Daikin RXF50B2V1B, RXF60B2V1B, RXF71A2V1B, RXP50L2V1B, RXP60L2V1B Installer reference guide [sv]

...
Installatörens
referenshandbok
R32 Split-serien
RXF50B2V1B RXF60B2V1B RXF71A2V1B
RXP50L2V1B RXP60L2V1B RXP71L2V1B
RXJ50N2V1B
RXA42B2V1B RXA50B2V1B
Installatörens referenshandbok
R32 Split-serien
Svenska

Innehållsförteckning

Innehållsförteckning
1 Allmänna säkerhetsföreskrifter 3
1.1 Om dokumentationen ................................................................ 3
1.1.1 Betydelse av varningstexter och symboler ................. 3
1.2 För installatören......................................................................... 3
1.2.1 Allmänt........................................................................ 3
1.2.2 Installationsplats ......................................................... 3
1.2.3 Köldmedium................................................................ 5
1.2.4 Bärare ......................................................................... 6
1.2.5 Vatten.......................................................................... 6
1.2.6 Elektricitet ................................................................... 6
2 Om dokumentationen 7
2.1 Om detta dokument................................................................... 7
2.2 Kort om installatörens referensguide......................................... 7
3 Om lådan 7
3.1 Översikt: Om lådan.................................................................... 7
3.2 Utomhusenheten ....................................................................... 7
3.2.1 Hur du packar upp utomhusenheten........................... 7
3.2.2 Hur du avlägsnar alla tillbehör från utomhusenheten . 8
4 Om enheten 8
4.1 Översikt: Om enheten ............................................................... 8
4.2 Identifikation .............................................................................. 8
4.2.1 Identifikationsetikett: Utomhusenhet........................... 8
5 Förberedelse 8
5.1 Översikt: Förberedelse .............................................................. 8
5.2 Förberedelse av installationsplatsen ......................................... 8
5.2.1 Installationsplatskrav för utomhusenheten.................. 9
5.2.2 Ytterligare krav för installationsplatsen för
utomhusenheten i kalla klimat..................................... 10
5.3 Förbereda köldmedierören ........................................................ 10
5.3.1 Krav för köldmedierör.................................................. 10
5.3.2 Köldmediumrörlängd och höjdskillnad ........................ 10
5.3.3 Isolering av köldmedierören........................................ 10
5.4 Förbereda dragning av elkablar ................................................ 11
5.4.1 Om att förbereda dragning av elkablar ....................... 11
6 Installation 11
6.1 Översikt: Installation .................................................................. 11
6.2 Öppna enheten.......................................................................... 11
6.2.1 Om öppning av enheten.............................................. 11
6.2.2 Hur du öppnar utomhusenheten ................................. 11
6.3 Montering av utomhusenheten.................................................. 11
6.3.1 Om montering av utomhusenheten............................. 11
6.3.2 Försiktighetsåtgärder vid montering av
utomhusenheten ......................................................... 11
6.3.3 Så här förbereder du installationsstrukturen............... 11
6.3.4 Så här installerar du utomhusenheten........................ 12
6.3.5 Så här gör du dräneringen.......................................... 12
6.3.6 Hur du förhindrar att utomhusenheten faller omkull.... 12
6.4 Anslutning av köldmedierören ................................................... 13
6.4.1 Om anslutning av köldmediumrör ............................... 13
6.4.2 Försiktighetsåtgärder vid anslutning av
köldmediumrör ............................................................ 13
6.4.3 Riktlinjer vid anslutning av köldmediumrör.................. 13
6.4.4 Riktlinjer för rörbockning ............................................. 14
6.4.5 Flänsning av röränden ................................................ 14
6.4.6 Använda stoppventilen och serviceporten .................. 14
6.4.7 Ansluta köldmediumrören till utomhusenheten........... 15
6.5 Kontroll av köldmedierören........................................................ 15
6.5.1 Om kontroll av köldmedierören................................... 15
6.5.2 Försiktighetsåtgärder vid anslutning av
köldmediumrör ............................................................ 15
