Dahua SD42C Series Installation Manual

Page 1
4-inch Intelligent Speed Dome Installation Manual
Version 1.1.2
Page 2
Table of Contents
1 INSTALLATION PREPARATION ....................................................................... 1
1.1 Basic Requirements ................................................................................................................. 1
1.2 Safety Check ............................................................................................................................. 1
1.3 Cable Requirements ................................................................................................................ 1
1.3.1 Video Cable Requirements ................................................................................................. 1
1.3.2 Power Supply Cable Requirements ................................................................................... 1
2 SPEED DOME INSTALLATION ......................................................................... 3
2.1 Check Accessories .................................................................................................................. 3
2.2 Open Device ............................................................................................................................. 3
2.3 Initial Setup ............................................................................................................................... 3
2.4 DIP Switch Setup ...................................................................................................................... 4
2.4.1 DIP Switch Location and Function .................................................................................... 4
2.4.2 DIP Switch Setup ................................................................................................................. 5
2.4.3 Address Setup ..................................................................................................................... 5
2.4.4 Baud Rate and Parity Setup................................................................................................ 5
2.4.5 Terminal Matching Resistance Setup ................................................................................ 6
2.5 Reset and SD Card Installation (Network Speed Dome) ...................................................... 7
3 CEILING MOUNT ............................................................................................. 10
3.1 Installation Components ....................................................................................................... 10
3.2 Installation Conditions .......................................................................................................... 10
3.3 Installation Steps ................................................................................................................... 10
4 WALL MOUNT .................................................................................................. 13
4.1 Mounting Component ............................................................................................................ 13
4.2 Installation Conditions .......................................................................................................... 13
4.3 Installation Steps ................................................................................................................... 13
5 IN-CEILING MOUNT ......................................................................................... 16
5.1 Mounting Component ............................................................................................................ 16
5.2 Installation Conditions .......................................................................................................... 16
Page 3
ii
5.3 Installation Steps ................................................................................................................... 16
6 APPENDIX THUNDER PROOF AND SURGE PROTECTION
(OUTDOORS) .......................................................................................................... 19
6.1 Lightning Protection (Indoors) ............................................................................................. 19
7 APPENDIX ABOUT RS485 BUS ................................................................. 21
7.1 RS485 Bus Main Feature ....................................................................................................... 21
7.2 RS485 Bus Transmission Distance ...................................................................................... 21
7.3 The Problem in Practical Use ............................................................................................... 21
7.4 RS485 Bus FAQ ...................................................................................................................... 22
8 APPENDIX THE 24V AC WIRE DIAMETER AND TRANSMISSION
DISTANCE RELATION TABLE ............................................................................... 23
9 APPENDIX 12V AC WIRE GAUGE AND TRANSMISSION DISTANCE
RELATION TABLE .................................................................................................. 24
10 APPENDIX V WIRE GAUGE REFERENCE TABLE ........................................ 26
Page 4
iii
Welcome
Thank you for purchasing our speed dome!
Please read the following safeguards and warnings carefully before you install or use the product!
Page 5
iv
Important Safeguards and Warnings
1. Qualified Engineer Needed
The installation engineer or maintenance engineer shall have corresponding CCTV system
installation certificate or maintenance qualification certificate.
The installation engineer or maintenance engineer shall have qualification certificate for work
at height.
The installation engineer or maintenance engineer shall have the basic knowledge and
operation technique for low-voltage cable layout and low-voltage electronic cable connection.
Please read the installation manual carefully and keep it well for future reference,
We are not liable for any problems caused by unauthorized modifications or attempted repair.
2. Lifting Appliance Requirement
Please select the proper speed dome installation mode and use the lifting appliances at the
safety environment.
The lifting appliances shall have the enough capacity to reach the installation height.
The lifting appliances shall have safe performance.
The precaution measures include two types: Warning and Note.
