Daikin RWEYQ144PCYD user guide manual

INSTALLATION MANUAL
System air conditioner
MODEL
RWEYQ72PCYD RWEYQ84PCYD RWEYQ144PCYD RWEYQ168PCYD RWEYQ216PCYD RWEYQ252PCYD
Read these instructions carefully before installation. Keep this manual in a handy place for future reference. This manual should be left with the equipment owner.
Lire soigneusement ces instructions avant I’installation. Concerver ce manuel à portée de main pour référence ultérieure. Ce manuel doit être donné au propriétaire de l’équipement.
RWEYQ72PCTJ RWEYQ84PCTJ RWEYQ144PCTJ RWEYQ168PCTJ RWEYQ216PCTJ RWEYQ252PCTJ
English
Français
Español
Lea cuidadosamente estas instrucciones antes de instalar. Guarde este manual en un lugar a mano para leer en caso de tener alguna duda. Este manual debe permanecer con el propietario del equipo.
1
2
figure 1
2
figure 3
1
13/16 (20)
1
(350)
13-3/4
[3]
30-11/16 (780)
2 (PCYD)
2 (PCTJ)
13/16 (20)
1
2
A
B
5
3
BB
4
A
A
A
A: 60 in. (1500 mm) B: 40 in. (1000 mm)
[4]
6
35-7/16
(900)
13-3/4
9-13/16
(250)
(350)
8
15-3/8
(390)
21-5/8
3-15/16 (100)
(550)
9
5
8
9
19-11/16
(500)
(300)
11-13/16
39-3/8 (1000)
75
13/16
(20)
7 7
5 5
9
8
6 6
13/16
(20)
10
8
Unit: in. (mm)
9
35-7/16 (900) 19-11/16 (500)
13/16
(20)
figure 2
3
1
4
2
(100)
3-15/16
2
15-3/4 (400)
29-5/16 (744)
3
(100)
3-15/16
12
13
7
14
6
8
2-3/8
(60)
5
11
9
10
[1]
15-3/4
(400)
15
Unit: in. (mm)
figure 6
2
4
Unit: in. (mm)
figure 4 figure 5 figure 7
[Heat recovery system][Heat pump system]
3
3
1
2
4
6
1
2
9
3 4
8
3
4
5
1
2
4
3
5
7
6
8
9
10
11
4
6
7
9
2
1
3
8
5
figure 8
figure 9
<RWEYQ-PCYD>
7
[Heat recovery system][Heat pump system]
7
A B C
1
3
<RWEYQ-PCTJ>
F1 F1F2 F2 Q1 Q2
TO IN/D UNIT
TO OUT/D UNIT TO MULTI UNIT
2
12
A1P
AB BC
F1 F2 F1 F2 F1 F2
A5P
ABC
C/H SELECTOR
4
5
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
6
7
[Heat recovery system][Heat pump system]
F1 F1F2 F2
IN/D OUT/D.BS
6
A1P
1F F F2 1Q
8
F1 F2
F1 F2
4
2
F1 F1F2 F2
IN/D OUT/D.BS
9
F1 F2
F1 F1F2 F2 Q1 Q2
TO IN/D UNIT
TO OUT/D UNIT TO MULTI UNIT
12
A5P
ABC
C/H SELECTOR
F1 F1F2 F2
IN/D OUT/D.BS
10
F1 F2
7
F1 F2
F1 F2
11
A B C
1
figure 10
A1P
BCF1F2 12QQ
A B C F1 F1F2 F2 Q1 Q2
C/H SELECTOR
TO IN/D UNIT
TO OUT/D UNIT TO MULTI UNIT
A1P
ABC1FF F21Q
2
3
4
F1 F2 F1 F2 F1 F2
5
6
4
F1 F1F2 F2
IN/D OUT/D.BS
8
F1 F2
ABCF1 F1F2 F2 Q1 Q2
C/H SELECTOR
TO IN/D UNIT
2
F1 F1F2 F2
IN/D OUT/D.BS
9
F1 F2
F1 F1F2 F2
IN/D OUT/D.BS
10
F1 F2
TO OUT/D UNIT TO MULTI UNIT
F1 F2
F1 F2
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
6
F1 F2
11
<RWEYQ-PCYD>
1
A1P
4
F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q1 Q2
8
23
56 6 6
A5P
A BC
9
7
<RWEYQ-PCYD>
1 4
X2M
12
A1P
2
X1M
F1 F2 F1 F2 Q1 Q2
5
A5P
X3M
ABC
43
3
3
<RWEYQ-PCTJ>
1
23
A1P
4
A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q1 Q2
7
56 6 6
9
8
1 23
4
LOW NOISE
TO OUT/D UNIT TO OUT/D UNIT TO OUT/D UNIT
F1 F2
F1
F2
F1 F2 F1 F2
6
5
7
<RWEYQ-PCTJ>
A1P
A B C F1 F2 F1 F2 Q1 Q2
1
12
X1M
X2M
2
X3M
43
3
figure 12figure 11
12
F1 F2 F1 F2
F1 F2
4
F1 F2
F1 F2
figure 13
1
figure 15
figure 14
11
10
2
12
13
14
A1P
TO IN/D
UNIT
F1 F2
ON
OFF
O U T
1
I
N
DS1
234
6
3
8
5
F1 F2 P1 P2
P1 P2
9
7
4
1
figure 16
<RWEYQ-PCYD>
A1P
ON
OFF
O U
T
1234
I
N
DS1
A5P
A B C
<RWEYQ-PCTJ>
O
ON
OFF
1
U T
1234
I
N
DS1
12
3
4
5
6
3
A1P
A B C
2
A B C
figure 17
<RWEYQ-PCTJ>
5
3
A B C
1
figure 18
<RWEYQ-PCYD>
2
1
4
6
7
8
9
5
3
10
11
1
4
6
2
7
8
9
10
11
figure 19
figure 20
1
figure 21
[Heat pump system]
2
3
[Heat recovery system]
1 2
3
4
78 9
10
[13]
4
14
5
11
5
15
16
6
12
17
4
1
2
A
3
B
5
[A-arrow view] [B-arrow view]
figure 22
(Fig. A) (Fig. B) (Fig. C)
C
figure 23
1
±15˚
2
[C-arrow view] [D-arrow view]
[Heat pump system]
1
2
[Heat recovery system]
R410A
1
5
D
3
3
4
11
10 10
12
9
7
3
4
15
5
6
16
18
14
figure 24
5
figure 25
13
1
9
10 10
12
R410A
7
3
2
4
8
15
17
5
4
3
2
[Heat pump system] [Heat recovery system]
1
2
5
3
6
4
1
figure 26 figure 27
6
18
1
2
1
2
4
3
4
3
RWEYQ72PCYD RWEYQ84PCYD RWEYQ144PCYD
RWEYQ168PCYD RWEYQ216PCYD RWEYQ252PCYD
RWEYQ72 PCTJ RWEYQ84 PCTJ RWEYQ14 4PCTJ
RWEYQ168PCTJ RWEYQ216PCTJ RWEYQ252PCTJ
VRV-WIV System
air conditioner
Installation
manual
CONTENTS
1. SAFETY CONSIDERATIONS ...................................................... 1
2. INTRODUCTION.......................................................................... 3
2-1 Combination......................................................................... 3
2-2 Standard operation limit ....................................................... 3
2-3 Standard supplied accessories ............................................ 3
2-4 Option accessories............................................................... 3
2-5 Technical specifications ....................................................... 4
2-6 Electrical specifications ........................................................ 4
3. SELECTION OF LOCATION........................................................ 5
4. INSPECTING AND HANDLING THE UNIT.................................. 6
5. UNPACKING AND PLACING THE UNIT ..................................... 6
6. WATER PIPING WORK............................................................... 6
7. HANDLING OF THE BRAZED PLATE-TYPE HEAT
EXCHANGER............................................................................... 7
7-1 When designing the equipment............................................ 7
7-2 Before starting a test run...................................................... 7
7-3 Daily service and maintenance ............................................ 7
7-4 Water quality ........................................................................ 7
7-5 Maintenance of plate-type heat exchanger .......................... 8
8. FIELD WIRING............................................................................. 8
8-1 Optional parts....................................................................... 8
8-2 Power supply circuit and wire requirements......................... 8
8-3 General ................................................................................ 9
8-4 Examples ............................................................................. 9
8-5 In case of a local setting..................................................... 11
9. REFRIGERANT PIPING ............................................................ 11
9-1 Selection of piping material ................................................ 11
9-2 Protection against contamination when installing pipes..... 12
9-3 Pipe connection.................................................................. 12
9-4 Connecting the refrigerant piping ....................................... 12
9-5 Example of connection....................................................... 14
9-6 Air tight test and vacuum drying......................................... 15
9-7 Pipe insulation.................................................................... 15
9-8 Checking of device and installation conditions................... 15
9-9 Additional refrigerant charge .............................................. 15
9-10 Stop valve operation procedure ......................................... 16
10. CHECKS AFTER INSTALLATION ............................................. 17
11. TEST RUN ................................................................................. 17
11-1 Air discharge ...................................................................... 17
11-2 Before turn on the power supply ........................................ 17
11-3 Check operation ................................................................. 17
11-4 Check of normal operation ................................................. 18
12. ONSITE SETTINGS ................................................................... 18
12-1 Energy saving and optimum operation............................... 18
13. CAUTION FOR REFRIGERANT LEAKS ................................... 21
1. SAFETY CONSIDERATIONS
Read these SAFETY CONSIDERATIONS for Installation carefully before installing air conditioning equipment. After completing the instal­lation, make sure that the unit operates properly during the startup oper­ation. Instruct the customer on how to operate and maintain the unit. Inform customers that they should store this Installation Manual with the Oper­ation Manual for future reference. Always use a licensed installer or contractor to install this product. Improper installation can result in water or refrigerant leakage, electrical shock, fire, or explosion. Meanings of DANGER, WARNING, CAUTION, and NOTE Symbols:
DANGER .....................Indicates an imminently hazardous situa-
tion which, if not avoided, will result in death or serious injury.
WARNING................... Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
CAUTION.................... Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTE.......................... Indicates situations that may result in
equipment or property-damage accidents only.
DANGER
• Refrigerant gas is heavier than air and replaces oxygen. A massive leak can lead to oxygen depletion, especially in base­ments, and an asphyxiation hazard could occur leading to se­rious injury or death.
• Do not ground units to water pipes, gas pipes, telephone wires, or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death. Addi­tionally, grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death.
• If refrigerant gas leaks during installation, ventilate the area immediately. Refrigerant gas may produce toxic gas if it comes in contact with fire. Exposure to this gas could cause severe injury or death.
• After completing the installation work, check that the refriger­ant gas does not leak throughout the system.
• Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death.
• Safely dispose all packing and transportation materials in ac­cordance with federal/state/local laws or ordinances. Packing materials such as nails and other metal or wood parts, includ­ing plastic packing materials used for transportation may cause injuries or death by suffocation.
WARNING
• Only qualified personnel must carry out the installation work. Installation must be done in accordance with this installation manual. Improper installation may result in water leakage, electric shock, or fire.
• When installing the unit in a small room, take measures to keep the refrigerant concentration from exceeding allowable safety limits. Excessive refrigerant leaks, in the event of an accident in a closed ambient space, can lead to oxygen deficiency.
• Use only specified accessories and parts for installation work. Failure to use specified parts may result in water leakage, electric shocks, fire, or the unit falling.
• Install the air conditioner on a foundation strong enough that it can withstand the weight of the unit. A foundation of insuffi­cient strength may result in the unit falling and causing injuries.
• Take into account strong winds, typhoons, or earthquakes when installing. Improper installation may result in the unit falling and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified personnel according to local, state and national regulations. An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
• Make sure that all wiring is secured, that specified wires are used, and that no external forces act on the terminal connec­tions or wires. Improper connections or installation may re­sult in fire.
• When wiring, position the wires so that the control box cover can be securely fastened. Improper positioning of the control box cover may result in electric shocks, fire, or the terminals overheating.
• Before touching electrical parts, turn off the unit.
• This equipment can be installed with a Ground-Fault Circuit Interrupter (GFCI). Although this is a recognized measure for additional protection, with the grounding system in North America, a dedicated GFCI may not be necessary.
• Securely fasten the outside unit terminal cover (panel). If the terminal cover/panel is not installed properly, dust or water may enter the outside unit causing fire or electric shock.
• When installing or relocating the system, keep the refrigerant circuit free from substances other than the specified refriger­ant (R410A) such as air. Any presence of air or other foreign substance in the refrigerant circuit can cause an abnormal pressure rise or rupture, resulting in injury.
• Do not change the setting of the protection devices. If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those spec­ified by Daikin are used, fire or explosion may occur.
• Indoor and outside units are for indoor installation only.
• Do not install the air conditioner in the following locations: (a) Where a mineral oil mist or oil spray or vapor is produced,
for example, in a kitchen. Plastic parts may deteriorate and fall off or result in water leakage.
(b) Where corrosive gas, such as sulfurous acid gas, is pro-
duced. Corroding copper pipes or soldered parts may result in refrigerant leakage.
(c) Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the control system and cause the unit to malfunction.
(d) Where flammable gas may leak, where there is carbon fiber,
or ignitable dust suspension in the air, or where volatile flammables such as thinner or gasoline are handled. Operat­ing the unit in such conditions can cause a fire.
• Take adequate measures to prevent the outside unit from be-
ing used as a shelter by small animals. Small animals making contact with electrical parts can cause malfunctions, smoke, or fire. Instruct the customer to keep the area around the unit clean.
CAUTION
• Do not touch the switch with wet fingers. Touching a switch with wet fingers can cause electric shock.
• Do not allow children to play on or around the unit to prevent injury.
• Do not touch the refrigerant pipes during and immediately af­ter operation as the refrigerant pipes may be hot or cold, de­pending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes. To avoid injury, give the pipes time to re­turn to normal temperature or, if you must touch them, be sure to wear proper gloves.
• Heat exchanger fins are sharp enough to cut. To avoid injury wear glove or cover the fins when working around them.
• Install drain piping to proper drainage. Improper drain piping may result in water leakage and property damage.
• Insulate piping to prevent condensation.
• Be careful when transporting the product.
• Do not turn off the power supply immediately after stopping operation. Always wait for at least 5 minutes before turning off the power supply. Otherwise, water leakage may occur.
