Daikin WGZ030DW, WGZ200DW, WGZ030DA, WGZ200DA Installation And Maintenance Manual

Installation and Maintenance Manual IM 1131-2
Water-Cooled Scroll Compressor Chiller
Group: Chillers
Part Number: IM1131-2
Date: June 2014
WGZ030DW - WGZ200DW, Packaged Water-Cooled Chillers
WGZ030DA - WGZ200DA, Condenserless Chillers
50/60 Hz
R-410A
© 2014 Daikin Applied
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Modbus
*AHRI Certification and ETL Listing apply to 60Hz models only
©2014 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice.
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pressure Drop Data . . . . . . . . . . . . . . . . . . . . . . . . 14
Dimensions - Packaged . . . . . . . . . . . . . . . . . . . . . 16
Dimensions - Condenserless . . . . . . . . . . . . . . . . 20
Lifting and Mounting Weights . . . . . . . . . . . . . . . . 25
Vibration Isolators . . . . . . . . . . . . . . . . . . . . . . . . . 28
Physical Data - Packaged Units . . . . . . . . . . . . . . 30
Physical Data - Units Less Condenser . . . . . . . . 33
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Start-Up and Shutdown . . . . . . . . . . . . . . . . . . . . 53
System Maintenance. . . . . . . . . . . . . . . . . . . . . . . 55
Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . 57
System Service . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Troubleshooting Chart . . . . . . . . . . . . . . . . . . . . . 59
Warranty Registration Form (Scroll) . . . . . . . . . . 60
Hazard Identification
DANGER
Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
Manufactured in an ISO Certified facility
Note: Cover photograph is an WGZ060-D. This manual covers WGZ-D vintage water-cooled scroll chillers.
2 IM 1131-2
Introduction
W G Z XXX D W
Water-Cooled
Global Design Scroll Compressor
Nominal Tons
Condenser
Design Vintage
W = Standard Packaged A = Less Condenser
Chiller Nomenclature
General Description
Daikin Applied WGZ water chillers are designed for indoor installations and are available with water-cooled condensers (Model WGZ-DW), or arranged for use with remote, air­cooled or evaporative condensers (Model WGZ-DA). Each water-cooled unit is completely assembled and factory wired before evacuation, charging and testing. They consist of hermetic scroll compressors, brazed-plate evaporators on Models WGZ 030 to 130 or shell-and-tube on Models WGZ 150 to 200, water-cooled condenser on Model WGZ-DW, and complete refrigerant piping.
Introduction
upon arrival. All shipping damage must be reported to the carrier and a claim must be filed with the carrier. The unit serial plate should be checked before unloading the unit to be sure that it agrees with the power supply available. Physical damage to unit after acceptance is not the responsibility of Daikin Applied.
Note: Unit lifting weights and Corner operating weightsare given in the weight tables beginning on page 25.
Units manufactured for use with remote condensers (Models WGZ-DA) have all refrigerant specialties factory-mounted and connection points for refrigerant discharge and liquid lines.
Liquid line components that are included are manual liquid line shutoff valves, charging valves, filter-driers, liquid line solenoid valves, sight glass/moisture indicators, and expansion valves. Other features include compressor crankcase heaters, and a MicroTech II microprocessor controller.
The electrical control center includes all equipment protection and operating controls necessary for dependable automatic operation. Optional unit-mounted disconnect switche(s) may not be present, inwhich case a field-supplied and installed, fused disconnect switch is required.
Inspection
When the equipment is received, all items should be carefully checked against the bill of lading to be sure of a complete shipment. All units must be carefully inspected for damage
Refrigerant Charge
Every model WGZ-DW water chiller with water-cooled condensers is shipped with a full refrigerant charge. For shipment, the charge is contained in the condenser and is isolated by the condenser liquid shutoff valve and the
compressor discharge valve common to a pair of compressors.
CAUTION
If the unit is damaged, allowing the refrigerant to escape, there can be danger of suffocation in the area since the refrigerant will displace the
air. Be sure to review Environmental Protection Agency (EPA)
requirements if damage occurs. Avoid exposing refrigerant to an open
flame.
A holding charge of nitrogen/helium is supplied in remote condenser models, WGZ-DA and must be removed prior to charging with refrigerant. The operating charge must be field
supplied and charged.
IM 1131-2 3
Installation
WG Z150-20 0C UNIT SHOWN
SPREADER BARS M UST
BE USED FOR STABILITY
DURING LIFTING OF
ALL SIZE UNITS
Remov ab le
Lifting
Ba r
(2) 2”
Lifting
Holes
Installation
Installation
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and
regulations, and experienced with this type of equipment.
CAUTION
Avoid contact with sharp edges. Personal injury can result
Location
WGZ chillers are intended only for installation in an indoor or weather protected area consistent with the NEMA 1 rating on the chiller, controls, and electrical panels. Equipment room temperature for operating and standby conditions is 40°F to 122°F (4.4°C to 50°C).
Because of the electrical control devices, the units should not be exposed to the weather. A plastic cover over the control box is supplied as temporary protection during shipment. A reasonably level and sufficiently strong floor is required for the water chiller. If necessary, additional structural members should be provided to transfer the weight of the unit to the nearest beams.
Space Requirements for Connections and Servicing
The chilled water and condenser water (on units with a water­cooled condenser) piping enters and leaves the unit from the right side when looking at the control panel. Left-hand condenser connections are an option. A clearance of at least 3 feet (1219 mm), or more if codes require, should be provided beyond this piping and on all other sides and ends of the unit for general servicing or for changing the compressors, if it ever becomes necessary. Allow a minimum of 4-foot clearance in front of the control panel or as required by the NEC or local codes.
On units equipped with a water-cooled condenser (Type WGZ­DW) clearance should also be provided for cleaning or removal of condenser tubes on one end of the unit. The clearance for cleaning depends on the type of apparatus used, but can be as much as the length of the condenser (10 feet, 3050 mm). Tube replacement requires the length of the condenser (as much as 12 feet) plus three feet of workspace.
Figure 1: Lifting the Unit
This space can often be provided through a doorway or other opening.
Moving the Unit
Refer to Lifting/Mounting weights beginning on page 25.
The packaged unit skid option is strongly recommended for ease of handling and to help prevent damage if a crane is not available for rigging at site. Properly designed field supplied skids or dollies are acceptable. Do not push unit along a floor without them. The condenserless models (AGZ-DA) are manufactured with a base suitable for moving with rollers.
All moving and handling of packaged units (Figure 1) must be performed with skids or dollies under the unit and they should not be removed until the unit is in the final location. Never put the weight of the unit against the control box.
In moving, always apply pressure to the base on the skids only and not to the piping or other components. A long bar will help move the unit. Avoid dropping the unit at the end of the roll.
