Daikin RXG09HVJU, FTXG09HVJU, RXG12HVJU, RXG15HVJU, FTXG12HVJU Engineeiring Data

...
EDUS04-906_b
H-Series
- Heat Pump -
EDUS04-906_b
Room Air Conditioners H-Series 1
Room Air Conditioners
H-Series
1. Power Supply..............................................................................................2
2. Functions.....................................................................................................3
3. Specifications..............................................................................................4
4. Dimensions .................................................................................................6
5. Wiring Diagrams..........................................................................................7
6. Piping Diagrams..........................................................................................8
7. Capacity Tables ..........................................................................................9
7.1 Heat Pump ................................................................................................... 9
8. Operation Limit..........................................................................................15
9. Sound Level ..............................................................................................16
9.1 Measuring Location .................................................................................... 16
9.2 Octave Band Level ..................................................................................... 17
10.Electric Characteristics..............................................................................19
11.Installation Manual ....................................................................................20
11.1 Indoor Units................................................................................................ 20
11.2 Outdoor Units ............................................................................................. 33
12.Operation Manual......................................................................................40
13.Optional Accessories ................................................................................71
13.1 Option List .................................................................................................. 71
13.2 Installation Manual ..................................................................................... 72
Heat Pump
Quaternity
FTXG09HVJU FTXG12HVJU FTXG15HVJU
RXG09HVJU RXG12HVJU RXG15HVJU
Power Supply EDUS04-906_b
2 Room Air Conditioners H-Series
1. Power Supply
Note:
Power Supply Intake ; Outdoor Unit
Indoor Units Outdoor Units Power Supply
Quaternity
FTXG09HVJU RXG09HVJU
1
φ, 208-230V, 60HzFTXG12HVJU RXG12HVJU
FTXG15HVJU RXG15HVJU
EDUS04-906_b Functions
Room Air Conditioners H-Series 3
2. Functions
(1) Inverter POWERFUL operation can be used for COOLING, DRY COOLING, and HEATING. (2) The function setting is cancelled as it is restarted automatically.(3) Temperature display 16~99°F (–9°C~37°C)
Category Functions
FTXG09/12/15HVJU
RXG09/12/15HVJU
Category Functions
FTXG09/12/15HVJU
RXG09/12/15HVJU
Basic Function
Inverter (with Inverter Power Control) Health &
Clean
Air-Purifying Filter
Operation Limit for Cooling (°FDB)
14~ 109
Photocatalytic Deodorizing Filter
Operation Limit for Heating (°FWB)
–4~
75
Air-Purifying Filter with Photocatalytic Deodorizing Function
PAM Control
Titanium Apatite Photocatalytic Air-Purifying Filter
Energy Saving During Operation Standby
Compressor Oval Scroll Compressor Deodorizing Filter for Streamer
Swing Compressor Flash Streamer Air-Purifying Rotary Compressor Air Filter (Prefilter) Reluctance DC Motor Wipe-clean Flat Panel
Comfortable Airflow
Power-Airflow Flap Washable Upper Grille Power-Airflow Dual Flaps Filter Cleaning Indicator (Remote Controller) Wide-Angle Louvers Mold Proof Operation — Vertical Auto-Swing (Up and Down) Mold Shock Operation — Horizontal Auto-Swing (Right and Left) Mold Proof Stick 3-D Airflow Comfort Sleep Operation 2 Comfort Airflow Mode Fresh Air Supply Ventilation — COOLING BREEZE Operation Home Leave Ventilation
Comfort Control
Auto Fan Speed Timer Weekly Timer — Indoor Unit Quiet Operation 24-Hour ON/OFF Timer Night Quiet Mode (Automatic) Count Up-down ON/OFF Timer
OFF only Outdoor Unit Quiet Operation (Manual) Night Set Mode INTELLIGENT EYE Worry Free
“Reliability & Durability”
Auto-Restart (after Power Failure) 2-Area INTELLIGENT EYE Self-Diagnosis (Remote Controller) Display Quick Warming Function Wiring Error Check
Hot-Start Function
Anticorrosion Treatment of Outdoor Heat
Exchanger
Automatic Defrosting Flexibility Multi-Split / Split Compatible Indoor Unit
Operation Automatic Operation H/P, C/O Compatible Indoor Unit
Humidifying Operation Chargeless Drying Operation Either Side Drain (Right or Left) DRY COOLING Operation Power Selection
Programme Dry Function
Low Temperature Cooling Operation
(5°F / -15°C)
Fan Only
°F/°C changeover R/C temperature display
(factory setting : °F)
3
Air-Purifying Operation
Lifestyle Convenience
New POWERFUL Operation (Non-Inverter) Remote
Control
5-Rooms Centralized Controller (Option)
Inverter POWERFUL Operation
1
2
Remote Control Adaptor
(Normal Open-Pulse Contact) (Option)
Dry Keep
JP set
Priority-Room Setting
Remote Control Adaptor
(Normal Open Contact) (Option)
Cooling / Heating Mode Lock — HOME LEAVE Operation DIII-NET Compatible (Adaptor) (Option) ECONO Mode Remote
Controller
Wireless Indoor Unit ON/OFF Switch Wired Signal Reception Indicator Multi-colored Indicator Monitor Brightness Setting Temperature & Humidity Level Information
Display (Remote Controller)
Childproof Lock R/C with Back Light
Note:  : Included Functions
— : No Functions
Specifications 60Hz 230V EDUS04-906_b
4 Room Air Conditioners H-Series
3. Specifications 60Hz 230V
Note:
The data are based on the conditions shown in the table below.
Models
Indoor Units FTXG09HVJU FTXG12HVJU
Outdoor Units
RXG09HVJU RXG12HVJU
Cooling Heating Cooling Heating
Capacity Rated (Min.~Max.)
Btu/h 9,000 (5,300~12,300) 12,000 (4,400~18,000) 12,000 (5,300~15,700) 16,000 (4,400~19,100)
Moisture Removal Pt/h 3.3 4.1 — Running Current (Rated) A 3.10 4.04 4.30 5.64 Power Consumption Rated
(Min.~Max.)