6.5.3 Hur du kontrollerar eventuella läckor .......................... 15
6.5.4 Hur du utför en vakuumtorkning.................................. 15
6.6 Påfyllning av köldmedium........................................................... 16
6.6.1 Om påfyllning av köldmedium...................................... 16
6.6.2 Om kylmediet............................................................... 16
6.6.3 Försiktighetsåtgärder vid påfyllning av köldmedium .... 17
6.6.4 Hur du avgör hur mycket ytterligare köldmedium som
behövs ......................................................................... 17
6.6.5 Så här räknar ut total påfyllningsmängd ...................... 17
6.6.6 Påfyllning av ytterligare köldmedium ........................... 17
6.6.7 Hur du fäster etiketten om fluorerade växthusgaser.... 17
6.7 Anslutning av elledningarna ....................................................... 17
6.7.1 Om att ansluta elledningarna....................................... 17
6.7.2 Försiktighetsåtgärder vid anslutning av elledningarna. 18
6.7.3 Riktlinjer vid anslutning av elledningarna..................... 18
6.7.4 Specifikationer för standardkablar ............................... 19
6.7.5 Hur du ansluter elkablarna på utomhusenheten.......... 19
6.8 Avsluta installationen av utomhusenheten ................................. 19
6.8.1 Hur du avslutar installationen av utomhusenheten...... 19
6.8.2 Stänga utomhusenheten.............................................. 19
6.9 Om kompressorn........................................................................ 20
7 Konfiguration 20
7.1 Anläggningsinställning................................................................ 20
7.1.1 Hur du ställer in anläggningsläget................................ 20
7.2 Standby-läge .............................................................................. 20
7.2.1 Om standby-läget......................................................... 20
7.2.2 Procedur för aktivering av standby-läge ...................... 20
8 Driftsättning 20
8.1 Översikt: driftsättning.................................................................. 20
8.2 Försiktighetsåtgärder vid driftsättning ........................................ 20
8.3 Checklista före driftsättning ........................................................ 21
8.4 Checklista under driftsättning ..................................................... 21
8.5 Hur du utför en testkörning......................................................... 21
8.6 Starta utomhusenheten för första gången.................................. 21
9 Överlämna till användaren 21
10 Underhåll och service 21
10.1 Översikt: Underhåll och service.................................................. 21
10.2 Säkerhetsföreskrifter vid underhåll ............................................. 22
10.3 Checklista för årligt underhåll av utomhusenheten .................... 22
11 Felsökning 22
11.1 Översikt: Felsökning ................................................................... 22
11.2 Försiktighetsåtgärder vid felsökning ........................................... 22
11.3 Lösa problem med hjälp av symptom......................................... 22
11.3.1 Symptom: Enheterna faller, vibrerar eller bullrar ......... 22
11.3.2 Symptom: enheten värmer INTE upp eller kyler som
förväntat ....................................................................... 22
11.3.3 Symptom: Vattenläckor................................................ 22
11.3.4 Symptom: Spänningsfall eller krypströmmar ............... 22
11.3.5 Symptom: Enheten fungerar INTE eller brännskador .. 22
11.4 Feldiagnos med lampa på utomhusenhetens kretskort.............. 22
12 Kassering 23
12.1 Översikt: Avfallshantering........................................................... 23
12.2 Nedpumpning ............................................................................. 23
12.3 Starta och stoppa forcerad kylning ............................................. 23
12.3.1 Så här startar och stoppar du tvingande kylning med
inomhusenhetens PÅ/AV-brytare................................. 23
12.3.2 Så här startar och stoppar du tvingande kylning med
inomhusenhetens fjärrkontroll...................................... 23
13 Tekniska data 24
13.1 Kopplingsschema ....................................................................... 24
13.2 Rördragningsschema ................................................................. 25
13.2.1 Rördragningsschema: Utomhusenhet ......................... 25
14 Ordlista 26
Installatörens referenshandbok
2
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_
4P513661-6B – 2018.05
RXA42+50B2
R32 Split-serien