• Do not use a charging cylinder. Using a charging cylinder may cause the refrigerant to deteriorate.
• Refrigerant R410A in the system must be kept clean, dry, and tight.
(a) Clean and Dry -- Foreign materials (including mineral oils
such as SUNISO oil or moisture) should be prevented from getting into the system.
(b) Tight -- R410A does not contain any chlorine, does not
destroy the ozone layer, and does not reduce the earth’s pro­tection again harmful ultraviolet radiation. R410A can con­tribute to the greenhouse effect if it is released. Therefore take proper measures to check for the tightness of the refrig­erant piping installation. Read the chapter Refrigerant Pip­ing and follow the procedures.
• Since R410A is a blend, the required additional refrigerant must be charged in its liquid state. If the refrigerant is charged in a state of gas, its composition can change and the system will not work properly.
• The indoor unit is for R410A. See the catalog for indoor mod­els that can be connected. Normal operation is not possible when connected to other units.
• Remote controller (wireless kit) transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types). Install the indoor unit far away from fluorescent lamps as much as possible.
NOTE
• Install the power supply and transmission wires for the indoor and outside units at least 3.5 feet (1 m) away from televisions or radios to prevent image interference or noise. Depending on the radio waves, a distance of 3.5 feet (1 m) may not be suf­ficient to eliminate the noise.
• Dismantling the unit, treatment of the refrigerant, oil and addi­tional parts must be done in accordance with the relevant lo­cal, state, and national regulations.
• Do not use the following tools that are used with conventional refrigerants: gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, or refrigerant recovery equipment.
• If the conventional refrigerant and refrigerator oil are mixed in R410A, the refrigerant may deteriorate.
• This air conditioner is an appliance that should not be acces­sible to the general public.
• The wall thickness of field-installed pipes should be selected in accordance with the relevant local, state, and national reg­ulations.
Codes and Regulations
This product is designed and manufactured to comply with national codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the installer. The manu­facturer assumes no responsibility for equipment installed in violation of any codes or regulations. Rated performance is achieved after charge adjustment (sub-cooling of 14±1°F (8±0.5°C) and superheat of 3±1°F (1.7±0.5°C)) and 72 hours of operation.
2. INTRODUCTION
This installation manual concerns VRV inverters of the Daikin RWEYQ-PC series. These units are designed for indoor installation and used for cooling and heat pump applications.
The RWEYQ-PC units can be combined with Daikin VRV series indoor units for air conditioning purposes. The present installation manual describes the procedures for unpack­ing, installing and connecting the RWEYQ-PC units. Installation of the indoor units is not described in this manual. Always refer to the installa­tion manual supplied with these units for their installation.
2-1 Combination
The indoor units can be installed in the following range.
Always use appropriate indoor units compatible with R410A.
To learn which models of indoor units are compatible with R410A, refer to the product catalogs.
• The Branch Selector units that combined with RWEYQ-PC units for changing the refrigerant flow to indoor units are T type (BSQ-TVJ, BS-Q54TVJ) only, or P type (BSVQ-PVJU, BSV-Q36PVJU) only. Do not combine the T type and P type in the system. Combination of T type and P type cause malfunction.
• Total capacity/quantity of indoor units Outside unit〉〈Total capacity index of indoor units〉〈Total quantity of indoor units RWEYQ72PCYD/CTJ RWEYQ84PCYD/CTJ RWEYQ144PCYD/CTJ RWEYQ168PCYD/CTJ RWEYQ216PCYD/CTJ RWEYQ252PCYD/CTJ
2-2 Standard operation limit
The figures below assume following operating conditions for indoor and outside units:
Equivalent pipe length ........................................25 ft. (7.6 m)
Level difference..................................................................... 0
Cooling Heating
120
110
100
90
80
70
60
50
6050 70 80 90 6050 70 80 90
In case of antifreeze usage Cooling Heating
120
110
100
90
80
70
60
50
40
30
20
6050 70 80 90 6050 70 80 90
A Entering water temperature (°F) B Indoor temperature (°FWB) C Indoor temperature (°FDB)
Range for continuous operation Range for operation Range for pull down operation Range for warming up operation
......... 36-93.5 12 units
......... 42-109 14 units
....... 72-187 24 units
....... 84-218 29 units
..... 108-280 36 units
..... 126-327.5 36 units
AA
120
110
100
90
80
70
60
50
CB
AA
110
100
90
80
70
60
50
40
30
20
10
CB
• Operation range of water flow rate is 13.2-39.6 gpm (50-150 L/min). (21.2-39.6 gpm (80-150 L/min) in case of antifreeze usage.)
The unit is designed for the following operation range;
Entering water temperature: 67-95°F (20-35°C) Water flow rate: 15.9gpm (60L/min) or more
• During cooling operation when the outside temperature is very low, it is possible that the thermostat switches off automatically in order to protect the unit from freezing.
• Hold ambient temperature at 35-104°FDB (2-40°CDB). Heat release from the unit (approx.): RWEYQ72: 2200 Btu/h (0.64kW), RWEYQ84: 2450 Btu/h (0.71kW) It is therefore recommended to always ventilate the room.
2-3 Standard supplied accessories
• Make sure that the following accessories are included. (Check by removing the front panel.)
Name
For discharge
gas
For suction
Quantity 1 pc. 1 pc. 1 pc. 7 pcs. 2 pcs.
(Note)
Shape
Name Conduit mounting plate
Quantity 2 pcs. 2 pcs.
Shape
gas (1)
Accessory pipes
For suction
gas (2)
[Others]
Installation manual
Operation manual
Clamp (A) Clamp (B)
White
Black
(Refer to figure 1)
1. • Operation manual
• Installation manual
•Clamp (A)
•Clamp (B)
• Conduit mounting plate
2. Accessory pipes
• For discharge gas
• For suction gas (1)
• For suction gas (2)
NOTE
The accessory pipe for discharge gas is used for the heat recovery sys­tem. (Not used for the heat pump system.)
2-4 Option accessories
To install the above outside units, the following optional parts are also required.
• Refrigerant branch kit (For R410A only: Always use an appropriate kit dedicated for your system.)
Heat pump system
REFNET header REFNET joint
Heat recovery system ..... For 3-tube piping
REFNET header REFNET joint
Heat recovery system ..... For 2-tube piping
REFNET header REFNET joint
• Outside unit multi connection piping kit (For R410A only: Always use an appropriate kit dedicated for your system.)
Number of outside units connected
Heat pump system BHFP22MA56U BHFP22MA84U
Heat recovery system BHFP26MA56U BHFP26MA84U
To select an optimum kit, refer to 9. REFRIGERANT PIPING
KHRP26M22H9 KHRP26M33H9 KHRP26M72H9 KHRP26A22T9 KHRP26A33T9
KHRP26M72TU9 KHRP26M73TU9
KHRP25M33H9 KHRP25M72H9
KHRP25A22T9 KHRP25A33T9
KHRP26M22H9 KHRP26M33H9 KHRP26A22T9 KHRP26A33T9
KHRP25M72TU9 KHRP25M73TU9
KHRP26M72H9 KHRP26M73HU9
KHRP26M72TU9 KHRP26M73TU9
2 units 3 units
KHRP26M73HU9
KHRP25M73HU9
2-5 Technical specifications
General
Nominal cooling capacity (2)
Nominal heating capacity (3) (MBH)
Nominal input cooling / heating (4)
Dimensions HxWxD
Weight (YDN/TJU)
Connections
refrigerant liquid pipe (in.) 3/8 3/8
refrigerant gas pipe (in.) 3/4 7/8
refrigerant discharge gas pipe (5)
Water piping connections
Inlet pipe (in.)
Outlet pipe (in.)
Drain pipe (in.)
General
Nominal cooling capacity (2)
Nominal heating capacity (3) (MBH)
Nominal input cooling / heating (4)
Dimensions HxWxD
Weight (YDN/TJU)
Connections
refrigerant liquid pipe (in.) 1/2 5/8
refrigerant gas pipe (in.) 1-1/8 1-1/8
refrigerant discharge gas pipe (5)
Water piping connections
Inlet pipe (in.)
Outlet pipe (in.)
Drain pipe (in.)
General
Nominal cooling capacity (2)
Nominal heating capacity (3)
Nominal input cooling / heating (4)
Dimensions HxWxD
Weight (YDN/TJU)
Connections
refrigerant liquid pipe (in.) 5/8 3/4
refrigerant gas pipe (in.) 1-1/8 1-1/4
refrigerant discharge gas pipe (5)
Water piping connections
Inlet pipe (in.)
Outlet pipe (in.)
Drain pipe (in.)
(1)
Refer to the engineering data book for the complete list of specifications.
(2)
The
normal cooling capacities are based on:
Indoor temperature:
–Entering
water temperature: –Equivalent pipe length: 25 ft. (7.6 m) –Level difference: 0
(3)
The
normal heating capacities are based on:
Indoor temperature:
Entering water temperature: –Equivalent pipe length: 25 ft. (7.6 m) –Level difference: 0
(4)
The nominal input includes total input of the unit: compressor and control circuit.
(5) In case of heat recovery system
(MBH)
(kW) 4.20 / 4.00 5.60 / 5.40
(in.
(mm))
(lbs.
(kg))
(in.) 5/8 3/4
(MBH)
(kW) 8.40 / 8.00 11.20 / 10.80
(in.
(mm))
(lbs.
(kg))
(in.) 7/8 7/8
(MBH)
(MBH)
(kW) 12.60 / 12.00 16.80 / 16.20
(in.
(mm))
(lbs.
(kg))
(in.) 1 1-1/8
80.6°FDB / 67°FWB (27°CDB / 19°CWB) 86°F (30°C)
68°FDB / 59°FWB (20°CDB / 15°CWB) 68°F (20°C)
(1)
RWEYQ72PCYD/CTJ RWEYQ84PCYD/CTJ
72 84
81 94.5
39-3/8×30-3/4×21-11/16
(1000×780×550)
343/330
(156/150)
1-1/4FPT
female Thread
1-1/4FPT
female Thread
1/2FPS
female Thread
RWEYQ144PCYD/CTJ RWEYQ168PCYD/CTJ
144 168
162 189
(39-3/8×30-3/4×21-11/16)×2
(1000×780×550)×2
343×2/330×2
(156×2/150×2)
(1-1/4FPT)×2
female Thread
(1-1/4FPT)×2
female Thread
(1/2FPS)×2
female Thread
RWEYQ216PCYD/CTJ RWEYQ252PCYD/CTJ
216 252
243 283.5
(39-3/8×30-3/4×21-11/16)×3
(1000×780×550)×3
343×3/330×3
(156×3/150×3)
(1-1/4FPT)×3
female Thread
(1-1/4FPT)×3
female Thread
(1/2FPS)×3
female Thread
343/330
(156/150)
1-1/4FPT
female Thread
1-1/4FPT
female Thread
1/2FPS
female Thread
343×2/330×2
(156×2/150×2)
(1-1/4FPT)×2
female Thread
(1-1/4FPT)×2
female Thread
(1/2FPS)×2
female Thread
343×3/330×3
(156×3/150×3)
(1-1/4FPT)×3
female Thread
(1-1/4FPT)×3
female Thread
(1/2FPS)×3
female Thread
Compressor
Oil type
Crankcase heater (W) 33 33
Refrigerant type R410A R410A
Refrigerant charge
Compressor
Oil type
Crankcase heater (W) (33)×2 (33)×2
Refrigerant type R410A R410A
Refrigerant charge
Compressor
Oil type
Crankcase heater (W) (33)×3 (33)×3
Refrigerant type R410A R410A
Refrigerant charge
RWEYQ72PCYD/CTJ RWEYQ84PCYD/CTJ
Synthetic (ether) oil Synthetic (ether) oil
(lbs.
(kg))
(lbs.
(kg))
(lbs.
(kg))
9.9 (4.5) 11.5 (5.2)
RWEYQ144PCYD/CTJ RWEYQ168PCYD/CTJ
Synthetic (ether) oil Synthetic (ether) oil
(9.9)×2 ((4.5)×2) (11.5)×2 ((5.2)×2)
RWEYQ216PCYD/CTJ RWEYQ252PCYD/CTJ
Synthetic (ether) oil Synthetic (ether) oil
(9.9)×3 ((4.5)×3) (11.5)×3 ((5.2)×3)
2-6 Electrical specifications
Model
Power supply
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 460 460
Voltage tolerance (%) ±10 ±10
Recommended fuses (A) 15 15
Compressor
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 460 460
Nominal running current (A) 5.3 7.0
Model
Power supply
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 460 460
Voltage tolerance (%) ±10 ±10
Recommended fuses (A) (15)×2 (15)×2
Compressor
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 460 460
Nominal running current (A) (5.3)×2 (7.0)×2
Model
Power supply
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 460 460
Voltage tolerance (%) ±10 ±10
Recommended fuses (A) (15)×3 (15)×3
Compressor
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 460 460
Nominal running current (A) (5.3)×3 (7.0)×3
RWEYQ72PCYD RWEYQ84PCYD
RWEYQ144PCYD RWEYQ168PCYD
RWEYQ216PCYD RWEYQ252PCYD
Model
Power supply
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 208/230 208/230
Voltage tolerance (%) ±10 ±10
Recommended fuses (A) 30 30
Compressor
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 208/230 208/230
Nominal running current (A) 11.6 15.4
Model
Power supply
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 208/230 208/230
Voltage tolerance (%) ±10 ±10
Recommended fuses (A) (30)×2 (30)×2
Compressor
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 208/230 208/230
Nominal running current (A) (11.6)×2 (15.4)×2
Model
Power supply
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 208/230 208/230
Voltage tolerance (%) ±10 ±10
Recommended fuses (A) (30)×3 (30)×3
Compressor
Phase 3~ 3~
Frequency (Hz) 60 60
Voltage (V) 208/230 208/230
Nominal running current (A) (11.6)×3 (15.4)×3
RWEYQ72PCTJ RWEYQ84PCTJ
RWEYQ144PCTJ RWEYQ168PCTJ
RWEYQ216PCTJ RWEYQ252PCTJ
3. SELECTION OF LOCATION
This unit does not have specifications for outdoor installation. The unit must be installed indoors (example: machine room, …).
Paying attention to the conditions mentioned below, select the place for installation with a prior approval of customer.
1.
The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation.
2.
Consider the space required for refrigerant piping work when install­ing. Refer to [Necessary Space].
