READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE
AND INFORMATION.
BEFOREINSTALLATION
■Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.
■Refer to the installation manual of the outdoor unit for items not
described in this manual.
■Caution concerning refrigerant series R410A:
The connectable outdoor units must be designed exclusively for
R410A.
■Do not place objects in direct proximity of the outdoor unit and
do not let leaves and other debris accumulate around the unit.
Leaves are a hotbed for small animals which can enter the unit.
Once in the unit, such animals can cause malfunctions, smoke
or fire when making contact with electrical parts.
Precautions
■Do not install or operate the unit in rooms mentioned below.
• Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)
• Where corrosive gas like sulphurous gas exists. (Copper tubing
and brazed spots may corrode.)
• Where volatile flammable gas like thinner or gasoline is used.
• Where machines generating electromagnetic waves exist.
(Control system may malfunction.)
• Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories). Also
in vehicles or vessels.
■When selecting the installation site, use the supplied paper
pattern for installation.
■Do not install accessories on the casing directly. Drilling holes in the
casing may damage electrical wires and consequently cause fire.
Accessories
Check if the following accessories are included with your unit.
123546
1x1x8x4x1x1x
78 911121013
1x1x1x1x1x1x1x
1Metal clamp
2Drain hose
3Washer for hanger bracket
4Screw
5Installation guide
6Installation and operation manual
7Insulation for fitting for gas pipe
8Insulation for fitting for liquid pipe
9Large sealing pad
10Medium 1 sealing pad
11Medium 2 sealing pad
12Small sealing pad
13Drain sealing pad
14Paper pattern for installation (upper part of packing)
14
1x
Optional accessories
■There are two types of remote controllers: wired and wireless.
Select a remote controller according to customers request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.
■This indoor unit requires installation of an optional decoration
panel.
Installation and operation manual
1
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
For the following items, take special care during
construction and check after installation is finished
Tick ✓
when
checked
Is the indoor unit fixed firmly?
■
■
■
■
■
■
■
■
■
■
The unit may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling or heating.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the
name plate?
The unit may malfunction or components may burn out.
Are wiring and piping correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded?
Dangerous at electric leakage.
Is the wiring size according to specifications?
The unit may malfunction or components may burn out.
Is nothing blocking the air outlet or inlet of either the indoor or
outdoor units?
It may result in insufficient cooling or heating.
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system might not be clear.
• When installing the wireless remote controller kit, the distance
between wireless remote controller and indoor unit might be
shorter if there are fluorescent lights who are electrically started
in the room. The indoor unit must be installed as far as possible
away from fluorescent lights.
2Ceiling height
This indoor unit may be installed on ceilings up to 3.5 m in height
(for 125 units: 4.2 m). However, it becomes necessary to make
field settings by the remote controller when installing the unit at
a height over 2.7 m (for 125 units: 3.2 m). To avoid accidental
touching, it is recommended to install the unit higher than 2.5 m.
Refer to "Field setting" on page 7 and to the decoration panel
installation manual.
3Air flow directions
Select the air flow directions best suited to the room and point of
installation. (For air discharge in 2 or 3 directions, it is necessary
to make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to "Field setting" on page 7.) (See
figure 1 ( = air flow direction))
1All round air discharge
2Air discharge in 4 directions
3Air discharge in 3 directions
4Air discharge in 2 directions
Notes to the installer
■Read this manual carefully to ensure correct installation. Be sure
to instruct the customer how to properly operate the system and
show him/her the enclosed operation manual.
■Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.
SELECTINGINSTALLATIONSITE
When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 mm thickness,
polyethylene foam).
For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 2 or 3
directions.
1Select an installation site where the following conditions
are fulfilled and that meets your customer's approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate water can be properly drained.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service can be
ensured.
• Where there is no risk of flammable gas leaking.
• Where piping between indoor and outdoor units is possible within
the allowable limit. (Refer to the installation manual of the outdoor
unit.)
