Daikin RXG35L Service Manual

Service
Manual
[Applied Models] z Inverter Pair : Heat Pump
Inverter Pair
Wall Mounted Type J-Series
SiBE041012_A
SiBE041012_A
i Table of Contents
Inverter Pair
Wall Mounted Type
J-Series
zHeat Pump
Indoor Unit
FTXG25JV1BW FTXG25JV1BS FTXG35JV1BW FTXG35JV1BS FTXG50JV1BW FTXG50JV1BS
Outdoor Unit
RXG25J2V1B RXG25K2V1B RXG35J2V1B RXG35K2V1B
RXG50K2V1B
SiBE041012_A
Table of Contents ii
1. Introduction ............................................................................................ vi
1.1 Safety Cautions ....................................................................................... vi
1.2 Used Icons ............................................................................................... x
Part 1 List of Functions ................................................................1
1. Functions.................................................................................................2
Part 2 Specifications .................................................................... 4
1. Specifications..........................................................................................5
Part 3 Printed Circuit Board Connector Wiring Diagram ...........10
1. Indoor Unit.............................................................................................11
2. Outdoor Unit..........................................................................................14
2.1 RXG25/35J2V1B, RXG25/35K2V1B ......................................................14
2.2 RXG50K2V1B ........................................................................................16
Part 4 Function and Control........................................................18
1. Main Functions......................................................................................19
1.1 Temperature Control ..............................................................................19
1.2 Frequency Principle................................................................................19
1.3 Operation Starting Control......................................................................21
1.4 Airflow Direction Control.........................................................................22
1.5 Fan Speed Control for Indoor Unit .........................................................23
1.6 Program Dry Operation ..........................................................................24
1.7 Automatic Operation...............................................................................25
1.8 Thermostat Control.................................................................................26
1.9 NIGHT SET Mode ..................................................................................27
1.10 ECONO Operation .................................................................................28
1.11 INTELLIGENT EYE Operation ...............................................................29
1.12 Inverter POWERFUL Operation .............................................................30
1.13 Other Functions......................................................................................32
2. Function of Thermistor ..........................................................................33
3. Control Specification .............................................................................34
3.1 Mode Hierarchy ......................................................................................34
3.2 Frequency Control..................................................................................35
3.3 Controls at Mode Changing / Start-up....................................................37
3.4 Discharge Pipe Temperature Control.....................................................39
3.5 Input Current Control ..............................................................................40
3.6 Freeze-up Protection Control .................................................................41
3.7 Heating Peak-cut Control .......................................................................41
3.8 Outdoor Fan Control...............................................................................42
3.9 Liquid Compression Protection Function................................................42
3.10 Defrost Control .......................................................................................43
3.11 Outdoor Electronic Expansion Valve Control .........................................44
3.12 Malfunctions ...........................................................................................47
Part 5 Operation Manual .............................................................48
1. System Configuration............................................................................49
SiBE041012_A
iii Table of Contents
2. Operation Manual..................................................................................50
2.1 Name of Parts ........................................................................................50
2.2 AUTO · DRY · COOL · HEAT · FAN Operation ......................................54
2.3 Adjusting the Airflow Direction and Rate ................................................56
2.4 COMFORT AIRFLOW Operation ...........................................................58
2.5 INTELLIGENT EYE Operation ...............................................................59
2.6 POWERFUL Operation ..........................................................................61
2.7 OUTDOOR UNIT QUIET Operation.......................................................62
2.8 ECONO Operation .................................................................................63
2.9 OFF TIMER Operation ...........................................................................64
2.10 ON TIMER Operation .............................................................................65
2.11 WEEKLY TIMER Operation ...................................................................66
Part 6 Service Diagnosis.............................................................72
1. Troubleshooting with LED.....................................................................74
1.1 Indoor Unit..............................................................................................74
1.2 Outdoor Unit ...........................................................................................74
2. Problem Symptoms and Measures.......................................................75
3. Service Check Function ........................................................................76
4. Troubleshooting ....................................................................................79
4.1 Error Codes and Description ..................................................................79
4.2 Indoor Unit PCB Abnormality .................................................................80
4.3 Freeze-up Protection Control or Heating Peak-cut Control....................82
4.4 Fan Motor (DC Motor) or Related Abnormality.......................................84
4.5 Thermistor or Related Abnormality (Indoor Unit)....................................86
4.6 Front Panel Open / Close Fault ..............................................................87
4.7 Signal Transmission Error (between Indoor Unit and Outdoor Unit)......88
4.8 Unspecified Voltage (between Indoor Unit and Outdoor Unit) ...............90
4.9 Outdoor Unit PCB Abnormality...............................................................91
4.10 OL Activation (Compressor Overload) ...................................................93
4.11 Compressor Lock ...................................................................................94
4.12 DC Fan Lock ..........................................................................................95
4.13 Input Overcurrent Detection ...................................................................96
4.14 Four Way Valve Abnormality..................................................................97
4.15 Discharge Pipe Temperature Control.....................................................99
4.16 High Pressure Control in Cooling .........................................................100
4.17 Compressor System Sensor Abnormality ............................................101
4.18 Position Sensor Abnormality ................................................................103
4.19 DC Voltage / Current Sensor Abnormality (25/35 Class) .....................106
4.20 CT or Related Abnormality (50 Class)..................................................107
4.21 Thermistor or Related Abnormality (Outdoor Unit)...............................109
4.22 Electrical Box Temperature Rise ..........................................................111
4.23 Radiation Fin Temperature Rise ..........................................................113
4.24 Output Overcurrent Detection ..............................................................115
4.25 Refrigerant Shortage ............................................................................117
4.26 Low-voltage Detection or Over-voltage Detection................................120
4.27 Signal Transmission Error on Outdoor Unit PCB (50 Class Only) .......122
5. Check ..................................................................................................123
5.1 Thermistor Resistance Check ..............................................................123
5.2 Fan Motor Connector Check ................................................................124
5.3 Power Supply Waveforms Check .........................................................124
SiBE041012_A
Table of Contents iv
5.4 Electronic Expansion Valve Coil Check ...............................................125
5.5 Four Way Valve Performance Check ...................................................126
5.6 Inverter Unit Refrigerant System Check...............................................126
5.7 “Inverter Checker” Check .....................................................................127
5.8 Rotation Pulse Check on the Outdoor Unit PCB ..................................129
5.9 Installation Condition Check .................................................................130
5.10 Discharge Pressure Check...................................................................130
5.11 Outdoor Fan System Check .................................................................131
5.12 Main Circuit Short Check......................................................................131
5.13 Capacitor Voltage Check......................................................................132
5.14 Power Module Check ...........................................................................132
Part 7 Removal Procedure ........................................................133
1. Indoor Unit...........................................................................................134
1.1 Removal of Air Filters / Front Panel .....................................................134
1.2 Removal of Horizontal Blades ..............................................................138
1.3 Removal of Front Grille ........................................................................140
1.4 Removal of Front Panel Mechanism ASSY..........................................143
