [0100] M = Manager [2001]
Table 7, Setpoints (setpoints with * are set at Daikin Applied factory)
Description Default Range PW
*Unit Mode (R22, R407C, R410ACool Cool, Cool w/Glycol, Ice w/Glycol, Test O
Unit Mode (R134a) Cool Cool, Cool w/Glycol, Heat, Test
#1 Only #1 Only, #2 Only, Auto, #1 Prim, #2 Prim M
35.0 °F
Cool, Cool w/Glycol, Cool/Ice w/Glycol
Test, Cool, Cool w/Glycol, Cool/Heat, COOL/HEAT
w/Glycol, Heat w/Glycol,
Without Glycol: 40.0 to 60.0°F
40.0 to 85.0°F (R134a Only)
With Glycol: 20.0 to 60.0°F (R22,R407C)
10.0 to 60.0°F (R410A)
#1 Only, #2 Only, Auto, #1 Prim,
#2 Prim
35 to 70 °F
If Speedtrol = Yes
-2.0 to70.0°F (R22,R407C)
-10.0 to 70.0 (R410A)
N/A (R134a)
M
M
O
O
O
O
M
M
Ice Time Delay 12 hrs 1 to 23 hrs M
Cooling Start Reset Delta T 10 ºF 0 to 16 ºF (Refrig = R134a only) O
Stage Up Delay 240 sec 90 to 480 seconds M
OMM 1130-221
4 4, 6 M
Table 7
Expansion Valve Type
Electronic
Thermal, Electronic
M
Circuit 1 EXV Control
Auto
Auto, Manual
M
Circuit 1 EXV Position
N/A
0-100%
M
Circuit 2 EXV Position
N/A
0-100%
M
MaxOpPress
156
142 – 170 psig
M
SuperheatTarg
10
8-12°F
M
Alarms
Low Evap Pressure-Hold
M
Water: 405 psig
Water: 355 – 425 psig
37.0 to 42.0 °F
7.5 to 42.0°F (R410A)
Cond. Freeze
34.0 °F
18 to 42 °F
M
High Condenser Pressure Stop
(Water-Cooled = Y
280 psi
420 psi
260 to 380 psi (R22, R407C)
375 TO 435 psi (R410A)
High Condenser Pressure Stop
(Water Cooled = N)
380 psi
565 psi
260 to 380 psi (R22, R407C)
425 to 570 psi (R410A)
High Condenser Pressure Stop (R134a)
185 psi
170 to 425 psi
M
Evap Flow Proof
5 sec.
5 to 15 seconds
M
Cond Flow Proof
5 sec.
5 to 15 seconds
M
Recirc Timeout
3 min.
1 to 10 minutes
M
* Ground Fault ProtectionN N,Y
M
Low OAT Start Time
60 sec.
30 to 240 seconds
M
Condenser Fans (Water Cooled = N)
Number of fans 4 4 to 8 (10 for R410a)
M
Speedtrol Option
No
No,Yes
M
Stg on Deadband Stg 2
15 °F
15 to 25°F
M
Stg on Deadband Stg 3
10°F
10 to 15°F
M
Stg on Deadband Stg 4
10°F
10 to 15°F
M
Stg Off Deadband Stg 1
20°F
15 to 20°F
M
Stg Off Deadband Stg 2
15°F
10 to 15°F
M
Stg Off Deadband Stg 3
10°F
6 to 10°F
M
Stg Off Deadband Stg 4
10°F
6 to 10°F
M
Forced Fan 3 (>105°F)
Cooling Tower (Water Cooled = Y)
Tower Control
None
None, Temperature
M
Tower Stages 2 0 to 2
M
Stage Up Time
2 min
1 to 60 min
M
Stage Down Time
5 min
1 to 60 min
M
Stage Differential
3.0 °F
1.0 to 10.0 °F
M
Stage #1 On
70 °F
40 to 120 °F
M
Stage #2 On
75 °F
40 to 120 °F
M
None, Valve Set point, Valve Stage, VFD
65 °F
60 to 120 °F
Valve Deadband
2.0 °F
1.0 to 10.0 °F
M
Stage Fan Down @
20%
0 to 100%
M
Valve Control Range (Min)
10%
0 to 100%
M
Valve Control Range(Max)
90%
0 to 100%
M
Valve Type
NC to tower
NC, NO
M
Minimum Start Position
0%
0 to 100%
M
Minimum Position @
60 °F
0 to 100 °F
M
Maximum Start Position
100%
0 to 100%
M
Error Gain
25
10 to 99
M
Slope Gain
25
10 to 99
M
Circuit 2 EXV Control Auto Auto, Manual M
, Continued
Description Default Range PW