• This is a class A product. In a domestic environment this product
may cause radio interference in which case the user may be
required to take adequate measures.
•Keep indoor unit, outdoor unit, inter unit wiring and remote
controller at least 1 meter away from televisions and radios. This
is to prevent image interference and noise in those electrical
appliances.
(Noise may be generated depending on the conditions under
which the electric wave is generated, even if 1 meter is kept.)
NOTE
Air flow directions as shown in figure 1 merely
serve as examples of possible air flow directions.
4Use suspension bolts for installation. Check whether the
ceiling is strong enough to support the weight of the indoor
unit. If there is a risk, reinforce the ceiling before installing
the unit.
(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see figure 2 ( = air flow
direction)
1Air discharge
2Air inlet
NOTE
Leave 200 mm or more space where marked with *; on
sides where the air outlet is closed.
ModelH
FXFQ20~63≥214
FXFQ80+100≥256
FXFQ125≥298
PREPARATIONSBEFOREINSTALLATION
1. Relation of ceiling opening to unit and suspension bolt
position.
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
Installation and operation manual
2
■Use the installation guide (delivered with the unit) for exact
vertical positioning of the unit.
Apply the short side
of the installation guide in case of
normal installation
Apply the long side
of the installation guide in case of
installation with fresh air intake kit
INDOORUNITINSTALLATION
When installing optional accessories (except for the decoration
panel), read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed. However, for existing
ceilings, install fresh air intake kit before installing the unit.
1. Install the indoor unit temporarily.
• Attach the hanger bracket to the suspension bolt. Be sure to fix it
securely by using a nut and washer from the upper and lower
sides of the hanger bracket.
• Securing the hanger bracket see figure 6.
1212
1Lower ceiling surface
2Underside of the unit
■Installation is possible when opening dimensions are as follows.
When installing the unit within the frame for fixing ceiling
materials. (See figure 4)
1Dimensions inside frame
2Opening dimension inside the frame for ceiling
3Frame
4Ceiling material
5Ceiling opening dimension
6Ceiling-panel overlapping dimension
NOTE
Installation is possible with a ceiling dimension of
910 mm (marked with *). However, to achieve a ceilingpanel overlapping dimension of 20 mm, the spacing
between the ceiling and the unit should be 35 mm or
less. If the spacing between ceiling and the unit is over
35 mm, attach ceiling material to the part or recover
the ceiling.
2. Make the ceiling opening needed for installation where
applicable. (For existing ceilings.)
• Refer to the paper pattern for installation for the ceiling opening
dimensions.
• Create the ceiling opening required for installation. From the side
of the opening to the casing outlet, implement the refrigerant and
drain piping and wiring for remote controller (unnecessary for
wireless type) and indoor-outdoor unit casing outlet. Refer to
each piping or wiring section.
• After making an opening in the ceiling, it may be necessary to
reinforce ceiling beams to keep the ceiling level and to prevent it
from vibrating. Consult the builder for details.
3.Install the suspension bolts. (use either a W3/8 or M10 size bolt.)
Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce the
ceiling in order to bear the weight of the unit. Adjust clearance from
the ceiling before proceeding further.
Installation example see figure 5.
1Nut (field supplied)
2Washer (supplied with the unit)
3Hanger bracket
4Double nut (field supply, tighten)
2. Fix the paper pattern for installation. (For new ceilings
only.)
• The paper pattern for installation corresponds with the measure-
ments of the ceiling opening. Consult the builder for details.
• The centre of the ceiling opening is indicated on the paper
pattern for installation. The centre of the unit is indicated on the
unit casing and on the paper pattern for installation.
• After removing the packaging material from the paper pattern for
installation, attach the paper pattern for installation to the unit
with the attached screws as shown in figure 8.
1Paper pattern for installation
2Centre of the ceiling opening
3Centre of the unit
4Screws (supplied with the unit)
• Adjust the height of the unit until it matches the indication in
figure 8.
3. Adjust the unit to the right position for installation.
(Refer to "Preparations before installation" on page 2.)