1.5 Removal of Display Lens ASSY...........................................................145
1.6 Removal of Reduction Motor / Limit Switch..........................................146
1.7 Removal of Fan Guards / Electrical Box ..............................................148
1.8 Removal of PCBs .................................................................................151
1.9 Removal of Swing Motors ....................................................................157
1.10 Removal of Indoor Heat Exchanger .....................................................158
1.11 Removal of Fan Rotor / Fan Motor.......................................................161
1.12 Removal of Vertical Blade ASSYs........................................................164
2. Outdoor Unit - 25/35 Class..................................................................165
2.1 Removal of Outer Panels / Fan Motor ..................................................165
2.2 Removal of Electrical Box ....................................................................174
2.3 Removal of PCBs .................................................................................177
2.4 Removal of Reactor / Partition Plate ....................................................185
2.5 Removal of Sound Blankets .................................................................187
2.6 Removal of Four Way Valve.................................................................189
2.7 Removal of Compressor.......................................................................192
3. Outdoor Unit - 50 Class.......................................................................194
3.1 Removal of Outer Panels .....................................................................194
3.2 Removal of Outdoor Fan / Fan Motor...................................................198
3.3 Removal of Electrical Box ....................................................................202
3.4 Removal of PCBs .................................................................................207
3.5 Removal of Sound Blankets / Thermistors ...........................................210
3.6 Removal of Four Way Valve.................................................................212
3.7 Removal of Electronic Expansion Valve...............................................213
3.8 Removal of Compressor.......................................................................214
Part 8 Trial Operation and Field Settings.................................217
1. Pump Down Operation........................................................................218
2. Forced Cooling Operation...................................................................219
3. Trial Operation ....................................................................................221
4. Field Settings ......................................................................................222
4.1 When 2 Units are Installed in 1 Room ..................................................222
SiBE041012_A
v Table of Contents
4.2 Standby Electricity Saving....................................................................223
4.3 Jumper and Switch Settings .................................................................223
5. Application of Silicon Grease to a Power Transistor
and a Diode Bridge .............................................................................224
Part 9 Appendix.........................................................................225
1. Piping Diagrams..................................................................................226
1.1 Indoor Unit............................................................................................226
1.2 Outdoor Unit .........................................................................................226
2. Wiring Diagrams..................................................................................228
2.1 Indoor Unit............................................................................................228
2.2 Outdoor Unit .........................................................................................228
SiBE041012_A Introduction
vi
1. Introduction
1.1 Safety Cautions
Cautions and Warnings
Be sure to read the following safety cautions before conducting repair work.
The caution items are classified into “ Warning” and “ Caution”. The “ Warning”
items are especially important since they can lead to death or serious injury if they are not followed closely. The “ Caution” items can also lead to serious accidents under some conditions if they are not followed. Therefore, be sure to observe all the safety caution items described below.
About the pictograms
This symbol indicates the item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates the prohibited action.
The prohibited item or action is shown in the illustration or near the symbol.
This symbol indicates the action that must be taken, or the instruction.
The instruction is shown in the illustration or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer.
1.1.1 Cautions Regarding Safety of Workers
Warning
Be sure to disconnect the power cable plug from the plug socket before disassembling the equipment for repair. Working on the equipment that is connected to the power supply may cause an electrical shock. If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits, do not touch any electrically charged sections of the equipment.
If the refrigerant gas is discharged during the repair work, do not touch the discharged refrigerant gas. The refrigerant gas may cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the welded section, evacuate the refrigerant gas completely at a well-ventilated place first. If there is gas remaining inside the compressor, the refrigerant gas or refrigerating machine oil discharges when the pipe is disconnected, and it may cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The refrigerant gas may generate toxic gases when it contacts flames.
The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. Be sure to discharge the capacitor completely before conducting repair work. A charged capacitor may cause an electrical shock.
Do not start or stop the air conditioner operation by plugging or unplugging the power cable plug. Plugging or unplugging the power cable plug to operate the equipment may cause an electrical shock or fire.
Introduction SiBE041012_A
vii
Be sure to wear a safety helmet, gloves, and a safety belt when working at a high place (more than 2 m). Insufficient safety measures may cause a fall accident.
In case of R-410A refrigerant models, be sure to use pipes, flare nuts and tools for the exclusive use of the R-410A refrigerant. The use of materials for R-22 refrigerant models may cause a serious accident such as a damage of refrigerant cycle as well as an equipment failure.
Warning
Caution
Do not repair the electrical components with wet hands. Working on the equipment with wet hands may cause an electrical shock.
Do not clean the air conditioner by splashing water. Washing the unit with water may cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning the equipment. The internal fan rotates at a high speed, and may cause injury.
Be sure to conduct repair work with appropriate tools. The use of inappropriate tools may cause injury.
Be sure to check that the refrigerating cycle section has cooled down enough before conducting repair work. Working on the unit when the refrigerating cycle section is hot may cause burns.
Use the welder in a well-ventilated place. Using the welder in an enclosed room may cause oxygen deficiency.
SiBE041012_A Introduction
viii
1.1.2 Cautions Regarding Safety of Users
Warning
Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools may cause an electrical shock, excessive heat generation or fire.
If the power cable and lead wires have scratches or deteriorated, be sure to replace them. Damaged cable and wires may cause an electrical shock, excessive heat generation or fire.
Do not use a joined power cable or extension cable, or share the same power outlet with other electrical appliances, since it may cause an electrical shock, excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and follow the local technical standards related to the electrical equipment, the internal wiring regulations, and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work may cause an electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and outdoor units. Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals. Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that the terminal cover does not lift off or dismount because of the cable. If the cover is not mounted properly, the terminal connection section may cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable. Damaged or modified power cable may cause an electrical shock or fire. Placing heavy items on the power cable, and heating or pulling the power cable may damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A / R-22) in the refrigerant system. If air enters the refrigerating system, an excessively high pressure results, causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and repair it before charging the refrigerant. After charging refrigerant, make sure that there is no refrigerant leak. If the leaking point cannot be located and the repair work must be stopped, be sure to perform pump-down and close the service valve, to prevent the refrigerant gas from leaking into the room. The refrigerant gas itself is harmless, but it may generate toxic gases when it contacts flames, such as fan and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation site has sufficient strength to withstand the weight of the equipment. If the installation site does not have sufficient strength and if the installation work is not conducted securely, the equipment may fall and cause injury.
Introduction SiBE041012_A
ix
Check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet securely. If the plug has dust or loose connection, it may cause an electrical shock or fire.
Be sure to install the product correctly by using the provided standard installation frame. Incorrect use of the installation frame and improper installation may cause the equipment to fall, resulting in injury.
For unitary type only
Be sure to install the product securely in the installation frame mounted on the window frame. If the unit is not securely mounted, it may fall and cause injury.
For unitary type only
When replacing the coin battery in the remote controller, be sure to dispose of the old battery to prevent children from swallowing it. If a child swallows the coin battery, see a doctor immediately.
Warning
Caution
Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of combustible gas leaks. If the combustible gas leaks and remains around the unit, it may cause a fire.
Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections may cause excessive heat generation, fire or an electrical shock.
If the installation platform or frame has corroded, replace it. Corroded installation platform or frame may cause the unit to fall, resulting in injury.
Check the grounding, and repair it if the equipment is not properly grounded. Improper grounding may cause an electrical shock.