Warning: It is to alert you there is an optional risk of death or series injury!  Note: It is to alert you there is an optional risk of damage or property loss!
Warning
1. All installation and operation here should conform to your local electrical safety codes. We assume no liability or responsibility for all the fires or electrical shock caused by improper handling or installation.
2. Be sure to use all the accessories (such as power adapter) recommended by manufacturer.
3. Do not connect several speed domes to one power adapter. It may result in overheat or fire if it exceeds the rated load.
4. Before you connect the cable, install or uninstall, or begin the daily maintenance work, please turn off the power and unplug the power cable.
5. Please make sure the produce is secure firmly on the wall or the ceiling.
6. Please turn off the power and unplug the power cable, If there is any smoke, disgusting smell, or noise. Please contact your local retailer or customer service centre for help.
7. All the examination and repair work should be done by the qualified service engineers. We are not liable for any problems caused by unauthorized modifications or attempted repair.
Page 6
v
Note
1. Safety Transportation
Heavy stress, violent vibration or water splash are not allowed during transportation, storage
and installation.
This series product must use split type package during the transportation.
We are not liable for any damage or problem resulting from the integrated package during
the transportation.
2. When device is malfunction
Shut down the device and disconnect the power cable immediately if there is smoke, abnormal smell or abnormal function. Please contact your local retailer ASAP.
3. Do not try to dismantle or modify the device
There is risk of personal injury or device damage resulting from opening the shell. Please contact your local retailer if there is internal setup or maintenance requirement.
We are not liable for any problems caused by unauthorized modifications or attempted repair.
4. Do not allow other object falling into the device
Please make sure there is no metal or inflammable, explosive substance in the speed dome. The above mentioned objects in the device may result in fire, short-circuit or damage. Please shut down the device and disconnect the power cable if there is water or liquid falling
into the camera. Please contact your local retailer ASAP.
Please pay attention to the camera. Avoid the sea water or rain to erode the camera.
5. Handle carefully
Do not allow this series product fall down to the ground. Avoid heavy vibration.
6. Installation Environment Requirement
This series speed dome should be installed in a cool, dry place away from direct sunlight,
inflammable, explosive substances and etc.
This series product shall be away from the strong electromagnetism radiant, please keep it
away from wireless power, TV transmitter, transformer and etc.
7. Daily Maintenance
Please use the soft cloth to clean dust on the shell, or you can use soft cloth with cleaning
liquid to clean the shell and then use soft cloth to make it dry.
Do not use gasoline, dope thinner or other chemical material to clean the shell. It may result
in shell transfiguration or paint flake.
Do not allow the plastic or rubber material to touch the shell for a long time. It may result in
paint flake.
Page 7
1
1 Installation Preparation
1.1 Basic Requirements
All installation and operation here should conform to your local electrical safety codes, fire
prevention laws and some related regulations.
Check if all the components are included according to the packing list. Make sure if the application scene of the speed dome conforms to the installation
requirements. Please contact your dealer if you have any questions.
Please use the product according to the operating environment.
1.2 Safety Check
Make sure the installation site has enough space to hold the product and its mounting
components.
Please make sure the ceiling or wall can sustain 8X weight of the speed dome and its
mounting components.
Please make sure the wall is thick enough to install expansion bolts (Users need to purchase
separately).
It needs to guarantee the installation height shall be more than 6m if it is the laser speed
dome.
1.3 Cable Requirements
1.3.1 Video Cable Requirements
75 ohm. Full cable with copper conductor.
95% knitted copper shield.
Please refer to Appendix for RS485 communication cable information.
International Model
Max Transmission Distance (Ft\M)
RG59/U
750Ft (229M)
RG6/U
1,000Ft (305M)
RG11/U
1,500Ft (457M)
Note
The above can be applied to analog speed dome and network speed dome
International Mode
Max Transmission Distance (M\Ft)
SYV-75-3 720P25fps\30fps)500M/1640Ft
720P50fps\60fps)300M/984Ft
1080P25fps\30fps)300M/984Ft
Note
The above can be applied to HDCVI speed dome
1.3.2 Power Supply Cable Requirements
Refer to Appendix Relationship Table Between AC 24V Wire Diameter and Transmission
Distance for AC 24V power supply device.