1 Allmänna säkerhetsföreskrifter

1 Allmänna
säkerhetsföreskrifter

1.1 Om dokumentationen

▪ Den ursprungliga dokumentationen har skrivits på engelska. Alla
andra språk är översättningar.
▪ Säkerhetsföreskrifterna i detta dokument omfattar oerhört viktig
information, så det är viktigt att följa dem noggrant.
▪ Installation av systemet, och alla aktiviteter som beskrivs i
installationshandboken samt installatörens referensguide får ENDAST utföras av en behörig installatör.

1.1.1 Betydelse av varningstexter och symboler

FARA
Anger en situation som leder till död eller allvarlig skada.
FARA: RISK FÖR ELCHOCK
Anger en situation som kan leda till att du får en elchock.
FARA: RISK FÖR BRÄNNSKADOR
Anger en situation som kan leda till brännskador på grund av extremt varma eller kalla temperaturer.
FARA: RISK FÖR EXPLOSION
Anger en situation som kan leda till en explosion.
VARNING
Anger en situation som kan leda till död eller allvarlig skada.
VARNING: BRANDFARLIGT MATERIAL
FÖRSIKTIGT
Anger en situation som kan leda till mindre eller måttliga skador.
NOTERING
Anger en situation som kan leda till skador på utrustningen eller lokalen.
INFORMATION
Anger användbara råd eller ytterligare information.
Symbol Förklaring
Läs igenom installations- och bruksanvisningen samt kopplingsinstruktionerna inför installation.
Läs servicehandboken inför underhålls- och serviceuppgifter.
Mer information finns i installations- och användarhandboken.

1.2 För installatören

NOTERING
Felaktig installation eller anslutning av utrustning eller tillbehör kan orsaka elchock, kortslutning, läckage, brand eller annan skada på utrustningen. Använd endast tillbehör, extrautrustning och reservdelar som tillverkats eller godkänts av Daikin.
VARNING
Se till att installationen, kontroller och använda material överensstämmer med gällande lagstiftning (utöver instruktionerna i dokumentationen Daikin).
FÖRSIKTIGT
Bär lämplig personlig skyddsutrustning (skyddshandskar, säkerhetsglasögon, etc.) under installationen, underhållet eller reparationen av systemet.
VARNING
Riv isär och kasta plastförpackningsmaterialet så att ingen, speciellt barn, inte kan leka med det. Möjlig risk: kvävning.
FARA: RISK FÖR BRÄNNSKADOR
▪ Vidrör INTE köldmedierör, vattenledningar eller interna
delar under eller omedelbart efter drift. De kan vara för varma eller för kalla. Vänta tills de återgår till normal temperatur. Använd skyddshandskar om du måste röra vid dem.
▪ Vidrör ALDRIG oavsiktligt läckage av köldmediet.
VARNING
Vidta nödvändiga åtgärder för att förebygga att smådjur söker skydd i enheten. Smådjur som kommer i kontakt med strömförande delar kan orsaka fel, rökutveckling eller eldsvåda.
FÖRSIKTIGT
Vidrör INTE enhetens luftintag eller aluminiumspjäll eftersom det finns risk för att du skadas.
NOTERING
▪ Placera INTE föremål eller utrustning ovanpå enheten.
▪ Sitt INTE, klättra eller stå på enheten.
NOTERING
Arbeten som utförs på utomhusenheten ska helst göras under torra väderförhållanden för att förhindra vatteninträngning.
I enlighet med gällande lagstiftning kan det vara nödvändigt att föra en loggbok över utrustningen. Denna ska alltid innehålla: information om underhåll, reparationsarbete, kontrollresultat, passningstider, etc.
Dessutom SKA minst följande information om systemet vara tillgänglig på lätt åtkomlig plats:
▪ Nedstängningsinstruktioner i händelse av nödfall
▪ Namn och adress till brandkår, polis och sjukhus
▪ Namn, adress och jourtelefonnummer till serviceavdelningar
I Europa ger EN378 nödvändig ledning för den här loggboken.

1.2.1 Allmänt

Kontakta din installatör om du INTE är säker på hur du installerar eller använder enheten.
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_ RXA42+50B2 R32 Split-serien 4P513661-6B – 2018.05

