These operating instructions describe the system "„RoCon UFH" for single room temperature control (also referred to as "product" in these operating instructions). These
operating instructions are part of the product.
•You may only use the product if you have fully read and understood these operating instructions.
•Verify that these operating instructions are always accessible for any type of work
performed on or with the product.
•Pass these operating instructions as well as all other product-related documents
on to all owners of the product.
•If you feel that these operating instructions contain errors, inconsistencies, ambiguities or other issues, contact the manufacturer prior to using the product.
•The wireless system described in these instructions is only available in certain
sales areas.
These operating instructions are protected by copyright and may only be used as provided for by the corresponding copyright legislation. We reserve the right to modifications.
The manufacturer shall not be liable in any form whatsoever for direct or consequential damage resulting from failure to observe these operating instructions or from failure to comply with directives, regulations and standards and any other statutory
requirements applicable at the installation site of the product.
EN
RoCon UFH
2
Information on safety
2Information on safety
2.1Safety messages and hazard categories
These operating instructions contain safety messages to alert you to potential hazards and risks. In addition to the instructions provided in these operating instructions,
you must comply with all directives, standards and safety regulations applicable at the
installation site of the product. Verify that you are familiar with all directives, standards
and safety regulations and ensure compliance with them prior to using the product.
Safety messages in these operating instructions are highlighted with warning symbols
and warning words. Depending on the severity of a hazard, the safety messages are
classified according to different hazard categories.
DANGER
DANGER indicates a hazardous situation, which, if not avoided, will result in
death or serious injury.
NOTICE
NOTICE indicates a hazardous situation, which, if not avoided, can result in
equipment damage.
EN
In addition, the following symbols are used in these operating instructions:
This is the general safety alert symbol. It alerts to injury hazards or
equipment damage. Comply with all safety instructions in conjunction with this symbol to help avoid possible death, injury or equipment damage.
This symbol alerts to hazardous electrical voltage. If this symbol is
used in a safety message, there is a hazard of electric shock.
RoCon UFH
3
Information on safety
2.2Intended use
This product may only be used to control the room temperature (heat/cool) of individual rooms with underfloor heating system.
The controller modules may only be used to control the thermostatic actuators via the
signals of the associated room controllers and the base module.
Any use other than the application explicitly permitted in these operating instructions
is not permitted and causes hazards.
Verify that the product is suitable for the application planned by you prior to using the
product. In doing so, take into account at least the following:
•All directives, standards and safety regulations applicable at the installation site of
the product
•All conditions and data specified for the product
•The conditions of the planned application
In addition, perform a risk assessment in view of the planned application, according
to an approved risk assessment method, and implement the appropriate safety measures, based on the results of the risk assessment. Take into account the consequences of installing or integrating the product into a system or a plant.
When using the product, perform all work and all other activities in conjunction with
the product in compliance with the conditions specified in the operating instructions
and on the nameplate, as well as with all directives, standards and safety regulations
applicable at the installation site of the product.
EN
2.3Predictable incorrect application
The product must never be used in the following cases and for the following purposes:
•Hazardous area (EX)
- If the product is operated in hazardous areas, sparks may cause deflagrations,
fires or explosions
•In conjunction with products which are used for health-saving or life-saving purposes or whose operation may incur hazards to humans, animals or property
RoCon UFH
4
Information on safety
2.4Qualification of personnel
Only appropriately trained persons who are familiar with and understand the contents
of these operating instructions and all other pertinent product documentation are
authorized to work on and with this product.
These persons must have sufficient technical training, knowledge and experience and
be able to foresee and detect potential hazards that may be caused by using the product.
All persons working on and with the product must be fully familiar with all directives,
standards and safety regulations that must be observed for performing such work.
2.5Personal protective equipment
Always wear the required personal protective equipment. When performing work on
and with the product, take into account that hazards may be present at the installation
site which do not directly result from the product itself.
