Daikin RXYQ72PYDN, RXYQ96PYDN, RXYQ120PYDN, RXYQ144PYDN, RXYQ168PYDN Installation Manual

...
INSTALLATION MANUAL
System air conditioner
English
Français
Español
RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN
<
If installed as a single unit
(Pattern 1)
1
3/8
3/8
1
2
(Pattern 2)
(Pattern 3)
1
2
11-3/4
>
11-3/4 11-3/4
4
19-5/8
3
3-7/8
4
2
19-5/8
3
2
(Pattern 1)
3/8
(Pattern 2)
(Pattern 3)
<
When installed in serial
3/8
1
3/4
2
3-7/8
3/4
3-7/8
1
11-3/4
2
2
>
4
19-5/8
3
3-7/8
19-5/8
1
2
2
4
3
60
5
3
40
60
60
4
60
(in.)
40
40
7-7/8
1
7-7/8
1
15-3/4 15-3/4
figure 1 figure 3figure 2
12
<3>
1
4
2
1
1
2
3-7/8
3-7/8
3-7/8
5
3
figure 4 figure 6figure 5
1
3
24-7/8
30-1/8
4
1
3
4
6
2
5
3
1
4
2
3
5
2
30-1/8
A B
29
figure 7 figure 8 figure 9 figure 10
3-7/8
1
3-7/8
4
3-7/8
5
3
2
1
44
2
3
figure 11 figure 12
1
3
6
5
9
14
9
7
8
15
15
6
5
9
9
16
9
10
13
17
11
12
20
2
5 4
19
6 3
1
3
10
6
5
7
7
11
7
8
5
7
9
7
2
4
6
1
2
4
8
18
9
13
12
figure 13-1
figure 13-2
A
1
2
5
figure 14
34
1
B
2
figure 15 figure 16
D
16-2
16-1
C
1
2
1
3
4
7
1
5
6
1
4
8
16-3
11
2
2
figure 17
figure 19
1
2
3 4
5
TO IN/D UNIT F1 F2
3 4
6
1
3
A1P
TO OUT/D UNIT
TO MULTI UNIT
F1 F2
Q1 Q2
2
7
2
4
A1P
TO MULTI UNIT Q1 Q2
figure 18-1
:
12
7
F1 F2 F1 F2 F1 F2
8
4
3
figure 18-2
1
5
1
2
3
2
F1 F2 F1 F2F1 F2
F1 F2 F1 F2
11
6
figure 20
1
(A1P)
2
3
1
2
figure 21 figure 23
5
figure 22
4
5
L1 L2 L3
1
6
3
4
2
7
4
8
7
15 15
11
1
2
10
12
9
1
3
2
4
: 19 : 20
6
5
14
8
9 10 11
12
13
16
F17
()
18
figure 24
figure 27
3
8
figure 25
2
4
6
5
7
1
figure 26
1
2
3
5
1
2
3
4
figure 28
1
2
6
3
4
2
5
figure 29 figure 30
3
1
4 5 6 7 8
12
13
9
10
2
: 15
()
: 16
: 17
: 18
11
14
19
9
figure 31
3
1
4 5 6
7 8
12
13
9
10
2
:
15
:
16
11
:
14
1
17
()
:
18
2
3
4
figure 32
RXYQ72PYDN RXYQ96PYDN RXYQ120PYDN RXYQ144PYDN
RXYQ168PYDN RXYQ192PYDN RXYQ216PYDN RXYQ240PYDN
CONTENTS
1. FIRST OF ALL.......................................................................... 1
1-1. Safety considerations........................................................1
1-2. Special notice of product...................................................2
1-3. Disposal requirements.......................................................3
2. INTRODUCTION......................................................................3
2-1. Combination ......................................................................3
2-2. Standard supplied accessories ......................................... 3
2-3. Option accessory...............................................................3
2-4. Technical and Electrical specifications.............................. 3
2-5. Main components..............................................................3
3. SELECTION OF LOCATION.................................................... 3
4. INSPECTING AND HANDLING THE UNIT.............................. 4
5. PLACING THE UNIT ................................................................4
6. REFRIGERANT PIPING ..........................................................5
6-1. Selection of piping material and
Refrigerant branching kit ...................................................5
6-2. Protection against contamination when installing pipes....5
6-3. Pipe connection................................................................. 5
6-4. Connecting the refrigerant piping ...................................... 5
6-5. Example of connection......................................................8
7. FIELD WIRING.......................................................................11
7-1. Power circuit, safety device and cable requirements ......11
7-2. Wiring Connection Example for Whole System...............11
7-3. Leading wire Procedure .................................................. 11
7-4. Transmission Wiring Connection Procedure................... 12
7-5. Power Wiring Connection Procedure ..............................12
7-6. Procedure for Wiring Inside Units....................................12
8. AIR TIGHT TEST AND VACUUM DRYING ...........................13
9. PIPE INSULATION................................................................. 13
10. CHECKING OF DEVICE AND
INSTALLATION CONDITIONS ..............................................14
11. ADDITIONAL REFRIGERANT CHARGE AND
CHECK OPERATION............................................................. 14
11-1.Before working ...............................................................14
11-2.Procedure of Adding Refrigerant charging and
check operation ...............................................................15
12. ONSITE SETTINGS ............................................................... 18
13. TEST RUN .............................................................................18
13-1.Before test run................................................................18
13-2.Test Run......................................................................... 18
13-3.Checks After Test Run ...................................................18
14. CAUTION FOR REFRIGERANT LEAKS ...............................19
1. FIRST OF ALL
This document is an installation manual for the Daikin RXYQ-P