Low Evap Pressure-Unload M
High Cond Pressure – Unload
High Cond Pressure – Stop
Evap. Freeze
* Phase Voltage ProtectionN N,Y M
See following section; Automatic Adjusted Limits
Air: 550 psig
Water: 420 psig
Air: 565 psig
38.0 °F
Glycol: 17.5 to 42.0°F (R134a,R22, R407C)
Air: 410- - 555 psig
Water: 375 – 435 psig
Air: 425 – 570 psig
M
M
M
M
M
Cond Sat Temp Target 100°F 80 to 120°F M
Forced Fan 1 (>75°F)
Forced Fan 2 (>90°F)
Valve/VFD Control None
Valve Setpoint
Stage Fan Up @ 80% 0 to 100% M
Maximum Position @
22WGZ030D through WGZ200D OMM 1130-2
Stage, Valve SP/VFD Stage
90 °F 0 to 100 °F
M
M
M
Automatic Adjusted Limits
Mode
Refrigerant Type
Range
Unit Mode = Cool
R134a, R410A
40 to 60°F
Unit Mode = Cool w/Glycol
R134a
20 to 60°F
Unit Mode = Cool w/Glycol
R410a
15 to 60°F
Unit Mode = Ice
R410A
20 to 40°F
Mode
Refrigerant Type
Range
Unit Mode= HEAT
R134a
110 to 160ºF
Mode
Refrigerant Type
Range
Unit Mode = Cool
R134a, R410A
36 to 42°F
Unit Mode = Cool w/Glycol, Ice
w/Glycol
Unit Mode = Cool w/Glycol, Ice
w/Glycol
Refrigerant Type
Range
R134a
N/A
R22, R407C
20 to 40°F
R410A
15 to 40°F
Mode
Refrigerant Type
Range
R410A
97 to 115 psi
w/Glycol
R410A
48 to 115 psi
Speedtrol
Range
Speedtrol = N
35 – 70°F
The following are set points that will be limited based on the option selected.
Evaporator Leaving W ate r Temperature
Conde
Evapor
Ice Lea
Low
nser Leaving Water Temperature
ator Freeze Temperature
R134a 18 to 42°F
R410A 12.5 to 42°F
ving W ater Temperature
Evaporator Pressure Inhibit Loading and Unloading
Unit Mode = Cool
Unit Mode = Cool w/Glycol, Ice
R134a
R134a
26 to 54 psi
12 to 54 psi
Ambient Lockout T empe rature
Low
Speedtrol = Y -2 – 70°F
NOTE:
The backup mechanical high pressure cutout is set at 450 psi for water cooled applications and
600 psi for air cooled for air-cooled applications.
OMM 1130-223
Dynamic Defaults
R134a
R410A
Low Evaporator Pressure Hold
29 psi
101 psi
405 psi WC
Some set points will have a particular default value loaded when another setting is changed.
Refrigerant Dependent Defaults
Set Point
Low Evaporator Pressure Unload
High Condenser Pressure Unload 170 psi
High Condenser Pressure 185 psi
Refrigerant Type
28 psi
550 psi AC
565 psi AC
420 psi WC
100 psi
AC = Air Cooled, WC = Water Cooled (R134a is water cooled ONLY)
Number of Fans Dependent Defaults
When the number of fans setting is changed, the forced fan set points will default to values as shown in
the following table:
Set Point
Forced Fan 1 (>75°F) 1 1 1 1
Forced Fan 2 (>90°F) 1 1 2 2
Forced Fan 3 (>105°F) 2 2 3 3
4 6 8 10
Number of Fans Set Point
Events & Alarms
Situations may arise that require some action from the chiller or that should be logged for future
reference. Conditions that cause a shutdown and require manual reset is known as a stop alarm. Other
conditions can trigger what is known as an event, which may or may not require action in response. All
stop alarms and events are logged.