W 570 (250~900) 780 (220~1,900) 860 (260~1,300) 1,160 (220~2,100) Power Factor % 80.0 84.0 87.0 89.5 EER (Rated)
Btu/h·W
15.8 14.0 — COP (Rated) W/W 4.51 4.04 Energy
Efficiency
SEER/HSPF 26.1 11.0 24.2 10.6
Piping Connections
Liquid inch (mm) φ 1/4” (6.4 mmm) φ 1/4” (6.4 mmm) Gas inch (mm) φ 3/8” (9.5 mm) φ 3/8” (9.5 mm)
Drain
inch (mm)
φ 11/16
” (17.5 mm)
φ 11/16
” (17.5 mm)
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes Max. Interunit Piping Length feet (m) 32 ft (10 m) 32 ft (10 m) Max. Interunit Height Difference feet (m) 26 ft (8 m) 26 ft (8 m) Chargeless feet (m) — Amount of Additional Charge of
Refrigerant
oz/ft
Indoor Units FTXG09HVJU FTXG12HVJU
Front Panel Color White White
Airflow Rate cfm (m³/min)
H 420 (11.9) 438 (12.4) 459 (13.0) 470 (13.3)
M 325 (9.2) 346 (9.8) 346 (9.8) 367 (10.4)
L 230 (6.5) 258 (7.3) 240 (6.8) 272 (7.7)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 57 57
Speed Steps 5 Steps, Quiet and Auto 5 Steps, Quiet and Auto Air Direction Control Right, Left, Horizontal and Downward Right, Left, Horizontal and Downward Air Filter Removable / Washable / Mildew Proof Removable / Washable / Mildew Proof Running Current (Rated) A 0.12 0.14 0.14 0.15 Power Consumption (Rated) W 24 26 29 31 Power Factor % 87 80.7 90.1 89.9 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) inch (mm) 12 × 35-1/16 × 8-1/4” (305 x 891 x 210 mm) 12 × 35-1/16 × 8-1/4” (305 x 891 x 210 mm) Packaged Dimensions (H×W×D) inch (mm) 11 × 37-5/8 × 14-7/8” (279 x 956 x 378 mm) 11 × 37-5/8 × 14-7/8” (279 x 956 x 378 mm) Weight Lbs (kg) 31 lbs (14 kg) 31 lbs (14 kg) Gross Weight Lbs (kg) 38 lbs (17 kg) 38 lbs (17 kg) Operation Sound H/M/L dBA 42 / 33 / 26 42 / 35 / 28 43 / 35 / 27 43 / 36 / 29
Outdoor Units RXG09HVJU RXG12HVJU
Casing Color Ivory White Ivory White
Compressor
Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type
Model 2YC36CXD 2YC36CXD
Motor Output W 1,100 1,100
Refrigerant Oil
Type FVC50K FVC50K
Charge oz 13.5 13.5
Refrigerant
Type R-410A R-410A
Charge Lbs 3.1 3.1
Airflow Rate cfm (m³/min)
H 1,178 (33.4) 1,095 (31.0) 1,262 (35.7) 1,111 (31.5) L————
Fan
Type Propeller Propeller
Motor Output W 60 60 Running Current (Rated) A 2.98 3.9 4.16 5.49 Power Consumption (Rated) W 546 754 831 1,129 Power Factor % 79.7 84.1 86.9 89.4
Dimensions (H×W×D) inch (mm)
22-3/8 × 31-5/16 ×11-1/4”
(568 x 795 x 286 mm)
22-3/8 × 31-5/16 ×11-1/4”
(568 x 795 x 286 mm)
Packaged Dimensions (H×W×D)
inch (mm) 25-3/16 ×36-7/16 ×14-7/8”
(568 x 795 x 286 mm
25-3/16 ×36-7/16 ×14-7/8”
(568 x 795 x 286 mm)
Weight Lbs(kg) 99 lbs (45 kg) 99 lbs (45 kg) Gross Weight Lbs(kg) 104 lbs (32 kg) 104 lbs (32 kg) Operation
Sound
H / L dBA 46 / — 46 / — 49 / — 48 / —
Drawing No. 3D062857 3D062858
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25ft (7.5 m)
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
EDUS04-906_b Specifications 60Hz 230V
Room Air Conditioners H-Series 5
60Hz 230V
Note:
The data are based on the conditions shown in the table below.
Model
Indoor Units FTXG15HVJU
Outdoor Units
RXG15HVJU
Cooling Heating
Capacity Rated (Min.~Max.)
Btu/h 15,000 (5,300~18,000) 18,000 (4,400~21,200)
Moisture Removal Pt/h 4.8 — Running Current (Rated) A 5.64 6.36 Power Consumption Rated
(Min.~Max.)
W 1,160 (260~1,930) 1,320 (230~2,120) Power Factor % 89.0 99.0 EER (Rated)
Btu/h·W
12.9 — COP (Rated) W/W 3.99 Energy
Efficiency
SEER/HSPF 21.0 10.0
Piping Connections
Liquid inch (mm) φ 1/4” (6.4 mmm) Gas inch (mm) φ 3/8” (9.5 mm) Drain inch (mm) φ 11/16
” (17.5 mm) Heat Insulation Both Liquid and Gas Pipes Max. Interunit Piping Length feet (m) 32’ (10 m) Max. Interunit Height Difference feet (m) 26’ (8 m) Chargeless feet (m) — Amount of Additional Charge of Refrigerant oz/ft
Indoor Unit FTXG15HVJU
Front Panel Color White
Airflow Rate cfm (m³/min)
H 487 (13.8) 494 (14.0)
M 371 (10.5) 392 (11.1)
L 258 (7.3) 293 (8.3)
Fan
Type Cross Flow Fan Motor Output W 57
Speed Steps 5 Steps, Quiet, Auto Air Direction Control Right, Left, Horizontal, Downward Air Filter Removable / Washable / Mildew Proof Running Current (Rated) A 0.15 0.16 Power Consumption (Rated) W 33 35 Power Factor % 95.7 95.1 Temperature Control Microcomputer Control Dimensions (H×W×D) inch (mm) 12 × 35-1/16 × 8-1/4” (305 x 891 x 210 mm) Packaged Dimensions (H×W×D) inch (mm) 11 × 37-5/8 × 14-7/8” (279 x 956 x 378 mm) Weight Lbs(kg) 31 lbs (14 kg) Gross Weight Lbs(kg) 38 lbs (17 kg) Operation
Sound
H/M/L dBA 45 / 37 / 29 44 / 38 / 31
Outdoor Unit RXG15HVJU
Casing Color Ivory White
Compressor
Type Hermetically Sealed Swing Type
Model 2YC36CXD
Motor Output W 1,100
Refrigerant Oil
Model FVC50K
Charge oz 13.5
Refrigerant
Model R-410A
Charge Lbs 3.1
Airflow Rate cfm (m³/min)
H 1,262 (35.7) 1,195 (33.8) L—
Fan
Type Propeller
Motor Output W 60 Running Current (Rated) A 5.49 6.2 Power Consumption (Rated) W 1,127 1,285 Power Factor % 89.3 90.1
Dimensions (H×W×D) inch (mm)
22-3/8 × 31-5/16 ×11-1/4”
(568 x 795 x 286 mm)
Packaged Dimensions (H×W×D) inch (mm)
25-3/16 ×36-7/16 ×14-7/8”
(568 x 795 x 286 mm)
Weight Lbs (kg) 99 Gross Weight Lbs(kg) 104 Operation
Sound
H / L dBA 50 / — 50 / —
Drawing No. 3D062859
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
25 ft (7.5 m)
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Dimensions EDUS04-906_b
6 Room Air Conditioners H-Series
4. Dimensions
FTXG09/12/15HVJU
RXG09/12/15HVJU
35-1/16(890)
45°
45
°
I.D. φ9/16(14)
CONNECTING PART
O.D. φ11/16(18)
TERMINAL BLOCK WITH EARTH TERMINAL
SIGNAL RECEIVER
55°
30°
25°
70°
APPROX.23-9/16(598)
1-7/16(37)
8-1/4(209)
10-3/4(273)
OPERATING STATE
12 (305)
10-13/16(275)
7-1/8(180.5)
33(838)
STANDARD LOCATIONS OF WALL HOLES
APPROX.25-13/16(655)
1-15/16(50)MIN.