Series VRV Inverter. Before installing the unit, read this manual thor­oughly, and following the instructions contained in it. After installation, do a test run to make sure the unit runs properly, and then explain how to operate and take care of the unit to the cus­tomer, using the operation manual. Lastly, make sure the customer keeps this manual, along with the operation manual, in a safe place.
1-1 Safety considerations
Please read these “SAFETY CONSIDERATIONS” carefully before installing air conditioning unit and be sure to install it correctly. After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained. Also, inform customers that they should store this installation manual along with the operation manual for future reference. This air conditioner comes under the term “appliances not accessible to the general public”.
VRVIII System air conditioner Installation manual
Safety Precaution
VRV System is a class A product. In a domestic environment this prod­uct may cause radio interference in which case the user may be required to take adequate measures.
Meaning of danger, warning, caution and note symbols.
DANGER .................... Indicates an imminently hazardous situa-
tion which,if not avoided, will result in death or serious injury.
WARNING .................. Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
CAUTION.................... Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate injury. It may also be sued to alert against unsafe practices.
NOTE.......................... Indicates a situation that may result in the
unit or property-damage-only accidents.
DANGER
• Refrigerant gas is heavier air and replaces oxygen. A massive leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• Do not ground units to water pipes, telephone wires or light­ning rods because incomplete grounding could cause a se­vere shock hazard resulting in severe injury or death, and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death.
• If the refrigerant gas leaks during installation, ventilate the area immediately.
Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan, heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
• After completing the installation work, check that the refriger­ant gas does not leak.
Refrigerant gas may produce toxic gas if it comes in contact with fire such as from a fan, heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
• Do not install unit in an area where flammable materials are present due to risk of explosion resulting in serious injury or death.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries. Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face the danger of death by suffocation.
WARNING
• Ask your dealer or qualified personnel to carry out installation work. Do not try to install the unit by yourself.
Improper installation may result in water leakage, electric shocks or fire.
• Perform installation work in accordance with this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
• When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding al­lowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information. Excessive refrig­erant in a closed ambient can lead to oxygen deficiency.
• Be sure to use only the specified accessories and parts for in­stallation work.
Failure to use the specified parts may result in water leakage, electric shocks, fire or the unit falling.
English 1
• Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the unit falling and causing injuries.
• Carry out the specified installation work after taking into ac­count strong winds, typhoons or earthquakes.
Improper installation work may result in the unit falling and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and this in­stallation manual.
An insufficient power supply capacity or improper electrical construc­tion may lead to electric shocks or fire.
• Make sure that all wiring is secured, the specified wires and used, and no external forces act on the terminal connections or wires.
Improper connections or installation may result in fire.
• When wiring the power supply and connecting the remote controller wiring and transmission wiring, position the wires so that the electric parts box lid can be securely fastened.
Improper positioning of the electric parts box lid may result in electric shocks, fire or the terminals overheating.
• Before touching electrical parts, turn off the unit.
• Securely install the outside unit terminal cover (panel).
If the terminal cover (panel) is not installed properly, dust or water may enter the outside unit and fire or electric shock may result.
• When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the speci­fied refrigerant (R410A), such as air.
Any presence of air or other foreign substance in the refrigerant cir­cuit causes an abnormal pressure rise or rupture, resulting in injury.
• Do not reconstruct or change the settings of the protection devices.
If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Daikin are used, fire or explosion may result.
• Do not touch the switch with wet fingers.