Unit Stop Alarms
The alarm output and red button is turned ON when any stop alarm occurs and turned off when all alarms
have been cleared.
Evaporator Flow Loss
Alarm description (as shown on screen): Evapo rator Flow Loss
Trigger:
1: Evaporator Pump State = Run AND Evaporator Flow Digital Input = No Flow for time > Evap Flow
Proof Set Point AND at least one compressor running.
2: Evaporator Pump State = Start for time greater than Recirc Timeout Set Point AND all pumps have
been tried AND Evaporator Flow Digital Input = No Flow.
Action T aken: R apid sto p all circu it s.
Reset:
This alarm can be cleared at any time manually via the keypad or via the BAS clear alarm signal.
If active via trigger condition 1:
24 WGZ030D through WGZ200D OMM 1130-2
When the alarm occurs due to this trigger, it can auto reset the first two times each day, with the third
occurrence being manual reset.
the auto-reset occurrences, the alarm will reset automatically when the evaporator state is Run again.
For
This means the alarm stays active while the unit waits for flow, then it goes through the recirculation
process after flow is detected. Once the recirc ula tion is complete, the evaporator goes to the Run state
which will clear the alarm. After three occurrences, the count of occurrences is reset and the cycle starts
over if the manual reset flow loss alarm is cleared.
If a
ctive via trigger condition 2:
If the flow loss alarm has occurred due to this trigger, it is always a manual reset alarm.
Condenser Flow Loss (Note: WaterCooled = On & TGZ units Only)
Alarm description (as shown on screen): Conden ser Flow Loss
Trigger:
1: Condenser Pump State = Run AND Condenser Flow Digital Input = No Flow for time > Cond Flow
Proof Set Point AND at least one compressor running.
2: Condenser Pump State = Start for time greater than Recirc Timeout Set Point AND all pumps have
been tried AND Condenser Flow Digital Input = No Flow.
Action T aken: R apid sto p all circu it s.
Reset:
This alarm can be cleared at anytime manually via the keypad or via the BAS clear alarm signal.
If a
ctive via trigger condition 1:
When the alarm occurs due to this trigger, it can auto reset the first two times each day, with the third
occurrence being manual reset.
For
the auto-reset occurrences, the alarm will reset automatically when the condenser pump state is Run
again. This means the alarm stays active while the unit waits for flow, then it goes through the
recirculation process after flow is detected. Once the recirculation is complete, the condenser pump goes
to the Run state which will clear the alarm. After three occurrences, the count of occurrences is reset and
the cycle starts over if the manual reset flow loss alarm is cleared.
If active via trigger condition 2:
If the flow loss alarm has occurred due to this trigger, it is always a manual reset alarm.
Low Evaporator Pressure
Alarm description (as shown on screen): Evap Press Low Cir N
Trigger: [Circuit State = Run AND Freezestat trip AND Low OAT Start not active]
OR Evaporator Press < Absolute Low Pressure Limit AND Circuit State = Run
The a
bsolute low pressure limit is 5 psi with R134a, R22, and R407C refrigerants and 20 psi with R410A
refrigerant.
Freezestat logic allows the circuit to run for varying times at low pressures. The lower the pressure, the
shorter the time the compressor can run. This time is calculated as follows:
[60 – 2.7 x freeze error] with R134a refrigerant, limited to a range of 20-60 seconds
[60 – 1.6 x freeze error] with R22 and R407C refrigerant, limited to a range of 20-60 seconds
[60 – freeze error] with R410A refrigerant, limited to a range of 20-60 seconds
OMM 1130-225
When the evaporator pressure goes below the Low Evaporator Pressure Unload set point, a timer starts.
If this timer exceeds the freeze time, then a ‘Evap Press Low Cir N’ alarm trip occurs. If the evaporator
pressure rises to the unload set point or higher, and the freeze time has not been exceeded, the timer will
reset.
Action T aken: Rapid stop circuit
Reset: This alarm can be cleared manually via the keypad if the evaporator pressure is above the absolute
low-pressure limit.
High Condenser Pressure
Alarm description (as shown on screen): Cond Press High Cir N
Trigger: Condenser Pressure > High Condenser Pressure Set Point
Action T aken: R apid stop circuit
Reset: This alarm can be cleared manually via the keypad.