1.2.2 Installationsplats

▪ Se till att det finns tillräckligt med utrymme runt enheten för
tillräcklig luftcirkulation.
▪ Se till att installationsplatsen håller för enhetens vikt och
vibrationer.
▪ Se till att området är väl ventilerat. Blockera ALDRIG några
ventilationsöppningar.
Installatörens referenshandbok
3
1 Allmänna säkerhetsföreskrifter
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
1.843 7.956
8.0
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
▪ Se till att enheten står på en jämn yta.
Installera INTE enheten på någon av följande platser:
▪ I miljöer med explosionsrisk.
▪ I närheten av maskiner som avger elektromagnetiska vågor.
Elektromagnetiska vågor kan störa styrsystemet och göra att utrustningen inte fungerar som den ska.
▪ På platser med risk för brand på grund av läckage av brandfarliga
gaser (t.ex. lösningsmedel eller bensin), kolfiber eller lättantändligt damm.
▪ På platser där frätande gas (t.ex. svavelsyrliga gaser) produceras.
Korrosion av kopparledningar eller lödda delar kan orsaka att köldmediet läcker ut.
Instruktioner för utrustning med köldmedium R32
Om tillämpligt.
VARNING
▪ Punktera EJ och bränn EJ.
▪ Använd INGA andra metoder för att påskynda
avfrostningsprocessen eller rengöring av utrustningen än de som rekommenderas av tillverkaren.
▪ Var medveten om att köldmedium R32 är luktfritt.
VARNING
Utrustningen ska förvaras så att inga mekaniska skador uppstår och i ett väl ventilerat rum utan antändningskällor i kontinuerlig drift (t.ex. öppna lågor, en gasvärmare i drift eller en elvärmare i drift). Rummets dimensioner ska vara enligt nedan.
Så här bestämmer du minsta golvyta
1 Bestäm total mängd påfyllt köldmedium i systemet
(= fabrikspåfyllt köldmedium + ytterligare påfyllt köldmedium).
2 Bestäm vilket diagram eller vilken tabell du vill använda.
▪ För inomhusenheter: Är enheten takmonterad,
väggmonterad eller stående på golvet?
▪ För utomhusenheter som installeras eller förvaras inomhus
samt lokala rör i oventilerade utrymmen beror detta på installationshöjden:
Om installationshöjden är… Använder du diagrammet eller
tabellen för…
<1,8m Enheter som står på golvet 1,8≤x<2,2M Väggmonterade enheter ≥2,2m Takmonterade enheter
3 Använd diagrammet eller tabellen för att bestämma minsta
golvyta.
NOTERING
▪ Återanvänd INTE kopplingar som redan har använts.
▪ Installationskopplingar som gjorts mellan delar av
köldmediumsystemet ska vara tillgängligt i underhållssyfte.
VARNING
Kontrollera att installation, service, underhåll och reparation följer instruktionerna från Daikin och tillämplig lagstiftning (till exempel nationella regler för gashantering) samt endast utförs av behöriga personer.
Krav på installationsutrymme
NOTERING
▪ Rör måste skyddas mot fysiska skador.
▪ Rörlängden måste hållas ned till ett minimum.
VARNING
Om apparater innehåller köldmediet R32 MÅSTE golvytan för rummet där apparaterna är installerade, används och förvaras vara större än den minsta golvytan som definieras i tabellen under A (m2). Detta gäller:
▪ Inomhusenheter utan sensor för köldmediumläckage.
För inomhusenheter med sensor för köldmediumläckage, se installationshandboken
▪ Utomhusenheter installerade eller förvarade inomhus
(till exempel vinterträdgård, garage, maskinrum)
▪ Rördragning i oventilerade utrymmen
Installatörens referenshandbok
4
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_
RXA42+50B2
R32 Split-serien
4P513661-6B – 2018.05
1 Allmänna säkerhetsföreskrifter
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
FARA: RISK FÖR EXPLOSION
Nedpumpning – läckage av köldmedium. Om du vill
tömma systemet och det finns en läcka i köldmediumkretsen:
▪ Använd INTE enhetens automatiska tömningsfunktion
som samlar allt köldmedium från systemet i utomhusenheten. Trolig konsekvens: Självantändning och explosion i kompressorn på grund av luft som kommer in i driftkompressorn.
▪ Använd ett separat återvinningssystem så att enhetens
kompressor INTE behöver köras.
VARNING
Återvinn ALLTID köldmedium. Släpp ALDRIG ut dem direkt i miljön. Använd en vakuumpump för att evakuera installationen.
NOTERING
När alla rör anslutits ska man kontrollera att inte gas läcker ut. Använd kvävgas för att utföra gasläckagekontroll.
NOTERING
▪ Fyll INTE på mer än den angivna mängden köldmedel
eftersom det kan skada kompressorn.
▪ När köldmediumsystemet ska öppnas MÅSTE
köldmedium hanteras enligt tillämplig lagstiftning.
m Total mängd påfyllt köldmedium i systemet
A
Minsta golvyta
min
(a) Ceiling-mounted unit (=Takmonterad enhet) (b) Wall-mounted unit (=Väggmonterad enhet) (c) Floor-standing unit (=Enhet som står på golvet)