9/16(15)
1-3/4(44.5)
1-3/16(30)MIN.
2-5/16(59.5)
1-15/16(50)MIN.
1-1/16(26.8)
2-1/2(63)
15°
15°
70°
55°
APPROX.21-9/16(548)
1-7/8(47)~2-3/8(60)
AIR FLOW (INDOOR)
1 - 3 / 4 (44.5)
9/16(14.5)
RIGHT/LEFT (AUTOMATIC)
45°
55°
60°
20°
7-1/16(180)
(SPACE FOR
MAINTENANCE)
UP/DOWN (AUTOMATIC)
SIGNAL TRANSMITTER
WALL HOLE FOR EMBEDDED PIPING φ2-9/16(65) HOLE
COOLING DRY COOLING DRY
GAS PIPE φ3/8(9.5)Cut
WIRELESS REMOTE CONTROLLER
DRAIN HOSE
HEATING
ROOM TEMP.
THERMISTOR
RIGHT
REQUIRED SPACE
REAR
WALL HOLE
LIQUID PIPE φ1/4(6.4)Cut
AIR PURIFYING (INDIVIDUAL OPERATION)
(SPACE FOR
PERFORMANCE)
GEAR CASE UNIT FIXED SCREWS (INSIDE PANEL)
INCLUDING MOUNTING PLATE
LEFT
(SPACE FOR PERFORMANCE)
THE MARK () SHOWS PIPING DIRECTION
BOTTOM
BLADE ANGLE
(ARC447A3)
φ2-9/16(65)
HOLE
FRONT GRILL FIXED SCREWS (INSIDE PANEL)
NAME
PLATE
MULTI-COLORED INDICATOR LAMP/ INDOOR UNIT ON/OFF SWITCH
(
)
TIMER LAMP
3D061002
(φ3/8 (9.5) CuT)
GAS STOP VALVE
3-1/8 (79)
31-5/16 (795)
19-7/8 (505)
1/2 (13)
4-5/8 (118)
1-15/16 (50)
OUTDOOR AIR THERMISTOR
1-15/16 (50)
2-15/16 (75)
1-15/16 (50)
5-7/8 (150)
BRAND NAME LABEL
(M8 OR M10)
4-HOLES FOR ANCHOR BOLTS
12-1/4 (311)
22-5/8 (574)
1-3/16 (29.5)
22-3/8 (569)
PORT
SERVICE
5-7/8 (150)
3-15/16 (100)
(φ1/4 (6.4) CuT)
STOP VALVE
LIQUID
11-1/4 (285)
HOSE FOR CONNECTION)
(I.Dφ5/8 (15.9)
DRAIN OUTLET
HANDLE
9/16 (15)
NAME PLATE
2-1/2 (63)
13/16 (20)
11-13/16 (300)
3-3/4 (95.5)
5/8 (15.7)
11/16 (17)
1-15/16 (50)
7 (178)
3-15/16 (100)
= LESS THAN 47-3/16 (1200)
WALL HEIGHT ON AIR OUTLET SIDE
MINIMUM SPACE FOR AIR PASSAGE
STOP VALVE COVER
IN CASE OF REMOVING
UNIT=INCH (mm)
(BASE PITCH)
3D062671A
EDUS04-906_b Wiring Diagrams
Room Air Conditioners H-Series 7
5. Wiring Diagrams
FTXG09/12/15HVJU
RXG09/12/15HVJU
FIELD WIRING.
outdoor
R1T
t°
LED2
H2P
M
Y2S
indoor
TURNED OFF AND THEN BACK
RESTART AUTOMATICALLY IF
NOTE THAT OPERATION WILL
THE MAIN POWER SUPPLY IS
ON AGAIN.
CAUTION
SIGNAL
RECEIVER
MM
t°
R2T
Y1S
MULTI
MONITOR
H1P
SIGNAL
TRANSMITTER
LED3
H3P
M
6
RED
S51
5
+
1
BLK
S402
5
4
S1
7
M3S
BLK
JA
Z1C N=4
M2S
GRN
1
1
13
A5P
RED
BLK
S2C
BLK
BLK
RED
BLK
S21
6
S401
H2
HUMIDITY
SENSOR
BLK
1
GRN
S1C
S32
7
BLK
S91
BLK
HIGH VOLTAGE UNIT
M1F
BLK
1
(16PIN)
ORG
M
JA
A4P
2
YLW
3
BLK
JUMPER
BLK
BLK
ORG
FG
/
BLK
BLK
TRANSMISSION
CIRCUIT
BLK
ORG
A3P
4
BLK
BLU
BLK
R1V
1
CN1
S41
1
-
H1
BLK
PNK
A1P
PNK
BLK
YLW
H3
S43
BLK
BLK
BLU
A2P
ORG
S57
BLK
2
1
BLK
BLK
1
PNK
S52
S1W
YLW
YLW
BLK
BLK
RED
BLK
YLW
RED
YLW
M1S
BLK
AN ADDRESS SETUP OF REMOTECONTROLLER
WHT
BLK
X1M
(H250V,T3.15A)
S403
BLU
BLK
S48
ORG
YLW
13
RED
BLK
STREAMER PART
-
PNK
WHT
BLK
HA
S56
WHT
RED
BLK
1
S46
BLK
M4S
WIRELESS
REMOTE
CONTROLLER
BLK
S58
1
BLU
YLW
ORG
BLU
YLW
BLK
BLU
BRN
BLK
BLK
GRN
: PROTECTIVE GROUND
3
F1U
: FLAME GROUND : FUSE
: PILOT LAMP
: FAN MOTOR
: PRINTED CIRCUIT BOARD
R1T, R2T
: CONNECTOR : OPERATION SWITCH : TERMINAL STRIP
: SWING MOTORM1S~M4S
F1U
M1F
H2P, H3P
S1~S403, CN1
FG
X1M
S1W
: THERMISTOR
A1P~A5P
: MULTI MONITORH1P
: LIM IT SWITCH FOR PANELS1C : LIM IT SWITCH FOR STREAMERS2C
: VARISTORR1V
: SOLENOID VALVE
Y1S, Y2S
: FERRITE COREZ1C
3D052768C
3
1 2
outdoor
L1R
DB1
NOTE
1. REFER TO THE NAMEPLATE FOR THE POWER REQUIREMENTS.
M
FIELD WIRING.