SiBE041012_A Introduction
x
1.2 Used Icons
Icons are used to attract the attention of the reader to specific information. The meaning of each icon is described in the table below:
Be sure to measure the insulation resistance after the repair, and make sure that the resistance is 1 M or higher. Faulty insulation may cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair. Faulty drainage may cause the water to enter the room and wet the furniture and floor.
Do not tilt the unit when removing it. The water inside the unit may spill and wet the furniture and floor.
Be sure to install the packing and seal on the installation frame properly. If the packing and seal are not installed properly, water may enter the room and wet the furniture and floor.
For unitary type only
Caution
Icon Type of
Information
Description
Note:
Note A “note” provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Caution
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get an unexpected result or has to restart (part of) a procedure.
Warning
Warning A “warning” is used when there is danger of personal injury.
Reference A “reference” guides the reader to other places in this binder or
in this manual, where he/she will find additional information on a specific topic.
SiBE041012_A
1 List of Functions
Part 1
List of Functions
1. Functions.................................................................................................2
SiBE041012_A Functions
List of Functions 2
1. Functions
Category Functions
FTXG25/35JV1BW(S)
RXG25/35J2V1B
Category Functions
FTXG25/35JV1BW(S)
RXG25/35J2V1B
Basic Function Inverter (with Inverter Power Control)
z
Health & Clean Air-Purifying Filter
Operation Limit for Cooling (°CDB)
–10
~ 46
Photocatalytic Deodorizing Filter
Operation Limit for Heating (°CWB)
–15
~ 20
Air-Purifying Filter with Photocatalytic Deodorizing Function
PAM Control
z
Titanium Apatite Photocatalytic Air-Purifying Filter
z
Standby Electricity Saving
z
Compressor Oval Scroll Compressor Air Filter (Prefilter)
z
Swing Compressor
z
Wipe-Clean Flat Panel
z
Rotary Compressor Washable Grille
Reluctance DC Motor
z
MOLD PROOF Operation
Comfortable Airflow
Power-Airflow Flap Heating Dry Operation
Power-Airflow Dual Flaps
z
Good-Sleep Cooling Operation
Power-Airflow Diffuser Timer WEEKLY TIMER Operation
z
Wide-Angle Louvers
z
24-Hour ON/OFF TIMER
z
Vertical Auto-Swing (Up and Down)
z
NIGHT SET Mode
z
Horizontal Auto-Swing (Right and Left) — Worry Free
“Reliability & Durability”
Auto-Restart (after Power Failure)
z
3-D Airflow Self-Diagnosis (Digital, LED) Display
z
COMFORT AIRFLOW Operation
z
Wiring Error Check Function
Comfort Control
Auto Fan Speed
z
Anti-Corrosion Treatment of Outdoor Heat Exchanger
z
Indoor Unit Quiet Operation
z
NIGHT QUIET Mode (Automatic) — Flexibility Multi-Split / Split Type Compatible Indoor Unit
z
OUTDOOR UNIT QUIET Operation (Manual)
z
Flexible Power Supply Correspondence
INTELLIGENT EYE Operation
z
High Ceiling Application
Quick Warming Function (Preheating Operation)
z
Chargeless 10 m
Hot-Start Function
z
Either Side Drain (Right or Left)
z
Automatic Defrosting
z
Power Selection
Operation Automatic Operation
z
Remote Control
5-Room Centralized Controller (Option)
z
Program Dry Operation
z
Fan Only
z
Remote Control Adaptor (Normal Open Pulse Contact) (Option)
z
Lifestyle Convenience
New POWERFUL Operation (Non-Inverter)
Remote Control Adaptor (Normal Open Contact) (Option)
z
Inverter POWERFUL Operation
z
DIII-NET Compatible (Adaptor) (Option)
z
Priority-Room Setting — Remote
Controller
Wireless
z
COOL / HEAT Mode Lock Wired (Option)
z
HOME LEAVE Operation
ECONO Operation
z
Indoor Unit ON/OFF Button
z
Signal Receiving Sign
z
Multi-Colored Indicator Lamp (Multi-Monitor Lamp)
z
R/C with Back Light
z
Temperature Display
Note:
z
: Holding Functions
— : No Functions
Functions SiBE041012_A
3 List of Functions
Category Functions
FTXG25/35JV1BW(S)
RXG25/35K2V1B
FTXG50JV1BW(S)
RXG50K2V1B
Category Functions
FTXG25/35JV1BW(S)
RXG25/35K2V1B
FTXG50JV1BW(S)
RXG50K2V1B
Basic Function Inverter (with Inverter Power Control)
zz
Health & Clean Air-Purifying Filter
Operation Limit for Cooling (°CDB)
10
~ 4610~ 46
Photocatalytic Deodorizing Filter
Operation Limit for Heating (°CWB)
–15
~ 20
–15
~ 20
Air-Purifying Filter with Photocatalytic Deodorizing Function
——
PAM Control
zz
Titanium Apatite Photocatalytic Air-Purifying Filter
zz
Standby Electricity Saving
z
Compressor Oval Scroll Compressor Air Filter (Prefilter)
zz
Swing Compressor
zz
Wipe-Clean Flat Panel
zz
Rotary Compressor Washable Grille
Reluctance DC Motor
zz
MOLD PROOF Operation
Comfortable Airflow
Power-Airflow Flap Heating Dry Operation
Power-Airflow Dual Flaps
zz
Good-Sleep Cooling Operation
Power-Airflow Diffuser — Timer WEEKLY TIMER Operation
zz
Wide-Angle Louvers
zz
24-Hour ON/OFF TIMER
zz
Vertical Auto-Swing (Up and Down)
zz
NIGHT SET Mode
zz
Horizontal Auto-Swing (Right and Left) Worry Free
“Reliability & Durability”
Auto-Restart (after Power Failure)
zz
3-D Airflow Self-Diagnosis (Digital, LED) Display
zz
COMFORT AIRFLOW Operation
zz
Wiring Error Check Function
Comfort Control
Auto Fan Speed
zz
Anti-Corrosion Treatment of Outdoor Heat Exchanger
zz
Indoor Unit Quiet Operation
zz
NIGHT QUIET Mode (Automatic) Flexibility
Multi-Split / Split Type Compatible Indoor Unit
zz
OUTDOOR UNIT QUIET Operation (Manual)
zz
INTELLIGENT EYE Operation
zz
Flexible Power Supply Correspondence
——
Quick Warming Function (Preheating Operation)
zz
High Ceiling Application
Hot-Start Function
zz
Chargeless 10 m 10 m
Automatic Defrosting
zz
Either Side Drain (Right or Left)
zz
Operation Automatic Operation
zz
Power Selection
Program Dry Operation
zz
Remote Control
5-Room Centralized Controller (Option)
zz
Fan Only
zz
Lifestyle Convenience
New POWERFUL Operation (Non-Inverter)
——
Remote Control Adaptor (Normal Open Pulse Contact) (Option)
zz
Inverter POWERFUL Operation
zz
Remote Control Adaptor (Normal Open Contact) (Option)
zz
Priority-Room Setting
DIII-NET Compatible (Adaptor) (Option)
zz
COOL / HEAT Mode Lock Remote
Controller
Wireless
zz
HOME LEAVE Operation Wired (Option)
zz
ECONO Operation
zz
Indoor Unit ON/OFF Button
zz
Signal Receiving Sign
zz
Multi-Colored Indicator Lamp (Multi-Monitor Lamp)
zz
R/C with Back Light
zz
Temperature Display
Note:
z
: Holding Functions
— : No Functions
SiBE041012_A
Specifications 4
Part 2
Specifications
1. Specifications..........................................................................................5
Specifications SiBE041012_A
5 Specifications
1. Specifications
50 Hz, 220 - 230 - 240 V
Note:
The data are based on the conditions shown in the table below.