4. Check if the unit is horizontally levelled.
• Do not install the unit tilted. The indoor unit is equipped with a
built-in drain pump and float switch. (If the unit is tilted against the
direction of the condensate flow (the drain piping side is raised),
the float switch may malfunction and cause water to drip.)
• Check if the unit is levelled at all four corners with a water level or
a water-filled vinyl tube as shown in figure 12.
1Water level
2Vinyl tube
5. Remove the paper pattern for installation. (For new ceilings
only.)
All the above parts are field supplied.
For other installation than standard installation, contact
your dealer for details.
Installation and operation manual
3
For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.
Execute heat insulation work completely on both sides of the gas
piping and the liquid piping. Otherwise, this can sometimes result in
water leakage.
Before rigging tubes, check which type of refrigerant is used.
All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.
■Use a pipe cutter and flare suitable for the used refrigerant.
■To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.
■Use copper alloy seamless pipes (ISO 1337).
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
■The outdoor unit is charged with refrigerant.
C
356
6
C
356
6
■To prevent water leakage, execute heat insulation work
completely on both sides of the gas and liquid piping. When
using a heat pump, the temperature of the gas piping can reach
up to approximately 120°C, use insulation which is sufficiently
heat resistant.
■Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.
Piping insulation procedure
Gas pipingLiquid piping
1Torque wrench
2Spanner
3Piping union
4Flare nut
12
3
4
■Do not mix anything other than the specified refrigerant, such as
air, etc..., inside the refrigerant circuit.
■Refer to Ta ble 1 for the dimensions of flare nut spaces and the
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)
■When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly.
Coat here with ether oil or ester oil
■If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a fire.
■Make sure there is no refrigerant gas leak. A toxic gas may be
released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.
■Finally, insulate as shown in the figure below (use the supplied
accessory parts)
1Piping insulation material (field supply)
2Flare nut connection
3Insulation for fitting (delivered with the unit)
4Piping insulation material (main unit)
5Main unit
6Clamp (field supply)
7Medium 1 sealing pad for gas piping (delivered with the unit)
Medium 2 sealing pad for liquid piping (delivered with the unit)
ATurn seams up
BAttach to base
CTighten the part other than the piping insulation material
DWrap over from the base of the unit to the top of the flare nut
connection
For local insulation, be sure to insulate local piping all
the way into the pipe connections inside the unit.
Exposed piping may cause condensation or may
cause burns when touched.
Cautions for brazing
■Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.
■When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).
12345
4
5
3
5
1
2
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
1Liquid pipe
2Gas pipe
3Insulation for fitting for liquid
pipe
4Insulation for fitting for gas
pipe
5Clamps
(use 2 clamps per insulation)
6
1Refrigerant piping
2Part to be brazed
3Taping
4Hands valve
5Pressure-reducing valve
6Nitrogen
6
Installation and operation manual
4
DRAINPIPINGWORK
m
Installation of drain piping
Install the drain piping as shown in figure and take measures against
condensation. Improperly rigged piping could lead to leaks and
eventually wet furniture and belongings.
■How to perform piping (See figure 7)
1Ceiling slab
2Hanger bracket
3Adjustable range
4Drain raising pipe (nominal diameter of vinyl pipe = 25 mm)
5Drain hose (supplied with the unit)
6Clamp metal (supplied with the unit)
1-1.5
1Hanging bar
■Install the drain pipes.
-Keep piping as short as possible and slope it downwards at a
gradient of at least 1/100 so that air may not remain trapped
inside the pipe.
-Keep pipe size equal to or greater than that of the connecting
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer
diameter).
- Push the supplied drain hose as far as possible over the
drain socket.
21
1Drain socket (attached to the unit)
2Drain hose (supplied with the unit)
- Tighten the metal clamp until the screw head is less than
4 mm from the metal clamp part as indicated in the
illustration.
- After the testing of drain piping is finished, attach the drain
sealing pad (4) supplied with the unit over the uncovered part
of the drain socket (= between drain hose and unit body).