If the unit must be hoisted, lift the unit from the removable lifting arms factory-bolted to each end of the unit adjacent to the tube sheet by attaching cables or chains to the end of the arms. A spreader bar must be used to protect the piping, control panel and other areas of the chiller (Figure 1). The lifting arms should be removed and discarded after use.
Do not attach slings to piping or equipment. Do not attempt to lift the unit by lifting points mounted on the compressors. They are for lifting only the compressor should one need to be removed from the unit. Move unit in the upright horizontal position at all times. Set unit down gently when lowering from the truck or rollers.
Placing the Unit
The small amount of vibration normally encountered makes this unit particularly desirable for basement or ground floor installations where the unit can be mounted directly to the floor. The floor construction should be such that the unit will not affect the building structure, or transmit noise and vibration into the structure.
4 IM 1131-2
Water Pipin g
Chilled
Wat er
LW T
T
Legend:
Temperat ure Sensor
Pressure Transduc er
Pressure (High Pressure Cutout)
Temperat aure Sensor, Leaving Chilled Water Control
T
T
T
P
P
1
LWT
Relief Valv e
Schrader Fitting
Thermal Expansion
Sight Glass / Moistu
Charging Valve
T
S
F-D Filter-Drier
Angle Valv e
Ball Valv e
NOTE: Standard condenser connections are on the control panel end.
Unit Configuration
WGZ 030DW to 130DW have two refrigerant circuits, two tandem scroll compressors (total of four), a single two­circuited brazed plate evaporator, a single two-circuited water-
cooled condenser, interconnecting refrigerant piping and a control panel with associated sensors and transducers. Models WGZ 150DW to 200DW have two trio-compressors (total of
6) and a shell-and-tube evaporator.
Figure 1: Schematic Piping Diagram (One of Two Circuits for Brazed Plate Evaporators)
Water Piping
Evaporator
1
Comp
#1
SP
Com p
#2
Condenser
Water
T
S
T
P
CV
Condenser
S
S
F-D
S
Valve
re In dicator
CV
Solenoid Valve
Install Vessel Drain Plugs at Start-up
Condensers are drained of water in the factory and are shipped with the condenser drain plugs in the heads removed and stored in a bag in the control panel. Be sure to replace plugs prior to filling the vessel with fluid.
General Piping Guidelines
Due to the variety of piping practices, it is advisable to follow the recommendations of local authorities for code compliance. They can supply the installer with the proper building and safety codes required for a safe and proper installation.
The piping should be designed with a minimum number of bends and changes in elevation to keep system cost down and performance up. Other piping design considerations include:
1 All piping should be installed and supported to prevent
the chiller connections from bearing any strain or weight of the system piping.
2 Vibration eliminators to reduce vibration and noise
transmission to the building.
3 Shutoff valves to isolate the unit from the piping system
during unit servicing.
4 Do not use PVC or CPVC piping for any water lines.
IM 1131-2 5
Water Piping
5 Manual or automatic air vent valves at the high points of
the system. Drains should be placed at the lowest points in the system.
6 On units with factory-mounted flow switches and where
flange connections (Victaulic-to-flange adaptors or weld­on flanges) are to be used, relocating the flow switch is required to allow for possible future replacement since the flange will interfere with unscrewing the switch. The following is recommended, before installing a flange, to avoid interference 1) Remove the flow switch before and plug the switch opening in the nozzle. 2) Install the Victaulic-to-flange adaptor or weld on flange.
3)Relocate the flow switch in the water piping outside the flange, close enough to it that the wire leads will reach and the switch can still be unscrewed.
7 Some means of maintaining adequate system water
pressure (e.g., expansion tank or regulating valve).
8 Temperature and pressure indicators located within 3 feet
(0.9 meters) of the inlet and outlet of the vessels to aid in unit servicing.
9 This product is equipped with a copper-brazed 304 series
stainless steel evaporator plate or a shell and tube evaporator with carbon steel shell and copper tubes. The water or other fluid used in these evaporators must be clean and non-corrosive to the materials used in the evaporator. The use of non-compatible fluids can void the equipment warranty. If the compatibility of the fluid with the evaporator is in question, a professional water quality consultant should administer the proper testing and evaluate compatibility
10 A strainer or some means of removing foreign matter
from the water before it enters the pump is recommended. It should be placed far enough upstream to prevent cavitation at the pump inlet (consult pump
manufacturer for recommendations). The use of a strainer will prolong pump life and thus maintain system performance.
11 A cleanable perforated basket strainer must also be
placed in the water line just prior to the inlet of the evaporator. On Models WGZ 030 to 130, use 0.062-inch perforations with 41% open area. On WGZ 150 TO 200 use 0.125-inch perforations with 40% open area. This will aid in preventing foreign material from entering and decreasing the performance of the evaporator.
12 If the unit is used as a replacement chiller on a
previously existing piping system, the system should be thoroughly flushed prior to unit installation. Regular water analysis and chemical water treatment on the evaporator and condenser is recommended immediately upon equipment start-up.
13 In the event glycol is added to the water system, as an
afterthought for freeze protection, recognize that the refrigerant suction pressure will be lower, cooling performance less, and water side pressure drop will be higher. If the percentage of glycol is large, or if propylene glycol is used instead of ethylene glycol, the added pressure drop and loss of performance could be substantial. Reset the freezestat and low leaving water alarm temperatures. The freezestat is factory set to default at 36°F (2.2°C). Reset the freezestat setting to approximately 4° to 5°F (2.3° to 2.8°C) below the leaving chilled water setpoint temperature. See the section titled "Glycol Solutions" for additional information concerning the use of glycol.
14 A preliminary leak check of the water piping should be
made before filling the system.
Note: A water flow switch or pressure differential switch
must be mounted in the evaporator outlet water line to signal that there is water flow before unit will start.
Figure 2: Typical Evaporator Field Water Piping (WGZ030 - WGZ130)
6 IM 1131-2
Figure 3: Typical Evaporator Field Water Piping (WGZ150 - WGZ200)
Gate
Wa te r
Strainer
Eliminator
Pressure
Protec t All Field Piping
A
Flow
Eliminator
Flow
Switch
Gate
Suc ti on
Vent
Out
Liquid
Drain
In
Vib ra ti o n
Valved
Gau ge
Vibration
Balancing
Valve
Valve
Valve
Flow
Water Piping
gainst Freezing
System Water Volume
It is important to have adequate water volume in the system to provide an opportunity for the chiller to sense a load change, adjust to the change, and then stabilize. The system water volume is the total amount of water in the evaporator, air handling equipment, and associated piping. As the expected load change becomes more rapid, a greater water volume is needed. If the water volume is too low, operational problems can occur including rapid compressor cycling, rapid loading and unloading of compressors, erratic refrigerant flow in the chiller, improper motor cooling, shortened equipment life and other undesirable occurrences.