Touching a switch with wet fingers can cause electric shock.
• Do not allow children to play on or around the unit as they could be injured.
• Refrigerant pipes may be very hot or very cold during or im­mediately after operation.
Touching them could result in burns or frostbite. To avoid injury give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
• Be sure to install a ground fault circuit interrupter.
Failure to install an earth leakage breaker may result in electric shocks, or fire.
CAUTION
• While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insu­late piping in order to prevent condensation.
Improper drain piping may result in water leakage and property damage.
• Be very careful about product transportation.
• Do not touch the refrigerant pipes during and immediately af­ter operation.
During and immediately after operation, the refrigerant pipes may be hot and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refriger­ant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not turn off the power immediately after stopping operation.
Always wait at least five minutes before turning off the power. Other­wise, water leakage and trouble may occur.
• Do not use a charging cylinder.
Using a charging cylinder may cause the refrigerant to deteriorate.
• The refrigerant R410A requires strict cautions for keeping the system clean, dry and tight.
A. Clean and dry
Foreign materials (including mineral oils such as SUNISO oil or moisture) should be prevented from getting mixed into the system.
B. Tight
R410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce the earth’s protection against harmful ultraviolet radiation. R410A can contribute slightly to the greenhouse effect if it is released. Therefore we should take special attention to check the tightness of the installation. Read the chapter “Refrigerant piping” carefully and follow these procedures correctly.
• Since R410A is a mixed refrigerant, the required additional re­frigerant must be charged in its liquid state. (If the refrigerant is charged in a state of gas, its composition changes and the system will not work properly.)
The indoor unit is for R410A. See the catalog for indoor unit models which can be connected. (Normal operation is not possible when connected to other units.)
• Remote controller (wireless kit) transmitting distance can re­sult shorter than expected in rooms with electronic fluores­cent lamps. (inverter or rapid start types)
Install the indoor unit as far away from fluorescent lamps as possible.
• Install in a machine room that has no water drops.
This unit is for indoor use.
• Do not install the air conditioner in the following locations:
(a) where a mineral oil mist or an oil spray or vapor is produced, for
example in a kitchen Plastic parts may deteriorate and fall off or result in water leakage.
(b) where corrosive gas, such as sulfurous acid gas, is produced
Corroding copper pipes or soldered parts may result in refrigerant leakage.
(c) near machinery emitting electromagnetic waves
Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the unit.
(d) where flammable gas may leak, where there are carbon fiber or
ignitable dust suspensions in the air, or where volatile flammables such as thinner or gasoline are handled. Operating the unit in such conditions may result in fire.
• Make sure to provide for adequate measures in order to prevent that the outside unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause mal­functions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
NOTE
• Install the indoor and outside units, power supply wires and transmission wires at least 3.5ft. away from televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.5ft. may not be suffi­cient to eliminate the noise.)
• Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accordance with the relevant local and national regulations.
• Do not use the following tools that are used with conventional refrigerants. (Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment.)
If the conventional refrigerant and refrigerator oil are mixed in the R410A, the refrigerant may deteriorate.
1-2 Special notice of product
[CLASSIFICATION]
This air conditioner comes under the term “appliances not accessible to the general public”.
[REFRIGERANT] VRVIII System use R410A refrigerant.
The refrigerant R410A requires strict cautions for keeping the sys-
tem clean, dry and tight. Read the chapter “REFRIGERANT PIPING” carefully and follow these procedures correctly.
2 English
A. Clean and dry
Foreign materials (including mineral oils such as SUNISO oil or moisture) should be prevented from getting mixed into the system.
B. Tight
Take care to keep the system tight when installing. R410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce the earth’s protection against harmful ultraviolet radiation. R410A can contribute slightly to the greenhouse effect if it is released.
Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in a state of gas, its composition changes and the system will not work properly.
[DESIGN PRESSURE]
Since design pressure is 478 psi, the wall thickness of pipes should be more carefully selected in accordance with the relevant local and national regulations.
1-3 Disposal requirements
Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accordance with the relevant local and national regulations.
2. INTRODUCTION
RXYQ-P series are designed for outdoor installation and used for
cooling and heating applications.
The indoor units that combined with RXYQ-P system for air condi­tioning are Daikin VRV series indoor units that compatible with R410A. To learn which indoor units are compatible with R410A, refer to the product catalogs. To combine with other refrigerant indoor unit will cause malfunction.
2-1 Combination
The system name and that independent units are as follows.