435
1
4 mm
1Drain socket (attached to the unit)
2Drain hose (supplied with the unit)
3Metal clamp (supplied with the unit)
4Drain sealing pad (supplied with the unit)
5Large sealing pad (supplied with the unit)
6Drain piping (field supply)
-Wrap the supplied large sealing pad over the metal clamp
and drain hose to insulate and fix it with clamps.
- Insulate the complete drain piping inside the building (field
supply).
- If the drain hose cannot be sufficiently set on a slope, fit the
hose with drain raising piping (field supply).
Installation and operation manual
5
A-A'
1Connect the drain hose to the drain raising pipes, and insulate
them.
2Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.
■Precautions
- Install the drain raising pipes at a height of less than 675 mm.
- Install the drain raising pipes at a right angle to the indoor
unit and no more than 300 mm from the unit.
-To prevent air bubbles, install the drain hose level or slightly
tilted up (≤75 mm).
NOTE
The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.
To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.
When unifying multiple drain pipes, install the
pipes as shown in figure 9. Select converging
drain pipes whose gauge is suitable for the
operating capacity of the unit.
1T-joint converging drain pipes
Testing of drain piping
After piping work is finished, check if drainage flows smoothly.
■Add approximately 1 l of water gradually through the air
discharge outlet.
Method of adding water. See figure 11.
1Plastic watering can (tube should be about 100 mm long)
2Service drain outlet (with rubber plug) (Use this outlet to
Check drainage flow during COOL running, explained in "Test
operation" on page 9.
■ In case electric wiring work is not finished
- Remove the control box lid. Connect the power supply
firmly to the terminal. See figure 10.
- Reattach the control box lid and turn on the power.
- Do not touch the drain pump. It may result in electric
shock.
1Control box lid
2Power supply wiring
3Power supply terminal block
4Clamp (field supply)
5Unit transmission wiring
6Te r minal block for transmission wiring
7Opening for cables
8Wiring diagram label
(on the back side of the control box lid)
9Earth cable
10Remote controller wiring
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
Inter unit wiring terminal block (3)
N
L
NOTE
For details, refer to "Electrical data".
Specifications for field supplied fuses and wire
- Confirm the drain operation looking at the drain socket.
- After checking the drainage flow, turn off the power,
remove the control box lid and disconnect the power
supply from the terminal again.
- Reattach the control box lid.
ELECTRICWIRINGWORK
General instructions
■All field supplied parts and materials and electric works must
conform to local codes.
■Use copper wire only.
■Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".
■All wiring must be performed by an authorized electrician.
■Attach the earth leakage circuit breaker and fuse to the power
supply line.
■A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
■This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal block wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.
■Be sure to ground the air conditioner.
■Do not connect the ground wire to:
- gas pipes: might cause explosions or fire if gas leaks.
- telephone ground wires or lightning rods: might cause
abnormally high electric potential in the ground during
lightning storms.
- plumbing pipes: no grounding effect if hard vinyl piping is
MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)
min. 198-max. 264 /
min. 198-max. 242
Power supply wiring
ModelField fusesWireSize
FXFQ20~12516 AH05VV-U3GLocal codes
Transmission wiring
ModelWireSize
FXFQ20~125Sheathed wire (2)
NOTE
■For details, refer to "Wiring example" on page 7.
0.75-1.25 mm
2
■Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:
• Outdoor unit - indoor unit: max. 1000 m
(total wiring length: 2000 m)
• Indoor unit - remote controller: max 500 m
WIRINGEXAMPLEANDHOWTOSETTHE
REMOTECONTROLLER
How to connect wiring (See figure 10)
■Power supply wiring
Remove the control box lid (1) and connect the wires to the
power supply terminal block inside (L, N) and connect the
ground wire to the grounding terminal. While doing this, pull the
wires inside through the hole in the casing and clamp the wires
along with other wires using a clamp as indicated in the figure.