For normal comfort cooling applications where the cooling load changes relatively slowly, a minimum system volume of two to three minutes times the flow rate (GPM) is recommended. For example, if the design chiller flow rate is 120 gpm, we recommend a system volume of 240 to 360 gallons.
For process applications where the cooling load can change rapidly, additional system water volume is needed. A process example would be the quenching of hot metal objects. The load would be very stable until the hot metal is dipped into the water tank. Then, the load would increase drastically.
Since there are many other factors that can influence performance, systems can successfully operate below these suggestions. But as the water volume decreases below these guidelines, the possibility of system instability increases.
Variable Chilled Water Flow
Reducing chilled water flow in proportion to load can reduce total system power consumption. Certain restrictions apply to the amount and rate of flow change. The rate of flow change should be a maximum of 10 percent of the change, per minute. Do not reduce flow lower than the part load minimum flows listed on page 14 or page 15.
Chilled Water Piping
The system water piping must be flushed thoroughly prior to making connections to the unit evaporator. It is required that a 40-mesh strainer be installed in the return water line before the
inlet to the chiller. Lay out the water piping so the chilled water circulating pump discharges into the evaporator inlet.
The return water line must be piped to the evaporator inlet connection and the supply water line must be piped to the evaporator outlet connection. If the evaporator water is piped in the reverse direction, a substantial decrease in capacity and efficiency of the unit will be experienced.
A flow switch must be installed in the horizontal piping of the supply (evaporator outlet) water line to prove water flow before starting the unit.
Drain connections should be provided at all low points in the system to permit complete drainage of the system. Air vents should be located at the high points in the system to purge air out of the system. The evaporators are not equipped with vent or drain connections and provision must be made in the entering and leaving chilled water piping for venting and draining.
Pressure gauges should be installed in the inlet and outlet water lines to the evaporator. Pressure drop through the evaporator should be measured to determine water flow from the flow/pressure drop curves beginning on page 14. Vibration eliminators are recommended in both the supply and return water lines.
Chilled water piping should be insulated to reduce heat loss and prevent condensation. Complete unit and system leak tests should be performed prior to insulating the water piping. Insulation with a vapor barrier would be the recommended type of insulation. If the vessel is insulated, the vent and drain connections must extend beyond the proposed insulation thickness for accessibility.
Chillers not run in the winter should have their water systems thoroughly drained if subject to sub-freezing temperatures. If the chiller operates year-round, or if the system is not drained for the winter, the chilled water piping exposed to sub-freezing ambient temperatures should be protected against freezing by wrapping the lines with a heater cable. In addition, an adequate percentage of glycol should be added to the system to further protect the system during low ambient temperature periods. It should be noted that water piping that has been left drained is
IM 1131-2 7
Water Piping
Su cti on
Li qui d
Li qui d
Water Sensor
subject to more corrosion than if filled with water. Use of a Vapor Corrosion Inhibitor (VCI) or some other protection should be considered.
Figure 4: Thermostat Well Location, WGZ 030 - 130
Su cti on Circuit #1
Circuit #2
Leaving Chilled
Circuit #2
Circuit #1
The chilled water sensor is factory installed in the leaving water connection on the evaporator. Care should be taken not to damage the sensor cable or lead wires when working around the unit. It is also advisable to check the lead wire before running the unit to be sure that it is firmly anchored and not rubbing on the frame or any other component. If the sensor is ever removed from the well for servicing, care must be taken to not wipe off the heat-conducting compound supplied in the
well.
CAUTION
The thermostat bulb should not be exposed to water
temperatures above 125°F (51.7°C) as this will damage it.
Flow Switch
A water flow switch must be mounted in the leaving evaporator and condenser water lines to prove adequate water flow before the unit can start. This will safeguard against slugging the compressors on start-up. It also serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze-up. Factory-mounted and wired evaporator and condenser flow switches are available as an option
If the optional factory flow switch is not supplied, a flow switch is available from Daikin Applied under part number
01750330. It is a "paddle" type switch and adaptable to any pipe size from 1 in. (25 mm) to 6 in. (152 mm) nominal. Certain flow rates are required to open the switch and are listed in Table 1. Wire from switch terminals Y and R to panel terminals 33 and 43 (chilled water) and 41 and 53 (condenser water). There is also a set of normally closed contacts on the switch that could be used for an indicator light or an alarm to indicate when a "no flow" condition exists.
1 Apply pipe sealing compound to only the threads of the
switch and screw unit into 1 in. (25 mm) reducing tee. The flow arrow must be pointed in the correct direction.
2 Piping should provide a straight length before and after
the flow switch of at least five times the pipe diameter without any valves, elbows, or other flow restricting
elements.
Make sure the arrow on the side of the switch is pointed in the direction of flow. The flow switch is designed to handle
the control voltage and should be connected according to
CAUTION
the wiring diagram.
Table 1: Paddle-Type Flow Switch Flow Rates
Pipe Size
NOTES (x)
Min.
Adjst.
Max.
Adjst.
Note (1): A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose. Note (2): Flow rates for a 2-inch paddle trimmed to fit the pipe. Note (3): Flow rates for a 3-inch paddle trimmed to fit the pipe. Note (4): Flow rates for a 3-inch paddle. Note (5): Flow rates for a 6-inch paddle.
Flow
No Flow
Flow
No Flow
inch 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8
mm 32 (2) 38 (2) 51 63 (3) 76 102 (4) 127 (4) 153 (4) 204 (5) gpm 5.8 7.5 13.7 18.0 27.5 65.0 125.0 190.0 205.0 Lpm 1.3 1.7 3.1 4.1 6.2 14.8 28.4 43.2 46.6 gpm 3.7 5.0 9.5 12.5 19.0 50.0 101.0 158.0 170.0 Lpm 0.8 1.1 2.2 2.8 4.3 11.4 22.9 35.9 38.6 gpm 13.3 19.2 29.0 34.5 53.0 128.0 245.0 375.0 415.0 Lpm 3.0 4.4 6.6 7.8 12.0 29.1 55.6 85.2 94.35455 gpm 12.5 18.0 27.0 32.0 50.0 122.0 235.0 360.0 400.0 Lpm 2.8 4.1 6.1 7.3 11.4 27.7 53.4 81.8 90.8
8 IM 1131-2
Water Piping
TablesFromGCorrectionFlowx
T
CapacityGlycolx
GPMGlycol
=
24
TablesfromGCorrectionFlowx
Tx
kW
LpsGlycol
Δ
=
18.4
° F ° C
10%
25.0 -3.9 0.997 0.999 1.030 1.113
20%
18.0 -7.8 0.993 0.997 1.060 1.226
30%
7.0 -14.0 0.987 0.995 1.092 1.369
40%
-7.0 -22.0 0.980 0.992 1.132 1.557
50%
-28.0 0.973 0.991 1.182 1.791
Flo w
"G"PD"P"
% E.G.