2.6Modifications to the product
Only perform work on and with the product which is explicitly described in these operating instructions. Do not make any modifications to the product which are not
described in these operating instructions.
EN
RoCon UFH
5
Transport and storage
3Transport and storage
The product may be damaged as a result of improper transport or storage.
NOTICE
INCORRECT HANDLING
•Verify compliance with the specified ambient conditions during transport or
storage of the product.
•Use the original packaging when transporting the product.
•Store the product in a clean and dry environment.
•Verify that the product is protected against shocks and impact during transport and storage.
Failure to follow these instructions can result in equipment damage.
EN
RoCon UFH
6
Product description
4Product description
The single room temperature controller RoCon UFH is used to control the temperature in rooms with underfloor heating system (heating and cooling). The controller
compares the actual temperature and the reference temperature and controls the volume flow of the heating water via the corresponding thermostatic actuators.
The room controllers measure the actual temperature in the corresponding rooms.
The reference temperature is adjusted via the rotary knob of the corresponding room
controllers.
The controller modules with 2 or 6 independent control circuits control the respective
thermostatic actuators via the signals of the room controllers and the base module.
Th base module supplies the room controllers with 5 V DC and the thermostatic actuators with 230 V AC. The single room temperature controller RoCon UFH can be
switched between heating and cooling via the base module. The control circuit pumps
can be controlled via the base module.
The optional timer module features a hundred year calendar. The display shows the
date, time and day of the week. The timer module features 2 independently programmable switching channels for temperature reduction. A total of 9 programmable memory blocks are available. The additional pump running time can be set via the timer
module. The timer module has a valve and pump protection function.
The single room temperature controller consists of a base module, at least one room
controller and at least one controller module. Multiple controller modules with 2 or 6
control circuits can be adapted.
The single room temperature controller RoCon UFH is available in 2 versions
•Room controller and controller modules are interconnected by a cable.
•Room controllers and controller module are connected via EnOcean
The single room temperature controller RoCon UFH is a modular system. The ver-
sions wired and wireless
(1)
can also be operated in mixed mode.
®
wireless
(1)
EN
:
(1)
.
(1)The wireless system is only available in certain sales areas.
RoCon UFH
7
Product description
4.1Overview of the individual RoCon UFH components
EN
ComponentVersions ExplanationOrdering
number
Base moduleRoCon UFH-BM-175137
Timer moduleRoCon UFH-UM-175138
Room temperature controller
Controller module
RoCon UFH-RD Wired175139
RoCon UFH-
(1)
RFT
RoCon UFH-
Wireless, temperature175142
Wired with 2 control circuits175141
RMD2
RoCon UFH-
Wired with 6 control circuits175140
RMD6
RoCon UFH-
RMF2A
RoCon UFH-
RMF6A
(1) The wireless system is only available in certain sales areas.
(1)
(1)
With external antenna and 2
control circuits
With external antenna and 6
control circuits
175144
175143
RoCon UFH
8
4.2Overview
Base module RoCon UFH-BM
Fig. 4-1: Front view base module
Product description
A. Fuse compartment
B. Operation mains voltage
C. Operation 5 V (LED green)
D. Pump Heating (LED red)
E. Pump Cooling (LED blue)
F. Cooling (LED blue)
G. Input switchover Heating/
H. Cascading output Heating/
I. Relay contact pump Cooling
J. Relay contact pump Heating
K. Mains voltage 230 V AC
L. Timer module (optional)
EN
(LED green)
Cooling
Cooling
RoCon UFH
9
Product description
Controller modules wired
EN
A. Controller module RoCon UFH-
RMD2
B. Controller module RoCon UFH-
RMD6
C. End cover
Fig. 4-2: Front view controller modules wired
RoCon UFH
1. Catch
2. Operation mains voltage (LED green)
3. Thermostatic actuator active (LED
yellow)
4. Terminal block for room controller
RoCon UFH-RD
5. Terminal block for thermostatic actuators
6. Fuse compartment
10
Product description
EN
Controller modules wireless
(1)
A. Controller module RoCon UFH
RMF2A
B. Controller module RoCon UFH
RMF6A
C. End cover
Fig. 4-3: Front view controller modules wireless
1. Teach-in key (LRN key)
2. Catch
3. Operation mains voltage (LED green)
4. Thermostatic actuator active (LED
yellow)
5. Wireless module
6. Terminal block for thermostatic actuators
7. Fuse compartment
8. Reset button (CLR button)
Information
Additional information on planning (e.g. "range planning"), installation and operation of EnOcean
(1)The wireless system is only available in certain sales areas.
