technical data
air conditioning systems
Round Flow Cassette
FXFQ-PVE9
technical data
air conditioning systems
Round Flow Cassette
FXFQ-PVE9
• Indoor Units • Round Flow Cassette • FXFQ-PVE9
TABLE OF CONTENTS
FXFQ-PVE9
1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Electrical Specifications (50Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Electrical Specifications (60Hz) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
•VRV® Systems • Indoor Units
1
1 Specifications
Indoor Unit VRV® Systems FXFQ-PVE9 Round Flow
1-1 TECHNICAL SPECIFICATIONS
Capacity Cooling kW 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0
Heating kW 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0
1
Power Input (50Hz) Cooling kW 0.033 0.033 0.047 0.052 0.066 0.093 0.187 0.209
Heating kW 0.027 0.027 0.034 0.038 0.053 0.075 0.174 0.200
1
Power Input (60Hz) Cooling kW 0.032 0.032 0.042 0.050 0.063 0.092 0.186 0.208
Heating kW 0.027 0.027 0.034 0.038 0.053 0.075 0.174 0.200
Casing Material Galvanised steel
Dimensions Unit Height mm 246 246 246 246 246 246 288 288
Weight Unit kg 19.5 19.5 19.5 19.5 22 22 25 25
Heat Exchanger Dimensions Nr of Rows 22222222
Fin Fin type Cross fin coil
Fan Type Turbo fan
Cooling High high m³/min 13 13 15 16 19 21 32 33
High m³/min 11.5 11.5 13 13.5 16.5 18 26 28.0
Low m³/min 1010111113.5152022.5
Fan Motor Model QTS48C15M
Refrigerant Name R-410A
Piping connections Liquid (OD) Type Flare connection
Gas Type Flare connection
Drain Diameter mm VP25 (I.D. 25/O.D. 32)
Sound absorbing insulation Polyurethane form
Decoration Panel Model BYCP125K-W1
Colour Fresh white
Dimensions Height mm 50
Weight kg 5.5
Air Filter Resin net with mold resistance
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating
Safety devices Fuse
Standard Accessories Operation manual
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
• Indoor Units • Round Flow Cassette • FXFQ-PVE9
FXFQ25PVE9 FXFQ32PVE9 FXFQ40PVE9 FXFQ50PVE9 FXFQ63PVE9 FXFQ80PVE9
Width mm 840 840 840 840 840 840 840 840
Depth mm 840 840 840 840 840 840 840 840
Fin Pitch mm 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
Face Area m² 0.267 0.267 0.267 0.267 0.446 0.446 0.535 0.535
Nr of Stages 666610101212
Output (high) W 56 56 56 56 56 56 120 120
Drive Direct drive
Diameter mm 6.35 6.35 6.35 6.35 9.52 9.52 9.52 9.52
Diameter mm 12.7 12.7 12.7 12.7 15.9 15.9 15.9 15.9
Width mm 950
Depth mm 950
Installation manual
Paper pattern for installation
Drain hose
Clamp metal
Washer fixing plate
Sealing pads
Clamps
Screws
Washer for hanging bracket
Insulation for fitting
Installation guide
: 35°CDB, equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
FXFQ100PVE9 FXFQ125PVE9
2
•VRV® Systems • Indoor Units
• Indoor Units • Round Flow Cassette • FXFQ-PVE9
1 Specifications
1-2 ELECTRICAL SPECIFICATIONS (50HZ)
Power Supply Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 0.3 0.3 0.3 0.3 0.4 0.5 1.3 1.5
Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15
Full load amps (FLA) A 0.2 0.2 0.2 0.2 0.3 0.4 1.0 1.2
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
1-3 ELECTRICAL SPECIFICATIONS (60HZ)
Power Supply Name VE
Phase 1~
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 0.3 0.3 0.3 0.3 0.4 0.5 1.3 1.5
Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15
Full load amps (FLA) A 0.2 0.2 0.2 0.2 0.3 0.4 1.0 1.2
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
FXFQ25PVE9 FXFQ32PVE9 FXFQ40PVE9 FXFQ50PVE9 FXFQ63PVE9 FXFQ80PVE9
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
FXFQ25PVE9 FXFQ32PVE9 FXFQ40PVE9 FXFQ50PVE9 FXFQ63PVE9 FXFQ80PVE9
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
FXFQ100PVE9 FXFQ125PVE9
FXFQ100PVE9 FXFQ125PVE9
3
1
1
•VRV® Systems • Indoor Units
3
• Indoor Units • Round Flow Cassette • FXFQ-PVE9
2 Safety device settings
FXFQ-PV9
Safety devices 25 32 40 50 63 80 100 120
PC board fuse °C 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A
1
2
FXFQ~PVE9
Fan motor thermal fuse °C--------
Fan motor thermal protector °C - - - - - - - -
3 Options
FXFQ-PV9
3D006691N
Option Note FXFQ25PVE9
Decoration panel BYCP125K-W1
Sealing material of air discharge outlet KDBH55K160F
Fresh air intake kit
Insulation kit for high humidity KDTP55K80 KDTP55K160
High efficiency filter unit
Replacement high efficiency filter
Replacement Ultra long life filter KAFP55H160H
Remote controller
Installation box for adaptor PCB KRP1H98
Panel spacer KDBP55H160FA
Chamber type
Chamber connection kit KKSJ55K160
Colorimetric method 65% KAFP556H80 KAFP556H160
Colorimetric method 90% KAFP557H80 KAFP557H160
Colorimetric method 65% KAFP552H80 KAFP552H160
Colorimetric method 90% KAFP553H80 KAFP553H160
Filter chamber KDDFP55H16 0
Replacement Long Life filter KAFP551K160
Ultra long life filter KAFP55H1 60
Branch duct chamber KDJP55H80 KDJP55H160
Wired type BRC1C62
Wireless type (HP/CO) BRC7F634F / BRC7F635F
Central remote control DCS302CA61
Unified ON/OFF control DCS301BA61
Schedule timer DST301BA61
Intelligent Touch control DCS601C51
Adapter for wiring KRP1C63
Group control adapter KRP4A53
Remote Sensor KRCS01-4B
Without T shape pipe KDDP55K160
Direct installation type KDDP55X160
With T shape pipe KDDP55K160K
FXFQ32PVE9
FXFQ40PVE9
FXFQ50PVE9
FXFQ63PVE9
FXFQ80PVE9
FXFQ100PVE9
FXFQ125PVE9
3D060297A
4