Freeze Point Capacity
"C"
Pow e r
"K"
° F ° C
10%
25.0 -3.9 0.994 0.998 1.016 1.106
20%
19.0 -7.2 0.987 0.995 1.032 1.211
30%
9.0 -13.0 0.978 0.992 1.057 1.380
40%
-5.0 - 21.0 0.964 0.987 1.092 1.703
50%
-27.0 -32.8 0.952 0.983 1.140 2.250
Fl ow
"G"PD"P"
% P. G.
Fre e ze Point Capacit y
"C"
Pow e r
"K"
Circuit #1
Outlet
Condenser
Control
Valve
Wa t er
Out let
Circuit #1
Inlet
Inlet
Glycol Solutions
Table 2: Ethylene Glycol Correction Factors
CAUTION
Do not use automotive antifreeze. Industrial glycols must be used.
Automotive antifreeze contains inhibitors that causes plating on
copper tubes. The type and handling of glycol used must be
consistent with local codes.
WGZ units are designed to operate with a leaving chilled fluid
Table 3: Propylene Glycol Correction Factors
temperature from 15°F (-9.4°C) to 60°F (16°C). Leaving chilled fluid temperatures below 40°F (4.6°C) result in suction temperatures at or below the freezing point of water and a glycol anti-freeze solution is required. The use of glycol in the evaporator will reduce the performance of the unit. The reduction in performance depends upon the glycol concentration and temperature. This should be taken into consideration during initial system design. Glycol in the condenser will have a negligible effect on performance because glycol at these higher temperatures will perform with characteristics similar to water.
Daikin Applied recommends a minimum concentration of 25% be provided on all glycol applications. Glycol concentrations below 25% are too diluted for long-term corrosion protection of ferrous metals and corrosion inhibitors need to be recalculated and possibly added to the system.
Chiller capacity, flow rate, evaporator pressure drop, and power input for glycol solutions can be calculated using the following formulas and reference to Tab le 2 for ethylene glycol and Table 3 for propylene glycol. Test coolant with a clean, accurate, glycol solution hydrometer (similar to that found in service stations) to determine the freezing point.
Note: Ethylene and propylene glycol ratings are outside the
scope of AHRI Standard 550/590 certification program.
Capacity is reduced compared to that with plain water. To find the reduced value, multiply the chiller's capacity when using water by the capacity correction factor C to find the chiller's capacity when using glycol.
Flow -To determine evaporator gpm (or T) knowing T (or gpm) and capacity:
Δ
For Metric Applications -- Determine evaporator lps (or T) knowing T (or lps) and kW:
Condenser Water Piping
Arrange the condenser water so the water enters the bottom connection of the condenser. The condenser water will discharge from the top connection. Failing to arrange the condenser water as stated above will negatively affect the capacity and efficiency.
Install pressure gauges in the inlet and outlet water lines to the condenser. Pressure drop through the condenser should be measured to determine flow on the pressure drop/flow curves beginning on page 14. Vibration eliminators are recommended in both the supply and return water lines. Install a 20-mesh strainer in the inlet piping to the condenser.
Water-cooled condensers can be piped for use with cooling towers, well water, or heat recovery applications. Cooling tower applications must be made with consideration of freeze protection and scaling problems. Contact the cooling tower manufacturer for equipment characteristics and limitations for the specific application. Head pressure control must be provided if the entering condenser water can fall below 60°F. The WGZ condenser has two refrigerant circuits with a common condenser water circuit. This arrangement makes head pressure control with discharge pressure actuated control valves difficult.
If the tower water temperature cannot be maintained at a 60°F minimum, or when pond, lake, or well water that can fall below 60°F (15°C) is used as the condensing medium, special discharge pressure control must be used. A water recirculating system with recirculating pump as shown in Figure 6 is recommended. This system also has the advantage of maintaining tube velocity to help prevent tube fouling. The
Pressure Drop - To determine glycol pressure drop through the cooler, enter the water pressure drop graph on page 14 at the actual glycol flow. Multiply the water pressure drop found there by P to obtain corrected glycol pressure drop.
Power -To determine glycol system kW, multiply the water
pump must cycle with the chiller.
Figure 5: Recirculating Discharge Water System
Cir cui t #2
Temp e r a t ur e
system kW by factor K.
Condenser
IM 1131-2 9
Cir cui t #2
Refrigerant Piping
Refrigerant Piping
Refrigerant Piping
Refrigerant piping, to and from the unit, should be sized and installed according to the latest ASHRAE Handbook. It is important that the unit piping be properly supported with sound and vibration isolation between tubing and hanger, and that the discharge lines be looped at the condenser and trapped at the compressor to prevent refrigerant and oil from draining into the compressors. Looping the discharge line also provides greater line flexibility.
NOTE: Do not install any refrigerant piping underground.
The discharge gas valves, liquid line solenoids, filter-driers, moisture indicators, and expansion valves are all factory mounted as standard equipment with the water chiller.
For remote condenser application (WGZ-DA) such as air­cooled or evaporative condenser, the chillers are shipped with a nitrogen/helium holding charge. The unit is evacuated in the factory to 500 microns before charging with the nitrogen.
The liquid line has a shutoff valve upstream from the liquid line solenoid valve and a copper tube cap to be brazed on this line after test to seal this line for shipment.
The discharge line has a ball valve installed between the compressor and the discharge stub tube with a copper tube cap brazed on the line after test to seal it for shipment.
The discharge gas valves, liquid line solenoids, filter-driers, moisture indicators, and expansion valves are all factory-
mounted as standard equipment with the water chiller.
DANGER
Do not apply heat, such as a brazing torch, to a sealed unit, vessel, or component. Internal gases can increase the internal pressure and cause a life-threatening explosion. Open the system when heating. The short line between a valve and brazed end cap can be drilled to vent it. Note that the valve may leak and the entire unit charge may be open to the cap.
It is important that the unit be kept tightly closed until the remote condenser is installed, piped to the unit and the high side evacuated.
When the field piping has been leak tested, evacuated, and is ready to charge, the unit valves can be opened and the system is ready to pressure test, evacuate and charge the entire system together at one time.
After the equipment is properly installed, leak tested, and evacuated, it can be charged with R-410A, and run at design load conditions. Add charge until the liquid line sight glass is clear, with no bubbles flowing to the expansion valve. Total operating charge will depend on the air-cooled condenser used and volume of the refrigerant piping.
NOTE: On WGZ-DA units (units with remote condensers), the installer is required to record the refrigerant charge by stamping the total charge and the charge per circuit on the serial plate in the appropriate blocks provided for this purpose.