Models
Indoor Unit FTXG25JV1BW FTXG25JV1BS
Outdoor Unit
RXG25J2V1B RXG25J2V1B
Cooling Heating Cooling Heating
Capacity Rated (Min. ~ Max.)
kW 2.5 (1.3 ~ 3.0) 3.4 (1.3 ~ 4.5) 2.5 (1.3 ~ 3.0) 3.4 (1.3 ~ 4.5)
Btu/h 8,500 (4,400 ~ 10,200) 11,600 (4,400 ~ 15,400) 8,500 (4,400 ~ 10,200) 11,600 (4,400 ~ 15,400)
kcal/h 2,150 (1,120 ~ 2,580) 2,920 (1,120 ~ 3,870) 2,150 (1,120 ~ 2,580) 2,920 (1,120 ~ 3,870) Running Current (Rated) A 3.2 - 3.0 - 2.9 4.4 - 4.2 - 4.1 3.2 - 3.0 - 2.9 4.4 - 4.2 - 4.1 Power Consumption
Rated (Min. ~ Max.)
W 560 (350 ~ 820) 780 (320 ~ 1,320) 560 (350 ~ 820) 780 (320 ~ 1,320)
Power Factor % 79.5 - 81.2 - 80.5 80.6 - 80.7 - 79.3 79.5 - 81.2 - 80.5 80.6 - 80.7 - 79.3 EER (Cooling) / COP (Heating)
Rated (Min. ~ Max.)
W/W 4.46 (3.71 ~ 3.66) 4.36 (4.06 ~ 3.41) 4.46 (3.71 ~ 3.66) 4.36 (4.06 ~ 3.41)
Piping Connections
Liquid mm φ 6.4 φ 6.4 Gas mm φ 9.5 φ 9.5
Drain mm φ 16.0 or φ 18.0 φ 16.0 or φ 18.0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length m 20 20 Max. Interunit Height Difference m 15 15 Chargeless m 10 10 Amount of Additional Charge of
Refrigerant
g/m 20 20
Indoor Unit FTXG25JV1BW FTXG25JV1BS
Front Panel Color White Silver
Airflow Rate
H
m³/min
(cfm)
8.8 (311) 9.6 (339) 8.8 (311) 9.6 (339) M 6.8 (240) 7.9 (279) 6.8 (240) 7.9 (279) L 4.7 (166) 6.2 (219) 4.7 (166) 6.2 (219) SL 3.8 (134) 5.4 (191) 3.8 (134) 5.4 (191)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 29 29 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.09 - 0.08 - 0.08 0.12 - 0.11 - 0.11 0.09 - 0.08 - 0.08 0.12 - 0.11 - 0.11 Power Consumption (Rated) W 18 - 18 - 18 24 - 24 - 24 18 - 18 - 18 24 - 24 - 24 Power Factor % 90.9 - 97.8 - 93.8 90.9 - 94.9 - 90.9 90.9 - 97.8 - 93.8 90.9 - 94.9 - 90.9 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) mm 295 × 915 × 155 295 × 915 × 155 Packaged Dimensions (H × W × D) mm 285 × 1,003 × 377 285 × 1,003 × 377 Weight kg 11 11 Gross Weight kg 15 16 Sound
Pressure Level
H / M / L / SL dB(A) 38 / 32 / 25 / 22 39 / 34 / 28 / 25 38 / 32 / 25 / 22 39 / 34 / 28 / 25
Sound Power Level dB 54 55 54 55
Outdoor Unit RXG25J2V1B RXG25J2V1B
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 1YC23AEXD 1YC23AEXD Motor Output W 600 600
Refrigerant Oil
Type FVC50K FVC50K Charge L 0.375 0.375
Refrigerant
Type R-410A R-410A Charge kg 1.05 1.05
Airflow Rate
H
m³/min
(cfm)
33.5 (1,183) 30.2 (1,066) 33.5 (1,183) 30.2 (1,066)
SL 30.1 (1,063) 25.6 (904) 30.1 (1,063) 25.6 (904)
Fan
Type Propeller Propeller Motor Output W 23 23
Running Current (Rated) A 3.11 - 2.92 - 2.82 4.28 - 4.09 - 3.99 3.11 - 2.92 - 2.82 4.28 - 4.09 - 3.99 Power Consumption (Rated) W 542 - 542 - 542 756 - 756 - 756 542 - 542 - 542 756 - 756 - 756 Power Factor % 79.2 - 80.7 - 80.1 80.3 - 80.4 - 79.0 79.2 - 80.7 - 80.1 80.3 - 80.4 - 79.0 Starting Current A 4.4 4.4 Dimensions (H × W × D) mm 550 × 765 × 285 550 × 765 × 285 Packaged Dimensions (H × W × D) mm 612 × 906 × 364 612 × 906 × 364 Weight kg 34 34 Gross Weight kg 38 38 Sound
Pressure Level
H / SL dB(A) 46 / 43 47 / 44 46 / 43 47 / 44
Sound Power Level
HdB61626162
Drawing No. 3D066165A 3D066436A
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling Heating Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB / 24°CWB
Indoor ; 20°CDB
Outdoor ; 7°CDB / 6°CWB
5 m
SiBE041012_A Specifications
Specifications 6
50 Hz, 220 - 230 - 240 V
Note:
The data are based on the conditions shown in the table below.
Models
Indoor Unit FTXG35JV1BW FTXG35JV1BS
Outdoor Unit
RXG35J2V1B RXG35J2V1B
Cooling Heating Cooling Heating
Capacity Rated (Min. ~ Max.)
kW 3.5 (1.4 ~ 3.8) 4.0 (1.4 ~ 5.0) 3.5 (1.4 ~ 3.8) 4.0 (1.4 ~ 5.0)
Btu/h 11,900 (4,800 ~ 13,000) 13,600 (4800 ~ 17,100) 11,900 (4,800 ~ 13,000) 13,600 (4800 ~ 17,100)
kcal/h 3,010 (1,200 ~ 3,270) 3,440 (1,200 ~ 4,300) 3,010 (1,200 ~ 3,270) 3,440 (1,200 ~ 4,300) Running Current (Rated) A 5.1 - 4.8 - 4.6 5.6 - 5.3 - 5.1 5.1 - 4.8 - 4.6 5.6 - 5.3 - 5. 1 Power Consumption
Rated (Min. ~ Max.)
W 890 (360 ~ 1,220) 990 (320 ~ 1,500) 890 (360 ~ 1,220) 990 (320 ~ 1,500)
Power Factor % 79.3 - 80.6 - 80.6 80.4 - 81.2 - 80.9 79.3 - 80.6 - 80.6 80.4 - 81.2 - 80.9 EER (Cooling) / COP (Heating)
Rated (Min. ~ Max.)