3.
There is no danger of fire due to leakage of inflammable gas.
4.
The piping length between the outside unit and the indoor unit may not exceed the allowable piping length. 9. REFRIGERANT PIPING.
5.
Locations where the noise of the unit operating will not disturb nearby houses, etc.
6.
Locations with airflow and ventilation holes capable of dissipating heat from the machine and where the ambient temperature around the outside unit is between 35 and 104°F (0 and 40°C) and the humidity does not exceed 80%.
[Necessary Space]
When installing, secure the space mentioned below without fail.
(Refer to figure 2)
1. In case of a single installation
2. In case of series installations
3. Top view
4. Side view
5. Outside unit
6. Service Space (front side)
7. Service Space (back side)
8. Space for installing water piping
Secure an enough space for removing the front panel.
9. Ventilation Space
above the area ( ) of the outside unit.
10. Secure spaces in the front, back and top sides as same as the case of single installation.
DANGER
Do not install unit in an area where flammable materials are
present due to risk of explosion resulting in serious injury or death.
Refrigerant is heavier than air and replaces oxygen. A massive leak could lead to oxygen depletion, especially in basements, and an as­phyxiation hazard could occur leading to serious injury or death. Re­fer to the chapter “Caution for refrigerant leaks”.
NOTE
1.
An inverter air conditioner may cause electronic noise generated from AM broadcasting. Examine where to install the main air con­ditioner and electric wires, keeping proper distances away from stereo equipment, personal computers, etc.
(Refer to figure 3)
1. Indoor unit
2. Branch switch, overcurrent breaker
3. Remote controller
4. Cool/Heat selector
5. Personal computer or radio
If the electric wave of AM broadcasting is particularly weak, keep dis­tances of 10 ft. (3 m) or more and use conduit tubes for power supply and transmission wiring.
2.
Water quality Water containing high level of foreign materials may cause the corrosion of heat exchanger and piping or scale accumulation. Use water satisfying “7-4 Water quality”.
3.
Cooling tower Use a closed type cooling tower without fail. (Open type tower cannot be used.)
4.
Strainer Install a strainer (50 mesh or more) without fail at the inlet of water piping. (If sands, wastes, rust particles, etc. are mixed in the water circulation system, damage to the plate-type heat exchanger may be caused by the corrosion of metal materials and clogging of the heat exchanger.)
WARNING
Do not install in the following locations.
Locations such as kitchens which contain a lot of mineral oil or steam in the atmosphere or where oil may splatter on the unit. Resin parts may deteriorate, causing the unit to fall or leak.
• Locations where sulfurous acids and other corrosive gases may be present in the atmosphere. Copper piping and soldered joints may corrode, causing refrigerant to leak.
• Locations where equipment that produces electromagnetic waves is found. The electromagnetic waves may cause the control system to mal­function, preventing normal operation.
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should be reported immediately to the carrier claims agent.
When handling the unit, take into account the following:
1.
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
2.
Choose the path along which the unit is to be brought in ahead of time.
3.
In order to prevent any damage to the unit during installation, use slings (cloth) or patch plates and lift the unit referring to figure 4.
4.
Lift the unit preferably with a crane and 2 belts of at least 27 ft. (8 m) long.
5.
When lifting the unit with a crane, always use protectors to prevent belt damage and pay attention to the position of the unit’s center of gravity.
6.
Be sure use the standard supplied accessories and dedicated parts as installation parts.
(Refer to figure 4)
1. Patch plates or clothes
2. Belt sling
NOTE
Use belt sling of 13/16 in. (20 mm) width or less which adequately
bears the weight of the product.
5. UNPACKING AND PLACING THE UNIT
• Make sure the area around the machine drains properly by setting up drainage grooves around the foundation.
• Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.
• Secure the unit to its base using foundation bolts. (Use four commer­cially available 7/16 in. (M12) foundation bolts, nuts, and washers.)
• The foundation bolt should protrude 13/16 in. (20 mm) from the foundation surface.
• Fix 4 foundation bolts.
• Support the unit with the foundation which is larger than the hatched area shown in figure 5.
(Refer to figure 5)
1. Front side
2. Position of foundation bolts
3. Hole for a foundation bolt
(φ11/16 in. (17 mm) holes at 4 corners)
4. Avoid such a foundation where the unit is supported by 4 corner points.
NOTE
In unavoidable circumstances, where the unit has to be installed
either touching or close to a wall; place the unit such that transmis­sion of vibration can be restricted or minimized. Vibrations can be dampened by using cushions, foam etc.
13/16 in.
(20 mm)
NOTE
Prepare a water drainage channel around the foundation to con-
densate waste water from around the unit.
If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities first.
Make sure the area around the machine drains properly by setting up drainage grooves around the foundation. (Condensate water is sometimes discharged from the outside unit when it is running.)
Use a nut with a resin clip plate to protect the nut tightening part from rusting.
Resin clip plate
6. WATER PIPING WORK
• The water pressure resistance of water piping of this outside unit is 285 psig.
• The connection port for water piping is located in the front. The con­nection ports for drain piping are located in the front and back. When using the back port, change the cast iron plug from the back to the front and securely close it.
• In indoor use, piping work should be such that now water drops on the outer plate.
• The lateral protruding section of the drain piping should be short (within 15-3/4 in. (400 mm)) and installed in a downward direction. The diameter of drain pipe should be the same as the diameter of unit connection (1/2 in.) or more.
• The diameter of water pipe should be the same as the diameter of unit connection (1-1/4 in.) or more.
• Install an air purge valve in the midway of the water piping to prevent cavitation.
• After completing the drain piping work, make sure that the water runs smoothly without any clogging by dust.
• Do not connect the drain outlet to the water outlet.
• Install a strainer (50 mesh or more) in the inlet of water piping within a distance of 4.9 ft. (1.5 m) from the outside unit. (If sand, waste or rust particles are mixed in the water circulation system, metal materials will become corrosive.)
• Install insulation on the inlet/outlet of water piping to prevent conden­sation and freezing. At installing insulation on water in/outlet pipe, use Polyurethane form thickness 3/16 in. (5 mm) for insulation of water piping socket on heat exchanger.
• Install insulation up to the base of heat exchanger as shown in the figure 6.
• Install a gate valve for chemical cleaning in an easy position to han­dle.
• Use water pipes compliant with the local and national codes.
• Run the water pump to flush inside of water piping. Then, clean the strainer.
• If there is a possibility of freezing, take measures to prevent freezing.
• Tighten securely the connection of water piping and socket with tightening torque of 220 ft.·lbf. (300 N·m) or less. (If a large torque is applied, the unit may be damaged.)
(Refer to figure 6)
1. Air purge
2. Outlet of water
3. Inlet of water
4. Gate valve
5. Water piping socket
6. Water piping
7. Insulation
8. Heat exchanger
9. Strainer
10. Drain valve
11. Connection port to draining piping
12. Insulation cover
13. 3-1/8 in. (80 mm) or less
14. Insulation of water piping socket
15. Drain piping
7. HANDLING OF THE BRAZED PLATE­TYPE HEAT EXCHANGER
CAUTION
A brazed plate-type heat exchanger is used for this unit. Because its structure is different from a conventional type heat exchanger, it must be handled in a different manner.
7-1 When designing the equipment
1.
Install a strainer (50 mesh or more) at the water inlet side adjacent to the outside unit in order to prevent any foreign materials such as dust, sand, etc. from entering.
2.
Depending on the water quality, scale may stick to the plate-type heat exchanger. In order to remove scale, it is necessary to use chemicals to clean it at regular intervals. To this end, install a gate valve in the water piping. Set up a piping connection port on the pip­ing between this gate valve and the outside unit for cleaning by chemicals.
3.
For the purpose of cleaning and water drain-off from the outside unit (water draining during a long period of non-use in winter, draining upon starting of season-off), install an “air discharge valve” and a “water draining plug” at the inlet/outlet ports of water piping. In addi­tion, install an “automatic air discharging valve” at the top of riser pip­ing or at the top of a portion where air tends to stay.
4.
Independent of the piping inlet of the outside unit, install a cleanable strainer at a portion close to the pump piping inlet.
5.
Carry out complete cooling/thermal insulation of water piping and outdoor dehumidification. If complete cooling or thermal insulation has not been carried out, any damage may be caused during severe winter due to freezing, in addition to thermal loss.
6.
When you stop operation during night or winter, it is necessary to take measures to prevent water-related circuits from natural freezing in the area the ambient temperature drops below 32°F (0°C) (by water drain off, keeping the circulation pump running, warming up by a heater, etc.) Freezing of water related circuits may result in any damage to the plate-type heat exchanger. Therefore, take appropriate measures depending on the circumstances of use.
(Refer to figure 7)
1. Example of piping
2. Water inlet piping
3. Strainer
4. Air discharge valve (for joint use with cleaning port)
5. Cleaning device
6. Strainer for pump
7. Automatic air discharge valve
8. Water outlet piping
9. Joint use with water draining plug
10. Plate-type heat exchanger
11. Outside unit
7-2 Before starting a test run
1.
Before starting a test run, please make sure that the piping work has been carried out in a proper manner. Especially, make sure that the strainer, air discharge valve, automatic water supply valve, expansion tank and cistern are positioned at their places correctly.
2.
After water has been completely filled in, first run the pump only, and then make sure that no air has been caught in the water circulation system and that the water flow rate is correct. If any air has been caught or the flow rate is not enough, the plate-type heat exchanger may freeze. Measure any water pressure loss before and after the outside unit and make sure that the flow rate is as designed. In case of any abnormality, stop the test run immediately and carry out trou­ble shooting to resolve the trouble.
3.
Following the installation manual, carry out a test run of the outside unit.
4.
After the test run has been completed, inspect the strainer at the inlet piping of the outside unit. Clean it if it is dirty.
7-3 Daily service and maintenance
1.
Management of water quality The plate-type heat exchanger has a structure that does not permit dismantling and cleaning, or replacing any parts. Please pay attention carefully to the quality of water to be used for the plate-type heat exchanger in order to prevent corrosion and sticking of scale. The water to be used for the plate-type heat exchanger should have at least the quality as specified in the table below. When using any corrosion prevention agent, scale depressant agent, etc., such agent should have no corrosive features against stainless steel and copper.
2.
Management of condenser water flow rate If the condenser water flow rate is not enough, it will result in freezing damage to the plate-type heat exchanger. Check for any clogging of the strainer, any air being caught, any reduction in the flow rate due to failure of the circulation pump by measuring the temperature and pressure differences at the inlet and outlet ports of the plate-type heat exchanger. If the aged difference in the temperature or pressure has increased beyond the proper range, the flow rate should have decreased. Stop the operation and remove the cause before restart­ing the operation.
3.
Steps to be taken if a freeze-protection device is activated If the freeze-protection device is activated during operation, be sure to remove the cause before restarting the operation. If the freeze-pro­tection device has been once activated, a partial freezing has already occurred. If you restart the operation without removing the cause, the plate-type heat exchanger will be closed and the ice cannot be melted, and in addition, the freezing process will be repeated, result­ing in any damage to the plate-type heat exchanger, and this can lead to refrigerant leaking or water entering the refrigerant circuit.
7-4 Water quality
Water quality standards for condenser water, hot water and makeup water (4) (6)
Item (5)
pH (77°F (25°C))
Electrical Conductivity (mS/ft. (mS/m)) (77°F (25°C))
Chloride ions
/L)
(mgcl
Sulfate ions
2-
/L)
(mgSO
4
Acid consumption (pH4.8) (mgCaCO
Total hardness (mgCaCO
Calcium hardness (mgCaCO
Ionic-state silica (mgSiO
Iron (mgFe/L)
Copper (mgCu/L)
Sulfate ion (mgS
Ammonium ion (mgNH
Residual chlorine (mgCl/L)
Free carbon dioxide (mgCO
Stability index
3
/L)
3
/L)
3
/L)
2
/L)
2-
/L)
+
4
/L)
2
/L)
Cooling water system (3)
Circulation system
Circulation
6.5 to 8.2 6.0 to 8.0 7.0 to 8.0 7.0 to 8.0
Less than
24.4 (80)
Less than
Less than
Less than
Less than
Less than
Less than 50Less than 30Less than 30Less than
Less than
Less than
Shall not be
detected
Less than
Less than
Less than
6.0 to 7.0
Makeup
water
Less than
9.1 (30)
Less than 50Less than 50Less than
200
Less than 50Less than 50Less than
200
Less than 50Less than 50Less than
100
Less than 70Less than 70Less than
200
Less than 50Less than 50Less than
150
Less than
1.0
Less than
0.3
Shall not be
Less than
1.0
Less than
0.3
Less than
4.0
Hot water system (2) Tendency (1)
Circulation
water
1.0
1.0
0.3
0.25
0.4
Makeup
water
Less than
9.1 (30)
50
50
50
70
50
30
Less than
0.3
Less than
0.1
Shall not be
detected
Less than
0.1
Less than
0.3
Less than
4.0
water
Standard items
Reference items
0.3
0.1
detected
0.1
0.3
4.0
(68 to 140°F (20 to 60°C))
Less than
9.1 (30)
Less than
Less than
Shall not be
detected
Less than
Less than
Less than
Corrosion Scale
{{
{{
{
{
{{
{
{
{
{
{
{{
{
{
{
{
[NOTES] (1) The circle marks in the columns for corrosion or scale to develop. (2) Corrosion has a tendency to occur when water temperature is high
(104°F (40°C) or more), and if metals with no protective coating whatever are directly exposed to water, it would be a good idea to take effective measures against corrosion such as adding a corro­sion inhibitor or deterioration treatment.
(3) In a condenser water circuit that uses a closed cooling tower, the
closed circuit circulating water and makeup water must satisfy its water quality standards for the hot water system, and passing water and makeup water must satisfy those for the circulation type cooling water system.
(4) The supply water must be clean tap water, industrial water or clean
underground water. Do not use purified or softened water.
(5) The fifteen items in the table above represent typical causes of cor-
rosion and scale.
(6) Once-through water may cause corrosion.
Do not use once-through water.
7-5 Maintenance of plate-type heat exchanger
The performance of a plate-type heat exchanger may decline due to scale accumulation. It may be damaged by freezing due to the drop of flow rate. For this reason, it is necessary to carry out programmed main­tenances at a regular interval in order to prevent the scale from being generated.
1.