■Unit transmission wiring and remote controller wiring
Remove the control box lid (1) and pull the wires inside through
the hole in the casing and connect to the terminal block for unit
transmission wiring (F1, F2) and remote controller wiring
(P1, P2). Securely fix the wiring using a clamp as indicated in
the figure.
■After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.
■Attach the control box lid.
Precautions
1Observe the notes mentioned below when wiring to the power
supply terminal block.
- Use a round crimp-style terminal for insulation sleeve for
connection to the terminal block for wiring the units. When
none are available, follow the instructions below.
12 3
- Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
- When clamping wiring, use the clamps (delivered with the
unit) to prevent outside pressure being exerted on the wiring
connections. Tie up firmly. When doing the wiring, make sure
the wiring is neat and does not cause the control box to stick
up. Close the cover firmly.
- When connecting wires of the same gauge, connect them
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
Installation and operation manual
6
Complete system example (3 systems)
See figures 13, 14 and 15.
Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. Use torques according to the table below.
Tightening torque (N•m)
Te r minal block for unit transmission and
remote controller
Te r minal block for power supply1.18~1.44
0.79~0.97
- When attaching the control box lid, make sure not to pinch
any wires.
- After all wiring connections are done, fill in any gaps in the
casing wiring holes with putty or insulation material (field
supply) thus to prevent small animals or dirt from entering the
unit from outside and causing short circuits in the control box.
2Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal block of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm2 (Ø1.6).
The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.
3Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.
4Remote controller wiring and unit transmission wiring should be
located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to electrical
noise.
5For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.
NOTE
The customer has the ability to select the remote
controller thermistor.
6Never connect the power supply wiring to the terminal block for
transmission wiring. This mistake could damage the entire system.
7Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire.
WIRINGEXAMPLE
1Outdoor unit
2Indoor unit
3Remote controller (Optional accessories)
4Most downstream indoor unit
5For use with 2 remote controllers
6BS unit
When using 1 remote controller for 1 indoor unit. (Normal
operation) (See figure 13).
For group control or use with 2 remote controllers
(See figure 14).
When including BS unit (See figure 15).
NOTE
It is not necessary to designate indoor unit address
when using group control. The address is automatically set when the power is activated.
Precautions
1. A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
2. For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.
3. Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.
INSTALLATIONOFTHEDECORATIONPANEL
Refer to the installation manual delivered with the decoration panel.
After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop.
FIELDSETTING
Field setting must be made from the remote controller in accordance
with the installation condition.
■Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".
■For setting and operation, refer to the "Field setting" in the
installation manual of the remote controller.
Fit the power supply wiring of each unit with a switch and fuse as
shown in figure 17.
1Power supply
2Main switch
3Power supply wiring
4Unit transmission wiring
5Switch
6Fuse
7BS unit (REYQ only)
8Indoor unit
9Remote controller
Installation and operation manual
7
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
Summary of field settings
Mode
First
No.
code
(Note 1)
No.
Description of setting
Filter contamination
- Heavy/Light
= Setting to define
time between 2 filter
cleaning display
indications. (When
0
contamination is
high, setting can be
changed to half the
time inbetween 2
filter cleaning
display indications.)
Thermostat sensor selection
2
Long-life
filter
10
(20)
Setting for display of time
between 2 filter cleaning display
3
indications
Information to I-manager,
5
I-touch controller
Thermostat sensor in group
6
control
Output signal X1-X2 of the
0
optional KRP1B PCB kit
ON/OFF input from outside
(T1/T2 input) = Setting when
1
forced ON/OFF is to be
operated from outside.
12
(22)
13
(23)
Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected,
Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01,
Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group
Note 7 : More settings for Differential automatic change over temperatures are:
Thermostat differential
changeover = Setting when
2
remote sensor is used.
Fan setting during thermostat
3
OFF at heating operation
Differential automatic
4
changeover
Auto-restart after power failure DisabledEnabled——
5
Setting for air outlet
velocity
This setting is to be
0
changed in function
of ceiling height.