®
wireless systems can be found at www.enocean.com.
RoCon UFH
11
Room controller
2
1
A
1B1
3
Product description
EN
A. Room controller wired UFH-RD
B. Room controller wireless UFH-RFT
1. Rotary knob for adjusting the reference temperature
(1)
2. LED red: Hearing
LED blue: Cooling
3. Solar cell
Fig. 4-4: Front view room controller
(1)The wireless system is only available in certain sales areas.
RoCon UFH
12
Product description
4.3Application examples
Fig. 4-5: Single room temperature controller-RoCon UFH with one controller module
RoCon UFH-RMD6 wired and 6 room controllers RoCon UFH-RD
EN
Fig. 4-6: Single room temperature controller RoCon UFH with one controller module
RoCon UFH-RMF6A wireless
(1)
and 6 room controllers RoCon UFH-RFT
(1)
(1) The wireless system is only available in certain sales areas.
RoCon UFH
13
4.4Technical data
ParameterBase module RoCon UFH-BM
General specifications
Dimensions housing
(W x H x D)
Weight215 g
Housing materialPC/ABS
ColourLight grey, similar to RAL 7047
Transmission power
max. 10 mW
Additional information:
www.enocean.com
See declaration of conformity (enclosed with the
product)
RoCon UFH
18
Product description
ParameterTimer module RoCon UFH-UM
General specifications
Dimensions (W x H x D)37 mm x 93 mm x 28 mm
Weight33 g
Housing materialABS
Temperature reduction4K
Functions
TimingDate, time, weekday
(leap year detection, switching between
daylight saving time and winter time)
Switching channels for temperature
reduction
Memory blocks for temperature reduction
Valve and pump protection function0 to 15 min, adjustable
Additional pump running time0 to 15 min, adjustable
Operating modes day, night, timer
DayHeating control without temperature reduc-
NightHeating control with permanent tempera-
TimerHeating control with temperature reduction
Operating temperature range
Ambient-10 … 60 °C
Storage-10 … 60 °C
Max. humidityNon-condensing
Supply voltage
Nominal voltageVia base module 3.3 V DC
Nominal power3 mW
Battery power> 3 months
Electrical safety
Degree of protection (EN 60529)IP 30
Electromagnetic compatibility (EMC)
Emitted interference/immunityEN 61326-1:2013
2, independently programmable
9, independently programmable
tion
ture reduction
according to programmed switching times
EN
Table 4-5: Technical specifications timer module
RoCon UFH
19
Product description
Daikin recommends the use of Daikin UFH-Sat8 actuators to ensure optimum system
performance. If actuators from other manufacturers are used, the following limit values must be met:
Operating voltageAC 230 V ±10 %, 50/60 Hz
Max. operating current9 mA
Max. inrush current140 mA / 200 ms
Max. operating power2 W
Special characteristicShort-circuit proof, protected against overvolt-
age
Actuators of other manufacturers
connected per control circuit
Table 4-6: Technical specifications for actuators
Max. 2
EN
RoCon UFH
20
Product description
4.5Dimensions
Individual dimensions
Fig. 4-7: Dimensions of the individual components
EN
Dimensions mounted
Fig. 4-8: Total lengths of versions D2/F2A (2 control circuits), D6/F6A (6 control circuits) and
D6/F6A+D2/F2A (8 control circuits)
RoCon UFH
21
Product description
4.6Information on RoCon UFH as per EN 60730-1:2016
•RoCon UFH is an electronic control type C as per EN 60730-1.