Before entering the season for use, carry out the following inspections:
1) Conduct a water quality test and make sure that it is within the standard.
2) Clean the strainer.
3) Make sure that the flow rate is correct.
4) Make sure that the operational conditions (pressure, flow rate, outlet temperature, etc.) are normal.
2.
Because the plate-type heat exchanger has a structure which does not permit disassembling and cleaning, follow the following proce­dures for cleaning:
1) For maintenance purposes it is required to provide for a connec­tion port on the water inlet and on the water outlet. You must con­nect a circulation pump in between these 2 connection por ts when cleaning the plate-type heat exchanger with chemicals. For cleaning the scale in the plate-type heat exchanger it is rec­ommended to use a solution with 5% diluted formic, citric, oxalic, acetic or phosphoric acid. Never use hydrochloric, sulfuric or nitric acid because such solu­tions have a strong corrosive feature.
2) Make sure to provide for a stop valve in front of that inlet water pipe connection port and for a stop valve after the outlet water pipe connection port.
3) Connect the piping for circulation of cleaning chemicals to the inlet and outlet piping of plate-type heat exchanger. Fill the clean­ing solution of 122-144°F (50-62°C) for a while in the plate-type heat exchanger. Then, circulate the cleaning solution by a pump for 2-5 hours. The time for cleaning depends on the temperature of cleaning solution or the degree of scale accumulation. Therefore, please watch the change of the dirtiness (color) of cleaning solution to determine the level of removal of scale.
4) After circulating the cleaning solution, discharge the solution from the plate-type heat exchanger, fill the heat exchanger with a solu­tion of 1-2% sodium hydroxide (NaOH) or sodium bicarbonate (NaHCO
ization purpose.
5) After the process of neutralization has been completed, rinse the inner part of the plate-type heat exchanger with care using fresh and clean water.
6) When using any cleaning agent sold in the market, check in advance that such agent has no corrosive features against stain­less steel and copper.
7) For details of cleaning method, ask the manufacturer of related cleaning agent.
3.
After cleaning has been completed, make sure that the unit can be operated in a normal fashion.
). Circulate this solution for 15-20 minutes for neutral-
3
8. FIELD WIRING
NOTE
• All field wiring and components must be installed by a licensed elec­trician and must comply with relevant local and national regulations.
• The field wiring must be carried out in accordance with the wiring diagrams and the instructions given below.
• Be sure to use a dedicated power supply circuit. Never use a power supply shared by another appliance.
• Do not operate until refrigerant piping work is completed. (If operated before complete the piping work, the compressor may be broken down.)
• Never remove thermistor, sensor or etc. when connecting power supply and transmission wiring. (If operated with thermistor, sensor or etc. removed, the compressor may be broken down.)
• This equipment can be installed with a Ground-Fault Circuit Inter­rupter (GFCI). Although this is a recognized measure for additional protection, with the grounding system in North America, a dedicated GFCI may not be necessary.
• This product have reversed phase protection detector only works when the product started up.
• Replace two of the three phases (L1, L2, and L3) during reverse­phase protection circuit operation. Reversed phase detection is not performed while the product is operating.
• Do not run the unit by short cutting the protection device (S1PH). If there exists the possibility of reversed phase, lose phase, momen­tary blackout or the power supply goes on and off while the product is operating, attach a reversed phase protection circuit locally. Run­ning the product in reversed phase may break the compressor and other parts.
• Attach the power supply wiring securely.
8-1 Optional parts
Cool/Heat selector
S1S .............................. Selector switch (fan, cool/heat)
S2S .............................. Selector switch (cool/heat)
NOTE
Use copper conductors only.
When using the adaptor for sequential start, refer to chapter “Exam-
ples”.
For transmission wiring to outside-outside transmission F1-F2, outside-indoor transmission F1-F2, refer to chapter “Examples”.
For transmission wiring to the central remote controller, refer to the installation manual of the central remote controller.
Use insulated wire for the power supply.
8-2 Power supply circuit and wire requirements
A power supply circuit (see table below) must be provided for connec­tion of the unit. This circuit must be protected with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and/or a cir­cuit breaker.
Phase and frequency
RWEYQ72/84PCYDφ3, 60 Hz 460 V 10.2 A 15 A AWG18-16
RWEYQ144/168PCYDφ3, 60 Hz 460 V 10.2+10.2 A 15+15 A AWG18-16
RWEYQ216/252PCYDφ3, 60 Hz 460 V 10.2+10.2+10.2 A 15+15+15 A AWG18-16
RWEYQ72/84PCTJφ3, 60 Hz 208/230 V 22.4 A 30 A AWG18-16
RWEYQ144/168PCTJφ3, 60 Hz 208/230 V 22.4+22.4 A 30+30 A AWG18-16
RWEYQ216/252PCTJφ3, 60 Hz 208/230 V 22.4+22.4+22.4 A 30+30+30 A AWG18-16
Vol ta ge
Minimum
circuit amp.
Recommended
fuses
NOTE
Select the power supply wire in accordance with relevant local and
national regulations.
Wire size must comply with the applicable local and national code.
Specifications for local power supply and branch wiring are in com-
pliance with local cord.
Transmission
wiring
selection
8-3 General
• Make sure to connect the power supply wire to the power supply ter­minal block and to clamp it as shown in figure 8, chapter “Field wiring connection”.
• As this unit is equipped with an inverter, installing a phase advancing capacitor will not only reduce the power factor improvement effect, but also may cause the capacitor to overheat due to high-frequency waves. Therefore, never install a phase advancing capacitor.
• Keep power supply imbalance within 2% of the supply rating.
1.
Large imbalance will shorten the life of the smoothing capacitor.
2.
As a protective measure, the product will stop operating and an error indication will be made, when power supply imbalance exceeds 4% of the supply rating.
• Follow the “wiring diagram” when carrying out any electrical wiring.
• Only proceed with wiring work after blocking off all power supply.
• Always ground wires. (In accordance with national regulations of the pertinent country.)
This unit uses an inverter, and therefore generates noise, which will have to be reduced to avoid interfering with other devices. The outer casing of the product may take on an electrical charge due to leaked electrical current, which will have to be discharged with the ground­ing.
This unit has a negative phase protection circuit. (If it operates, only operate the unit after correcting the wiring.)
WARNING
• Do not ground units to gas pipes, sewage pipes, lightning rods, or
telephone ground wires because incomplete grounding could cause a severe shock hazard resulting in severe injury or death.
Gas pipes: can explode or catch fire if there is a gas leak. Sewage pipes: no grounding effect is possible if hard plastic pip-
ing is used. Telephone ground wires and lightning rods: dangerous when struck by lightning due to an abnormal rise in electrical potential in the grounding.
8-4 Examples
System example (Refer to figure 8)
Picking power supply and transmission wiring
1. Field power supply
2. Main switch
3. Disconnect switch
4. Fuse
5. Remote controller
6. Outside unit
7. Branch Selector unit
8. Indoor unit
9. Cool/Heat selector
power supply wiring (sheathed wire) transmission wiring (sheathed wire)
CAUTION
• Use a conduit for the power supply wiring. Outside the unit, make sure the low-voltage electric wiring (i.e. for the
• remote controller, transmission, etc.) and the high-voltage electric wir­ing do not pass near each other, keeping them at least 5 in. apart. Prox­imity may cause electrical interference, malfunctions, and breakage.
• Be sure to connect the power supply wiring to the power supply ter­minal block and secure it as described in Field wiring connection.
• Transmission wiring should be secured as described in Field wiring
connection.
• Secure the wiring with the accessory clamps so that it does not touch the piping.
• Make sure the wiring and the control box cover do not stick up above the structure, and close the cover firmly.
WARNING
Never connect power supply wiring to the terminal block for remote
controller wiring as this could damage the entire system.
(Refer to figure 9)
1. Power supply wiring and wiring for pump operation
(High voltage)
2. Transmission wiring (Low voltage)
3. Set apart
Connect the wire to the terminal block on printed circuit board with care since too much pressure may cause breakage of the printed circuit board. Field wiring connection: transmission wiring, interlock circuit, pump operation output and Cool/Heat selector. Power supply and transmission wiring: Connect it using conduit mounting plates.
Top plate
Conduit mounting plate (accessory)
Conduit (field supply)
Top plate
Lock nut (field supply)
[In case of single outside unit]
(Refer to figure 10)
1. Cool/Heat selector
2. Printed circuit board (A1P)
3. Take care of the polarity
4. Use the conductor of sheathed wire (2 wire) (no polarity)
5. Terminal board (field supply)
6. Indoor unit
7. Never connect the power supply wire.
8. Branch Selector unit A
9. Branch Selector unit B
10. Last Branch Selector unit
11. Cooling only unit
12. ABC I/P printed circuit board (A5P)
[In case of multiple outside units]
(Refer to figure 11)
1. Unit A (Master unit)
2. Unit B
3. Unit C
4. TO IN/D UNIT
5. TO OUT/D UNIT
6. TO MULTI UNIT
7. To Cool/Heat selector (only Heat pump system)
8. To indoor unit
9. To other systems
• The transmission wiring between the outside units in the same pipe line must be connected to the Q1/Q2 (TO MULTI UNIT) terminals. Connecting the wires to the F1/F2 (TO OUT/D UNIT) terminals results in system malfunction.
• The wiring for the other pipe line must be connected to the F1/F2 (TO OUT/D UNIT) terminals of the printed circuit board in the outside unit to which the transmission wiring for the indoor units is connected.
• The outside unit to which the transmission wiring for the indoor units is connected is master unit.
• The transmission wiring between the outside units must be 98 ft. (30 m) in length at maximum.
NOTE
• Be sure to keep the power supply and transmission wiring apart from each other. Be careful about polarity of the transmission wiring. Make sure that the transmission wiring is clamped as shown in the figure in chapter “Field wiring connection”. Check that wiring does not make contact with refrigerant piping. Firmly close the cover and arrange the electric wires so as to prevent the cover or other parts from coming loose.
[Setting the interlock circuit and pump operation output.]
Pump operation output [high voltage]
• Use insulated wires of the size as mentioned below having rated volt­age of 250 V or more: For single core: AWG16 or larger (conduit pipe work) For multiple cores: AWG18 or larger
*The wiring for pump operation output is to be procured locally.
(Refer to figure 12)
1. Pump operation output terminal (X2M).
When water pump is linked with system operation, water pump operation circuit shall be set between terminals (1) and (2). Contact specification --- 220 VAC, 3 mA-0.5 A
2. Printed circuit board (A1P)
3. Mount an insulation sleeve.
4. Connection of interlock circuit
Do not forget to connect an interlock circuit (an auxiliary a­contact of electromagnetic switch for the water pump) to each outside unit. (Select without fail an auxiliary a-contact able to switch min­imum load of DC15 V, 1 mA.)
When connecting for each outside unit Connect to the terminal block (X3M) as shown in the bottom right of the sketch.
When connecting multiple outside units as 1 single unit (centralized interlock) For this unit, it is possible to make a centralized interlock of multiple outside units using an adapter (sold separately as an accessory) for external control of outside units. For details of wiring connection, refer to How to central-
ized interlock wiring.
5. ABC I/P printed circuit board (A5P)
How to the centralized interlock wiring
• When centralized interlock is done, see 8-5 In case of a local set­ting -(3).
• No wiring to terminal block X3M is necessary when centralized inter­lock is employed.
• For multiple outside units, external/external transmission wiring shall be done for master unit only.
(Refer to figure 13)
1. Outside unit A
2. Outside unit B
3. Outside unit C
4. Adapter for external control
5. Interlock circuit of water pump
6. Out-Out transmission wiring
7. Use the conductor of sheathed wire (2 wire) (no polarity)
[Setting the cool/heat operation type]
1. Performing cool/heat setting with the remote controller con-
nected to the indoor unit. Keep the Cool/Heat selector switch (DS1) on the printed circuit board (A1P) at the factory setting position OFF.
(Refer to figure 16)
1. Remote controller
2. Performing cool/heat setting with the Cool/Heat selector.
Connect the Cool/Heat selector (optional) to the A/B/C termi­nals and set the Cool/Heat selector switch (DS1) on the printed circuit board (A1P) to ON.
(Refer to figure 17)
1. Cool/Heat selector
2. ABC I/P printed circuit board (A5P)
• The wiring from the indoor units must be connected to the F1/F2 (In­Out) terminals on the printed circuit board in the outside unit.
• For the above wiring, always use sheathed vinyl wire with AWG18-16 (2 core wire). (3 core wire is allowable for the Cool/Heat selector only.)
NOTE
• All transmission wire is field supply.
• Be sure to follow the limits below. If the transmission wiring is beyond these limits, it may result in malfunction of transmission. Maximum wiring length: 3280 ft. (1000 m) Total wiring length: 6560 ft. (2000 m) Max. branches No. of branches: 16 Wire length between outside units: 98 ft. (30 m)
Up to 16 branches are possible for transmission wiring. No branch­ing is allowed after branching.
Never connect the power supply to transmission wiring terminal block. Otherwise the entire system may break down.
(Refer to figure 14)
1. Branch
2. Subbranching
For low-noise operation, it is necessary to get the optional “Exter­nal control adaptor for outside unit”. For details, see the installation manual attached to the adaptor.
Field wiring connection:
L1, L2, L3, phase of the power supply wiring should be clamped to the safety catch using the included clamp material. The green and yellow striped wrapped wires should be used for ground­ing. Make sure to connect the power supply wire to the power supply termi­nal block and fix it using attached clamp as shown in figure 15 and 19.
(Refer to figure 15)
1. Power supply
2. Branch switch, overcurrent breaker
3. Grounding wire
4. Attach insulation sleeves.
5. Power supply terminal block
6. Grounding terminal
7. Retain the ground wires along with the power supply wires
using the accessory clamp (A).
8. Grounding wire
9. When wiring, do not allow the ground wires to contact the
compressor lead wires. If the wires contact each other, adverse effects may occur to other units.
10. When connecting two wires to one terminal, ensure that the crimp-style terminals face with each other back to back. Moreover, make sure that the wire of the smaller gauge is located above.
11. Terminal block
12. Crimp-style terminal
13. Wire gauge: Small
14. Wire gauge: Large
(Refer to figure 19)
1. Intake for power supply wiring, pump operation output (high
voltage) and ground wiring.
2. Stop valve for discharge gas (high temperature part)
3. Insert the accessory clamp (B) in the hole of the fixing plate
for stop valves.