: PROTECTIVE GROUND
indoor
VW
IPM1
U
(CONDENSER)
BLU
FU1
W
R2T
V
BLK
E2
S70
WHT
X1M : TERMINAL STRIP
102°C
(OUTDOOR)
BLU
(DISCHARGE)
M1F
GRN/YLW
3
MRM20
BLU
YLW
3.15A
WHT
X1A : CONNECTOR
ORG
GRN/ YLW
HL1
6
HR1
3
RED
YLW
Z2C
N=3
WHT
M
Y1R
: REVERSING SOLENOIDE VALVE COIL
1
BLK
L1, L2 : LIVE
Q1L
1
YLW
W
4
R1T
R1T, R2T, R3T : THERMISTOR
MR4, MRM10 MRM20 : MAGNETIC RELAY
BLK
YLW
S80
OL1
Z1C
N=4
ORG
2
1
M1F : FAN MOTOR
U
BLU
PPL
2
PCB1 : PRINTED CIRCUIT BOARD
DB3
FU1, FU2, FU3 : FUSE
1
L2
1
Q1L : OVERLOAD PROTECTOR
X1M
S90
V1
3
M1C
WHT
YLW
S
BRN
3
1
GRN
Z3C N=3
MRM10
3.15A
WHT
FU3
V2
U
1
RED
S45
MR4
SA1 : SURGE ARRESTER
FU2
Y1E
L1R : REACTOR
L
BLK
YLW
BLK
2
HN1
RED
V1, V2: VARISTOR
Y1E
: ELECTRONIC EXPANSION VALVE COIL
RED
E1
DB1, DB2, DB3 : DIODE BRIDGE
7
BRN
Z4C N=2
L
DB2
RED
ORG
S20
M
PCB1
X1A
L
1
R3T
IPM1 : INTELLIGENT POWER MODULE
V
M1C : COMPRESSOR MOTOR
YLW
30A
OL2
6
SA1
YLW
BLK
Z1C, Z2C, Z3C, Z4C
: FERRITE CORE
HR2
Y1R
+
_
~
~
+
+
+
_
_
+
+
_
_
_
+ _
~
~
~
~
+ _
t° t° t°
1~
3D061486
Piping Diagrams EDUS04-906_b
8 Room Air Conditioners H-Series
6. Piping Diagrams
FTXG09/12/15HVJU
RXG09/12/15HVJU
SV
SV
M
(UNDER DEHUMIDIFICATION OPERATION)
FIELD PIPING
FAN MOTOR
HEATING
HEAT EXCHANGER
SINGLE UNION JOINT
HEAT EXCHANGER
REFRIGERANT FLOW
THERMISTOR ON HEAT EXCH.
AT RATED VOLTAGE: CLOSED
SINGLE UNION JOINT
SOLENOID VALVE
1/ 4(6.4)CuT
FIELD PIPING 3/8(9.5)CuT
COOLING
1/4(6.4)CuT
CROSS FLOW FAN
INDOOR UNIT
3/8(9.5)CuT
4D061001
OUTDOOR TEMPERATURE THERMISTOR
(7.9)CuT
FIELD PIPING
(7.9)CuT
COOLING
GAS STOP VALV E
M
MOTOR OPERATED VALV E
OUTDOOR UNIT
FOUR WAY VALVE ON : HEATING
1/2(12.7)CuT
(3/8(9.5)CuT)
HEAT EXCHANGER
3/8(9.5)CuT
(6.4)CuT
FILTER
(12.7)CuT
LIQUID STOP VALV E
HEAT EXCHANGER THERMISTOR
HEATING
1/2(12.7)CuT
FAN MOTOR
(6.4)CuT
PROPELLER FAN
MUFFLER
WITH
FILTER
FIELD PIPING
1/4(6.4)CuT
1/4(6.4)CuT
MUFFLER
COMPRESSOR
AUXILIARY
HEAT EXCHANGER
DISCHARGE PIPE THERMISTOR
1/4(6.4)CuT
(7.9)CuT
(1/4(6.4)CuT)
MUFFLER
3/8(9.5)CuT
MUFFLER
FILTER
REFRIGERANT FLOW
1/2(12.7)CuT
1/2
5/16
5/16
9/32(7.0)CuT
9/32(7.0)
CuT
9/32(7.0)CuT
5/16
(7.9)CuT
5/16
UNIT=INCH(mm)
1/4
1/4
3D062171A
EDUS04-906_b Capacity Tables
Room Air Conditioners H-Series 9
7. Capacity Tables
7.1 Heat Pump
FTXG09HVJU + RXG09HVJU (60Hz 230V)
Cooling
Heating
AFR 11.9
BF 0.10
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 2.702.420.442.582.370.482.462.310.522.412.290.542.342.260.562.212.200.61
16.0 22 2.832.380.442.702.330.482.582.280.522.532.260.542.462.230.572.332.180.61
18.0 25 2.952.560.442.832.510.482.702.460.532.652.440.542.582.410.572.462.370.61
19.426.73.012.750.442.892.700.492.762.660.532.712.640.54
2.64 2.61 0.57 2.52 2.56 0.61
22.0 30 3.192.670.453.072.630.492.952.590.532.902.570.552.822.550.572.702.510.62
24.0 32 3.312.620.453.192.580.493.072.540.533.022.530.552.942.510.582.822.470.62
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 89.6 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.268.09.238.270.448.818.080.488.397.890.528.227.810.547.977.700.567.557.520.61
60.871.69.648.140.449.227.960.488.807.780.528.647.710.548.397.610.577.977.440.61
64.4 77.0 10.06 8.72 0.44 9.64 8.56 0.48 9.22 8.39 0.53 9.05 8.33 0.54 8.80 8.23 0.57 8.38 8.07 0.61
67.0 80.0 10.27 9.37 0.44 9.85 9.22 0.49 9.43 9.06 0.53 9.26 9.00 0.54
9.01 8.90 0.57 8.59 8.75 0.61
71.6 86.0 10.89 9.11 0.45 10.47 8.97 0.49 10.05 8.83 0.53 9.88 8.78 0.55 9.63 8.70 0.57 9.21 8.56 0.62
75.2 89.6 11.30 8.93 0.45 10.88 8.81 0.49 10.46 8.68 0.53 10.30 8.63 0.55 10.05 8.56 0.58 9.63 8.43 0.62
AFR 12.4
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB -10.0 -5.0 0 6.1 10.0
°C TC PI TC PI TC PI TC PI TC PI
15.0 2.39 0.66 2.79 0.69 3.19 0.72 3.67 0.76 3.98 0.78
21.1 2.25 0.68 2.65 0.71 3.04 0.74
3.52 0.78 3.84 0.81
22.0 2.22 0.68 2.62 0.71 3.02 0.74 3.50 0.78 3.81 0.81
24.0 2.18 0.69 2.57 0.72 2.97 0.75 3.45 0.79 3.77 0.82
25.0 2.15 0.69 2.55 0.72 2.95 0.76 3.42 0.79 3.74 0.82