Discharge lines must be designed to handle oil properly and to protect the compressor from damage that can result from condensing liquid refrigerant in the line during shutdown. Total friction loss for discharge lines of 3 to 6 psi (20.7 to 41.4 kPa) is considered good design. Careful consideration must be given for sizing each section of piping to insure that gas velocities are sufficient at all operating conditions to carry oil. If the velocity in a vertical discharge riser is too low, considerable oil can collect in the riser and the horizontal header, causing the compressor to lose its oil and result in damage due to lack of lubrication. When the compressor load is increased, the oil that had collected during reduced loads can be carried as a slug through the system and back to the compressor, where a sudden increase of oil concentration can cause liquid slugging and damage to the compressor.
Any horizontal run of discharge piping should be pitched away from the compressor approximately 1/8 inch (6.4 mm) per foot (meter) or more. This is necessary to move, by gravity, any oil lying in the header. Oil pockets must be avoided because oil needed in the compressor would collect at such points and the compressor crankcase can become starved.
It is recommended that any discharge lines coming into a horizontal discharge header rise above the centerline of the discharge header. This is necessary to prevent any oil or condensed liquid from draining to the compressor heads when the compressor is not running.
In designing liquid lines, it is important that the liquid reach the expansion valve without flash gas since this gas will reduce the capacity of the valve. Because "flashing" can be caused by a pressure drop in the liquid line, the pressure losses due to friction and changes in static head should be kept to a minimum.
A check valve must be installed in the liquid line in all applications where the ambient temperature can drop below the equipment room temperature. This prevents liquid migration to the condenser, helps maintain a supply of refrigerant in the liquid line for initial start-up, and keeps liquid line pressure high enough on "off" cycle to keep the expansion valve closed.
On systems as described above, a relief valve or relief-type check valve, must be used in the liquid line as shown in piping systems (shown in and Its purpose is to relieve dangerous hydraulic pressures that could be created as cool liquid refrigerant trapped in the line between the check valve and the expansion or shutoff valve warms up. Install a relief device in the hot gas piping at the condenser coil as shown in Figure 7 and Figure 8. Install a discharge check valve in the discharge line, in a horizontal run, close to the condenser.
10 IM 1131-2
Recommended Line Sizing for Field Piping
Fitting Type 7/8" 1 1/8" 1 3/8" 1 5/8" 2 1/8" 2 5/8" 3 1/8"
90º Standar d
2.0 2.6 3.3 4.0 5.0 6.0 7.5
90º Long Radius
1.4 1.7 2.3 2.6 3.3 4.1 5.0
90º Str ee t
3.2 4.1 5.6 6.3 8.2 10.0 12. 0
45º Standar d
0.9 1.3 1.7 2.1 2.6 3.2 4.0
45º Str ee t
1.5 2.1 3.0 3.4 4.5 5.2 6.4
180º Be n d
3.2 4.1 5.6 6.3 8.2 10.0 12. 0
Full Size
1.4 1.7 2.3 2.6 3.3 4.1 5.0
Re ducing
2.0 2.6 3.3 4.0 5.0 6.0 7.5
Globe Valve, Open
22.0 29.0 38.0 43.0 55.0 69.0 84.0
Gat e V alve , Op e n
0.9 1.0 1.5 1.8 2.3 2.8 3.2
Angle Valve, Open
9.0 12.0 15.0 18.0 24.0 29.0 35.0
Valves
El b o w s
Tees
Unit Size WGZ030 WGZ035 WGZ040 WGZ 045 WGZ050 WGZ055 WGZ060 WGZ070 WGZ080 WGZ090
Line Size (in.)
1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8
Unit Size WGZ100 WGZ115 WGZ130 WGZ 150 WGZ170 WGZ200
Line Size (in.)
2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8
Up to Up to Up to Up to Up to
50 Equiv. Ft 75 Equiv. Ft 100 Equiv. Ft 125 Equiv. Ft 150 Equiv. Ft
WGZ030
7/8" 7/8 " 7/8 " 7/8 " 7/8 " 7/8 "
WGZ035
7/8" 7/8 " 7/8 " 7/8 " 7/8 " 1 1/8 "
WGZ040
7/8" 7/8 " 7/8 " 7/8 " 1 1/8 " 1 1/8 "
WGZ045
7/8" 7/8 " 7/8 " 7/8 " 1 1/8 " 1 1/8 "
WGZ050
7/8" 7/8 " 7/8 " 7/8 " 1 1/8 " 1 1/8 "
WGZ055
7/8" 7/8 " 7/8 " 1 1/8” 1 1/8 " 1 1/8 "
WGZ060
7/8" 7/8 “ 7/8 " 1 1/8 " 1 1/8 " 1 1/8 "
WGZ070
1 1/8” 1 1/8” 1 1/8 " 1 1/8 " 1 1/8 " 1 1/8”
WGZ080
1 1/8” 1 1/8 " 1 1/8 " 1 1/8” 1 1/8” 1 1/8”
WGZ090
1 1/8” 1 1/8 " 1 1/8 " 1 1/8” 1 1/8” 1 1/8”
WGZ100
1 1/8” 1 1/8 " 1 1/8 " 1 1/8” 1 1/8” 1 1/8”
WGZ115
1 1/8” 1 1/8 " 1 1/8 " 1 1/8” 1 3/8” 1 3/8”
WGZ130
1 1/8” 1 1/8 " 1 3/8” 1 1/8” 1 3/8” 1 3/8”
WGZ150
1 3/8” 1 3/8” 1 1/8 " 1 3/8” 1 3/8” 1 3/8”
WGZ170
1 3/8” 1 3/8” 1 1/8 " 1 3/8” 1 3/8” 1 3/8”
WGZ- 200
1 3/8” 1 3/8” 1 1/8 " 1 3/8” 1 3/8” 1 3/8”
Unit Mode l
Recommende d Liquid Line Size (in.)
Conn. Size
at Unit
Final design should be based on ASHRAE design standards.
Table 1: Equivalent Feet for Fittings
Table 2: Maximum Line Size for Oil Carry Up a Discharge Riser, R-410A
Refrigerant Piping
Table 3: Recommended Liquid Line Size, R-410A
IM 1131-2 11
Refrigerant Piping
Up t o Up to Up t o Up t o Up t o
50 Eq uiv. Ft 75 Equiv. Ft 100 Equiv. Ft 125 Equiv. Ft 150 Equiv. Ft
WGZ030
1 3/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8" 1 1/8"
WGZ035
1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"
WGZ040
1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"
WGZ045
1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"
WGZ050
1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"
WGZ055
1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8" 1 3/8"
WGZ060
1 3/8" 1 3/8" 1 5/8” 1 5/8” 1 5/8” 1 5/8”
WGZ070
1 3/8" 1 3/8" 1 5/8” 1 5/8” 1 5/8” 1 5/8”
WGZ080
1 5/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8”
WGZ090
1 5/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8”
WGZ100
1 5/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8” 1 5/8”
WGZ115
1 5/8” 1 5/8” 1 5/8” 2 1/8" 2 1/8" 2 1/8"
WGZ130
1 5/8” 1 5/8” 2 1/8" 2 1/8" 2 1/8" 2 1/8"
WGZ150
2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8"
WGZ170
2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8"
WGZ200
2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 1/8" 2 5/8"
Re comme nded Dis charge Line Sizes
Conn. Size
at Unit
Unit Mo de l
Condenser
Relief Valve
Check Valve
Purge Valve
Discharge Line
Loop
Receiver
Bypass
To
Evap.
