Daikin RXH20CVMB, RXH25CVMB, RXH35CVMB Technical Data Manual

RXH-C
Pair Application,
Inverter Controlled Unit
technical data
Split Sky Air
air conditioning systems
Split - Sky Air
EEDE04-1/2 • 02/2004
Prepared in Belgium by Goekint Graphics
Zandvoordestraat 300 B - 8400 Ostend Belgium Internet: http://www.daikineurope.com
Specifications are subject to change without prior notice.
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products.
TABLE OF CONTENTS
RXH-C
1 Features ................................................................................. 2
2 Specifications
....................................................................... 3
Technical specifications Electrical specifications
3 Capacity tables ................................................................... 5
4 Dimensional drawings
..................................................... 7
5 Operation range
................................................................. 8
6 Piping diagrams
.................................................................. 9
7 Wiring diagrams
................................................................. 10
8 Sound level
.......................................................................... 11
Sound level data Sound pressure spectrum
9 Accessories .......................................................................... 13
Standard accessories Optional accessories
10 Center of gravity ................................................................ 14
11 Installation
............................................................................ 15
Pair Application, Inverter Controlled Unit R-410A RXH20-25-35CVMB
1
Split - Sky Air Outdoor Units
1
Features
Outdoor units for pair application
+ Daikin outdoor units can be mounted easily on a roof or terrace or simply placed against an outside wall.
They are fitted with a swing compressor, renowned for its low noise and high energy efficiency.
Pair Application, Inverter Controlled Unit R-410A RXH20-25-35CVMB
1
1
2
Split - Sky Air Outdoor Units
2
Specifications
TECHNICAL SPECIFICATIONS
OUTDOOR UNITS RXH20CVMB RXH25CVMB RXH35CVMB
DIMENSIONS Unit H mm 560
W mm 695
D mm 265 WEIGHT kg 31 COLOUR Unit Ivory white SOUND LEVEL Sound pressure (1) (Cooling) high/low dB(A) 46/* 46/* 48/*
Sound pressure (1) (Heating) high/low dB(A) 47/* 47/* 48/* Sound power (2) (Cooling) high dB(A) 61 61 63 Sound power (2) (Heating) high dB(A) 62 62 63
FAN Air flow rate (Cooling) high/low rpm 29/* 29/* 27.5/*
Air flow rate (Heating) high/low rpm 25.5/* 25.5/* 23.5/* Speed (Cooling) high rpm 720 720 710 Speed (Heating) high rpm 690 690 690 Model Propeller fan Motor output W 25
HEAT EXCHANGER Type Colgate fin,J8 grooved tube
Rows x stages x fin pitch mm 1 x 24 x 1.49 2 x 24 x 1.41
REFRIGERANT CIRCUIT Refrigerant type R-410A
Refrigerant charge kg 0.79 0.79 1.01 Maximum allowable distance between indoor and
outdoor
m
15 15 15
Maximum allowable level difference 15 15 15 Refrigerant control Motor operated expansion valve
COMPRESSOR Type Hermetically sealed swing type
Model 1YC23NXD#A Motor output 600 Oil type FVC50K Oil charge volume ! 0.375
PIPING CONNECTIONS liquid mm φ6.4
gas mm φ9.5
drain mm φ18.0 INSULATION MATERIAL Heat insulation Both liquid and gas pipes
* This information was not available at the time of publication.
ELECTRICAL SPECIFICATIONS
OUTDOOR UNITS RXH20CVMB RXH25CVMB RXH35CVMB
CURRENT Nominal running current
cooling/heating
A 3.12/3.82 3.52/4.22 4.72/4.72
Max. running current
cooling/heating
A Please refer to electrical data
Starting current
cooling/heating
A 4.0 4.4 4.9
OUTDOOR UNITS RXH20CVMB RXH25CVMB RXH35CVMB
POWER SUPPLY VM NOMINAL DISTRIBUTION
SYSTEM VOLTAGE
Phase 1 Frequency Hz 50 Voltage V 230
3D044446 3D044447 3D044448
NOTES
1 The sound pressure level is measured in an anechoic room at 1m distance from the unit. It is a relative value, depending on the distance and
acoustic environment. For measuring conditions: please refer to item 8 of this chapter.
2 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
Pair Application, Inverter Controlled Unit R-410A RXH20-25-35CVMB
1
2
3
Split - Sky Air Outdoor Units
ELECTRICAL DATA
RXH20CVMB
Indoor unit Outdoor unit
Power supply Compressor OFM IFM
Hz-Volts
Voltage range
MCA MFA RHz RLA W FLA W FLA
FTXS20CVMB RXH20CVMB 50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
14.0 15 42 2.81 25 0.35 18 0.20
3D044323
RXH25CVMB
Indoor unit Outdoor unit
Power supply Compressor OFM IFM
Hz-Volts
Voltage range
MCA MFA RHz RLA W FLA W FLA
FTXS25CVMB RXH25CVMB 50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
14.0 15 47 3.21 25 0.35 18 0.20
3D044324
RXH35CVMB
Indoor unit Outdoor unit
Power supply Compressor OFM IFM
Hz-Volts
Voltage range
MCA MFA RHz RLA W FLA W FLA
FTXS35CVMB RXH35CVMB 50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
14.0 15 70 4.41 25 0.35 18 0.20
3D044325
SYMBOLS
MCA : Min. Circuit Amps (A) MFA : Max. Fuse Amps (A) RHz : Rated operating frequency(Hz) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps W : Rated motor output (W)
NOTES
1. RLA is based on the following conditions: Indoor temp.: 27°CDB/19.0°CWB Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop down lists, click the search button. Finally, click on the document title of your choice.
Pair Application, Inverter Controlled Unit R-410A RXH20-25-35CVMB
2
Specifications
1
2
4
Split - Sky Air Outdoor Units