The system name
RXYQ72PYDN ..............RXYQ72PYDN
RXYQ96PYDN ..............RXYQ96PYDN
RXYQ120PYDN ............RXYQ120PYDN
RXYQ144PYDN ............RXYQ72PYDN RXYQ72PYDN
RXYQ168PYDN ............RXYQ72PYDN RXYQ96PYDN
RXYQ192PYDN ............RXYQ72PYDN RXYQ120PYDN
RXYQ216PYDN ............RXYQ96PYDN RXYQ120PYDN
RXYQ240PYDN ............RXYQ120PYDN RXYQ120PYDN
The indoor units can be installed in the following range.
Outside unit〉 〈Total capacity index of indoor units
RXYQ72PYDN ..............36 ~ 93.5
RXYQ96PYDN ..............48 ~ 124.5
RXYQ120PYDN ............60 ~ 156
RXYQ144PYDN ............72 ~ 187
RXYQ168PYDN ............84 ~ 218
RXYQ192PYDN ............96 ~ 249.5
RXYQ216PYDN ............108 ~ 280.5
RXYQ240PYDN ............120 ~ 312
For installing the 2 units multi system, Outside unit multi connection piping kit "BHFP22P100U" are required.
If the total capacity of the connected indoor units exceeds the capac­ity of the outside unit, cooling and heating performance may drop when running the indoor units. See the capacity table in the Engi­neering Data Book for details.
2-2 Standard supplied accessories
Confirm the following accessories are included. The storage location of the accessories is shown in figure 1.
NOTE
Do not throw away any of the accessories until installation is complete. They are needed for installation work.
Independent units
Name
Quantity
Shape
Name
72P type
96P type
Quantity
120P type
Shape
Name
72P type
96P type
Quantity
120P type
Shape
Clamp(1)
9 pcs.
(Small)
Liquid side accessory pipe (1)
1 pc.
High side equalizer accessory pipe (1)
1 pc.
Clamp(2)
2 pcs.
Liquid side accessory pipe (2)
1 pc.
Clamp(3)
1 pc.
Operation manual
Installation manual
"REQUEST FOR THE INDICATON"
"ADDITIONAL REF. CHARGE" label
(Large)
Gas side accessory pipe (1)
1 pc.
1 pc.
φ3/4 φ7/8
High side equalizer accessory pipe (2)
Low side equalizer accessory pipe (1)
1 pc.
φ3/4 φ1 φ3/4
Low side equalizer accessory pipe (2)
1 pc.
O.D φ1 I.D φ1
Manuals, etc.
1 pc. about each item
label (Installation records)
Gas side accessory pipe (2)
1 pc.
1 pc.
1 pc.
φ1 φ1-1/8 φ7/8
L type accessory joint (1)
1 pc. 1 pc.
1 pc.
φ1
L type accessory joint (2)
2 pcs.
(Refer to figure 1)
1. Clamps, Manuals, etc.
2. Accessory pipes
2-3 Option accessory
To install the outside units, the following optional parts are also required. To select an optimum kit, refer to “6. REFRIGERANT PIPING”.
Outside unit multi connection piping kit
Number of outside units connected 2 units Kit name BHFP22P100U
Refrigerant branching kit
REFNET header KHRP26M22H KHRP26M33H KHRP26M72H REFNET joint KHRP26M22T KHRP26M33T
KHRP26M72TU KHRP26M73TU
Make sure that any separately purchased accessories are designed for use with R410A.
2-4 Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of specifications.
2-5 Main components
For main components and function of the main components, refer to the Engineering Data Book.
3. SELECTION OF LOCATION
Select a location for installation that meets the following conditions and get the customer’s permission.
1.
Select the location of the unit in such a way that neither the dis­charged air nor the sound generated by the unit disturb anyone.
2.
The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation.
3.
The piping length between the outside unit and the indoor unit may not exceed the allowable piping length. (Refer to “6. REFRIGERANT PIPING”)
4.
Locations where the unit’s suction vent and outlet vent do not gener­ally face the wind. Wind blowing directly into the suction or outlet vents will interfere with the unit’s operation. If necessary, install some kind of obstruction to block the wind.
5.
The space around the unit is adequate for servicing and the mini­mum space for air inlet and air outlet is available. (See the “Installation Space Examples” for the minimum space requirements.)
English 3
Installation Space Examples
The installation space requirement shown in figure 2 is a reference
for cooling operation when the outdoor temperature is 95°F. If the design outdoor temperature exceeds 95°F or the heat load exceeds maximum capacity in all the outside unit, take an even large space on the intake shown in figure 2.