Preferred Subcooler Hook-up
Reli ef Valve
of Liquid Line Check Valve)
Pi
tc
h
Check Valve
Table 4: Recommended Horizontal or Downflow Discharge Line Size, R-410A
Typical Arrangements
Figure 7 illustrates a typical piping arrangement involving a
remote air-cooled condenser located at a higher elevation than the compressor and receiver. This arrangement is commonly encountered when the air-cooled condenser is on a roof and the compressor and receiver are on grade level or in a basement equipment room.
Figure 8 illustrates another very common application where
the air-cooled condenser is located on essentially the same level as the compressor and receiver. The discharge line piping in this case is not too critical. The principal problem encountered with this arrangement is that there is frequently
Figure 1: Condenser Above Compressor and Optional Receiver Installation
(Vent to Outdoors or to Condenser Side
12 IM 1131-2
Subcoo ler
eceiver
insufficient vertical distance to allow free drainage of liquid refrigerant from the condenser coil to the receiver.
Notice, in both illustrations, that the hot gas discharge line is looped at the bottom and top of the vertical run. This is done to prevent oil and condensed refrigerant from flowing back into the compressor and causing damage. The highest point in the discharge line should always be above the highest point in the condenser coil. It is advisable to include a purging vent at this point to extract non-condensables from the system.
The receiver is used when it is desired to have refrigerant storage capacity in addition to the pumpdown capability of the condenser.
Figure 2: Condenser and Compressor on Same Level, Optional Receiver Installation
Con denser
Relief Va lve
Check Valve
Purge V alve
(V e nt t o O u td oo rs or to Condens er Side of Liquid Line Check Valve)
P
c
h
Check
r
Receiver
Bypass
To
Preferred Subcooler Ho ok -up
Check
Note:
The receiver is bypassed during normal operation.
Dis charge Line
it
Refrigerant Piping
Receiver notes:
Factory-Mounted Condenser
Units with the standard water-cooled, factory-mounted condenser are provided with complete refrigerant piping and full operating refrigerant charge at the factory.
There is a remote possibility on water-cooled units utilizing low temperature pond or river water as a condensing medium, and if the water valves leak, that the condenser and liquid line refrigerant temperature could drop below the equipment room temperature on the "off" cycle. This problem only arises during periods when cold water continues to circulate through the condenser and the unit remains off due to satisfied cooling load.
If this condition occurs cycle the condenser pump off with the unit or check the liquid line solenoid valve for proper operation.
Relief Valve Piping
The ANSI/ASHRAE Standard 15, Safety Standard for Refrigeration Systems, specifies that pressure relief valves on vessels containing Group 1 refrigerant (R-410A) "shall discharge to the atmosphere at a location not less than 15 feet (4.6 meters) above the adjoining ground level and not less than 20 feet (6.1 meters) from any window, ventilation opening or exit in any building." The piping must be provided with a rain cap at the outside terminating point and with a drain at the low point on the vent piping to prevent water buildup on the
IM 1131-2 13
Valve
Valve
Relief Valve
Subcooler
Evap.
Re ceive
1 The arrangement shown is required if the system
refrigerant charge exceeds the condenser coil pumpdown capacity.
2 This arrangement is used for head pressure control by
adding a back-flooding valve.
3 When a receiver is not required, the piping from the
condenser outlet to the subcooler inlet is omitted. Flow is from the subcooling coil directly to the evaporator.
atmospheric side of the relief valve. Also, a flexible pipe section should be installed in the line to eliminate any piping stress on the relief valve(s).
The size of the discharge pipe from the pressure relief valve should not be less than the size of the pressure relief outlet (5/8 in. flare). See Figure 9 for pipe size when combining low side relief on compressor suction with the condenser relief valve.
NOTE: Fittings should be provided to permit vent piping to be easily disconnected for inspection or replacement of the relief valve.
Figure 3: Relief Valve Piping
The relief valve setting is 450 psi (3100 kPa) for water cooled and 600 psi (4175 kPa) for air-cooled applications.
Pressure Drop Data
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
I
I
JJK
K
L
L
M
M
N
N
O
O
P
P
A
1
10
100
10 100 1000
Flow Rate (gpm)
Dp (ft)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
GPM Ft L/S kPa GPM Ft L/S kPa GPM Ft L/S kPa
WGZ030D A
56.3 2.6 3.5 7.7 90.0 6.3 5.6 18.8 150.0 16.6 9.4 49.7
WGZ035D B
64.9 3.6 4.1 10.8 103.8 8.8 6.5 26.3 173.0 23.2 10.8 69.4
WGZ040D C
76.3 2.9 4.8 8.6 122.1 7.0 7.6 20.9 203.5 18.5 12.7 55.2
WGZ045D D
85.3 3.9 5.3 11.6 136.5 9.5 8.5 28.4 227.5 25.1 14.2 74.9
WGZ050D E
96.4 3.0 6.0 9.1 154.2 7.4 9.6 22.1 257.0 19.5 16.1 58.4
WGZ055D F
105.8 4.1 6.6 12.1 169.2 9.9 10.6 29.6 282.0 26.1 17.6 78.1
WGZ060D G
113.4 5.2 7.1 15.4 181.5 12.6 11.3 37.7 302.5 33.3 18.9 99.4
WGZ070D H
131.6 4.3 8.2 12.8 210.6 10.5 13.2 31.4 351.0 27.7 21.9 82.8
WGZ080D I
146.8 3.9 9.2 11.6 234.9 9.5 14.7 28.4 391.5 25.1 24.5 74.9
WGZ090D J
163.3 3.8 10.2 11.3 261.3 9.2 16.3 27.5 435.5 24.3 27.2 72.6
WGZ100D K
183.4 3.8 11.5 11.3 293.4 9.2 18.3 27.5 489.0 24.3 30.6 72.6
WGZ115D L
237.6 5.0 14.8 15.1 380.1 12.3 23.8 36.8 633.5 32.5 39.6 97.0
WGZ130D M
237.6 6.6 14.8 19.8 380.1 16.2 23.8 48.4 633.5 42.8 39.6 127.8
WGZ150D N
277.9 6.5 17.4 19.3 444.6 15.8 27.8 47.2 741.0 41.7 46.3 124.7
WGZ170D O
317.4 5.7 19.8 17.1 507.9 14.0 31.7 41.8 846.5 37.0 52.9 110.5
WGZ200D P
352.7 7.7 22.0 23.0 564.3 18.8 35.3 56.2 940.5 49.6 58.8 148.3
Curve
Ref
Model
Inch-Pound S.I.