W/W 3.93 (3.89 ~ 3.11) 4.04 (4.38 ~ 3.33) 3.93 (3.89 ~ 3.11) 4.04 (4.38 ~ 3.33)
Piping Connections
Liquid mm φ 6.4 φ 6.4 Gas mm φ 9.5 φ 9.5
Drain mm φ 16.0 or φ 18.0 φ 16.0 or φ 18.0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length m 20 20 Max. Interunit Height Difference m 15 15 Chargeless m 10 10 Amount of Additional Charge of
Refrigerant
g/m 20 20
Indoor Unit FTXG35JV1BW FTXG35JV1BS
Front Panel Color White Silver
Airflow Rate
H
m³/min
(cfm)
10.1 (357) 10.8 (381) 10.1 (357) 10.8 (381) M 7.3 (258) 8.6 (304) 7.3 (258) 8.6 (304) L 4.6 (162) 6.4 (226) 4.6 (162) 6.4 (226) SL 3.9 (138) 5.6 (198) 3.9 (138) 5.6 (198)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 29 29 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.13 - 0.12 - 0.12 0.16 - 0.15 - 0.14 0.13 - 0.12 - 0.12 0.16 - 0.15 - 0.14 Power Consumption (Rated) W 26 - 26 - 26 32 - 32 - 32 26 - 26 - 26 32 - 32 - 32 Power Factor % 90.9 - 94.2 - 90.3 90.9 - 92.8 - 95.2 90.9 - 94.2 - 90.3 90.9 - 92.8 - 95.2 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) mm 295 × 915 × 155 295 × 915 × 155 Packaged Dimensions (H × W × D) mm 285 × 1,003 × 377 285 × 1,003 × 377 Weight kg 11 11 Gross Weight kg 15 16 Sound
Pressure Level
H / M / L / SL dB(A) 42 / 34 / 26 / 23 42 / 36 / 29 / 26 42 / 34 / 26 / 23 42 / 36 / 29 / 26
Sound Power Level dB 58 58 58 58
Outdoor Unit RXG35J2V1B RXG35J2V1B
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 1YC23AEXD 1YC23AEXD Motor Output W 600 600
Refrigerant Oil
Type FVC50K FVC50K Charge L 0.375 0.375
Refrigerant
Type R-410A R-410A Charge kg 1.05 1.05
Airflow Rate
H
m³/min
(cfm)
36.0 (1,271) 30.2 (1,066) 36.0 (1,271) 30.2 (1,066)
SL 30.1 (1,063) 25.6 (904) 30.1 (1,063) 25.6 (904)
Fan
Type Propeller Propeller Motor Output W 23 23
Running Current (Rated) A 4.97 - 4.68 - 4.48 5.44 - 5.15 - 4.96 4.97 - 4.68 - 4.48 5.44 - 5.15 - 4.96 Power Consumption (Rated) W 864 - 864 - 864 958 - 958 - 958 864 - 864 - 864 958 - 958 - 958 Power Factor % 79.0 - 80.3 - 80.3 80.1 - 80.9 - 80.5 79.0 - 80.3 - 80.3 80.1 - 80.9 - 80.5 Starting Current A 5.6 5.6 Dimensions (H × W × D) mm 550 × 765 × 285 550 × 765 × 285 Packaged Dimensions (H × W × D) mm 612 × 906 × 364 612 × 906 × 364 Weight kg 34 34 Gross Weight kg 38 38 Sound
Pressure Level
H / SL dB(A) 48 / 44 48 / 45 48 / 44 48 / 45
Sound Power Level
HdB63636363
Drawing No. 3D066437A 3D066438A
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling Heating Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB / 24°CWB
Indoor ; 20°CDB
Outdoor ; 7°CDB / 6°CWB
5 m
Specifications SiBE041012_A
7 Specifications
50 Hz, 220 - 230 - 240 V
Note:
The data are based on the conditions shown in the table below.
Models
Indoor Unit FTXG25JV1BW FTXG25JV1BS
Outdoor Unit
RXG25K2V1B RXG25K2V1B
Cooling Heating Cooling Heating
Capacity Rated (Min. ~ Max.)
kW 2.5 (1.3 ~ 3.0) 3.4 (1.3 ~ 4.5) 2.5 (1.3 ~ 3.0) 3.4 (1.3 ~ 4.5)
Btu/h 8,500 (4,400 ~ 10,200) 11,600 (4,400 ~ 15,400) 8,500 (4,400 ~ 10,200) 11,600 (4,400 ~ 15,400)
kcal/h 2,150 (1,120 ~ 2,580) 2,920 (1,120 ~ 3,870) 2,150 (1,120 ~ 2,580) 2,920 (1,120 ~ 3,870) Running Current (Rated) A 3.2 - 3.0 - 2.9 4.4 - 4.2 - 4.1 3.2 - 3.0 - 2.9 4.4 - 4.2 - 4. 1 Power Consumption
Rated (Min. ~ Max.)
W 560 (350 ~ 820) 780 (320 ~ 1,320) 560 (350 ~ 820) 780 (320 ~ 1,320)
Power Factor % 79.5 - 81.2 - 80.5 80.6 - 80.7 - 79.3 79.5 - 81.2 - 80.5 80.6 - 80.7 - 79.3 EER (Cooling) / COP (Heating)
Rated (Min. ~ Max.)
W/W 4.46 (3.71 ~ 3.66) 4.36 (4.06 ~ 3.41) 4.46 (3.71 ~ 3.66) 4.36 (4.06 ~ 3.41)
Piping Connections
Liquid mm φ 6.4 φ 6.4 Gas mm φ 9.5 φ 9.5
Drain mm φ 16.0 or φ 18.0 φ 16.0 or φ 18.0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length m 20 20 Max. Interunit Height Difference m 15 15 Chargeless m 10 10 Amount of Additional Charge of
Refrigerant
g/m 20 20
Indoor Unit FTXG25JV1BW FTXG25JV1BS
Front Panel Color White Silver
Airflow Rate
H
m³/min
(cfm)
8.8 (311) 9.6 (339) 8.8 (311) 9.6 (339) M 6.8 (240) 7.9 (279) 6.8 (240) 7.9 (279) L 4.7 (166) 6.2 (219) 4.7 (166) 6.2 (219) SL 3.8 (134) 5.4 (191) 3.8 (134) 5.4 (191)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 29 29 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.09 - 0.08 - 0.08 0.12 - 0.11 - 0.11 0.09 - 0.08 - 0.08 0.12 - 0.11 - 0.11 Power Consumption (Rated) W 18 - 18 - 18 24 - 24 - 24 18 - 18 - 18 24 - 24 - 24 Power Factor % 90.9 - 97.8 - 93.8 90.9 - 94.9 - 90.9 90.9 - 97.8 - 93.8 90.9 - 94.9 - 90.9 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) mm 295 × 915 × 155 295 × 915 × 155 Packaged Dimensions (H × W × D) mm 285 × 1,003 × 377 285 × 1,003 × 377 Weight kg 11 11 Gross Weight kg 15 16 Sound
Pressure Level
H / M / L / SL dB(A) 38 / 32 / 25 / 22 39 / 34 / 28 / 25 38 / 32 / 25 / 22 39 / 34 / 28 / 25
Sound Power Level dB 54 55 54 55
Outdoor Unit RXG25K2V1B RXG25K2V1B
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 1YC23AEXD 1YC23AEXD Motor Output W 600 600
Refrigerant Oil
Type FVC50K FVC50K Charge L 0.375 0.375
Refrigerant
Type R-410A R-410A Charge kg 1.05 1.05
Airflow Rate
H
m³/min
(cfm)
33.5 (1,183) 30.2 (1,066) 33.5 (1,183) 30.2 (1,066)
SL 30.1 (1,063) 25.6 (904) 30.1 (1,063) 25.6 (904)
Fan
Type Propeller Propeller Motor Output W 23 23
Running Current (Rated) A 3.11 - 2.92 - 2.82 4.28 - 4.09 - 3.99 3.11 - 2.92 - 2.82 4.28 - 4.09 - 3.99 Power Consumption (Rated) W 542 - 542 - 542 756 - 756 - 756 542 - 542 - 542 756 - 756 - 756 Power Factor % 79.2 - 80.7 - 80.1 80.3 - 80.4 - 79.0 79.2 - 80.7 - 80.1 80.3 - 80.4 - 79.0 Starting Current A 4.4 4.4 Dimensions (H × W × D) mm 550 × 765 × 285 550 × 765 × 285 Packaged Dimensions (H × W × D) mm 612 × 906 × 364 612 × 906 × 364 Weight kg 34 34 Gross Weight kg 38 38 Sound
Pressure Level
H / SL dB(A) 46 / 43 47 / 44 46 / 43 47 / 44
Sound Power Level
HdB61626162
Drawing No. 3D072846 3D072844
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling Heating Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB / 24°CWB
Indoor ; 20°CDB
Outdoor ; 7°CDB / 6°CWB
5 m
SiBE041012_A Specifications
Specifications 8
50 Hz, 220 - 230 - 240 V
Note:
The data are based on the conditions shown in the table below.