27.0 2.10 0.70 2.50 0.73 2.90 0.76 3.37 0.80 3.69 0.83
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 14.0 23.0 32.0 43.0 50.0
°F TC PI TC PI TC PI TC PI TC PI
59.0 8.15 0.66 9.52 0.69 10.88 0.72 12.52 0.76 13.58 0.78
70.0 7.67 0.68 9.03 0.71 10.38 0.74
12.01 0.78 13.10 0.81
71.6 7.57 0.68 8.94 0.71 10.30 0.74 11.94 0.78 13.00 0.81
75.2 7.44 0.69 8.77 0.72 10.13 0.75 11.77 0.79 12.86 0.82
77.0 7.34 0.69 8.70 0.72 10.07 0.76 11.67 0.79 12.76 0.82
80.6 7.17 0.70 8.53 0.73 9.89 0.76 11.50 0.80 12.59 0.83
Capacity Tables EDUS04-906_b
10 Room Air Conditioners H-Series
3D063098A
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures outof the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft (7.5 m) Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
7. Cooling capacity at -10 degrees Celsius / 14 degrees Fahrenheit.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR
EWB EDB -10 (°CDB)
°C °C TC SHC PI
14.0 20 3.44 2.77 0.31
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR
EWB EDB 14 (°FDB)
°F °F TC SHC PI
57.2 68.0 11.75 9.44 0.31
EDUS04-906_b Capacity Tables
Room Air Conditioners H-Series 11
FTXG12HVJU + RXG12HVJU (60Hz 230V)
Cooling
Heating
AFR 13.0
BF 0.14
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 3.612.860.663.442.780.723.282.710.793.212.680.813.112.630.852.952.550.91
16.0 22 3.772.810.663.602.740.733.442.670.793.382.640.823.282.600.853.112.530.92
18.0 25 3.932.980.673.772.910.733.602.840.793.542.810.823.442.770.863.282.710.92
19.426.74.013.160.673.853.100.733.683.030.803.623.010.82
3.52 2.97 0.86 3.36 2.91 0.92
22.0 30 4.253.060.674.093.000.743.932.950.803.862.920.833.762.890.873.602.830.93
24.0 32 4.422.990.684.252.940.744.092.880.814.022.860.833.932.830.873.762.780.93
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 89.6 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 12.30 9.77 0.66 11.75 9.50 0.72 11.19 9.24 0.79 10.96 9.13 0.81 10.63 8.98 0.85 10.07 8.72 0.91
60.8 71.6 12.86 9.60 0.66 12.30 9.35 0.73 11.74 9.11 0.79 11.52 9.01 0.82 11.18 8.86 0.85 10.62 8.62 0.92
64.4 77.0 13.41 10.15 0.67 12.85 9.92 0.73 12.29 9.69 0.79 12.07 9.60 0.82 11.73 9.46 0.86 11.17 9.24 0.92
66.9 80.1 13.69 10.80 0.67 13.13 10.57 0.73 12.57 10.35 0.80 12.35 10.26 0.82
12.01 10.13 0.86 11.45 9.91 0.92
71.6 86.0 14.52 10.44 0.67 13.96 10.25 0.74 13.40 10.05 0.80 13.18 9.97 0.83 12.84 9.86 0.87 12.28 9.67 0.93
75.2 89.6 15.07 10.20 0.68 14.51 10.02 0.74 13.95 9.84 0.81 13.73 9.77 0.83 13.39 9.66 0.87 12.83 9.49 0.93
AFR 13.3
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB -10.0 -5.0 0 6.1 10.0
°C TC PI TC PI TC PI TC PI TC PI
15.0 3.19 0.98 3.72 1.02 4.25 1.07 4.88 1.13 5.31 1.17
21.1 3.00 1.01 3.52 1.05 4.05 1.10
4.69 1.16 5.11 1.20
22.0 2.96 1.01 3.49 1.06 4.02 1.11 4.66 1.17 5.08 1.20
24.0 2.90 1.02 3.43 1.07 3.96 1.12 4.59 1.18 4.72 1.18
25.0 2.87 1.03 3.40 1.08 3.92 1.12 4.52 1.17 4.52 1.16
27.0 2.80 1.04 3.33 1.09 3.86 1.13 4.11 1.13 4.11 1.12
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 14.0 23.0 32.0 43.0 50.0
°F TC PI TC PI TC PI TC PI TC PI
59.0 10.88 0.98 12.69 1.02 14.50 1.07 16.65 1.13 18.12 1.17
70.0 10.22 1.01 12.03 1.05 13.83 1.10
16.00 1.16 17.45 1.20
71.6 10.10 1.01 11.91 1.06 13.72 1.11 15.90 1.17 17.33 1.20
75.2 9.89 1.02 11.70 1.07 13.51 1.12 15.66 1.18 16.11 1.18
77.0 9.79 1.03 11.60 1.08 13.38 1.12 15.41 1.17 15.41 1.16
80.6 9.55 1.04 11.36 1.09 13.17 1.13 14.01 1.13 14.01 1.12
Capacity Tables EDUS04-906_b
12 Room Air Conditioners H-Series
3D063099A
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft (7.5 m) Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
7. Cooling capacity at -10 degrees Celsius / 14 degrees Fahrenheit.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR
EWB EDB -10 (°CDB)
°C °C TC SHC PI
14.0 20 3.65 2.66 0.47
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR
EWB EDB 14 (°FDB)
°F °F TC SHC PI
57.2 68.0 12.45 9.08 0.47
EDUS04-906_b Capacity Tables