Selection for air flow direction
This setting is to be changed
1
when blocking pad optional kit
is used.
Airflow direction range setting
This setting is to be changed
when range of swing flap
4
movement needs to be
changed.
indoor units can also be set individually.
10-2-02 or 10-2-03 have priority.
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have
priority.
Second code No.054°C
other
models
FXFQ125
only
065°C
076°C
087°C
■When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.
Second code No. (Note 2)
01020304
±2,500 hrs.
Light
Use both the
unit sensor (or
remote sensor if
installed) AND
the remote
controller
sensor.
(See note 5+6)
DisplayDo not display ——
Only unit sensor
value (or remote
sensor value if
installed).
Use unit sensor
only (or remote
sensor if
installed).
(See note 6)
Thermostat-on +
compressor run
Forced OFF
1°C0.5°C——
LLSet speed
0°C1°C2°C
≤2.7 m>2.7 ≤3.0 m>3.0 ≤3.5 m—
≤3.2 m>3.2 ≤3.6 m>3.6 ≤4.2 m—
4-way flow3-way flow2-way flow—
Upper
±1,250 hrs.
Heavy
Use unit sensor
only (or remote
sensor if
installed).
(See note 5+6)
Sensor value as
set by 10-2-0X
or 10-6-0X.
Use both the
unit senor (or
remote sensor if
installed) AND
the remote
controller
sensor. (See
note 4+5+6)
—Operation
ON/OFF
operation
NormalLower—
––
Use remote
controller
sensor only.
(See note 5+6)
——
——
——
OFF
(See note 3)
—
Malfunction
—
3°C
(See
note 7)
Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".
Main/sub changeover
1. Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. (See figure 19)
(The remote controller PC board is attached to the upper part of
the remote controller.)
2. Tu rn the main/sub changeover switch on one of the two remote
controller PC boards to "S". (See figure 20)
(Leave the switch of the other remote controller set to "M".)
1Remote controller PC board
2Factory setting
3Only one remote controller needs to be changed
Computerised control (forced off and on/off operation)
1. Wire specifications and how to perform wiring.
• Connect input from outside to terminals T1 and T2 of the terminal
block (remote controller to transmission wiring).
Wire specificationSheathed vinyl cord or cable (2 wire)
Gauge
0.75-1.25 mm
2
LengthMax. 100 m
External terminal
Contact that can ensure the minimum applicable load
of 15 V DC, 1 mA
See figure 18.
1Input A
2. Actuation
• The following table explains "forced off" and "on/off operations" in
response to input A.
Forced offon/off operation
Input "on" stops operation
Input "off" enables control
input off ➜ on: turns on the unit
(impossible by remote controllers)
input on ➜ off: turns off the unit
(by remote controller)
3. How to select forced off and on/off operation
•Turn the power on and then use the remote controller to select
operation.
• Set the remote controller to the field set mode. For details, refer
to the chapter "How to set in the field", in the remote controller
manual.
• When in the field set mode, select mode No. 12, then set the first
code (switch) No. to "1". Then set second code (position) No. to
"01" for forced off and to "02" for on/off operation. (forced off at
factory set.) (See figure 16)
For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
Installation and operation manual
8
TESTOPERATION
Refer to the installation manual of the outdoor unit.
NOTE
The operation lamp of the remote controller will flash when an error
occurs. Check the error code on the liquid crystal display to identify
the trouble. Refer to the installation manual attached to the outdoor
unit or contact your dealer. See figure 22.
1Drain pumping device (built-in) drain water is removed from the
When performing field settings or test operation
without attaching the decoration panel, do not touch
the drain pump. This may cause electric shock.
room during cooling
2Remove the air filter (actions 2 to 4 in the illustration).
Pull the air filter clip on both the bottom left and the right side of
the filter toward you, and detach the filter.
3Clean the air filter. (See figure 23)
Use vacuum cleaner or wash the air filter with water.
When the air filter is very dirty, use soft brush and neutral
detergent.
4Remove water and dry in the shade.