Models
Indoor Unit FTXG35JV1BW FTXG35JV1BS
Outdoor Unit
RXG35K2V1B RXG35K2V1B
Cooling Heating Cooling Heating
Capacity Rated (Min. ~ Max.)
kW 3.5 (1.4 ~ 3.8) 4.0 (1.4 ~ 5.0) 3.5 (1.4 ~ 3.8) 4.0 (1.4 ~ 5.0)
Btu/h 11,900 (4,800 ~ 13,000) 13,600 (4800 ~ 17,100) 11,900 (4,800 ~ 13,000) 13,600 (4800 ~ 17,100)
kcal/h 3,010 (1,200 ~ 3,270) 3,440 (1,200 ~ 4,300) 3,010 (1,200 ~ 3,270) 3,440 (1,200 ~ 4,300) Running Current (Rated) A 5.1 - 4.8 - 4.6 5.6 - 5.3 - 5.1 5.1 - 4.8 - 4.6 5.6 - 5.3 - 5. 1 Power Consumption
Rated (Min. ~ Max.)
W 890 (360 ~ 1,220) 990 (320 ~ 1,500) 890 (360 ~ 1,220) 990 (320 ~ 1,500)
Power Factor % 79.3 - 80.6 - 80.6 80.4 - 81.2 - 80.9 79.3 - 80.6 - 80.6 80.4 - 81.2 - 80.9 EER (Cooling) / COP (Heating)
Rated (Min. ~ Max.)
W/W 3.93 (3.89 ~ 3.11) 4.04 (4.38 ~ 3.33) 3.93 (3.89 ~ 3.11) 4.04 (4.38 ~ 3.33)
Piping Connections
Liquid mm φ 6.4 φ 6.4 Gas mm φ 9.5 φ 9.5
Drain mm φ 16.0 or φ 18.0 φ 16.0 or φ 18.0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length m 20 20 Max. Interunit Height Difference m 15 15 Chargeless m 10 10 Amount of Additional Charge of
Refrigerant
g/m 20 20
Indoor Unit FTXG35JV1BW FTXG35JV1BS
Front Panel Color White Silver
Airflow Rate
H
m³/min
(cfm)
10.1 (357) 10.8 (381) 10.1 (357) 10.8 (381) M 7.3 (258) 8.6 (304) 7.3 (258) 8.6 (304) L 4.6 (162) 6.4 (226) 4.6 (162) 6.4 (226) SL 3.9 (138) 5.6 (198) 3.9 (138) 5.6 (198)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 29 29 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.13 - 0.12 - 0.12 0.16 - 0.15 - 0.14 0.13 - 0.12 - 0.12 0.16 - 0.15 - 0.14 Power Consumption (Rated) W 26 - 26 - 26 32 - 32 - 32 26 - 26 - 26 32 - 32 - 32 Power Factor % 90.9 - 94.2 - 90.3 90.9 - 92.8 - 95.2 90.9 - 94.2 - 90.3 90.9 - 92.8 - 95.2 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) mm 295 × 915 × 155 295 × 915 × 155 Packaged Dimensions (H × W × D) mm 285 × 1,003 × 377 285 × 1,003 × 377 Weight kg 11 11 Gross Weight kg 15 16 Sound
Pressure Level
H / M / L / SL dB(A) 42 / 34 / 26 / 23 42 / 36 / 29 / 26 42 / 34 / 26 / 23 42 / 36 / 29 / 26
Sound Power Level dB 58 58 58 58
Outdoor Unit RXG35K2V1B RXG35K2V1B
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 1YC23AEXD 1YC23AEXD Motor Output W 600 600
Refrigerant Oil
Type FVC50K FVC50K Charge L 0.375 0.375
Refrigerant
Type R-410A R-410A Charge kg 1.05 1.05
Airflow Rate
H
m³/min
(cfm)
36.0 (1,271) 30.2 (1,066) 36.0 (1,271) 30.2 (1,066)
SL 30.1 (1,063) 25.6 (904) 30.1 (1,063) 25.6 (904)
Fan
Type Propeller Propeller Motor Output W 23 23
Running Current (Rated) A 4.97 - 4.68 - 4.48 5.44 - 5.15 - 4.96 4.97 - 4.68 - 4.48 5.44 - 5.15 - 4.96 Power Consumption (Rated) W 864 - 864 - 864 958 - 958 - 958 864 - 864 - 864 958 - 958 - 958 Power Factor % 79.0 - 80.3 - 80.3 80.1 - 80.9 - 80.5 79.0 - 80.3 - 80.3 80.1 - 80.9 - 80.5 Starting Current A 5.6 5.6 Dimensions (H × W × D) mm 550 × 765 × 285 550 × 765 × 285 Packaged Dimensions (H × W × D) mm 612 × 906 × 364 612 × 906 × 364 Weight kg 34 34 Gross Weight kg 38 38 Sound
Pressure Level
H / SL dB(A) 48 / 44 48 / 45 48 / 44 48 / 45
Sound Power Level
HdB63636363
Drawing No. 3D072847 3D072845
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling Heating Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB / 24°CWB
Indoor ; 20°CDB
Outdoor ; 7°CDB / 6°CWB
5 m
Specifications SiBE041012_A
9 Specifications
50 Hz, 220 - 230 - 240 V
Note:
The data are based on the conditions shown in the table below.