Room Air Conditioners H-Series 13
FTXG15HVJU + RXG15HVJU (60Hz 230V)
Cooling
Heating
AFR 13.8
BF 0.16
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 20.0 25.0 30.0 32.0 35.0 40.0
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 4.513.360.894.303.260.984.103.151.064.023.111.103.893.051.153.692.961.23
16.0 22 4.713.300.904.513.200.984.303.111.074.223.071.104.103.011.153.892.921.24
18.0 25 4.913.460.904.713.370.994.503.281.074.423.241.114.303.191.164.093.111.24
19.426.75.013.650.904.813.560.994.603.481.074.523.441.11
4.40 3.39 1.16 4.20 3.31 1.25
22.0 30 5.323.520.915.113.441.004.913.371.084.833.341.124.703.291.174.503.221.25
24.0 32 5.523.430.925.323.361.005.113.291.095.033.261.124.913.221.174.703.151.26
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 68.0 77.0 86.0 89.6 95.0 104.0
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 15.38 11.46 0.89 14.68 11.11 0.98 13.98 10.76 1.06 13.70 10.62 1.10 13.28 10.42 1.15 12.58 10.08 1.23
60.8 71.6 16.07 11.26 0.90 15.37 10.93 0.98 14.67 10.60 1.07 14.39 10.48 1.10 13.98 10.28 1.15 13.28 9.97 1.24
64.4 77.0 16.76 11.80 0.90 16.07 11.49 0.99 15.37 11.19 1.07 15.09 11.07 1.11 14.67 10.89 1.16 13.97 10.60 1.24
67.0 80.0 17.11 12.45 0.90 16.41 12.15 0.99 15.71 11.86 1.07 15.43 11.75 1.11
15.01 11.58 1.16 14.31 11.29 1.25
71.6 86.0 18.15 12.00 0.91 17.45 11.75 1.00 16.75 11.49 1.08 16.47 11.39 1.12 16.05 11.24 1.17 15.35 10.98 1.25
75.2 89.6 18.84 11.69 0.92 18.14 11.45 1.00 17.44 11.22 1.09 17.16 11.13 1.12 16.74 10.99 1.17 16.04 10.76 1.26
AFR 14.0
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB -10.0 -5.0 0 6.1 10.0
°C TC PI TC PI TC PI TC PI TC PI
15.0 3.59 1.11 4.19 1.16 4.78 1.22 5.50 1.28 5.98 1.33
21.1 3.37 1.15 3.97 1.20 4.56 1.25
5.28 1.32 5.62 1.34
22.0 3.34 1.15 3.93 1.21 4.53 1.26 5.24 1.33 5.41 1.32
24.0 3.26 1.16 3.86 1.22 4.46 1.27 4.97 1.31 4.97 1.28
25.0 3.23 1.17 3.82 1.22 4.42 1.28 4.76 1.28 4.76 1.26
27.0 3.15 1.18 3.75 1.24 4.33 1.29 4.33 1.23 4.33 1.20
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 14.0 23.0 32.0 43.0 50.0
°F TC PI TC PI TC PI TC PI TC PI
59.0 12.25 1.11 14.29 1.16 16.32 1.22 18.76 1.28 20.39 1.33
70.0 11.51 1.15 13.54 1.20 15.57 1.25
18.02 1.32 19.19 1.34
71.6 11.38 1.15 13.42 1.21 15.45 1.26 17.89 1.33 18.45 1.32
75.2 11.13 1.16 13.17 1.22 15.20 1.27 16.97 1.31 16.97 1.28
77.0 11.01 1.17 13.04 1.22 15.08 1.28 16.23 1.28 16.23 1.26
80.6 10.76 1.18 12.79 1.24 14.76 1.29 14.76 1.23 14.76 1.20
Capacity Tables EDUS04-906_b
14 Room Air Conditioners H-Series
3D063100A
Symbols Note:
AFR : Airflow rate (m3/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.)
4. About SHC which are not mentioned on the table, please calculate them with around values in direct proportion.
5. Capacities are based on the following conditions. Corresponding refrigerant piping length : 25ft (7.5 m) Level difference : 0ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
7. Cooling capacity at -10 degrees Celsius / 14 degrees Fahrenheit.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heating capacity (kW) / (kBtu/h)
PI : Power input (kW)
Temp: Celsius / TC, SHC, PI: kW
INDOOR OUTDOOR
EWB EDB -10 (°CDB)
°C °C TC SHC PI
14.0 20 3.66 2.70 0.46
Temp: Fahrenheit / TC, SHC: kBtu / PI: kW
INDOOR OUTDOOR
EWB EDB 14 (°FDB)
°F °F TC SHC PI
57.2 68.0 12.49 9.21 0.46
EDUS04-906_b Operation Limit
Room Air Conditioners H-Series 15
8. Operation Limit
RXG09/12/15HVJU
41
104
14
Heating
73.4
Level difference
Continuous operation
-4
50
Outdoor temp. (°FWB)
68
50
68
(-4°FDB)
68
0ft
Outdoor temp. (°FDB)
Air flow rate
High
77
778682.4
50
Cooling
5
75
32
Indoor temp. (°FDB)
Indoor temp. (°FWB)
25ft
14
32
109
86
Notes:
23
59
59
86
Pull-down period
Continuous operation
Equivalent piping length
68
50
on the following conditions.
The graphs are based
3D063096
Sound Level EDUS04-906_b
16 Room Air Conditioners H-Series
9. Sound Level
9.1 Measuring Location
Note:
1. Operation sound is measured in an anechoic chamber.
2. The data are based on the conditions shown in the table below.
Indoor Unit
Outdoor Unit
Cooling Heating Piping Length
Indoor ; 80°FDB/67°FWB
Outdoor ; 95°FDB/75°FWB
Indoor ; 70°FDB/60°FWB
Outdoor ; 47°FDB/43°FWB
16.4ft (5 m)
3.3ft
2.6ft
(R5162)
3.3ft
(R4796)
EDUS04-906_b Sound Level
Room Air Conditioners H-Series 17
9.2 Octave Band Level
9.2.1 Indoor Units
FTXG09HVJU
FTXG12HVJU
FTXG15HVJU
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz 60Hz
208/230V 208/230V
SCALE
(H) (L)
42 26
60Hz 208/230V(H)
60Hz 208/230V(L)
STANDARD EXTERNAL STATIC PRESSURE
NC-60
NC-50
NC-40
NC-30
NC-20
60Hz
208/230V
SCALE
60Hz
208/230V
(H) (L)
A42 28
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
208/230V 60Hz
208/230V 60Hz
Cooling Heating
3D063060
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-40
NC-20
NC-30
NC-60
NC-50
208/230V 60Hz
60Hz
(L)
208/230V
(H)
208/230V
2743
60Hz
SCALE
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(H)
60Hz 208/230V(L)
Cooling Heating
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(L)
60Hz 208/230V(H)
208/230V 60Hz
(L)
208/230V
60Hz
(H)
208/230V
A43 29
60Hz
NC-60
NC-30
NC-20
NC-40
NC-50
3D063061
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-50
NC-60
NC-40
NC-30
NC-20
(L)
208/230V
2945
(H)
208/230V
60Hz 60Hz
208/230V 60Hz
60Hz 208/230V(L)
60Hz 208/230V(H)
Cooling
STANDARD EXTERNAL STATIC PRESSURE
NC-50
NC-30
NC-60
NC-40
NC-20
(H)
208/230V
31
60Hz
(L)
208/230V
60Hz
44
208/230V 60Hz
STANDARD EXTERNAL STATIC PRESSURE
60Hz 208/230V(L)
60Hz 208/230V(H)
Heating
3D063080
Sound Level EDUS04-906_b
18 Room Air Conditioners H-Series
9.2.2 Outdoor Units
RXG09HVJU
RXG12HVJU
RXG15HVJU
POWER SOURCE
JIS STANDARD (JIS9612)
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD (JIS9612)
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-60
NC-30
NC-50
NC-20
NC-40
208-230V
60Hz
46
208-230V 60Hz
Cooling
NC-50
NC-40
NC-30
NC-20
NC-60
208-230V
60Hz
46
208-230V 60Hz
Heating
3D063010
POWER SOURCE
JIS STANDARD (JIS9612)
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD (JIS9612)
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-60
NC-40
NC-50
NC-20
NC-30
60Hz
208-230V
49
208-230V 60Hz
Cooling
NC-20
NC-50
NC-60
NC-30
NC-40
48
60Hz
208-230V
208-230V 60Hz
Heating
3D063011
COOLING
NC-40
NC-30
NC-50
NC-60
NC-20
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
60Hz 208/230V
208/230V 60Hz
51
Cooling
208/230V
60Hz
NC-40
NC-30
NC-50
NC-60
NC-20
60Hz 208/230V
208/230V 60Hz
51
Heating
208/230V
60Hz
HEATING
3D047647A
POWER SOURCE
JIS STANDARD (JIS9612)
OPERATING CONDITIONS
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
70
60
20
30
50
40
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
63 125
OCTAVE BAND CENTER FREQUENCY (Hz
)
250 500 1000 2000 4000 8000
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
70
60
20
30
50
40
63
OCTAVE BAND CENTER FREQUENCY (Hz
)
125 250 500 1000 2000 4000 8000
OCTAVE BAND SOUND PRESSURE LEVEL
dB
(
0dB=0.0002
μ
bar
)
THRESHOLD HEARING
APPROXIMATE
FOR CONTINUOUS NOISE
POWER SOURCE
JIS STANDARD (JIS9612)
OPERATING CONDITIONS
OVER ALL ( dB )
SCALE
A
(
B.G.N IS ALREADY RECTIFIED
)
COOLING HEATING
NC-20
NC-50
NC-30
NC-60
NC-40
208-230V
50
60Hz
208-230V 60Hz
Cooling
NC-60
NC-30
NC-50
NC-20
NC-40
208-230V
60Hz
50
208-230V 60Hz
Heating
3D063012
EDUS04-906_b Electric Characteristics
Room Air Conditioners H-Series 19
10.Electric Characteristics
3D063013
Representative Unit Combination Power Supply COMP OFM IFM
Indoor Unit Outdoor Unit Hz-Volts Voltage Range MCA MOP RHz RLA W FLA W FLA
FTXG09HVJU RXG09HVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
14.5 15 29
2.3 60 0.10 57
0.13
60-230 2.1 0.12
FTXG12HVJU RXG12HVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
14.5 15 43
3.7 60 0.13 57
0.15
60-230 3.3 0.14
FTXG15HVJU RXG15HVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
14.5 15 54
5.1 60 0.13 57
0.17
60-230 4.6 0.15
Symbols: Note:
MCA : MIN. CIRCUIT AMPS (A) 1. RLA is based on the following conditions.
Indoor temp. : 80°FDB / 67°FWB (26.7°CDB / 19.4°CWB) Outdoor temp. : 95°FDB (35°CDB)
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. Be sure to install a ground leak detector. (One that can handle higher harmonics.) (This unit uses an inverter, which means that it must be used a ground leak detector capable handling high harmonics in order to prevent malfunctioning of the ground leak detector itself.)
MOP : MAX. OVERCURRENT PROTECTION (A)
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)
RHz : RATED OPERATING FREQUENCY (Hz)
Installation Manual EDUS04-906_b
20 Room Air Conditioners H-Series
11.Installation Manual
11.1 Indoor Units
Read these SAFETY CONSIDERATIONS for Installation carefully before installing an air conditioner or heat pump. After completing the installation, make sure that the unit operates properly during the startup operation.
Instruct the customer on how to operate and maintain the unit. Inform customers that they should store this Installation Manual with the Operation Manual for future reference.
Always use a licensed installer or contractor to install this product. Improper installation can result in water or refrigerant leakage, electrical shock, fire, or explosion.
Meanings of DANGER, WAR N ING, CAUTION, and NOTE Symbols:
DANGER .............. Indicates an imminently hazardous
situation which, if not avoided, will result in death or serious injury.
WARNING ............ Indicates a potentially hazardous
situation which, if not avoided, could result in death or serious injury.
CAUTION ............. Indicates a potentially hazardous
situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE .................. Indicates situations that may result in
equipment or property-damage accidents only.
• Refrigerant gas is heavier than air and replaces oxygen. A massive leak can lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death.
• Do not ground units to water pipes, gas pipes, telephone wires, or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death. Additionally, grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death.
• If refrigerant gas leaks during installation, ventilate the area immediately. Refrigerant gas may produce toxic gas if it comes into contact with fire. Exposure to this gas could cause severe injury or death.
• After completing the installation work, check that the refrigerant gas does not leak throughout the system.
• Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death.
• Safely dispose all packing and transportation materials in accordance with federal/state/local laws or ordinances. Packing materials such as nails and other metal or wood parts, including plastic packing materials used for transportation may cause injuries or death by suffocation.
• Only qualified personnel must carry out the installation work. Installation must be done in accordance with this installation manual. Improper installation may result in water leakage, electric shock, or fire.
• When installing the unit in a small room, take measures to keep the refrigerant concentration from exceeding allowable safety limits. Excessive refrigerant leaks, in the event of an accident in a closed ambient space, can lead to oxygen deficiency.
• Use only specified accessories and parts for installation work. Failure to use specified parts may result in water leakage, electric shocks, fire, or the unit falling.
• Install the air conditioner or heat pump on a foundation strong enough that it can withstand the weight of the unit. A foundation of insufficient strength may result in the unit falling and causing injuries.