4. Power supply wiring, pump operation output (high voltage) and ground wiring.
5. Retain the power supply wiring, pump operation output (high voltage) and ground wiring with the accessory clamp (B) to prevent them from touching with the stop valve for dis­charge gas.
6. Insert the accessory clamp (B) in the hole of the bottom of control box.
7. Intake for transmission wiring. (low voltage)
8. Make sure to provide for a downward loop in the transmis-
sion wiring right in front of the location where the wiring is to be fixed over the top plate of the control box. This in order to prevent that condensate drips off the wiring into the control box.
9. Fix the transmission wiring to resin clamps with the acces­sory clamps (A).
10. Pass the transmission wiring (low voltage) through the wire clip.
11. Retain the power supply wiring, pump operation output (high voltage) and ground wiring to the bottom of control box with the accessory clamp (B).
WARNING
• Use only specified wire and connect wires to terminals tightly. Be careful that wires do not place external stress on terminals. Keep wires in neat order so as not to obstruct other equipment. Incom­plete connections could result in overheating, and in worse cases, electric shock or fire.
CAUTION
Precautions when laying power supply wiring
Use round pressure terminals for connections to the power supply terminal block.
terminal
When none is available, follow the instructions below.
Do not connect wiring of different thicknesses to the power supply terminal block. (Slack in the power supply wiring may cause abnormal heat.)
When connecting wiring which is the same thickness, do as shown in the figure below.
Connect same­thickness wiring to both sides.
For wiring, use the designated power supply wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will strip the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
See the table below for tightening torque for the terminal screws.
M5 (Power supply terminal block) M5 (Ground)
M3 (Transmission wiring terminal block)
Precautions when connecting the ground
When pulling the ground wire out, wire it so that it comes through the cut out section of the cup washer. (An improper ground connection may prevent a good ground from being achieved.)
Round pressure terminal
It is forbidden to connect two to one side.
Power supply wireRound pressure
Cup washer
It is forbidden to connect wiring of different thicknesses.
Tightening torque
(ft.·lbf. (N·m))
2.21-3.02 (3.0-4.1)
0.59-0.72
(0.80-0.96)
Cut out section
8-5 In case of a local setting
If necessary, do the local settings as mentioned in the table below. For setting, refer to the plate “Cares to be taken in servicing” attached to the cover of control box.
Typical local settings For other settings than mentioned in the table below, refer to the
equipment design materials and service manual.
(1) Setting of switching between
cooling and heating
(2) Setting to prohibit sequenced
start
(3) Setting of centralized interlock
Setting of external demand
(4) Setting of abnormal display
when interlock contact is OFF
CAUTION
A separate adapter (sold separately as an accessory) for external control of an outside unit is necessary when doing a demand oper­ation from an external instruction, setting of cooling and heating through a centralized remote controller for cooling and heating (sold separately as an accessory) and setting of centralized inter­lock. For details, refer to the manual attached to the adapter.
This setting is done when switching between cooling and heating is performed by a switching remote controller (sold separately as an accessory) installed on the outside unit.
This setting is done when the outside units are not started in a sequenced order.
These settings are done when the interlocks are connected in a lump-sum manner or when performing a demand opera­tion by external instruction.
This setting is done when making an abnormal display (HJ) on a remote controller when the interlock contact is OFF (when the heat source water pump is not operated).
9. REFRIGERANT PIPING
CAUTION
After completing installation, be sure to open the valves. (See 9-9 Additional refrigerant charge for details) (Operating the unit with the valves shut will break the compressor.) Use R410A to add refrigerant. (The R410A refrigerant cylinder has a pink stripe painted around it.) All field piping must be installed by a licensed refrigeration techni­cian and must comply with relevant local and national regulations.
CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING
Do not use flux when brazing copper-to copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (B-Cu93P-710/795: ISO
3677) which does not require flux. Note: Flux has an extremely negative effect on refrigerant piping
systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.
NOTE
Installation tools:
Gauge manifold, charge hose, etc.
Make sure to use installation tools that are exclusively used for R410A installations to withstand the pressure and to prevent for­eign materials (e.g. mineral oils such as SUNISO and moisture) from mixing into the system. (The screw specifications differ for R410A and R407C.)
Vacuum pump
1.
Use a 2-stage vacuum pump with a non-return valve.
2.
Make sure the pump oil does not flow oppositely into the system while the pump is not working.
3.
Use a vacuum pump which can evacuate to 500 microns.
9-1 Selection of piping material
1.
Foreign materials inside pipes (including oils for fabrication) must be 9 mg/10 ft or less.
2.
Use the following material specification for refrigerant piping:
Construction material: Phosphoric acid deoxidized seamless copper for refrigerant.
Size: Determine the proper size referring to chapter “Example of connection”.
The wall thickness of the refrigerant piping should comply with relevant local and national regulations. For R410A the design pressure is 450 psig (3.1 MPa).
3.
Make sure to use the particular branches of piping that have been selected referring to chapter “Example of connection”.
4.
Refer to chapter “Stop valve operation procedure” in 9-10 about the stop valve operation procedure.
5.
Make sure to perform the piping installation within the range of the maximum allowable pipe length, allowable level difference and allow­able length after branching as indicated in chapter “Example of con­nection”
6.
For installation of the refrigerant branch kit, refer to the installation manual delivered with the kit. And follow the conditions listed below.
Mount the REFNET joint so that it branches either horizontally or vertically.
Mount the REFNET header so that it branches horizontally.
(Refer to figure 22)
1. Horizontal connections
2. Up to ± 30° or vertically
7.
Restriction for the installation of the outside unit multi connection piping kit
3. Horizontal connections
To connect the piping between outside units, an optional piping kit (multi connection piping kit) is always required. When installing the piping, follow the instructions in the installation manual that comes with the kit.
• Install the joint horizontally within a lean of ±15° with caution name­plate on top. Refer to figure 23 (Fig. A). Do not connect it vertically. Refer to figure 23 (Fig. B).
• Reserve the straight part of 19-11/16 in. (500 mm) or more to the branch pipe and do not bend the local pipe in that area. Straight part of 19-11/16 in. (500 mm) or more can be reserved if a local pipe
(straight pipe) of 4-3/4 in. (120 mm) or more is connected to the joint. Refer to figure 23 (Fig. C).
• Incorrect installation may cause breakage of outside unit.
(Refer to figure 23)
1. Caution nameplate
2. Horizontal line
3. Ground
4. Straight part of 19-11/16 in. (500 mm) or more
5. Local pipe
(4-3/4 in. (120 mm) length or more)
Precautions when selecting branch piping.
• If the overall equivalent length of piping between the outside units and indoor units is 262.5 ft. (80 m) or more, be sure to enlarge the main pipe in the liquid-side branch piping. Depending on the length of the refrigerant piping, the cooling/heat­ing capacity may drop, but even in such cases it is ok to enlarge the main pipe.
(Refer to figure 21)
1. Outside unit
2. Main pipe
3. Enlarge
4. The first refrigerant branch kit.
5. Indoor unit
[Liquid side]
RWEYQ72/84P type: ...................................................φ3/8”→ φ1/2”
RWEYQ144P type: ......................................................φ1/2”→ φ5/8”
RWEYQ168/216P type: ...............................................φ5/8”→ φ3/4”
RWEYQ252P type: ......................................................φ3/4”→ φ7/8”
9-2 Protection against contamination when install-
ing pipes
Take measures to prevent foreign materials like moisture and
contamination from mixing into the system.
Place Installation period Protection method
Outdoor
Indoor Regardless of the period
More than a month Pinch the pipe Less than a month
Pinch or tape the pipe
Great caution is needed when passing copper tubes through
walls.
9-3 Pipe connection
Only use the flare nuts included with the unit.
Using different flare nuts may cause the refrigerant to leak.
Be sure to perform a nitrogen blow when brazing.
(Brazing without performing nitrogen replacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes, adversely affecting valves and com­pressors in the refrigerating system and preventing normal oper­ation.)
Do not use a flux when brazing the refrigerant pipe joints.
Use phosphor copper brazing (B-Cu93P-710/795: ISO 3677) which does not require flux. (Flux has an extremely negative effect on refrigerant piping sys­tems. For instance, if chlorine based flux is used, it will cause pipe corrosion. If the flux contains fluorine, it will damage the refriger­ant oil.)
DANGER
Use of oxygen could cause an explosion resulting in severe injury
or death. Only use nitrogen gas.
Refrigerant gas may produce toxic gas if it comes in contact with fire
such as from a fan heater, stove or cooking device. Exposure to this gas could cause severe injury or death.
NOTE
The pressure regulator for the nitrogen released when doing the
brazing should be set to 2.9 psig (0.02 MPa) or less.
(Refer to figure 18)
1. Refrigerant piping
2. Location to be brazed
3. Nitrogen
4. Taping
5. Manual valve
6. Regulator
Precautions when connecting pipes
• See the following table for flare part machining dimensions.
• When connecting the flare nuts, apply refrigerant oil to the inside of the flares and turn them three or four times at first. (Use ester oil or ether oil.)
• See the following table for tightening torque. (Applying too much torque may cause the flares to crack.)
• After all the piping has been connected, check the gas leak with nitrogen.
pipe size
(in.)
φ
3/8
φ
1/2
φ
5/8
tightening torque
(ft.·lbf. (N·m))
24.1 - 29.4 (32.7-39.9)
36.5 - 44.5 (49.5-60.3)
45.6 - 55.6 (61.8-75.4)
A
(in. (mm))
0.504 - 0.520 (12.8-13.2)
0.638 - 0.654 (16.2-16.6)
0.760 - 0.776 (19.3-19.7)
flare shape
(in. (mm))
90˚±2
45˚±2
A
R=0.016-0.031 (0.4-0.8)
Not recommendable but in case of emergency
You must use a torque wrench but if you are obliged to install the unit without a torque wrench, you may follow the installation method men­tioned below.
After the work is finished, make sure to check that there is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that posi­tion, further tighten the flare nut the angle shown below:
(Unit: in. (mm))
Pipe size Further tightening angle Recommended arm length of tool
φ
3/8
φ
1/2
φ
5/8
φ
3/4
60 to 90 degrees Approx. 7-7/8 (200)
30 to 60 degrees Approx. 9-13/16 (250)
30 to 60 degrees Approx. 11-13/16 (300)
20 to 35 degrees Approx. 17-3/4 (425)
9-4 Connecting the refrigerant piping
Connect piping to outside unit by using accessory pipes
(Refer to figure 20)
1. Gas side piping
2. (field supply)
3. Gas side accessory pipe (for suction gas (1))
4. Liquid side pipe (field supply)
5. Flare nut (Included in the unit)
6. Accessory pipes (for discharge gas and suction gas (2))
is not used.
7. Piping on discharge gas side (field supply)
8. Piping on suction gas side (field supply)
9. Cut off the hatched area and use it as a cover for the drilled.
10. Hatched area
11. Accessory pipe (for discharge gas)
12. Accessory pipe (for suction gas)
13. Guideline for pipe machining
14. Accessory pipe (for suction gas (2))
15. Brazing
16. Accessory pipe (for suction gas (1))
17. Before fitting to the product, apply brazing.
NOTE
Be sure to use the attached pipe when carrying out piping work in
the field.
Be sure that the local piping does not touch other pipes, the bottom panel or side panel. Especially for the bottom and side connection, be sure to protect the local piping with the provided insulation, to prevent it from coming into contact with the casing.
Precautions for installation of units
NOTE
The outside unit multi connection piping kit that is sold separately as
an option (BHFP22MA56U + 84U, BHFP26MA56U + 84U) is neces­sary for the multi installation of outside units.
• See the installation manual attached to the kit with attention to instal-
lation restrictions described in “connecting the refrigerant piping” when installing.
Cautions for installation of multiple outside units
1.
The piping between the outside units must be routed level or slightly upward to avoid the risk of oil detention to the piping side.
Pattern 1
Pattern 2
to indoor unit
to indoor unit
Piping between outside units
3.
If the piping length between the outside unit connection piping kit or between the outside units exceeds 80 in. (2m), create a rise of 8 in. (200mm) or more in the gas piping within a length of 80 in. (2m) from the kit.
If 80 in. (2 m) or less
Piping between outside unit
80 in. (2 m)
to indoor unit
or less
Change to pattern 1 or pattern 2
Prohibited pattern
to indoor unit
2.
The gas piping (both discharge and suction gas piping in case of the heat recovery system) after branched, install without fail a trap of 8 in. or more using the piping included in the piping kit for connecting the outside unit. Otherwise, the refrigerant may stay within the pip­ing, causing any damage to the outside unit.
Downward inclination
Oil remains in piping
Downward inclination
8 in. (200 mm) or more
Prohibited pattern
No trap has been installed in the gas piping.
to indoor unit
If 80 in. (2 m) or more
to indoor unit
80 in. (2 m)
or less
Rising height: 8 in. (200 mm) or more
Oil may remain in the farthest outside unit.
Change to pattern 1 or pattern 2
9-5 Example of connection
In case of a system of switching between cooling and heating, all systems use 2-tube piping (for suction gas piping and liquid piping). No Branch
Selector unit is required.