Page 8
2
Refer to Appendix Relationship Table Between DC 12V Wire Diameter and Transmission
Distance for DC 12V power supply device.
Page 9
3
2 Speed Dome Installation
2.1 Check Accessories
Before installation, please check the accessories one by one according to the packing list. Please make sure all the components listed are included.
2.2 Open Device
Note
This section is for analog speed dome, network speed dome and intelligent tracking speed dome. Open the package and then take out the device. Remove the transparent cover and take out the packing material EPE around the speed dome module. Please remove the paster from the pedestal. See Figure 2-1.
Figure 2-1
2.3 Initial Setup
Address code: 1 Baud rate: 9600 Parity: None
120Ω matched resistance: OFF
Page 10
4
2.4 DIP Switch Setup
2.4.1 DIP Switch Location and Function
The corresponding functions between analog speed dome and HDCVI speed dome are different, which will be separately introduced below.
2.4.1.1 Analog Speed Dome
It is to take ceiling mount speed dome for example. Open the transparent cover of the device and you can see there are two DIP switches on the PTZ, which are used to set speed dome address, baud rate and parity. The location of DIP switch is shown in Figure 2-2.
Figure 2-2
2.4.1.2 HDCVI Speed Dome
It is to take ceiling mount speed dome for example. Open the transparent cover of the device and you can see there are two DIP switches on the PTZ, which are used to set speed dome address, baud rate. The location of DIP switch is shown in Figure 2-3.
Figure 2-3
Page 11
5
2.4.2 DIP Switch Setup
It has to set address number and baud rate before controlling the speed dome, the speed dome will respond to those control commands after these settings are completed.
Note
For wall-mounted speed dome, it has to install back the transparent dome cover component
after taking out EPE and set DIP switch well.
It has to cut off the power and restart the device after related information has been reset,
which is to make new settings valid.
There are two DIP switches on the PTZ which are used to confirm the parameters of speed dome address, baud rate and parity. When the switch is moved to ON as 1, then 1 is the lowest bit and 8 is the highest bit for the address DIP setting; 1 is the lowest bit and 4 is the highest bit for the baud rate and parity DIP setting.
Note
The intelligent speed dome can self-adapt to PELCO-D, PELCO-P and industrial standard protocol, control protocol doesnt need to be set via DIP switch.
2.4.3 Address Setup
The speed dome can use DIP switch to set address number, coding mode adopts binary coding. 1~8 bits are valid bit, the highest address bit is 255, the address label is shown in Figure 2-1, please refer to Figure 2-1 for the address bit setup.
Figure 2-1
Address
1 2 3 4 5 6 7
8
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
2
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
3
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
4
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
5
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
6
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
7
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
8
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
……
…………………………………………………………………
254
OFF
ON
ON
ON
ON
ON
ON
ON
255
ON
ON
ON
ON
ON
ON
ON
ON
Table 2-1
2.4.4 Baud Rate and Parity Setup
The functions which need to be set between analog speed dome and HDCVI speed dome, which will be introduced separately.
2.4.4.1 Analog Speed Dome
It is to set parity and baud rate of the speed dome. 1 and 2 bit is the baud rate setting bit while 3 and 4 bit is the parity setting bit. Please refer to Figure 2-2 for the label, refer to Table 2-2 and Table 2-3 for settings.
Page 12
6
Figure 2-2
1 2 Baud Rate
OFF
OFF
9600bps
ON
OFF
4800bps
OFF
ON
2400bps
ON
ON
1200bps
Table 2-2
3 4 Parity
OFF
OFF
NONE
ON
OFF
EVEN
OFF
ON
ODD
ON
ON
NONE
Table 2-3
2.4.4.2 HDCVI Speed Dome
It is to set baud rate of the speed dome. Bit 1 and 2 is baud rate setting bit. Refer to Figure 2-3 for the label and refer to Table 2-4 for the setting.