During installation, install the units using the most appropriate of the patterns shown in figure 2 for the location in question, taking into consideration human traffic and wind.
If the number of units installed is more than that shown in the pattern in figure 2, install the units so there are no short circuits.
As regards space in front of the unit, consider the space needed for the local refrigerant piping when installing the units.
If the work conditions in figure 2 do not apply, contact your dealer or Daikin directly.
(Refer to figure 2)
1. Front side
2. No limit to wall height
3. Service space of front side
4. Service space of suction side
For Patterns 1 and 2 in figure 2 :
Wall height for front side – no higher than 59 in.
Wall height on the suction side – no higher than 19-5/8 in.
Wall height for sides – no limit.
If the height is exceeded the above, calculate h1 and h2 shown in
the figure below, and add h2/2 to the service space of front side and h1/2 to the service space of suction side.
h2
<Front side> <Suction side>
59
DANGER
• Do not install unit in an area where flammable materials are
present due to risk of explosion resulting in serious injury or death.
• Refrigerant gas in heavier air and replaces oxygen. A massive
leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious inju­ry or death. Refer to the chapter “CAUTION FOR REFRIGERANT LEAKS”
NOTE
1.
An inverter air conditioner may cause electronic noise generated from AM broadcasting. Examine where to install the main air condi­tioner and electric wires, keeping proper distances away from stereo equipment, personal computers, etc. Particularly for locations with weak reception, ensure there is a dis­tance of at least 10 ft for indoor remote controllers, place power wir­ing and transmission wiring in conduits, and ground the conduits.
(Refer to figure 3)
1. Indoor unit
2. Branch switch, overcurrent breaker
3. Remote controller
4. COOL/HEAT selector
5. Personal computer or radio
2.
When installing in locations where there is heavy snowfall, imple­ment the following snow measures.
Ensure the base is high enough that intakes are not clogged by
snow.
Remove the rear intake grille to prevent snow from accumulating
on the fins.
or more
2
h2
19 - 5/8 +
Service
space
or more
h1
+
2
h1
19-5/8
1.
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
2.
Decide on the transportation route.
3.
If a forklift is to be used, pass the forklift arms through the large open­ings on the bottom of the unit. (Refer to figure 4)
4.
If hanging the unit, use a cloth sling to prevent damaging the unit. Keeping the following points in mind, hang the unit following the pro­cedure shown in figure 5.
Use a sling sufficiently strong to hold the mass of the unit.
Use 2 belts of at least 27 ft long.
Place extra cloth or boards in the locations where the casing
comes in contact with the sling to prevent damage.
Hoist the unit making sure it is being lifted at its center of gravity.
5.
After installation, remove the transportation clasp (yellow) attached to the large openings. (Refer to figure 4)
(Refer to figure 4)
1. Packaging material
2. Forklift
3. Removal of shipping brackets
4. Shipping bracket (Remove the screws.)
(Refer to figure 5)
1. Belt sling
2. Wear plate
5. PLACING THE UNIT
Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise. (Refer to figure 6)
The base should support the unit with the extent larger than hatched
area in figure 7. If protective rubber is to be attached, attach it to the whole face of the base.
The height of the base should be at least 5-7/8 in. from the floor.
Secure the unit to its base using foundation bolts. (Use four commer-
cially available M12-type foundation bolts, nuts, and washers.)
The foundation bolts should be inserted 13/16 in..
(Refer to figure 6)
1. Independent base (four corner type)
2. Independent base (with center support type)
3. Beam base (Horizontal)
4. Beam base (Vertical)
5. Center of the product
(Refer to figure 7)
1. Foundation bolt point (φ9/16 in. dia, : 4positions)
2. (Depth of product)
3. (Inner dimension of the base)
4. (Outer dimension of the base)
Model A (in.) B (in.)
72 · 96 · 120P type 48-13/16 43-3/8
NOTE
There are restrictions on the refrigerant pipe connecting order
between outside unit in the case of the multi system. See “2-1 Combination” for detail.
When installing on a roof, make sure the roof floor is strong enough and be sure to water-proof all work.
Make sure the area around the machine drains properly by setting up drainage grooves around the foundation. Drain water is sometimes discharged from the outside unit when it is running.
For anti-corrosion type, use nuts with resin washers. If the paint on nut connections comes off, the anti-corrosion effect may decrease.
Resin washers
13/16 in.
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should
be reported immediately to the carrier claims agent.
When handling the unit, take into account the following :
4 English
Loading...
+ 17 hidden pages