8 )
· Indoor un ts
( 1 - 8 )
Branch Se ector unts
( B1 - B6 )
Coo ng on y
( 7
o
8
H1
H2
n
l
m
REFNET header
j
Heat recovery system
( 1 - 6 )
h
34567
f
gi k
2
a
e
d
1
B1 B2 B3 B4 B5 B6
c
b
Outs de unt
Indoor un ts
( 1 - 8 )
( B1 - B6 )
Branch Se ector unts
Example 3
6 )
·
Coo ng on y
( 5
H2
8
7
o
B
n p
l
B5
m
k
Heat recovery system
( 1 - 4 , 7 · 8 )
j
i
REFNET ont (A·B)
b
A
g
h
23456
B2 B3 B4
f
e
1
B1
Indoor un ts
( 1 - 8 )
c
d
a
H1
REFNET header
Outs de unt
Branch Se ector unts ( B1 - B5 )
Example 2
s
8 )
8
·
Coo ng on y
( 7
H2
H1
r
qom
p
REFNET ont (A-G)
de
B3 B4
n
CDE
c
B2
l
Heat recovery system
( 1 - 6 )
k
234567
b
j
G
i
1
h
Indoor un ts
( 1 - 8 )
B1
g
f
Outs de unt
AB
a
Branch with REFNET joint Branch with REFNET joint and REFNET header Branch with REFNET header
( B1 - B4 )
Branch Se ector unts
Example 1
n
l
m
REFNET header
B6B5B4B3B2B1
j
k
h
f
g
e
d
b
a
Example 6
Indoor un ts
( 1 - 8 )
Branch Se ector unts
( B1 - B5 )
H2
8
p
o
B
REFNET header
n
l
B5
k
j
i
b
A
g
h
B2 B3 B4
f
e
B1
c
d
am
Example 5
s
r
e
q
p
d
REFNET ont (A-G)
o
n
c
l
m
k
j
b
i
1234567
h
FG
B1 B2 B3 B4
g
f
A CD
F rst outsde
a
Example 4
Heat recovery
system ( 1 - 6 )
Coo ng on y
o
8
H1
H2
Outs de
4567
i
123
c
Heat recovery system
( 1 - 4 , 7 · 8 )
H1
7
456
REFNET ont (A·B)
Outs de unt
t
3
2
s
1
r
u
8
H1
H2
H3
Outs de unt
branch
8 )
·
( 7
H3
un t
6 )
·
Coo ng on y
( 5
H3
8 )
·
Coo ng on y
( 7
Heat recovery
system ( 1 - 6 )
Indoor un ts
( 1 - 8 )
( B1 - B4 )
Branch Se ector unts
(Example 3,6) unit 8 : a + o 390 ft. (120 m)
(Example 2,5) unit 6 : a + b + l 390 ft. (120 m), 8 : a + m + n + p 390 ft. (120 m)
Pipe length between outside (2) and indoor units 390 ft. (120 m)
(Example 1,4) unit 8 : a + b + c + d + e + s 390 ft. (120 m)
Equivalent pipe length between outside (2) and indoor units 459 ft. (140 m) (assume equivalent pipe length of REFNET joint to be 1.6 ft. (0 5 m), hat of REFNET header to be 3.3 ft. (1 m), that of BS(V)Q36,60 is 13 ft. (4 m) and BS(V)Q96 is 19 t. (6 m), that of BS(V)4,6Q is 19 ft. (6 m) and BS8,10,12Q is 33 ft. (10 m) for calculation purposes.)
r 33 ft. (10 m) (Equivalent length ≤ 43 ft. (13 m))
t
u
Piping length from outside branch to outside unit 33 ft. (10 m) Equivalent length: max 43 ft. (13 m)
Total piping length from outside unit (2) to all indoor units 980 ft. (300 m)
s
r
Equivalent length ≤ 43 ft. (13 m))
Equivalent length ≤ 43 ft. (13 m))
u+t 33 ft. (10 m) (
u+s 33 ft. (10 m) (
Difference in height between outside and indoor units (H1) 164 ft. (50 m) (Max 130 ft. (40 m) if the outside unit is below)
Difference in height between indoor units (H2) 49 ft. (15 m)
BHFP22MA56U
KHRP26M33H9
KHRP26M72H9
KHRP26M73HU9
BHFP22MA84U
KHRP26M22H9, KHRP26M33H9
Outside unit
Refrigerant branch kit name
(Example 3,6) unit 8 : o 130 ft. (40 m) (Example 2,5) unit 6 : b + l 130 ft. (40 m), 8 :m + n + p 130 ft. (40 m)
KHRP25M33H9
KHRP25M72H9
KHRP25M73HU9
In case of 3-tube piping In case of 2-tube piping
Indoor
<72
72x<111
111x<246
246
capacity index
down stream of REFNET header.
How to select REFNET header
Select suitable one from the table below according to the total capacity of indoor units to be connected to the
KHRP26A33T9
KHRP26M72TU9
KHRP26M73TU9
Refrigerant branch kit name
)
KHRP25A33T9
A
KHRP25M72TU9
KHRP25M73TU9
Heat recovery system Heat pump system
Outside unit
capacity type
Choose from the following table in accordance with the capacity of the outside unit.
(Example 1,2,4,5 : REFNET joint
RWEYQ72, 84
RWEYQ144, 168
(Example 1,4) unit 8 : b + c + d + e + s 130 ft. (40 m)
Difference in height between outside unit (main) and outside unit (sub) (H3) 6.5 ft. (2 m)
Pipe length from first refrigerant branch kit (either REFNET joint or REFNET header ) to indoor unit 130 ft. (40 m)
How to select REFNET joint:
• When using REFNET joints at the first branch counted from the outside unit side.
RWEYQ216, 252
BHFP26MA56U
BHFP26MA84U
Heat recovery system Heat pump system
2 units
3 units
of outside unit
Number of units
Select from the table below according to the number of outside units.
How to select an outside branch kit (Needed when the outside unit type is RWEYQ144 or more.)
KHRP26A22T9
KHRP26A33T9
KHRP26M72TU9
Refrigerant branch kit name
KHRP25A22T9
KHRP25A33T9
KHRP25M72TU9
In case of 3-tube piping In case of 2-tube piping
Indoor
<72
72x<111
111x<246
capacity index
For REFNET joints other than the first branch, select the proper branch kit model based on the total capacity index.
(Unit: in.)
φ 1/4
Liquid pipe
φ 3/8
φ 1/2
Discharge gas pipe
Piping size (outer diameter)
φ 1/2
φ 5/8
Suction gas pipe
Indoor unit
be connected to downstream.
(Example 3,6) In case of REFNET Header,
For the gas piping size in case of 2-tube piping between refrigerant branch kit/Branch
indoor units of 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Piping between refrigerant branch kit and refrigerant branch kit/Branch Selector unit
Piping between Branch Selector unit and refrigerant branch kit
• Select one from the table below according to the total capacity of indoor units to
(Unit: in.)
Liquid pipe
, indoor units of 7 + 8
B
Discharge gas pipe
capacity type
Selector unit and refrigerant branch k t, select the size of suction gas piping.
under the generic term of the system.
The size of connection piping should not exceed the refrigerant piping size selected
Indoor unit connection piping size
<24
φ 3/8
φ 5/8
φ 3/4
24x<72
Piping size (outer diameter)
φ 3/4
φ 7/8
Suction gas pipe
KHRP26M73TU9
KHRP25M73TU9
Capacity type
(Example 2,5) In case of REFNET Joint
of outside unit
(Example 2,5) In case of REFNET Header, indoor units of 1 + 2 + 3 + 4 + 5 + 6
Piping between outside branch and outside unit (part C)
(Unit: in.)
Liquid pipe
, indoor units of 5 + 6 + 7 + 8
C
Discharge gas pipe
increase the size of the main pipe of liquid piping side.
RWEYQ72
φ 3/8
φ 5/8
the sizes of discharge and suction gas pipes.
RWEYQ84
Piping size increase in case of long piping
When the equivalent length is 262.5 ft. (80 m) or more, it is necessary to
When the equivalent length is 262.5 ft. (80 m) or more, do not increase
φ 1/2
φ 5/8
φ 3/4
φ 3/4
φ 7/8
φ 1-1/8
Piping size (outer diameter)
φ 3/4
φ 7/8
φ 1-1/8
φ 1-3/8
Suction gas pipe
246
Capacity type
of outside unit
RWEYQ72
RWEYQ84
RWEYQ144
RWEYQ168
RWEYQ216
Piping between outside unit and refrigerant branch kit (part A)
• Match to the size of connection piping of outside unit
(Example 1,4) In case of REFNET Joint
RWEYQ252
φ 3/8
φ 3/4
φ 7/8
72x<111
(Unit: in.) Indoor unit connection piping size
φ 1/2
φ 5/8
φ 3/4
φ 1/4
φ 3/8
Liquid pipeGas pipe
φ 1-1/8
Piping size (outer diameter)
φ 1/2
φ 5/8
φ 1-1/8
φ 1-1/4
Indoor unit
111x<162
162x<246
capacity type
246
07-18 type
Piping between Branch Selector unit (refrigerant branch kit) and indoor unit
Match to the size of the connection piping on the indoor unit.
24-48 type
(Unit: in.)
φ 1/2
φ 5/8
φ 3/4
φ 7/8
When increasedStandard size
Piping size (outer diameter)
φ 3/8
φ 1/2
φ 5/8
φ 3/4
Capacity type
of outside unit
RWEYQ72,84
RWEYQ144
RWEYQ168,216
(Unit: in.)
RWEYQ252
φ 1/2
φ 5/8
Liquid pipe
Diameter of liquid pipe (main pipe portion)
φ 7/8
Discharge gas pipe
Piping size (outer diameter)
φ 1-1/8
Suction gas pipe
Capacity type
of outside unit
of the outside unit to be connected to upstream
RWEYQ144
Piping between outside branches (part B)
Select the size from the following table based on the total capacity
RWEYQ168
r:φ 3/8× 3 ft.
t:φ 3/8× 3 ft.
s:φ 3/8× 3 ft.
: φ 1/4×10 ft.
n:φ 1/4×10 ft.
o:φ 1/4×10 ft.
m
i:φ 1/2×10 ft. j:φ 1/4×10 ft.
k:φ 1/4×10 ft.
f:φ 3/8×10 ft.
g:φ 1/4×10 ft.
e:φ 3/8×10 ft.
a:φ 3/4×30 ft.
b:φ 5/8×10 ft.
c:φ 3/8×10 ft.
(Heat recovery system)
If the outside unit is
RWEYQ252 and the
piping lengths are as
Example for refrigerant branch using REFNET joint and REFNET header for RWEYQ252
×0.074 lbs./ft.
(0.12 N·m)
(Unit: lbs. (kg))

φ1/2
iquid piping size at
Total length (ft. (m)) of

Heat recovery system Heat pump system
×0.114 lbs./ft.
(0.18 N·m)

φ5/8
System name
Total length (ft. (m)) of
liquid piping size at

+ +
Corrected
×0.168 lbs./ft.
(0.26 N·m)

3/4
φ
Total length (ft. (m)) of
liquid piping size at

×0.235 lbs./ft.
(0 37 N·m)

7/8
φ
iquid piping size at
Total length (ft. (m)) of

R= +
u:φ 5/8× 1 ft.
p:φ 1/4×10 ft.
23.3 (lbs.)
l:φ 1/4×10 ft.
h:φ 1/4×20 ft.
d:φ 3/8×10 ft.
b+ua c+d+e+f+r+s+t g+h+j+k+l+m+n+o+pi
R= 30 0.168 + 11 0.114 + 10 0.074 + 49 0.036 + 100 0.015 + 13 = 23.298
at right
13 (6)
6.6 (3)
9.9 (4.5)
13 (6)
6.6 (3)
9.9 (4.5)
1 unit (72 / 84)
2 unit multi (144 / 168)
3 unit multi (216 / 252)
volume by
outside unit
+
×0.015 bs./ft.
(0.022 N·m)

φ /4
iquid piping size at
Total length (ft. (m)) of

+
×0.036 lbs. ft.
(0.059 N·m)

φ3/8
Total leng h (ft. (m)) of
liquid piping size at

+
unit installed
Single outside
(RWEYQ72, 84)
Indoor
unit side
Gas p png
L qud p p ng
Discharge gas piping
Suction gas piping
Branch
Selector
unit
L qud p p ng
(3-tube p png) (2-tube p png)
D scharge gas pp ng
Example of connection
(Connection of 8 indoor units Heat pump system)
Outside
unit side
Suct on gas pp ng
(Thick line): 3-tube piping
• Piping between outside unit and Branch Selector unit
installed
outside units
When multiple
Liquid piping
Suction gas piping
Liquid piping
(Thin line): 2-tube piping
[]
• Piping between Branch Selector unit and indoor unit,
greater)
(RWEYQ144 or
Actual pipe length
Equivalent length
)
(
and indoor units
Between outside
If the system capacity is RWEYQ144 or more,
re-read the [outside unit] as [the first outside branch
seen from the indoor unit side].
Maximum
allowable
Actual pipe length
Difference in height
Difference in height
Total extension length
length
Difference in height
Between outside branch and outside unit
(In case of RWEYQ144 or more)
Between outside and indoor units
Between indoor and indoor units
Between outside and outside units
Allowable
height
length
Actual pipe length
Refrigerant branch kits can only be
Refrigerant branch kit selection
Allowable length after the branch
used with R410A.
Example of downstream indoor units
For an outside unit multi installation (RWEYQ144, 168, 216, 252 type),
make the settings in accordance with the following figure.
Pipe size selection
Piping between outside branch and outside unit (part C)
Piping between outside branches (part B)
If a negative result is gotten for R from the formula at right,
Piping between outside unit and refrigerant branch kit (part A)
How to calculate the additional refrigerant
to be charged
Additional refrigerant to be charged R (lbs. (kg))
(R should be rounded off in units of 0.1 lbs. (kg))
NOTE:
no refrigerant needs to be added.
9-6 Air tight test and vacuum drying
The units were checked for leaks by the manufacturer. Confirm that the valves are firmly closed before Air tight test or vacuum drying. To prevent entry of any impurities and ensure sufficient pressure resis­tance, always use the special tools dedicated for R410A.
Air tight test: Make sure to use nitrogen gas. (For the service port location, refer to the “Caution” label attached on the front panel [right] of the outside unit.)
(Refer to figure)
1. [Service Precautions] label
2. Control box cover
3. [Caution] label
Pressurize the liquid and gas pipes to 500 microns (do not pressurize more than 500 microns). If the pressure does not drop within 24 hours, the system passes the test. If the pressure drops, check where the nitrogen leaks from.
Vacuum drying: Use a vacuum pump which can evacuate to 500 microns.
1.
Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2 hours and bring the system to 500 microns or less. After keeping the system under that condi­tion for more than 1 hour, check if the vacuum gauge rises or not. If it rises, the system may either contain moisture inside or have leaks.
2.
Following should be executed if there is a possibility of moisture remaining inside the pipe (if piping work is carried out during the raining season or over a long period of time rainwater may enter the pipe during work). After evacuating the system for 2 hours, pressurize the system to
7.25 psig (0.05 MPa) (vacuum break) with nitrogen gas and evac­uate the system again using the vacuum pump for 1 hour to 500 microns or less (vacuum drying). If the system cannot be evacuated to 500 microns within 2 hours, repeat the operation of vacuum break and vacuum drying. Then, after leaving the system in vacuum for 1 hour, confirm that the vacuum gauge does not rise.