Figure 2-3
1 2 Baud Rate
OFF
OFF
9600bps
ON
OFF
4800bps
OFF
ON
2400bps
ON
ON
1200bps
Table 2-4
2.4.5 Terminal Matching Resistance Setup
It is the connection mode of device terminal 120Ω resistance, terminal resistance 120Ω is
already equipped on the power panel, there are two connection modes, which is shown in Figure 2-4.
Page 13
7
Figure 2-4
Refer to Figure 2-5 for the default connection mode, at this moment, the jumper cap on the
power board is connected to the location 2~3 of the socket and 120Ω resistance hasn’t been
connected yet.
Figure 2-5
It needs to plug out the jumper cap from 2~3 location when it needs to connect to 120Ω
resistance, and then connect to the location of 1~2. In this case, 120Ω resistance is connected to the circuit, which is shown in Figure 2-6.
Figure 2-6
2.5 Reset and SD Card Installation (Network Speed Dome)
You can see that the reset button is located on the PTZ mainboard (shown in Figure 2-7 and Figure 2-8) after opening the device. The reset button is used for network system reset.
Page 14
8
Figure 2-7
Figure 2-8
The SD card of speed dome has to be installed on the camera module, which is shown in Figure 2-9. It is used for data storage.
Page 15
9
Figure 2-9
Note
Please contact our technical support if you have any confusion.
Page 16
10
3 Ceiling Mount
3.1 Installation Components
The ceiling mount installation component is shown as in Figure 3-1.
Figure 3-1
3.2 Installation Conditions
The ceiling-mounted speed dome can be installed in the hard construction wall in the indoor environments. Before the installation, please make sure:
The wall is thick enough to install the expansion bolt. The ceiling can sustain at least 8x weight of the speed dome.
3.3 Installation Steps
There are two methods of cable outlet for ceiling mount:
Do not dig holes on the ceiling; pull the cable through side cable exit of the speed dome. Dig holes on the ceiling; pull the cable through inside the ceiling.
Step 1
Confirm mounting position and cable outlet mode. Use the ceiling installation position map to dig holes on the ceiling and then put the four plastic expansion bolts into the holes you just dug.
Step 2
Page 17
11
As it is shown in Figure 3-2, place the cable well according to the cable outlet mode. Connect the corresponding power, video output, RS-485 control cable, alarm input and output port (according to requirement), and then use insulated rubber tape to twine the cable connector well to make it waterproof.
Note
The video port is covered with heat-shrinkable tube with high shrinkage ratio, it needs to
heat and shrink the tubes on both sides after the video port is well connected, which is to make sure the video port is moistureproof and waterproof.
The step can be applied to ceiling-mounted, wall-mounted and in-ceiling speed dome.
Figure 3-2
Step 3
Use four screws together with insulated cover to fix the ceiling-mounted speed dome pedestal component onto the ceiling, screws shall be twisted into the expansion bolts which have been set.
Step 4
AS it is shown in Figure 3-3, line up the arrow symbol on the speed dome external enclosure to the bar symbol of the pedestal. Use three screws (provided) to secure the external enclosure on the pedestal and fix firmly.
Page 18
12
Figure 3-3
Page 19
13
4 Wall Mount
4.1 Mounting Component
The wall-mounted bracket and outdoor speed dome is shown as in Figure 4-1.
Figure 4-1
4.2 Installation Conditions
The wall-mounted speed dome can be installed in the hard construction wall in both indoor and outdoor environments. Before the installation, please make sure:
The wall is thick enough to install the expansion bolt. The wall can sustain at least 8X weight of the speed dome and bracket.