Minimum Flow & Pr. Drop Nominal Flow & Pr. Drop
Inch-Pound Inch-PoundS.I. S.I.
Pressure Drop Data
Figure 1: WGZ-D Condenser Pressure Drop Curves
Table 1: WGZ-D CondenserPressure Drop Data
14 IM 1131-2
Max imum Flow & Pr. Drop
Figure 2: WGZ-D Evaporator Pressure Drop Curves
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
I
I
J
J
K
K
L
L
M
M
N
N
O
O
P
P
A
1
10
100
10 100 1000
Flow Rate (gpm)
Dp (ft)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
GPM Ft L/S kPa GPM Ft L/S kPa GPM Ft L/S kPa
WGZ030D A
45.0 4.9 2.8 14.7 72.0 12.0 4.5 35.9 120.0 31.7 7.5 94.7
WGZ035D B
51.9 5.4 3.2 16.3 83.0 13.3 5.2 39.8 138.3 35.1 8.6 104.9
WGZ040D C
61.1 6.3 3.8 19.0 97.7 15.5 6.1 46.3 162.8 40.9 10.2 122.3
WGZ045D D
68.3 6.0 4.3 18.0 109.2 14.7 6.8 43.9 182.0 38.8 11.4 116.0
WGZ050D E
77.1 6.1 4.8 18.2 123.4 14.9 7.7 44.5 205.7 39.3 12.9 117.6
WGZ055D F
84.6 6.5 5.3 19.3 135.4 15.8 8.5 47.2 225.7 41.7 14.1 124.7
WGZ060D G
90.8 5.9 5.7 17.7 145.2 14.5 9.1 43.3 242.0 38.3 15.1 114.4
WGZ070D H
105.3 6.5 6.6 19.3 168.5 15.8 10.5 47.2 280.8 41.7 17.6 124.7
WGZ080D I
117.4 4.9 7.3 14.7 187.9 12.0 11.7 35.9 313.2 31.7 19.6 94.7
WGZ090D J
130.6 5.2 8.2 15.7 209.0 12.8 13.1 38.3 348.3 33.8 21.8 101.0
WGZ100D K
146.7 4.8 9.2 14.4 234.7 11.8 14.7 35.3 391.2 31.1 24.4 93.1
WGZ115D L
169.4 5.0 10.6 15.1 271.0 12.3 16.9 36.8 451.7 32.5 28.2 97.0
WGZ130D M
190.1 5.3 11.9 15.9 304.1 13.0 19.0 38.9 506.8 34.3 31.7 102.6
WGZ150D N
222.3 6.2 13.9 18.6 355.7 15.2 22.2 45.4 592.8 40.1 37.1 119.9
WGZ170D O
253.9 7.4 15.9 22.0 406.3 18.0 25.4 53.8 677.2 47.5 42.3 142.0
WGZ200D P
282.1 9.0 17.6 26.9 451.4 22.0 28.2 65.8 752.3 58.1 47.0 173.6
Curve
Ref
S.I. Inch-Pound S.I.Inch-Pound Inch-PoundS.I.
Nomina l Flow & Pr. Drop
Model
Minimum Flow & Pr. Drop
Pressure Drop Data
Table 2: WGZ-D Evaporator Pressure Drop Data
IM 1131-2 15
Maximum Flow & Pr. Drop
Dimensions - Packaged
121.1
3075
3.8
98
134.6
3419
9.7
246
X
Y
29.0
.875 DIA. MOUNTING HOLES (4)
737
13.3
338
2.0
51
23.3
592
Z
"A"
15
.59 REF.
*333611521* p. 1 of 2
CERTIFIED, WGZ030-060D, PACKAGE
CIRCUIT 2
OUTLET
INLET
DRAIN
VENT
WATER CONNECTIONS
MICROTECH II USER INTERFACE
CONDENSER
COULD BE ON OPPOSITE
NOTE: CONDENSER
END IF ORDERED AS LH.
CIRCUIT 1
RELIEF VALVES
3.9
100
EVAPORATOR
FOR SHIPPING
OUTLET
REMOVE BRKT.
DISC. HANDLE
.88 KNOCKOUTS
.88 KNOCKOUTS
CONNECTIONS
INLET
ON OPPOSITE SIDE
REMOVABLE
ONLY
POWER
CONTROL
CONNECTIONS
770
30.3
1609
63.4
30.4
771
14.1
359
8.2
209
32.0
813
1140
44.9
1016
40.0
314
12.4
508
20.0
33.0
837
6.0
153
VICTAULIC
SIZE (NOM) A SIZE (NOM) X Y Z
2.5 14.4 4 59.2 22.4 14. 1
(64) (366) (102) ( 1504) (569) (358)
2.5 13.7 4 59.9 23.3 14. 2
(64) (349) (102) ( 1522) (592) (361)
2.5 13.0 4 59.5 23.2 14. 2
(64) (331) (102) (1511) (589) (361)
2.5 11.7 4 59.1 23.3 14. 2
(64) (296) (102) ( 1501) (592) (361)
2.5 10.3 4 58.9 20.2 14. 2
(64) (260) (102) ( 1496) (513) (361)
2.5 9.6 4 58.520.314.2
(64) (243) (102) ( 1486) (516) (361)
2.5 7.8 4 57.920.514.3
(64) (199) (102) ( 1471) (521) (363)
CHILLER WATER
CONNECTION
IN(MM) VICTAULIC
CENTER OF
GRAVITY
WGZ
MOD EL
NUMBER
WGZ030D
WGZ055D
WGZ060D
WGZ035D
WGZ040D
WGZ045D
WGZ050D
Dimensions - Packaged
Figure 1: WGZ030DW - 060DW (Packaged)
CONNECTION IN(MM)
CONDENSER WAT ER
16 IM 1131-2
Figure 2: WGZ070DW (Packaged)
145.5
3695
10.2
259
121.1
3075
14.2
361
X
Y
2.0
51
29.0
.875 DIA MOUNTING HOLES (4)
737
13.0
330
23.5
597
Z
*333611621* p. 1&2 of 3
CERTIFIED, WGZ070-130D
VENT
DRAIN
CG
NOTE: CONDENSER
WATER CONNECTIONS
CONDENSER
OUTLET
COULD BE ON OPPOSITE
MICROTECH II USER IN TERFACE
INLET
END IF ORDERED AS LH.
RELIEF VALVES
CIRCUIT 2 CIRCUIT 1
4 IN. VICTAULIC
CONNECTIONS
4.0
102
ONLY
REMOVE BRKT.