NOTE
Make sure to perform air tight test and vacuum drying using the service ports of the stop valve shown in the table below.
One outside unit installed
Multiple outside units installed
Liquid pipe stop valve Discharge gas pipe stop valve Suction gas pipe stop valve
Liquid pipe stop valve Discharge gas pipe stop valve Suction gas pipe stop valve Oil-equalizing pipe stop valve
1
2
9-7 Pipe insulation
After finishing the leak test and vacuum drying, the piping must be insu­lated. Take into account the following points:
• Make sure to insulate the connection piping and refrigerant branch kits entirely.
• Be sure to insulate the liquid-side, suction gas-side and discharge gas-side piping for the inter-unit piping and the refrigerant branch kits. Not insulating them may cause leaking. (The gas piping can reach temperatures of 250°F (120°C). Be sure the insulation used can withstand such temperatures.)
• If you think the humidity around the cooling piping might exceed 86°F (30°C) and RH80%, reinforce the insulation on the cooling pip­ing (at least 13/16 in. (20 mm) thick). Condensation might form on the surface of the insulation.
• If there is a possibility that condensation on the stop valve might drip down into the indoor unit through gaps in the insulation and piping because the outside unit is located higher than the indoor unit, etc., this must be prevented by caulking the connections, etc.
WARNING
• Be sure to insulate connection piping, as touching them can cause
burns.
9-8 Checking of device and installation conditions
Be sure to check the followings.
1.
Make sure there is no faulty power supply wiring or loosing of a nut. See 8. FIELD WIRING.
2.
Make sure there is no faulty transmission wiring or loosing of a nut. See 8. FIELD WIRING.
3.
Make sure there is no faulty refrigerant piping. See 9. REFRIGERANT PIPING.
4.
Make sure piping size is correct. See 9-1 Selection of piping material.
5.
Make sure insulation work is done. See 9-7 Pipe insulation.
6.
3
Make sure insulation resistance of main power supply circuit is not deteriorated. Using a megatester for 500 V, check that the insulation resistance of 2MΩ or more is attained by applying a voltage of 500 V DC between power supply and ground terminals. Never use the megatester for the transmission wiring (between outside and indoor unit, outside and Cool/Heat selector and etc.).
9-9 Additional refrigerant charge
WARNING
• To avoid injury always use protective gloves and eye protection when charging refrigerant.
To avoid injury do not charge with unsuitable substances. Use only the appropriate refrigerant.
NOTE
Refrigerant cannot be charged until field wiring has been com-
pleted. Refrigerant may only be charged after performing the leak test and the vacuum drying (see above). When charging a system, care shall be taken that its maximum per­missible charge is never exceeded, in view of the danger of liquid hammer. Refrigerant containers shall be opened slowly.
TO AVOID COMPRESSOR BREAKDOWN. DO NOT CHARGE THE REFRIGERANT MORE THAN THE SPECIFIED AMOUNT TO RAISE THE CONDENSING PRESSURE.
• This outside unit is factory charged with refrigerant and depending
on pipe sizes and pipe lengths some systems require additional charging of refrigerant.
• Determine the amount of refrigerant to be added by referring to the
table, write it down on the included “Added Refrigerant” plate and attach it to the rear side of the front cover. Note: refer to the example of connection for the amount to be added.
Additional refrigerant charge procedure (1)-normally
• Charge the refrigerant to the liquid pipe in its liquid state. Since
R410A is a mixed refrigerant, its composition changes if charged in a state of gas and normal system operation would no longer be assured.
• Make sure to use installation tools you exclusively use on R410A
installations to withstand the pressure and to prevent foreign materi­als from mixing into the system.
1.
Before charging, check whether the tank has a siphon attached or not.
How to charge with the siphon tank.
Charge with the tank upright.
There is a siphon tube inside, so there is no need to turn the tank upside-down.
Other ways of charging with the tank.
Charge with the tank upside-down.
2.
After the vacuum drying is finished, charge the additional refrigerant in its liquid state through the liquid pipe stop valve service port. Tak­ing into account following instructions:
Check that gas and liquid pipe stop valves are closed.
Stop the compressor and charge the specified weight of refriger-
ant. (If the outside unit is not in operation and the total amount cannot be charged, follow the Additional refrigerant charge procedure (2) shown below.)
NOTE
Procedures for charging additional refrigerant. (Refer to figure 24)
1. Pressure reducing valve
2. Nitrogen
3. Refrigerant tank
4. With a siphon
5. Measuring instrument
6. Vacuum pump
7. Va l ve A
8. Va l ve B
9. Charge hose
10. Outside unit
11. Gas side
12. Liquid side
13. Discharge gas side
14. Suction gas side
15. Stop valve service port
16. To indoor unit
17. To indoor units / Branch Selector units
18. Dotted lines represent onsite piping
Additional refrigerant charge procedure (2)-by Additional refriger­ant charge operation
To learn the system settings for additional refrigerant charging, refer to the [Service Precautions] label attached on the back of the control box cover in the outside unit.
1.
Fully open all stop valves (valve A and valve B must be left fully closed).
2.
After ten minutes, fully close liquid pipe stop valve and then, open the valve by turning 180°. Start the additional refrigerant charge operation. See [Service Precautions] label for detail. If it is difficult to charge the refrigerant additionally, decrease the water temperature or warm the refrigerant tank. (Warm the refrigerant tank with a stupe or a warm hot water of 104°F (40°C) or less.)
3.
After the system is charged with a specified amount of refrigerant, press the RETURN button (BS3) on the printed circuit board (A1P) in the outside unit to stop the additional refrigerant charge operation.
4.
Immediately open both liquid and gas pipe stop valve. (If the stop valve is not opened immediately, liquid seal may cause the pipes to burst.)
NOTE
If the refrigerant cylinder is siphonal, set it upright while charging
additional refrigerant.
9-10 Stop valve operation procedure
CAUTION
Do not open the stop valve until 1-6 of “9-8 Checking of device and installation conditions” are completed. If the stop valve is left open without turning on power supply, it may cause refrigerant to buildup in the compressor, leading to insulation degradation.
Opening stop valve
1.
Remove the cap and turn the valve counterclockwise with the hexa­gon wrench.
2.
Turn it until the shaft stops. Do not apply excessive force to the stop valve. Doing so may break the valve body, as the valve is not a backseat type. Always use the special tool.
3.
Make sure to tighten the cap securely.
Closing stop valve
1.
Remove the cap and turn the valve clockwise with the hexagon wrench.
2.
Securely tighten the valve until the shaft contacts the main body seal.
3.
Make sure to tighten the cap securely. For the tightening torque, refer to the table on the below.
Tightening torque
Stop
valve size
Liquid
side
Gas side
(Refer to figure 25)
Caution
• Do not damage the cap sealing.
• Always use a charge hose for service port connection.
• After tightening the cap, check that no refrigerant leaks are present.
• After working, securely tighten the cover of service port without fail by specified torque.
• When loosening a flare nut, always use two wrenches in combina­tion. When connecting the piping, always use a spanner and torque wrench in combination to tighten the flare nut.
• When connecting a flare nut, coat the flare (inner and outer faces) with ether oil or ester oil and hand-tighten the nut 3 to 4 turns as the initial tightening.
• Do not forget to open the stop valve before starting operation.
(Refer to figure 26)
Tightening torque (ft.·lbf. (N·m)) (Turn clockwise to close)
(valve body)
3.98-4.87 (5.4-6.6)
19.91-24.33 (27-33)
Shaft
Hexagonal
wrench
1/8 in. (4 mm)
Hexagonal
wrench
3/8 in. (10 mm)
Cap
(valve
cover)
9.95-12.17
(13.5-16.5)
26.54-32.44 (36-44)
Service port
8.48-10.25 (11.5-13.9)
8.48-10.25 (11.5-13.9)
Flare nut
24.1-29.4
(32.7-39.9)
_
Gas side
accessory
pipe (1)
_
16.22-20.65 (22-28)
1. Service port
2. Cap
3. Hexagon hole
4. Shaft
5. The main body seal
1. Remove the cap and turn the valve counterclockwise with
the hexagon wrenches until it stops.
2. Discharge gas side
3. Liquid side
4. Suction gas side
5. Never remove the partition flange for any reason.
6. Full close on the suction gas side
10. CHECKS AFTER INSTALLATION
WARNING
• Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system.
Attach the power supply wire securely.
To avoid injury, always make sure that the circuit breaker on the power
supply panel of the installation is switched off before doing any work.
After the installation, check the following before switching on the circuit breaker:
1.
The position of the switches that requires an initial setting Make sure that switches are set according to your application needs before turning the power supply on.
2.
Power supply wiring and transmission wiring Use a designated power supply and transmission wiring and make sure that it has been carried out according to the instructions described in this manual, the wiring diagrams and local and national regulations.
3.
Pipe sizes and pipe insulation Make sure that correct pipe sizes are installed and that the insulation work is properly executed.
4.
Additional refrigerant charge The amount of refrigerant to be added to the unit should be written on the included “Additional Refrigerant” label, and attach it to the rear side of the front cover.
5.
Measurement of insulation in main power supply circuit Using a megatester for 500 V, check that the insulation resistance of 2MΩ or more is attained by applying a voltage of 500 V DC between power supply and ground terminals. Never use the megatester for the transmission wiring.
6.
Installation date Be sure to keep record of the installation date on the “Additional Refrigerant” label.
11. TEST RUN
CAUTION
After completing installation, be sure to open the valves. (Operating the unit with the valves shut will break the compressor.)
11-1 Air discharge
• Running the heat source water pump, carry out air discharge
process until the water comes out from the air discharge hole of local piping. (For the operation to be done for the first time after installation, you need to perform a checking operation.)
11-2 Before turn on the power supply
• Close the control box cover securely before turning on power supply.
• Make settings for outside unit printed circuit board (A1P) after turn-
ing on the power supply and check the LED display from inspection door that is on the control box cover.
11-3 Check operation
When running the unit for the first time after installation, be sure to per­form a test operation following these steps. (Not performing a test oper­ation when the unit is first installed may prevent the unit from operating properly.)
• During the operation, monitor the outside unit operation status and
check for any incorrect wiring.
(1) Check the connection of interlock
circuit
(2)• As necessary, configure the system
settings onsite by using the dipswitch (DS1) on the outside unit printed circuit board (A1P) and push button switches (BS1 to 5).
• When the system is in the multiple­outside unit configuration, perform the configuration on the main unit. (Any settings made on a sub unit will be ignored.)
After this, close the control box cover.
(3) Turn ON the power supply to the out-
side units and indoor units.
(4) Star t the heat source water pump
and fill the heat source water in the outside unit.
Make sure that the temperature of
(5)
heat source water is kept within the operation range (50-113°F (10-45°C)).
(6) Check the LED on the printed circuit board (A1P) in the outside unit to see if the
data transmission is performed normally.
LED display (Default status before delivery)
One outside unit installed
When multiple outside unit
)
installed (
() The base (main) unit is the outside unit to which the interconnecting wiring for the
indoor units is connected. The other outside units are sub units.
(7)• Using the push button switches
(BS1 - 5) on the pr inted circuit board (A1P) of outside unit, carr y out a local setting, if necessary.
• When the system is in the multiple­outside unit configuration, perform the configuration on the main unit. (Any settings made on a sub unit will be ignored.)
(8) Check all stop valves are opened.
If some stop valve is closed, open them. (Refer to 9-10 Stop valve operation procedure.)
(9)Perform the check operation following
the instructions printed on the [Service Precautions] label.
Microcomputer operation monitor
Master station Sub station 1 Sub station 2
HAP H1P H2P H3P H4P H5P H6P H7P H8P
The outside unit cannot be operated if the interlock circuit has not been connected.
Always perform configuration after tur ning ON the power supply. To learn the setting method, refer to the [Service Precautions] label attached at the position shown in the figure on the right (Control box cover in outside unit). (Remember, the actual settings you have made must be recorded on the [Service Precautions] label.)
Make sure to turn ON the power supply 6 hours before starting the operation. This is necessary to warm the crankcase prelim­inarily by the electric heater.
The outside unit cannot be operated if the heat source water pump is not r unning.
The outside unit cannot be operated at a temperature outside the operation range.
Ready/
Page
Cooler/heater changeover
Error
Bulk
Individual
Always perform configuration after tur ning ON the power supply. To learn the setting method, refer to the [Service Precautions] label attached at the position shown in the figure on the right (Control box cover in outside unit). (Remember, the actual settings you have made must be recorded on the [Service Precautions] label.)
[CAUTION]
Do not leave any stop valve closed. Otherwise the compressor will fail. For Heat recovery system of cooling and heating: Open all stop valves on the suction side, discharge gas side and liquid side. For cooling and heating switching operation system: Open the stop valves on discharge gas side and liquid side. (Keep the stop valve on
suction side fully closed.)
If you push the test run button (BS4) on the printed circuit board (A1P) of the outside unit for 5seconds, the test run star ts. If you want to interrupt the test run, push the RETURN button (BS3) on pr inted circuit board (A1P). The system continues resid­ual operation for about 1 minute (maximum 10 minutes) and then stops. (During test run, you cannot stop it by a command from a remote controller.)
You need to perform the above settings on the printed circuit board by access­ing the printed circuit board through the inspection door on the control box cover.
Bulk
(main)
(sub)
LED display: OFF ON Blinking
Low noise
Demand
Multi
(Refer to figure 27)
1. Control box
2. Control box cover
3. Inspection door
4. [Service Precautions] label
Cautions for check operation
• If the system is started within about 12 minutes after the outside/ indoor units are turned ON, the compressor will not run and H2P lights up. Before starting an operation, always verify that the LED dis­play shows the contents of the table in 11-3 Check operation (6).
• The system may require up to 10 minutes until it can start the com­pressor after an operation start. This is a normal operation to equal­ize the refrigerant distribution.
• The check operation does not provide any means of checking the indoor units individually. For that purpose, perform normal operation using the remote controller after the check operation. Check operation is not possible in other modes such as collection mode.
• If the setting of indoor remote controller is changed before the check operation, it may not be performed correctly and malfunction code “UF” may be displayed.
Remote controller displays malfunction code
Malfunc-
tion code
E3 E4 F3
F6 UF U2
U1
U1 U2 U4
U7 UA
UF
E3
F6 UF U2
E4
F3
U7 UF
UF
E4
HJ
U3
Installation error Remedial action
The stop valve of an out­side unit is left closed.