1.2.3 Köldmedium

Om tillämpligt. Se installationshandboken eller installatörens referenshandbok för mer information.
NOTERING
Se till att köldmedierören överensstämmer med gällande lagstiftning. I Europa är EN378 den gällande standarden.
NOTERING
Se till att utomhusledningar och -anslutningar INTE utsätts för belastning.
VARNING
Under kontroller får du ALDRIG trycksätta apparaterna med ett tryck som överstiger det högsta tillåtna trycket (anges på enhetens märkplåt).
VARNING
Vidta tillräckliga försiktighetsåtgärder vid köldmedieläckage. Om köldmediegas läcker ska området ventileras omedelbart. Möjliga risker:
▪ För hög koncentration av köldmedium i trånga
utrymmen kan leda till syrebrist.
▪ Giftig gas kan bildas om köldmediegas kommer i
kontakt med öppen låga.
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_ RXA42+50B2 R32 Split-serien 4P513661-6B – 2018.05
VARNING
Se till att det inte finns något syre i systemet. Köldmedium får endast fyllas på efter utförd läckagetest och vakuumtorkning.
▪ Om den måste fyllas på finns information på enhetens namnplåt.
Här anges typ av kylmedium och nödvändig mängd.
▪ Utomhusenheten har fyllts på med köldmedium från fabrik och
beroende på rörtjocklek och rörlängder kan vissa system behöva ytterligare påfyllning av köldmedium.
▪ Använd endast verktyg den kylmediumtyp som används i
systemet för att upprätthålla nödvändigt tryck och förhindra att främmande föremål kommer in i systemet.
▪ Fyll på kylmediumvätska som följer:
Om
Ett hävertrör finns
Påfyllning med cylindern upprätt.
(d.v.s. cylindern är markerad med "Liquid filling siphon attached" – hävert för vätskepåfyllning ansluten)
Ett hävertrör finns INTE Påfyllning med cylindern upp och
ned.
▪ Öppna kylmediumcylindrar långsamt.
▪ Fyll på kylmediet i vätskeform. Om du fyller på det i gasform är
normal drift inte möjlig.
Installatörens referenshandbok
5
1 Allmänna säkerhetsföreskrifter
FÖRSIKTIGT
När köldmediumpåfyllningen är slutförd eller när du tar en paus ska du omedelbart stänga ventilen på köldmediumtanken. Om ventilen INTE omedelbart stängs kan det återstående trycket ge ytterligare påfyllning av köldmedium. Trolig konsekvens: Felaktig mängd köldmedium.

1.2.4 Bärare

Om tillämpligt. Se installationshandboken eller installatörens referenshandbok för mer information.
VARNING
Valet av bärare MÅSTE ske i enlighet med gällande bestämmelser.
VARNING
Vidta tillräckliga försiktighetsåtgärder vid bärarläckage. Om bärare läcker ut måste utluftning ske omedelbart och därefter kontaktar du din lokala återförsäljare.
VARNING
Omgivningstemperaturen inuti enheten kan bli mycket högre än rumstemperaturen, t.ex. 70°C. Om bärare läcker ut kan varma delar inuti enheten skapa en riskfull situation.
VARNING
Användning och installation av tillämpningen MÅSTE följa de säkerhets- och miljömässiga föreskrifter som anges i gällande lagstiftning.
VARNING
▪ Använd ENDAST kopparledningar.
▪ Se till att lokal kabeldragning görs i enlighet med
gällande lagstiftning.
▪ All lokal kabeldragning MÅSTE utföras i enlighet med
kopplingsschemat som medföljer produkten.
▪ Kläm ALDRIG kabelbuntar och se till att de INTE
kommer i kontakt med icke-isolerade ledningar eller vassa kanter. Kontrollera att ingen extern belastning påfrestar kabelanslutningarna.
▪ Se till att installera jordledare. Jorda INTE enheten till
en vattenledning, ett vågfrontskydd eller en jordledning för telefon. Ofullständig jordning kan leda till elektriska stötar.
▪ Se till att använda en dedikerad strömkrets. Dela
ALDRIG strömförsörjning med någon annan apparat.
▪ Se till att nödvändiga säkringar eller kretsbrytare
installeras.
▪ Se till att installera en jordfelsbrytare. Om inte detta
följs kan det resultera i elektriska stötar eller eldsvåda.
▪ Vid installation av jordfelsbrytaren ska du kontrollera att
den är kompatibel med invertern (som klarar högfrekvent elektriskt brus) för undvika att jordfelsbrytaren löser ut i onödan.
NOTERING
Säkerhetsåtgärder vid dragning av elledningar:

1.2.5 Vatten

Om tillämpligt. Se installationshandboken eller installatörens referenshandbok för mer information.
NOTERING
Se till att vattenkvaliteten uppfyller EU-direktivet 98/83 EG.

1.2.6 Elektricitet

FARA: RISK FÖR ELCHOCK
▪ Stäng AV all strömförsörjning innan du avlägsnar
kopplingsdosans skyddskåpa och kopplar elektriska ledningar eller rör vid elektriska delar.
▪ Stäng av strömförsörjningen i mer än 1 minut och mät
spänningen vid kontakterna på huvudkretsens kondensatorer eller elektriska komponenter innan du utför reparationer. Spänningen MÅSTE vara mindre än 50 V likspänning innan du kan röra vid elektriska komponenter. Se kopplingsschemat för kontakternas placering.
▪ Rör INTE vid elektriska komponenter med våta händer.
▪ Lämna INTE enheten obevakad när serviceluckan har
avlägsnats.
VARNING
Om enheten INTE är fabriksinstallerad MÅSTE en huvudbrytare eller andra medel för att kunna koppla ifrån enheten installeras, med en kontaktseparation i alla poler som resulterar i fullständig bortkoppling enligt villkoren i överspänningsklassIII, i den fasta kabeldragningen.
▪ Anslut INTE kablar med olika tjocklek till
strömförsörjningsplinten (för mycket spelrum kan orsaka onormal värme).
▪ När du ansluter kablar av samma tjocklek gör du enligt
anvisningarna ovan.
▪ Vid ledningsdragning använder du angiven strömkabel
och ansluter den ordentligt. Fäst den sedan så att inte plinten utsätts för belastning utifrån.
▪ Använd en lämplig skruvmejsel för att dra åt
terminalskruvarna. En skruvmejsel med för litet huvud förstör skruven och gör det omöjligt att dra åt den.
▪ Om du drar åt terminalskruvarna för hårt kan de gå
sönder.
VARNING
▪ När du är färdig med elanslutningarna kontrollerar du
att alla elektriska komponenter och kontakter i eldosan är ordentligt anslutna.
▪ Se till att alla skyddskåpor är stängda innan du sätter
igång enheten.
NOTERING
Gäller endast om strömförsörjningen har tre faser och kompressorn har en PÅ/AV startmetod.
Om det föreligger risk för omvänd faskoppling efter tillfälligt strömavbrott och/eller om strömmen kommer och går när produkten är i drift, då kan man montera ett externt fasskydd. Om produkten körs med fasfel kan kompressorn och andra komponenter skadas.
Installatörens referenshandbok
6
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_
4P513661-6B – 2018.05
RXA42+50B2
R32 Split-serien

2 Om dokumentationen

2 Om dokumentationen

2.1 Om detta dokument

INFORMATION
Se till att användaren har den tryckta dokumentationen, samt be honom/henne att förvara dem för framtida referensbruk.
Målgrupp
Behöriga installatörer
Dokumentuppsättning
Detta dokument är en del av en dokumentuppsättning. Den kompletta dokumentuppsättningen består av:
Allmänna försiktighetsåtgärder:
▪ Försiktighetsåtgärder som du MÅSTE läsa före installation
▪ Format: Papper (i lådan för utomhusenheten)
Installationshandbok för utomhusenheten:
▪ Installationsanvisningar
▪ Format: Papper (i lådan för utomhusenheten)
Installatörens referenshandbok:
▪ Förberedelse av installationen, referensdata…
▪ Format: Digitala filer på http://www.daikineurope.com/support-
and-manuals/product-information/
De senaste versionerna av den medföljande dokumentationen kan finnas på Daikins lokala webbplats eller genom din återförsäljare.
Den ursprungliga dokumentationen har skrivits på engelska. Alla andra språk är översättningar.
Tekniska data
Delar av de senaste tekniska data är tillgängliga på den regionala
Daikin-webbplatsen (allmänt tillgänglig).
Alla de senaste tekniska data finns på Daikin extranät (inloggning
krävs).