INLET
FOR SHIPPING
.88 KNOCKOUTS
CONNECTIONS
REMOVABLE
.88 KNOCKOUTS
CONTROL
DISC. HANDLE
CONNECTIONS
EVAPORATOR
CG
ON OPPOSITE SIDE
OUTLET
POWER
3 IN. VICTAULIC
CONNECTIONS
14.5
369
20.0
508
65.5
1664
35.2
894
32.6
827
1016
40.0
1434
56.4
866
34.1
454
17.9
253
10.0
813
32.0
40.2
1021
.6
15
A
OUTLET
INLET
6.0
152
VICTAULI C
SIZE (NOM) A SIZ E (NOM) X Y Z
3
CHILLER WATER
CONNECTION
IN(MM) VICTAULIC
CENTER OF
GRAVITY
WGZ
MOD EL
NUMBER
WGZ070D
(76)
11.3
(287)
4
(102)
61.7 (1568)
28.2
(716)
15.0
(381)
Dimensions - Packaged
CONNECTION IN(MM)
CONDENSER WATER
IM 1131-2 17
Dimensions - Packaged
121.1
3075
14.2
361
L
T
Y
X
"A"
2.0
51
29.0
.875 DIA MOUNTING HOLES (4)
737
13.0
330
23.5
597
Z
*333611621* p. 3 of 4
CERTIFIED, WGZ070-130D
MICROTECH II USER INTERFACE
CIRCUIT 2
CIRCUIT 1
CONDENSER
RELIEF VALVES
VENT
OUTLET
INLET
DRAIN
NOTE: CONDENSER
WATER CONNECTIONS
COULD BE ON OPPOSITE
END IF ORDERED AS LH.
4.0
102
6.0
152
POWER
CONNECTIONS
.88 KNOCKOUTS
REMOVABLE
DISC. HANDLE
CONTROL
CONNECTIONS
.88 KNOCKOUTS
ON OPPOSITE SIDE
REMOVE BRKT.
FOR SHIPPING
ONLY
EVAPORATOR
INLET
OUTLET
40.0
1016
56.4
1434
34.1
866
17.9
454
10.0
253
32.0
813
20.0
508
14.5
369
65.5
1664
35.2
894
40.2
1022
32.6
827
MAXI MUM
OVERALL
LENGTH IN (MM)
CONDENSER WATER
CONNECTION IN(MM)
VICT AULIC
L SIZE (NOM) A SIZE (NOM) T X Y Z
149 3 8.8 4 13.8 64.2 29.5 15
(3785) ( 76) (224) (102) (351) (1631) (74 9) (38 1)
149 3 8.0 4 13.8 67.2 32.6 16
(3785) ( 76) (203) (102) (351) (1707) (82 8) (40 6)
149 3 6.0 4 13.8 69.2 35.4 17
(3785) ( 76) (152) (102) (351) (1758) (89 9) (43 2)
148 3 3.1 4 12.9 68 35.6 17
(3759) (76) (79) (102) (328) ( 1727) (904) (432)
149 3 1.0 4 13.7 67.7 36.1 17
(3785) (76) (25) (102) (348) ( 1720) (917) (432)
CHILLER WATER
CONNECTION
IN(MM) VICTAULIC
CENTER OF
GRAVITY
WGZ130D
WGZ080D
WGZ
MODE L
NUMBER
WGZ090D
WGZ100D
WGZ115D
Figure 3: WGZ080DW - 130DW (Packaged)
18 IM 1131-2
Figure 4: WGZ150DW - 200DW (Packaged)
4.0
102
170.3
4327
145.1
3685
14.2
361
T
Y
X
MICROTECH II USER INTERFACE
CIRCUIT 2
CIRCUIT 1
CONDENSER
RELIEF VALVES
VENT
DRAIN
OUTLET
INLET
EVAPORATOR
DRAIN
VENT
9.6
243
18.3
464
32.0
813
40.0
1016
20.0
508
12.5
318
H
41.0
1042
37.1
943
34.5
876
29.0
.875 DIA. MOUNTING HOLES (4)
737
2.0
51
36.9 EVAP
INLET/
OUTLET
938
13.3
337
35.8
908
Z
POWER
CONNECTIONS
.88 KNOCKOUTS
REMOVABLE
DISC. HANDLE
CONTROL
CONNECTIONS
.88 KNOCKOUTS
ON OPPOSITE SIDE
REMOVE BRKT.
FOR SHIPPING
ONLY
1.3
34
23.5
596
77.2
1961
EVAPORATOR
OUTLET
EVAPORATOR
INLET
CERTIFIED, WGZ150-200D
1 2
OF
*333611701001*
Dimensions - Packaged
IM 1131-2 19
Dimensions - Condenserless
Y
X
2.0
51
23.5
597
Z
41.3
1050
26.8
681
*333611531* p. 1 of 2
CERT., WGZ030-060D, LESS COND
CIRCUIT 1
CIRCUIT 2
MICROTECH II USER INTERFACE
137.0
3480
152
312
12.3
6.0
20.2
512
ONLY
OUTLET
FOR SHIPPING
DISC. HANDLE
REMOVABLE REMOVE BRKT.
.88 DIA. KNOCKOUTS
INLET
ON OPPOSITE SIDE
EVAPORATOR
CONTROL CONNECTION
POWER
CONNECTIONS
.88" DIA. KNOCKOUTS
ISOLATOR HOLES (4)
762
DISCHARGE
60.0
419
CONNECTIONS
5.9
150
CONNECTIONS
LIQUID
1524
2.5
64
2.0
6.1
155
34.0
864
40.0
1016
9.0
229
20.0
508
51
16.5
EVAP. AND
30.0
30.4
772
.88 LIQUID
INLET
OUTLET
CONNECTIONS
1.38 DISCHARGE
CONNECTIONS
98.8
178
7.0
2509
2334
91.9
38.2
970
31.4
798 258
A
10.2
6.0
152
SIZE (NOM) A X Y Z
2.5 22.4 67.3 22.8 13.3
(64) (569) (1709) (579) (338)
2.5 21.7 68.2 23.8 13.4
(64) (551) (1732) (605) (340)
2.5 21.0 67.6 23.9 13.5
(64) (533) (1717) (607) (343)
2.5 19.6 67.1 24.0 13.6
(64) (498) (1704) (610) (345)
2.5 18.2 66.7 24.4 13.6
(64) (462) (1694) (620) (345)
2.5 17.5 66.1 24.5 13.6
(64) (445) (1679) (622) (345)
2.5 15.8 65.7 24.6 13.7
(64) (401) (1669) (625) (348)
CHILLER WATER
CONNECTION
CENTER OF GRAVITY
WGZ
MODEL
NUMBER
WGZ030D
WGZ055D
WGZ060D
WGZ035D
WGZ040D
WGZ045D
WGZ050D
Dimensions - Condenserless
Figure 5: WGZ030DA - 060DA (Condenserless)
IN(MM) VICTAULIC
20 IM 1131-2
Loading...
+ 44 hidden pages