Models
Indoor Unit FTXG50JV1BW FTXG50JV1BS
Outdoor Unit
RXG50K2V1B RXG50K2V1B
Cooling Heating Cooling Heating
Capacity Rated (Min. ~ Max.)
kW 5.0 (1.7 ~ 5.3) 5.8 (1.7 ~ 6.5) 5.0 (1.7 ~ 5.3) 5.8 (1.7 ~ 6.5)
Btu/h 17,100 (5,800 ~ 18,100) 19,800 (5,800 ~ 22,200) 17,100 (5,800 ~ 18,100) 19,800 (5,800 ~ 22,200)
kcal/h 4,300 (1,460 ~ 4,560) 4,990 (1,460 ~ 5,590) 4,300 (1,460 ~ 4,560) 4,990 (1,460 ~ 5,590) Running Current (Rated) A 7.2 - 6.9 - 6.6 7.4 - 7.1 - 6.8 7.2 - 6.9 - 6.6 7.4 - 7.1 - 6. 8 Power Consumption
Rated (Min. ~ Max.)
W 1,560 (450 ~ 1,880) 1,600 (520 ~ 2,500) 1,560 (450 ~ 1,880) 1,600 (520 ~ 2,500)
Power Factor % 98.5 - 98.3 - 98.5 98.3 - 98.0 - 98.0 98.5 - 98.3 - 98.5 98.3 - 98.0 - 98.0 EER (Cooling) / COP (Heating)
Rated (Min. ~ Max.)
W/W 3.21 (3.78 ~ 2.82) 3.63 (3.27 ~ 2.60) 3.21 (3.78 ~ 2.82) 3.63 (3.27 ~ 2.60)
Piping Connections
Liquid mm φ 6.4 φ 6.4 Gas mm φ 12.7 φ 12.7
Drain mm φ 18.0 φ 18.0 Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length m 30 30 Max. Interunit Height Difference m 20 20 Chargeless m 10 10 Amount of Additional Charge of
Refrigerant
g/m 20 20
Indoor Unit FTXG50JV1BW FTXG50JV1BS
Front Panel Color White Silver
Airflow Rate
H
m³/min
(cfm)
10.3 (364) 11.4 (402) 10.3 (364) 11.4 (402) M 8.5 (300) 9.8 (346) 8.5 (300) 9.8 (346) L 6.7 (237) 8.1 (286) 6.7 (237) 8.1 (286) SL 5.7 (201) 7.1 (251) 5.7 (201) 7.1 (251)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 40 40 Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.16 - 0.15 - 0.14 0.19 - 0.18 - 0.17 0.16 - 0.15 - 0.14 0.19 - 0.18 - 0.17 Power Consumption (Rated) W 32 - 32 - 32 38 - 38 - 38 32 - 32 - 32 38 - 38 - 38 Power Factor % 90.9 - 92.8 - 95.2 90.9 - 91.8 - 93.1 90.9 - 92.8 - 95.2 90.9 - 91.8 - 93.1 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H × W × D) mm 295 × 915 × 155 295 × 915 × 155 Packaged Dimensions (H × W × D) mm 285 × 1,003 × 377 285 × 1,003 × 377 Weight kg 11 11 Gross Weight kg 15 16 Sound
Pressure Level
H / M / L / SL dB(A) 44 / 40 / 35 / 32 44 / 40 / 35 / 32 44 / 40 / 35 / 32 44 / 40 / 35 / 32
Sound Power Level dB 60 60 60 60
Outdoor Unit RXG50K2V1B RXG50K2V1B
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type Model 2YC36BXD 2YC36BXD Motor Output W 1,100 1,100
Refrigerant Oil
Type FVC50K FVC50K Charge L 0.65 0.65
Refrigerant
Type R-410A R-410A Charge kg 1.6 1.6
Airflow Rate
H
m³/min
(cfm)
50.9 (1,797) 45.0 (1,589) 50.9 (1,797) 45.0 (1,589)
SL 48.9 (1,727) 43.1 (1,522) 48.9 (1,727) 43.1 (1,522)
Fan
Type Propeller Propeller Motor Output W 53 53
Running Current (Rated) A 7.04 - 6.75 - 6.46 7.21 - 6.92 - 6.63 7.04 - 6.75 - 6.46 7.21 - 6.92 - 6.63 Power Consumption (Rated) W 1,528 - 1,528 - 1,528 1,562 - 1,562 - 1,562 1,528 - 1,528 - 1,528 1,562 - 1,562 - 1,562 Power Factor % 98.7 - 98.4 - 98.6 98.5 - 98.1 - 98.2 98.7 - 98.4 - 98.6 98.5 - 98.1 - 98.2 Starting Current A 7.4 7.4 Dimensions (H × W × D) mm 735 × 825 × 300 735 × 825 × 300 Packaged Dimensions (H × W × D) mm 797 × 960 × 390 797 × 960 × 390 Weight kg 48 48 Gross Weight kg 53 53 Sound
Pressure Level
H / SL dB(A) 48 / 44 48 / 45 48 / 44 48 / 45
Sound Power Level
HdB63636363
Drawing No. 3D071585 3D072083
Conversion Formulae
kcal/h = kW × 860
Btu/h = kW × 3412
cfm = m³/min × 35.3
Cooling Heating Piping Length
Indoor ; 27°CDB / 19°CWB
Outdoor ; 35°CDB / 24°CWB
Indoor ; 20°CDB
Outdoor ; 7°CDB / 6°CWB
5 m
SiBE041012_A
Printed Circuit Board Connector Wiring Diagram 10
Part 3
Printed Circuit Board
Connector Wiring Diagram
1. Indoor Unit.............................................................................................11
2. Outdoor Unit..........................................................................................14
2.1 RXG25/35J2V1B, RXG25/35K2V1B ......................................................14
2.2 RXG50K2V1B ........................................................................................16
Indoor Unit SiBE041012_A
11 Printed Circuit Board Connector Wiring Diagram
1. Indoor Unit
Connectors and Other Parts
PCB (1): Control PCB
PCB (2): Signal Receiver / Display PCB
PCB (3): INTELLIGENT EYE Sensor PCB
1) S21 Connector for centralized control (HA)
2) S25 Connector for INTELLIGENT EYE sensor PCB
3) S32 Connector for indoor heat exchanger thermistor
4) S41 Connector for swing motors
5) S42 Connector for reduction motor (front panel mechanism) and limit switch
6) S46 Connector for signal receiver / display PCB
7) S200 Connector for fan motor
8) H1, H2, H3, FGConnector for terminal board
9) JB Fan speed setting when compressor stops for thermostat OFF JC Power failure recovery function (auto-restart) Refer to page 223 for detail.
10) LED A LED for service monitor (green)
11) F1U Fuse (3.15 A, 250 V)
12) V1 Varistor
1) S51 Connector for control PCB
2) S52 Connector for room temperature thermistor
3) S1W Forced operation ON/OFF button
4) H1P LED for operation (multi-color)
5) H2P LED for INTELLIGENT EYE (green)
6) JA Address setting jumper Refer to page 222 for detail.