•RoCon UFH is suitable for continuous operation.
•The type of disconnection of the actuators and pumps is micro disconnection.
•The PTI value of the insulation (PCBs) is 175.
•RoCon UFH corresponds to installation category 3.
•RoCon UFH corresponds to overvoltage category 2.
•The limit value for the SELV circuit is DC 5 V.
•The maximum permissible click rate is 1/minute.
•The test voltage for the EMC noise immunity tests is ±1 kV (±2 kV).
4.7Information on RoCon UFH as per EN 15500:2017
•Type: Fixed point function.
•Zone type: Constant conditions.
•Application groups: Individual zone control equipment.
•Output types: On/off actuators.
•Sensor type: NTC ±5 %.
•Certified value of control accuracy: 0.6 K (0.5 K).
EN
RoCon UFH
22
Mounting
5Mounting
5.1Mounting site
The product must be mounted in the vicinity of the heating circuit manifold.
5.2Mounting of the product
Verify that the product is disconnected from mains
1. Open the cover using a
screwdriver.
Fig. 5-1: Opening the cover
EN
Fig. 5-2: Removing the end cover
RoCon UFH
2. Pull off the end cover.
23
Mounting
3. Connect the controller module(s) to the product and
secure both with the catch.
Fig. 5-3: Connecting the base module to the controller module(s)
4. Refit the end cover onto the
last controller module.
EN
Fig. 5-4: Refitting the end cover
RoCon UFH
5. Make the electrical connections (see chapter 5.3)
24
Mounting
EN
6. Refit the cover and close it.
Fig. 5-5: Closing the cover
RoCon UFH
25
Mounting
5.3Electrical connection
DANGER
ELECTRIC SHOCK
•Verify that the degree of protection against electric shock (protection class,
double insulation) is not reduced by the type of electrical installation.
Failure to follow these instructions will result in death or serious injury.
DANGER
ELECTRIC SHOCK CAUSED BY LIVE PARTS
•Disconnect the mains voltage supply before performing the work and ensure
that it cannot be switched on.
•Verify that no hazards can be caused by electrically conductive objects or
media.
Failure to follow these instructions will result in death or serious injury.
Verify that a connection con-
cept has been created.
- Verify that the correct
assignment of the switching channels for the timer
module has been considered.
Verify that all cables are dis-
connected from power.
1. Strip the cables as shown.
Fig. 5-6: Stripping the cables
EN
RoCon UFH
26
5.3.1Connection diagram
A
L
N
FP
Mounting
B
EN
A. 230 V AC supply
B. Input heating/cooling
- open: Heating
- closed: Cooling
- internal control voltage:
DC 5 V
C. Cascading output voltage-
free relay contact
max.AC250V, 3A
max. DC 30 V, 3 A
D. Options
E. Pump cooling
max. AC 250V, 3A
F. Pump heating
max. AC 250V, 3A
L
N
PE
D
Fig. 5-7: Connection diagram base module
RoCon UFH
C
27
Mounting
CA V032
Pump
Relays
Heat
Cool OutIn
Heat/Cool
C
A
V032
Pump
Relays
Heat
Cool OutIn
Heat/Cool
CA V
0
3
2
Pump
Relays
Heat
Cool OutIn
Heat/Cool
PE
C
B
F
A
A
A
P
L
L
N
N
2MB1MB
BM3
5.3.2Connection diagram in the case of multiple products
EN
A. Upper floor
B. Ground floor
C. Basement
D. Heating
E. Pump cooling
max. AC 250V, 3A
F. Pump heating
max. AC 250V, 3A
Fig. 5-8: Connection diagram for cascading example
RoCon UFH
28