Mechanical High Pressure/Motor Protect
Alarm description (as shown on screen): MHP or Motor Prot N
Trigger: MHP/MP input is low and over 150 seconds lapsed since controller boot-up
Action T aken: R apid stop circuit
Reset: This alarm can be cleared manually via the keypad if the MHP/MP input is high.
Phase Voltage Protection
Alarm description (as shown on screen): Phase/Voltage Cir N
Trigger: PVM input is low and Phase Voltage set point = enable.
Action T aken: R apid stop circuit
Reset: Auto reset when PVM input is high
Ground Fault Protection
Alarm description (as shown on screen): Ground Fault Cir N
Trigger: GFP input is low and Ground Fault set point = enable.
Action T aken: R apid stop circuit
Reset: This alarm can be cleared manually via the keypad.
Low OAT Restart Fault
Alarm description (as shown on screen): Low OAT Start Fail N
Trigger: Circuit has failed three low OAT start attempts
Action T aken: R apid stop circuit
Reset: This alarm can be cleared manually via the keypad.
Evaporator Water Freeze Protect
Alarm description (as shown on screen): Evap Water Freeze
Trigger: Evaporator LWT drops below evaporator freeze protect set point AND Unit State = Auto
Action T aken: R apid sto p all circu it s
Reset: This alarm can be cleared manually via the keypad or via the BAS clear alarm signal, but only if
the alarm trigger conditions no longer exist.
Leaving Evaporator Water Temperature Sensor Fault
Alarm description (as shown on screen): Evap LWT Sens Fault
Trigger: Sensor shorted or open
Action T aken: Normal stop all circuits
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.
Leaving Condenser Water Temperature Sensor Fault
Alarm description (as shown on screen): CondLWT Sens Fault
Trigger: Sensor shorted or open AND TGZ unit (refrig = R134a) AND operating in ‘heat’ mode.
26 WGZ030D through WGZ200D OMM 1130-2
Action T aken: Normal stop all circuits
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.
Suction Temperature Sensor Fault
Alarm description (as shown on screen): SuctT Sensor Fail N
Trigger: Sensor shorted or open AND Expansion Valve Type = Electronic
Action T aken: R apid stop circuit
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.
Evaporator Pressure Sensor Fault
Alarm description (as shown on screen): EvapP Sensor Fail N
Trigger: Sensor shorted or open. If failing high (open), logic has been added that requires the Leaving
Evaporator Temperature to be below 75°F. This will prevent nuisance trips due to conditions where the
evaporator water temperature is high which could cause false alarms.
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.
Condenser Pressure Sensor Fault
Alarm description (as shown on screen): CondP Sensor Fail N
Trigger: Sensor shorted or open
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.
Condenser Entering or Outdoor Air Temperature Sensor Fault
Alarm description (as shown on screen): OAT Sensor Fault
Trigger: Sensor shorted or open
Action T aken: Normal stop all circuits
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range
Evaporator Water Freeze Protect
Alarm description (as shown on screen): Evap Water Freeze
Trigger: Evaporator LWT drops below evaporator freeze protect set point AND Unit State = Auto
Action T aken: R apid sto p all circu it s
Reset: This alarm can be cleared manually via the keypad or via the BAS clear alarm signal, but only if
the alarm trigger conditions no longer exist.
No Pressure Change at Start
Alarm description (as shown on screen): NoPressChgAtStartN
Trigger: Circuit has failed twice on a No Pressure Change at Start Condition. A No Pressure Change at
Start Conditio n in d icates that after the start of the first compressor on the circuit, at least a 1 psi drop in
evaporator pressure OR a 1 psi increase in condenser pressure has not occurred after 15 seconds of
compressor operation.
Action T aken: R apid stop circuit
Reset: This alarm can be cleared manually via the keypad.
EXB Comm Failure on CP1
Alarm description (as shown on screen): No EXB comm CP1
Trigger: CP1 does not have communication with either EXB1 for 60 seconds after power up. This alarm
will only occur if 10 Fan , evaporator pump #2, or condenser pump #2 operation is selected. After
communication is established, when communication is lost to either EXB an immediate shutdown occurs.
Action T aken: R apid sto p all circu it s
Reset: Auto clear when EXB1 is communicating with CP1.
OMM 1130-227
Loading...
+ 61 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.