2.2 Kort om installatörens referensguide

Kapitel Beskrivning
Avfallshantering Avfallshantering för systemet Tekniska data Systemspecifikationer Ordlista Definition av termer

3 Om lådan

3.1 Översikt: Om lådan

I det här kapitlet finns en beskrivning av vad du måste göra när lådan med utomhusenheten är levererad till platsen.
Här finns information om:
▪ Uppackning och hantering av enheten
▪ Ta bort tillbehör från enheterna
Tänk på följande:
▪ Enheten MÅSTE kontrolleras för skador vid leveransen.
Eventuella skador SKA omedelbart anmälas till transportbolagets representant.
▪ Placera den förpackade enheten så nära installationsplatsen som
möjligt för att skydda den från transportskador.
▪ Förbered den väg där enheten ska transporteras in.
▪ Vid skötsel av enheten beaktas nedanstående:
Ömtåligt, hantera enheten försiktigt.
Förvara alltid enheten stående upprätt för att undvika skador.
Tillse att enheten inte kommer i kontakt med regn eller fukt.
Det KRÄVS minst 2personer för att lyfta enheten.

3.2 Utomhusenheten

3.2.1 Hur du packar upp utomhusenheten

Kapitel Beskrivning
Allmänna försiktighetsåtgärder
Om dokumentationen Vilken dokumentation finns för
Om lådan Så här packar du upp enheterna och tar
Om enheten Så här identifierar du enheten Förberedelser Det här ska du göra och veta innan du
Installation Det här ska du göra och veta för
Konfiguration Det här ska du göra och veta för att
Driftsättning Det här ska du göra och veta för att
Överlämning till användaren
Underhåll och service Så här underhåller och servar du
Felsökning Vad ska göras vid problem
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_ RXA42+50B2 R32 Split-serien 4P513661-6B – 2018.05
Försiktighetsåtgärder som du MÅSTE läsa före installation
installatören
bort tillbehören
kommer till platsen
installation av systemet
konfigurera systemet efter installation
driftsätta systemet efter installation Det här ska du ge till och förklara för
användaren
enheterna
Installatörens referenshandbok
7

4 Om enheten

1
2
b ec d
a
f6×g
d Flerspråkig dekal med information om fluorgaser som
påverkar växthuseffekten
e Dräneringsplugg (längst ned i förpackningen)
f Dräneringslock (1)
g Dräneringslock (2)
4 Om enheten
VARNING: BRANDFARLIGT MATERIAL
Köldmediet i enheten är brandfarligt.

4.1 Översikt: Om enheten

I det här kapitlet finns information om:
▪ Identifiering av utomhusenheten

4.2 Identifikation

NOTERING
Vid installation eller underhåll av flera enheter samtidigt ska du se till att INTE blanda ihop servicepanelerna för de olika modellerna.

4.2.1 Identifikationsetikett: Utomhusenhet

3.2.2 Hur du avlägsnar alla tillbehör från utomhusenheten

1 Lyft utomhusenheten.
2 Ta ut tillbehören i förpackningens botten.
FÖRSIKTIGT
Hantera alltid utomhusenheten enligt nedanstående anvisningar:
Plats

5 Förberedelse

5.1 Översikt: Förberedelse

I det här kapitlet finns en beskrivning av vad du måste göra och veta innan du kommer till platsen.
Här finns information om:
▪ Förberedelse av installationsplatsen
▪ Förberedelse av köldmediumrör
▪ Förberedelse av elkablar
a Allmänna försiktighetsåtgärder b Installationshandbok för utomhusenheten c Dekal med information om fluorgaser som påverkar
växthuseffekten
Installatörens referenshandbok
8