4.3 Installation Steps
Step 1
Dig a hole of 50mm diameter for cable exit in the mounting wall where the speed dome will be installed.
Step 2
As it is shown in Figure 4-1, twist the adapter block into the internal thread of the wall-mounted bracket, until it reaches the end and then fix the set screw firmly.
Page 20
14
Figure 4-1
Step 3
Pull the composite cable through the adapter block and pull it out of the other end of the wall­mounted bracket. Line up the tab on the top of the external enclosure to the internal hole of the adapter block and then push it to the end, and then tighten three screws of the adapter block firmly. Please note this step is very important. Please make sure the screws are firm, otherwise, it may result in falling risk of the intelligent speed dome.
Step 4
Take the mounting hole on the bottom of wall-mounted bracket (align the bracket cable outlet hole with the circular hole on the wall), draw the punching position on the wall and dig holes, then bury the expansion bolts into the holes you just dug.
Step 5
Connect the composition cable and then pull it through the hole in the wall. Use four hex screws and flat washer to fix the wall-mounted bracket on the wall where the expansion bolts have been inserted. Refer to Figure 4-2 for more details. So far, the speed dome installation has been completed, which is shown in Figure 4-3.
Page 21
15
Figure 4-2
Figure 4-3
Page 22
16
5 In-ceiling Mount
5.1 Mounting Component
The in-ceiling bracket and speed dome body is shown as below. See Figure 5-1.
Figure 5-1
5.2 Installation Conditions
The in-ceiling speed dome can be installed in the hard construction ceiling in indoor environment. Before the installation, please make sure:
The thickness of ceiling shall be between 10mm and 40mm. The ceiling can sustain at least 8X weight of the speed dome and bracket.
5.3 Installation Steps
Step 1
As it is shown in Figure 5-2, it is to paste the in-ceiling installation position map after the mounting location has been confirmed, and then take it as template to draw punching position on the ceiling and dig holes.
Page 23
17
Figure 5-2
Step 2
As it is shown in Figure 5-3, Connect the composition cable and then put the cable into the hole you just dug. Push the in-ceiling bracket and dome body to the hole you just dug, twist the set screw to tighten the hanging board firmly.
Figure 5-3
Step 3
As it is shown in Figure 5-4, use three screws to fix the in-ceiling decoration enclosure component on the in-ceiling bracket components and tighten them firmly. See Figure 5-5.
Page 24
18
Figure 5-4
Figure 5-5
Page 25
19
6 APPENDIX Ⅰ THUNDER PROOF AND SURGE
PROTECTION (Outdoors)
This series speed dome adopts TVS lighting protection technology. It can effectively prevent damages from various pulse signals below 6000V, such as sudden lighting and surge. While maintaining your local electrical safety code, you still need to take necessary precaution measures when installing the speed dome in the outdoor environment.
The distance between the signal transmission cable and high-voltage device (or high-voltage
cable) shall be at least 50 meters.
Outdoor cable layout shall go under the penthouse if possible. For vast land, please use sealing steel tube under the land to implement cable layout and
connects one point to the earth. Open floor cable layout is forbidden.
In area of strong thunderstorm hit or near high sensitive voltage (such as near high-voltage
transformer substation), you need to install additional high-power thunder protection device or lightning rod.
The thunder protection and earth of the outdoor device and cable shall be considered in the
building whole thunder protection and conform to your local national or industry standard.
System shall adopt equal-potential wiring. The earth device shall meet anti-jamming and at
the same time conforms to your local electrical safety code. The earth device shall not short circuit to N (neutral) line of high voltage power grid or mixed with other wires. When connect
the system to the earth alone, the earth resistance shall not be more than 4Ω and earth
cable cross-sectional area shall be no less than 25 mm². See Figure 6-1
Figure 6-1
6.1 Lightning Protection (Indoors)
Page 26
20
The yellow and green GND wire or GND screw of the speed dome should be reliably connected by several strands of copper wire with no less than 25mm²and indoor equipotential GND terminal. Please refer to Figure 6-2 for lightningproof installation mode.