5Install the air filter back in place (perform actions 2 to 4 in the
illustration in reverse order).
Attach the air filter to the suction grille by hanging it over the
projected portion above the suction grille.
Press the bottom of the air filter against the projections on the
bottom of the grille to snap the air filter into its place.
6Close the suction grille by performing procedure step 1 in
reverse order.
7After turning on the power, press the FILTER SIGN RESET
button.
The "TIME TO CLEAN AIR FILTER" display vanishes.
MAINTENANCE
CAUTION
■Only a qualified service person is allowed to perform
maintenance.
■Before obtaining access to terminal devices, all power supply
circuits must be interrupted.
■To clean the air conditioner, be sure to stop operation and turn
the power switch off.
Otherwise, an electric shock and injury may result.
■Do not wash the air conditioner with water.
Doing so may result in an electric shock.
■Be careful with scaffoldings.
Caution must be exercised when working in high places.
■After a long use, check the unit stand and fitting for damage. If
damaged, the unit may fall and cause injury.
■Do not touch the heat exchanger fins.
The fins are sharp and could result in cutting injuries.
■When cleaning the heat exchanger, be sure to remove the
control box, fan motor, drain pump and float switch. Water or
detergent may deteriorate the insulation of electronic
components and result in burn-out of these components.
How to clean the air filter
Clean the air filter when the display shows "" (TIME TO CLEAN
AIR FILTER).
Increase the frequency of cleaning if the unit is installed in a room
where the air is extremely contaminated.
(As a yardstick for yourself, consider cleaning the filter once a half
year.)
If dirt becomes impossible to clean, change the air filter. (Air filter for
exchange is optional.)
NOTE
1Open the suction grille (See figure 21) (action 1 in the
Installation and operation manual
Do not wash the air filter with hot water of more than
50°C. Doing so may result in discoloration and/or
deformation.
Do not expose the unit to fire. Doing so may result in
burning.
illustration).
Push both levers simultaneously in the direction of the arrow as
indicated in the illustration and carefully lower the grille.
(Identical procedure for closing.)
9
NOTE
Do not remove the air filter except when cleaning.
Unnecessary handling may damage the filter.
How to clean the suction grille
(See figure 21)
1Open the suction grille (action 1 in the illustration).
Refer to procedure step 1 in "How to clean the air filter" on
page 9.
2Detach the suction grille (actions 5 to 6 in the illustration).
First detach the 2 strings from the pins of the decoration panel.
Hold the suction grille open at 45 degrees and lift it upward to
unhook it from the decoration panel.
3Remove the air filter (actions 2 to 4 in the illustration).
Refer to procedure step 2 in "How to clean the air filter" on
page 9.
4Clean the suction grille.
Wash with a soft bristle brush and neutral detergent or water,
and dry thoroughly. See figure 24.
NOTE
When the suction grille is very dirty, use a typical
kitchen cleaner and let it sit for about 10 minutes.
Then, wash it with water.
Do not wash the suction grille with hot water of more
than 50°C. Doing so may result in discoloration and/or
deformation.
5Install the air filter back in place (perform actions 2 to 4 in the
illustration in reverse order).
6Reattach the suction grille by performing procedure step 2 in
reverse order (perform actions 5 to 6 in the illustration in reverse
order).
7Close the suction grille by performing procedure step 1 in
reverse order.
How to clean the air outlet and outside panels
■Clean with a soft cloth.
■When it is difficult to remove stains, use water or neutral
detergent.
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B
NOTE
Do not use gasoline, benzene, thinner, polishing
powder, liquid insecticide. It may cause discoloring or
warping.
Do not let the indoor unit get wet. It may cause an
electric shock or a fire.
Do not scrub firmly when washing the blade with water.
The surface sealing may peel off.
Do not use water or air of 50°C or higher for cleaning
air filters and outside panels.
DISPOSALREQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
NOTES
FXFQ20~125P7VEB
VRV System air conditioners
4PW31578-1B