The phases of the power supply to the outside units are reversed.
No power is supplied to an outside, Branch Selector or indoor unit (including phase interruption).
A model which cannot be connected in a multi-out­side-unit system has been connected in a multi-outside-unit system.
DIP switch setting of Branch Selector unit is incorrect.
Combination with T type (BSQ-TVJ, BS­Q54TVJ) and P type(BSVQ-PVJU, BSV-Q36PVJU) cause error.
Incorrect transmission between units
Refrigerant overcharge
Insufficient refrigerant
If the multi-outside-unit termi­nal is connected when there is one outside unit installed.
The operation mode on the remote controller was changed before the check operation. The heat source water is not circulating.
The check operation has not been performed.
Open the stop valve. Check referring to the table in
9-9 Additional refrigerant charge.
Exchange two of the three phases (L1, L2, L3) to make a positive phase connection. Check if the power supply wiring for the outside units are connected correctly. (If the power supply wire is not con­nected to L2 phase, no malfunction display will appear and the com­pressor will not work.) Check if the ground fault circuit interrupter in the outside unit is ON.
Change to individual piping, and
disconnect the wiring from the multi-outside-unit terminals (Q1, Q2).
Set up a DIP switch referring to service precautions of Branch Selector unit.
Configure the system with only T type, or only P type.
Check if the refrigerant piping and the unit transmission wiring are consistent with each other.
Recalculate the required amount of refrigerant from the piping length and correct the refrigerant charge level by recovering any excessive refrig­erant with a refrigerant recovery machine.
Check if the additional refrig­erant charge has been fin­ished correctly.
Recalculate the required amount of refrigerant from the piping length and add an ade­quate amount of refrigerant.
Remove the wiring from the multi-outside-unit terminals (Q1, Q2).
Set the operation mode on all indoor unit remote controllers to “cooling.”
Make sure that the water pump is running.
Perform the check operation.
E3 is activated, so On/Off but­ton is pressed on the remote controller, but this does not
E2
tu r n E3 o ff. Or E 2 is act ivated .
E3
In case of above, there is a malfunction of the compres­sor in the outside unit.
Measure the insulation resis­tance of the compressor to check the condition of the com­pressor.
11-4 Check of normal operation
After the check operation is completed, operate the unit normally. Check the below items.
Make sure the indoor and outside units are operating normally (If a
knocking sound can be heard in the liquid compression of the com­pressor, stop the unit immediately and then energize the heater for a sufficient length of time before restarting the operation.)
Run each indoor unit one at a time and make sure the corre­sponding outside unit is also running.
Check to see if cold (or hot) air is coming out of the indoor unit.
Press the fan direction and fan strength buttons on the indoor unit
to check if they operate properly.
NOTE
Cautions for normal operation check
Once stopped, the compressor will not restart in about 5 minutes
even if the On/Off button of an indoor unit in the same system is pressed. When the system operation is stopped by the remote controller, the out-
side units may continue operating for further 5 minutes at maximum.
If the system has not undergone any check operation by the test operation button since it was first installed, an malfunction code “U3” is displayed. In this case, perform check operation referring to 11-3 Check operation.
After the test operation, when handing the unit over to the cus­tomer, make sure the control box cover, the inspection door, and the unit casing are all attached.
12. ONSITE SETTINGS
12-1 Energy saving and optimum operation
This VRV pump system is equipped with advanced energy saving func­tionality. Depending on the priority, emphasizes can be put on energy saving or comfort level. Several parameters can be selected, resulting in the optimal balance between energy consumption and comfort for the particular application.
[2-8]= Te target temperature during cooling operation
Default value=5
Te setting (cooling operation)
2. 43°F (6°C)
3. 45°F (7°C)
hhkhhh
k
Change [2-8]=2-7 in function of required operation method dur­ing cooling.
[2-9]= Tc target temperature during heating operation
Default value=3
hhkhhh
k
Change [2-9]=1, 3 or 6 in function of required operation method during heating.
4. 46°F (8°C)
5. 48°F (9°C)(default)
6. 50°F (10°C)
7. 52°F (11°C)
Tc setting (heating operation)
1. 106°F (41°C)
3. 109°F (43°C)(default)
6. 115°F (46°C)
hhhhkh
k
hhhh
k
hhhkhh
k
hhhkh
k
hhhkkh
k
hhh
k
k k k
kkk
hhhhh hhhh hhhkkh
kk
k
k
kk
[2-49]= Te target temperature during simultaneous operation
Default value=5
Te setting (simultaneous operation)
2. 43°F (6°C)
3. 45°F (7°C)
hhh
kkk
Change [2-49]=2-7 in function of required operation method during simultaneous operation.
[2-51]= Cooling comfort setting
Default value=1
kkkhhkk
Change [2-51]=0, 1, 2 or 3 in function of required limitation. This setting is used in conjunction with setting [2-8].
[2-52]= Heating comfort setting
Default value=1
kkkhk
Change [2-52]=0, 1, 2 or 3 in function of required limitation. This setting is used in conjunction with setting [2-9].
Several patterns are available and explained below. Modify the param­eters to the needs of your building and to realize the best balance between energy consumption and comfort.
4. 46°F (8°C)
k
5. 48°F (9°C)(default)
6. 50°F (10°C)
7. 52°F (11°C)
Cooling comfort setting
0. Eco
1. Mild (default)
2. Quick
3. Powerful
Heating comfort setting
0. Eco
1. Mild (default)
hh
2. Quick
3. Powerful
hhhhkh
k
hhhh
k
hhhkhh
k
hhhkh
k
hhhkkh
k
hhh
k
hhhhhh
k
hhhhh
k
hhhhkh
k
hhhh
k
hhhhhh
k
hhhhh
k
hhhhkh
k
hhhh
k
kk
k
kkk
k
kk
k
kk
12-1-1 Two main operation methods are available:
Automatic The refrigerant temperature is set by default to a certain start value (defined by field setting). Depending on the load of the indoor units, the refrigerant temperature is adjusted. When there is a big/small load, according behaviour to match this load is executed. Depending on the operation mode (cooling, heating or heat recov­ery), field settings are available to define the standard refrigerant temperature start point. They are explained below. E.g., when your system is operating in cooling, you do not need as much cooling under low ambient temperatures (e.g., 77°F (25°C)) as under high ambient temperatures (e.g., 95°F (35°C)). Using this idea, the system automatically starts increasing its refrig­erant temperature, automatically reducing the delivered capacity and increasing the system's efficiency based on indoor unit load feedback.
To define the start value during cooling operation, change field setting [2-8] = 5 (default; corresponding to Te = 48°F (9°C) to the required value).
E.g., when your system is operating in heating, you do not need as much heating under high ambient temperatures (e.g., 59°F (15°C)) as under low ambient temperatures (e.g., 23°F (–5°C)). Using this idea, the system automatically starts decreasing its refrig­erant temperature, automatically reducing the delivered capacity and increasing the system’s efficiency.
To define the start value during heating operation, change field setting [2-9] = 3 (default; corresponding to Tc = 109°F (43°C) to the required value).
When the system is used as a heat recovery system, the start refrig­erant temperature during heat recovery mode for cooling can be selected differently than during cooling operation. To define the start value for cooling operation during heat recovery operation, change field setting [2-49] = 5 (default; corresponding to Te = 48°F (9°C) to the required value).
Hi-sensible/economic (cooling/heating) The refrigerant temperature is set higher/lower (cooling/heating) compared to basic operation. The focus under high sensible mode is comfort feeling for the customer. The selection method of indoor units is important and has to be con­sidered as the available capacity is not the same as under basic operation. For details concerning to Hi-sensible applications, please
contact your dealer.
To activate this setting under cooling operation, change field set­ting [2-8] to the appropriate value, matching the requirements of the pre-designed system containing a high sensible solution.
Value [2-8] Te target
3 45°F (7°C) 4 46°F (8°C) 5 48°F (9°C) 6 50°F (10°C) 7 52°F (11°C)
To activate this setting under heating operation, change field set­ting [2-9] to the appropriate value, matching the requirements of the pre-designed system containing a high sensible solution.
Value [2-9] Tc target
1 106°F (41°C) 3 109°F (43°C)
To maintain the target settings, it is required to set the comfort setting to Eco. The comfort modes are explained below.
12-1-2 Several comfort settings are available
For each of above modes a comfort level can be selected. The comfort
level is related to the timing and the effort (energy consumption) which is put in achieving a certain room temperature by temporarily changing the refrigerant temperature to different values in order to achieve requested conditions more quickly.
Powerful Overshoot (during heating operation) or undershoot (during cooling operation) is allowed compared to the requested refrigerant temper­ature, in order to achieve the required room temperature very fast. The overshoot is allowed from the start up moment. In case of cooling operation the evaporating temperature is allowed to go down to 37°F (3°C) on temporary base depending on the situ­ation. In case of heating operation the condense temperature is allowed to go up to 120°F (49°C) on temporary base depending on the situa­tion. When the request from the indoor units becomes more moderate, the system will eventually go to the steady state condition which is defined by the operation method above.
To activate the powerful comfort setting under cooling operation, change field setting [2-51]=3. This setting is used in conjunction with setting [2-8].
To activate the powerful comfort setting under heating operation, change field setting [2-52]=3. This setting is used in conjunction with setting [2-9].
Quick Overshoot (during heating operation) or undershoot (during cooling operation) is allowed compared to the requested refrigerant temper­ature, in order to achieve the required room temperature very fast. The overshoot is allowed from the start up moment. In case of cooling operation the evaporating temperature is allowed to go down to 43°F (6°C) on temporary base depending on the situ­ation. In case of heating operation the condense temperature is allowed to go up to 115°F (46°C) on temporary base depending on the situa­tion. When the request from the indoor units becomes more moderate, the system will eventually go to the steady state condition which is defined by the operation method above.
To activate the quick comfort setting under cooling operation, change field setting [2-51]=2. This setting is used in conjunction with setting [2-8].
To activate the quick comfort setting under heating operation, change field setting [2-52]=2. This setting is used in conjunction with setting [2-9].
Mild Overshoot (during heating operation) or undershoot (during cooling operation) is allowed compared to the requested refrigerant temper­ature, in order to achieve the required room temperature very fast. The overshoot is not allowed from the start up moment. The start up occurs under the condition which is defined by the operation mode above. In case of cooling operation the evaporating temperature is allowed to go down to 43°F (6°C) on temporary base depending on the situ­ation. In case of heating operation the condense temperature is allowed to go up to 115°F (46°C) on temporary base depending on the situa­tion. When the request from the indoor units becomes more moderate, the system will eventually go to the steady state condition which is defined by the operation method above. The start up condition is different from the powerful and quick com­fort setting.
To activate the mild comfort setting under cooling operation, change field setting [2-51]=1. This setting is used in conjunction with setting [2-8].
To activate the mild comfort setting under heating operation, change field setting [2-52]=1. This setting is used in conjunction with setting [2-9].
Eco The original refrigerant temperature target, which is defined by the operation method (see above) is kept without any correction, unless for protection control.
To activate the mild comfort setting under cooling operation, change field setting [2-51]=0. This setting is used in conjunction with setting [2-8].
To activate the mild comfort setting under heating operation, change field setting [2-52]=0. This setting is used in conjunction with setting [2-9].
Example: Room temperature evolution during cooling
D
E
F
A
BC
A Indoor unit set temperature
B Operation start
C Operating time
D Mild
E Quick
F Power fu l
Example: Room temperature evolution during heating
A
EF
D
BC
A Indoor unit set temperature
B Operation start
C Operating time
D Mild
E Quick
F Power fu l
No matter which control is selected, variations on the behavior of the system are still possible due to protection controls to keep the unit oper­ating under reliable conditions. The intentional target, however, is fixed and will be used to obtain the best balance between energy consump­tion and comfort, depending on the application type.
13. CAUTION FOR REFRIGERANT LEAKS
DANGER
Refrigerant gas is heavier than air and replaces oxygen. A massive
leak could lead to oxygen depletion, especially in basements, and an asphyxiation hazard could occur leading to serious injury or death.
Calculate the smallest room volume (ft.3 (m3))
2.
In case like the following, calculate the volume of (A), (B) as a single room or as the smallest room.
Where there are no smaller room divisions
A.
(Points to note in connection with refrigerant leaks)
Introduction
The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.
The VRV System, like other air conditioning systems, uses R410A as refrigerant. R410A itself is an entirely safe non-toxic, non-combustible refrigerant. Nevertheless care must be taken to ensure that air condi­tioning facilities are installed in a room which is sufficiently large. This assures that the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.
Maximum concentration level
The maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.
3
The unit of measurement of the concentration is lbs./ft. weight in lbs. (kg) of the refrigerant gas in 1 ft.
occupied space).
Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.
1. direction of the refrigerant flow
2. room where refrigerant leak has occurred (outflow of all the
refrigerant from the system)
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant is heavier than air.
Procedure for checking maximum concentration
Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.
Calculate the amount of refrigerant (lbs. (kg)) charged to each sys-
1.
tem separately.
amount of refriger­ant in a single unit system (amount of refrigerant with which the system is charged before leaving the factory)
NOTE
Where a single refrigerant facility is divided into 2 entirely indepen-
dent refrigerant systems then use the amount of refrigerant with which each separate system is charged.
additional charging amount (amount of
+
refrigerant added locally in accordance with the length or diameter of the refrig­erant piping)
3
(1 m3)
(kg/m3) (the
volume of the
1
2
total amount of refriger-
=
ant (lbs. (kg)) in the system
Where there is a room division but there is an opening
B.
between the rooms sufficiently large to permit a free flow of air back and forth.
1
2
1. opening between rooms
2. partition
(Where there is an opening without a door or where there are open­ings above and below the door which are each equivalent in size to
0.15% or more of the floor area.) Calculating the refrigerant density using the results of the calcula-
3.
tions in steps 1 and 2 above.
total volume of refrigerant in the refrigerant system
3 (m3
size (ft. which there is an indoor unit installed
If the result of the above calculation exceeds the maximum concen­tration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum con­centration.
Dealing with the situations where the result exceeds the maximum
4.
concentration level. Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system. Please consult your Daikin supplier.
)) of smallest room in
maximum concen-
tration level (lbs./ft.
3
(kg/m3))
3P365916-17C EM14A009A
(1503)
HT
Loading...