• Take into account strong winds, typhoons, or earthquakes when installing. Improper installation may result in the unit falling and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local. state, and national regulations. An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
• Make sure that all wiring is secured, that specified wires are used, and that no external forces act on the terminal connections or wires. Improper connections or installation may result in fire.
• When wiring, position the wires so that the terminal box lid can be securely fastened. Improper positioning of the terminal box lid may result in electric shocks, fire, or the terminals overheating.
• Before touching electrical parts, turn off the unit.
• It is recommended to install a ground fault circuit interrupter if one is not already available. This helps prevent electrical shocks or fire.
• Securely fasten the outside unit terminal cover (panel). If the terminal cover/panel is not installed properly, dust or water may enter the outside unit causing fire or electric shock.
• When installing or relocating the system, keep the refrigerant circuit free from substances other than the specified refrigerant (R-410A) such as air. Any presence of air or other foreign substance in the refrigerant circuit can cause an abnormal pressure rise or rupture, resulting in injury.
EDUS04-906_b Installation Manual
Room Air Conditioners H-Series 21
• Do not change the setting of the protection devices. If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Daikin are used, fire or explosion may occur.
• Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock.
• Do not allow children to play on or around the unit to prevent injury.
• Do not touch the refrigerant pipes during and immediately after operation as the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to return to normal temperature or, if you must touch them, be sure to wear proper gloves.
• Install drain piping to proper drainage. Improper drain piping may result in water leakage and property damage.
• Insulate piping to prevent condensation.
• Be careful when transporting the product.
• Do not turn off the power immediately after stopping operation. Always wait for at least 5 minutes before turning off the power. Otherwise, water leakage may occur.
• Do not use a charging cylinder. Using a charging cylinder may cause the refrigerant to deteriorate.
• Refrigerant R-410A in the system must be kept clean, dry, and tight.
(a) Clean and Dry -- Foreign materials (including
mineral oils such as SUNISO oil or moisture) should be prevented from getting into the system.
(b) Tight -- R-410A does not contain any chlorine,
does not destroy the ozone layer, and does not reduce the earth’s protection again harmful ultraviolet radiation. R-410A can contribute to the greenhouse effect if it is released. Therefore take proper measures to check for the tightness of the refrigerant piping installation. Read the chapter Refrigerant Piping and follow the procedures.
• Since R-410A is a blend, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in a state of gas, its composition can change and the system will not work properly.
• The indoor unit is for R-410A. See the catalog for indoor models that can be connected. Normal operation is not possible when connected to other units.
• Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types). Install the indoor unit far away from fluorescent lamps as much as possible.
• Indoor units are for indoor installation only. Outdoor units can be installed either outdoors or indoors. This unit is for indoor use.
• Do not install the air conditioner or heat pump in the following locations: (a) Where a mineral oil mist or oil spray or vapor is
produced, for example, in a kitchen. Plastic parts may deteriorate and fall off or result in water leakage.
(b) Where corrosive gas, such as sulfurous acid gas, is
produced. Corroding copper pipes or soldered parts may result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the control system and cause the unit to malfunction.
(d) Where flammable gas may leak, where there is
carbon fiber, or ignitable dust suspension in the air, or where volatile flammables such as thinner or gasoline are handled. Operating the unit in such conditions can cause a fire.
• Take adequate measures to prevent the outside unit from being used as a shelter by small animals. Small animals making contact with electrical parts can cause malfunctions, smoke, or fire. Instruct the customer to keep the area around the unit clean.
• Install the power supply and control wires for the indoor and outdoor units at least 3.5 feet away from televisions or radios to prevent image interference or noise. Depending on the radio waves, a distance of 3.5 feet may not be sufficient to eliminate the noise.
• Dismantling the unit, treatment of the refrigerant, oil and additional parts must be done in accordance with the relevant local, state, and national regulations.
• Do not use the following tools that are used with conventional refrigerants: gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, or refrigerant recovery equipment.
• If the conventional refrigerant and refrigerator oil are mixed in R-410A, the refrigerant may deteriorate.
• This air conditioner or heat pump is an appliance that should not be accessible to the general public.
• As design pressure is 478 psi, the wall thickness of field-installed pipes should be selected in accordance with the relevant local, state, and national regulations.
Installation Manual EDUS04-906_b
22 Room Air Conditioners H-Series
Accessories
Mounting plate
1
Wireless remote controller
1
Installation manual
1
Deodorizing filter for streamer
1
Remote controller holder
1
Mounting plate fixing screws
3/16” × 1”L (M4 × 25mm)
9
Titanium apatite photocatalytic
air-purifying filter
1
Dry batteries AAA. LR03
(alkaline)
2
Fixing screws for remote
controller holder 1/8” × 13/16”L (M3 × 20mm)
2
Indoor unit fixing screws
3/16” × 1/2”L (M4 × 12mm)
3
Operation manual
1
A
E
J
B
F
K
C
G
L
D
H
EDUS04-906_b Installation Manual
Room Air Conditioners H-Series 23
3
Indoor Unit Installation Drawings
1.
Removing and installing indoor unit.
• Installation method
1) Using the marks (3 locations) on top of the indoor unit, attach the mounting plate hooks
onto the indoor unit.
2) Attach the tabs on the bottom frame onto the
mounting plate. If the tabs are not hooked onto the plate, remove the front grille to hook them. (Check to see if the tabs are hooked securely.)
• Removal method
Push up the mark part on the bottom of the front grille, discharge the tabs, and then remove the unit while lifting it up.
Ta b
Bottom frame
Mark (rear side)
A Mounting
plate
To remove the unit, push up the bottom of the bottom frame with your fingers to free tabs. (Mark parts (2 locations) on the bottom of the front grille.)
A Mounting
plate
A
A
F Remote controller holder
Fixing screws for remote controller holder 1/8” × 13/16”L (M3 × 20mm) (2)
Wrap the insulation pipe with the finishing tape from bottom to top.
Install the hose with a downward slope.
Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipe’s cut line.
1-3/16” (30mm) or more from ceiling
1-15/16” (50mm) or more from walls (on both sides)
Mounting plate fixing screws 3/16” × 1”L (M4 × 25mm) (9)
A
Mounting plate
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
Use when opening the front panel and securing.
Supporting plate
Supporting plate
How to open the service lid
Front panel
Air filter
2)
1)
The service lid is removable.
Opening the lid
1) Remove the screws on the service lid.
2) Hold the knobs on the service lid and pull forward.
Before screwing the remote controller holder to the wall, make sure that control signals are properly received by indoor unit.
C
Titanium apatite photocatalytic air-purifying filter
B
Deodorizing filter for streamer
Hook
E
Wireless remote controller
Set the dry batteries AAA. LR03 (alkaline)
G
L
The securing tape is applied. Be sure to remove it before installation.
A
K
Loading...
+ 56 hidden pages