5.2 Förberedelse av installationsplatsen

Installera INTE enheten på platser som ofta används som arbetsplats. Vid byggarbeten (t.ex. slipning) där mycket damm skapas MÅSTE enheten täckas över.
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_
4P513661-6B – 2018.05
RXA42+50B2
R32 Split-serien
5 Förberedelse
>100
>50
>350
(mm)
b
a
>100
>50
b
a
>100
b
a
b
a
>350
>350
>50
b
a
b
a
b
c
Välj en installationsplats med tillräckligt utrymme för att kunna bära enheten in och ut från platsen.
FÖRSIKTIGT
▪ Kontrollera att installationsplatsen klarar enhetens vikt.
Dålig installation är en skaderisk. Det kan också orsaka vibrationer och driftsbuller.
▪ Se till att lämna tillräckligt serviceutrymme.
▪ Installera INTE enheten så att den är i kontakt med
innertaket eller en vägg eftersom detta kan orsaka vibrationer.
▪ Välj en plats där den varma/kalla luften som släpps ut från
enheten eller driftsljud INTE stör någon.
▪ Se till att det finns tillräckligt med utrymme runt enheten för
tillräcklig luftcirkulation.
▪ Undvik områden där antändliga gaser eller ämnen kan läcka ut.
Installera strömkablar på minst 1 meters avstånd från tv- eller radioapparater för att förebygga störningar. Beroende på radiovågorna kan ett avstånd på 3meter INTE vara tillräckligt.
VARNING
Placera INGA föremål under inomhus- och/eller utomhusenheten som kan bli fuktiga. Kondens på enheten eller köldmediumrör, smuts från luftfiltret eller blockering av dräneringen kan orsaka att vätska droppar ned och orsakar nedsmutsning eller skador.
NOTERING
▪ Stapla INTE enheterna på varandra.
▪ Häng INTE enheten i taket.
Kraftig vind (≥18 km/h) som blåser mot utomhusenhetens luftutlopp orsakar kortslutning (suger in frånluft). Det kan leda till:
▪ försämrad driftskapacitet;
▪ regelbunden isbildning när uppvärmningsfunktionen används;
▪ funktionsavbrott på grund av minskat lågtryck eller en ökning av
högtrycket;
▪ en trasig fläkt (om kraftig vind ständigt blåser mot fläkten kan den
börja rotera för snabbt, tills den går sönder).
Det rekommenderas att du installerar en avskärmningsplåt när luftutloppet är exponerat för vind.
Det rekommenderas att du installerar utomhusenheten med luftinloppet mot väggen och INTE direkt exponerat för vinden.
VARNING
Utrustningen ska förvaras i ett rum utan antändningskällor i kontinuerlig drift (t.ex. öppna lågor, en gasvärmare i drift eller en elvärmare i drift).

5.2.1 Installationsplatskrav för utomhusenheten

INFORMATION
Se även följande krav:
▪ Allmänna krav på installationsplats. Se kapitlet
“Allmänna säkerhetsföreskrifter”.
▪ Krav på köldmedierör (längd, höjdskillnader). Se mer i
kapitlet “Förberedelser”.
Tänk på följande riktlinjer för utrymmet:
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_ RXA42+50B2 R32 Split-serien 4P513661-6B – 2018.05
a Luftutlopp b Luftintag
NOTERING
Vägghöjden på utomhusenhetens utloppssida MÅSTE vara ≤1200mm.
a Avskärmningsplåt b Rådande vindriktning c Luftutlopp
Installera INTE enheten på någon av följande platser:
▪ Ljudkänsliga områden (t.ex. i närheten av ett sovrum) så att
driftsljudet inte stör. Obs! Om ljudet mäts vid faktiska installationsförhållanden kan det uppmätta värdet vara högre än ljudtrycksnivån som anges i Sound spectrum i databoken på grund av omgivande buller och ljudreflektioner.
INFORMATION
Ljudtrycksnivån understiger 70dBA.
▪ Platser där mineraloljedimma, oljesprej eller ånga kan finnas i
luften. Plastdelar kan skadas och trilla av eller orsaka en vattenläcka.
Vi rekommenderar INTE att du installerar enheten på följande platser eftersom det kan förkorta enhetens livslängd:
▪ Där spänningsstyrkan fluktuerar mycket
▪ I fordon eller fartyg
▪ Där sura eller alkaliska ångor
Installation i närheten av havet. Kontrollera att utomhusenheten INTE utsätts för direkta havsvindar. Detta för att undvika korrosion orsakad av höga saltnivåer i luften, vilket kan förkorta enhetens livslängd.
Installatörens referenshandbok
9
Loading...
+ 19 hidden pages