1) S36 Connector for control PCB
SiBE041012_A Indoor Unit
Printed Circuit Board Connector Wiring Diagram 12
PCB Detail PCB (1): Control PCB
S42
S41
S32
JB JC
S200
H3
H2
FG
S46
S21
S25
LED A
V1
F1U
H1
2P254830-1
Indoor Unit SiBE041012_A
13 Printed Circuit Board Connector Wiring Diagram
PCB (3): INTELLIGENT EYE Sensor PCB
PCB (2): Signal Receiver / Display PCB
S52 S51
S1W JA
H2P
H1P
3P254832-1
S36
3P255914-1
SiBE041012_A Outdoor Unit
Printed Circuit Board Connector Wiring Diagram 14
2. Outdoor Unit
2.1 RXG25/35J2V1B, RXG25/35K2V1B
Connectors and Other Parts
PCB(1): Filter PCB
PCB(2): Main PCB
PCB(3): Forced Cooling Operation Switch PCB
1) S11 Connector for main PCB
2) AC1, AC2, S Connector for terminal board
3) E1, E2 Terminal for earth
4) HL2, HN2 Connector for main PCB
5) HR1 Connector for reactor
6) FU1 Fuse (3.15 A, 250 V)
7) FU3 Fuse (20 A, 250 V)
8) V2, V3 Varistor
1) S10 Connector for filter PCB
2) S20 Connector for electronic expansion valve coil
3) S40 Connector for overload protector
4) S50 Connector for magnetic relay
5) S70 Connector for fan motor
6) S80 Connector for four way valve coil
7) S90 Connector for thermistors (outdoor temperature, outdoor heat exchanger, discharge pipe)
8) S100 Connector for forced cooling operation switch PCB
9) HL3, HN3 Connector for filter PCB
10) HR2 Connector for reactor
11) U, V, W Connector for compressor
12) FU2 Fuse (3.15 A, 250 V)
13) LED A LED for service monitor (green)
14) V1 Varistor
15) J5 Jumper for improvement of defrost performance Refer to page 223 for detail.
1) S110 Connector for main PCB
2) SW1 Forced cooling operation ON/OFF switch
Outdoor Unit SiBE041012_A
15 Printed Circuit Board Connector Wiring Diagram
PCB Detail PCB(1): Filter PCB
PCB(2): Main PCB
PCB(3): Forced Cooling Operation Switch PCB
HR1
HL2
3P254234-1
FU1
HN2
S
FU3
AC2
E1, E2
AC1
S11
V3V2
S50
(on main PCB)
S10
J5
S90
FU2 S100 S50
2P254206-4 2P254206-9
S70
S40
S20
S80
HL3
HN3
V1
LED A
UVW
HR2
SW1
S110
3P255755-1
SiBE041012_A Outdoor Unit
Printed Circuit Board Connector Wiring Diagram 16
2.2 RXG50K2V1B
Connectors and Other Parts
PCB (1): Main PCB
PCB (2): Service Monitor PCB
1) S10 Connector for terminal board (indoor - outdoor transmission)
2) S20 Connector for electronic expansion valve coil
3) S40 Connector for overload protector
4) S51, S101 Connector for service monitor PCB
5) S70 Connector for fan motor
6) S80 Connector for four way valve coil
7) S90 Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
8) AC1, AC2 Connector for terminal board (power supply)
9) E1, E2 Connector for earth
10)HR1, HR2 Connector for reactor
11)U, V, W Connector for compressor
12)FU1 Fuse (30 A, 250 V)
13)FU2, FU3 Fuse (3.15 A, 250 V)
14)V2, V3, V5 V6, V11 Varistor
1) S52, S102 Connector for main PCB
2) LED A LED for service monitor (green)
3) SW1 Forced cooling operation ON/OFF switch
4) SW4-C Switch for improvement of defrost performance
Refer to page 223 for detail.
Outdoor Unit SiBE041012_A
17 Printed Circuit Board Connector Wiring Diagram
PCB Detail PCB (1): Main PCB
PCB (2): Service Monitor PCB
V3
V11
AC1
FU2
E1 E2
FU3 W
2P282217-1
S40S20S80 V US70S90 S51
S10
AC2
S101
V5
V6
V2
FU1
HR1
HR2
S102
SW1
3P169059-1
LED A
SW4-C
S52
SiBE041012_A
Function and Control 18
Part 4
Function and Control
1. Main Functions......................................................................................19
1.1 Temperature Control ..............................................................................19
1.2 Frequency Principle................................................................................19
1.3 Operation Starting Control......................................................................21
1.4 Airflow Direction Control.........................................................................22
1.5 Fan Speed Control for Indoor Unit .........................................................23
1.6 Program Dry Operation ..........................................................................24
1.7 Automatic Operation...............................................................................25
1.8 Thermostat Control.................................................................................26
1.9 NIGHT SET Mode ..................................................................................27
1.10 ECONO Operation .................................................................................28
1.11 INTELLIGENT EYE Operation ...............................................................29
1.12 Inverter POWERFUL Operation .............................................................30
1.13 Other Functions......................................................................................32
2. Function of Thermistor ..........................................................................33
3. Control Specification .............................................................................34
3.1 Mode Hierarchy ......................................................................................34
3.2 Frequency Control..................................................................................35
3.3 Controls at Mode Changing / Start-up....................................................37
3.4 Discharge Pipe Temperature Control.....................................................39
3.5 Input Current Control ..............................................................................40
3.6 Freeze-up Protection Control .................................................................41
3.7 Heating Peak-cut Control .......................................................................41
3.8 Outdoor Fan Control...............................................................................42
3.9 Liquid Compression Protection Function................................................42
3.10 Defrost Control .......................................................................................43
3.11 Outdoor Electronic Expansion Valve Control .........................................44
3.12 Malfunctions ...........................................................................................47
Main Functions SiBE041012_A
19 Function and Control
1. Main Functions
1.1 Temperature Control
Definitions of Temperatures
The definitions of temperatures are classified as following.
Room temperature: temperature of lower part of the room
Set temperature: temperature set by remote controller
Room thermistor temperature: temperature detected by room temperature thermistor
Target temperature: temperature determined by microcomputer
Temperature Control
The temperature of the room is detected by the room temperature thermistor. However, there is difference between the “temperature detected by room temperature thermistor” and the “temperature of lower part of the room”, depending on the type of the indoor unit or installation condition. Practically, the temperature control is done by the “target temperature appropriately adjusted for the indoor unit” and the “temperature detected by room temperature thermistor”.
1.2 Frequency Principle
Main Control Parameters
The compressor is frequency-controlled during normal operation. The target frequency is set by the following 2 parameters coming from the operating indoor unit:
The load condition of the operating indoor unit
The difference between the room thermistor temperature and the target temperature
Additional Control Parameters
The target frequency is adapted by additional parameters in the following cases:
Frequency restrictions
Initial settings
Forced cooling operation
Inverter Principle To regulate the capacity, a frequency control is needed. The inverter makes it possible to vary
the rotation speed of the compressor. The following table explains the conversion principle:
Target temperature
Set temperature
Room temperature
Room thermistor temperature
(R12321)
Phase Description
1 The supplied AC power source is converted into the DC power source for the present. 2 The DC power source is reconverted into the three phase AC power source with variable
frequency. When the frequency increases, the rotation speed of the compressor increases resulting
in an increased refrigerant circulation. This leads to a higher amount of the heat exchange per unit.
When the frequency decreases, the rotation speed of the compressor decreases
resulting in a decreased refrigerant circulation. This leads to a lower amount of the heat exchange per unit.
Loading...
+ 212 hidden pages