Figure 6-2
Page 27
21
7 APPENDIX ABOUT RS485 BUS
7.1 RS485 Bus Main Feature
RS485 is semi duplex communication cable of impedance 120Ω. Its max load amount is 32 effective loads (including main control device and devices to be charged).
7.2 RS485 Bus Transmission Distance
When we take 0.56mm (24AWG) twisted-pair as communication cable, the max transmission distance (theoretically) are listed below (according to different baud rates).
In the following situations, the max transmission distance shall become shorter accordingly:
The communication cable is a little bit thin; The surrounding environment has strong electromagnetic interference; There are too much devices connected to the RS485 bus;
And vice versa, the max transmission distance shall become longer.
7.3 The Problem in Practical Use
In practical usage, we usually adopt star type connection. The terminal resistance shall connect to the furthest two devices (Such as device 1# and device 15# in Figure 7-1 ). But this connection way does not conform to RS485 Bus standard. When the distances between devices are too long, the signal reflection occurs and anti-jamming decreases, thus the signal reliability becomes very low. You can see speed dome is not under control or speed dome is running automatically and cannot stop.
Figure 7-1
In this situation, we recommend RS485 distributor. This device can turn star type connection into the connection that conforms to RS485 bus industry standard, which can avoid the above mentioned problems and enhance communication reliability. See Figure 7-2.
Baud Rate
Max Distance
2400 BPS
1800M
4800 BPS
1200M
9600 BPS
800M
Page 28
22
Figure 7-2
7.4 RS485 Bus FAQ
Phenomenon
Possible Reasons
Solution
Speed dome can run self­diagnosis but I cannot control it.
Host address(baud rate) and
speed dome address(baud rate) are not match;
Positive and negative end of
RS485 Bus are misconnected;
Connection cable is loose RS485 Bus connection are cut
off;
Modify host or speed dome setup Switch RS485 positive end and
negative end
Fix connection cable firmly Replace RS485 Bus.
I can control the speed dome but is not smooth
RS485 Bus connection are not
good
One RS485 bus is off The distance between host and
speed dome is too far
Parallel connected too much
speed domes.
Connect RS 485 Bus again Replace RS485 Bus Add terminal matching resistance Add RS485 distributor.
Page 29
23
8 APPENDIX THE 24V AC WIRE DIAMETER AND
TRANSMISSION DISTANCE RELATION TABLE
It is to recommend max transmission distance when the cable diameter is fixed and the 24V AC voltage loss rate is below 10%. For the AC device, the max permission voltage power consumption is 10%. For example, when a device of rated power 20W installed 141 inches (42m) away from the transformer, then the min cable diameter needed is 0.8000mm.
mm
Feetm w
0.8000
1.000
1.250
2.000 5
488.52 148.90
763.31 232.66
1192.67 363.53
3053.25 930.63
10
244.26 74.45
381.66 116.33
596.34 181.76
1526.62 465.31
15
162.84 49.63
254.44 77.55
397.56 121.18
1017.75 310.21
20
122.13 37.23
190.83 58.16
298.17 90.88
763.31 232.66
25
97.70 29.78
152.66 46.53
238.53 72.71
610.65 186.13
30
81.42 24.82
127.22 38.78
198.78 60.59
508.87 155.10
35
69.79 21.27
109.04 33.24
170.38 51.93
436.18 132.95
40
61.06 18.61
95.41 29.08
149.08 45.44
381.66 116.33
45
54.28 16.54
84.81 25.85
132.52 40.39
339.25 103.40
50
48.85 14.89
76.33 23.27
119.27 36.35
305.32 93.06
55
44.41 13.54
69.39 21.15
108.42 33.05
277.57 84.60
60
40.71 12.41
63.61 19.39
99.39 30.29
254.44 77.55
65
37.58 11.45
58.72 17.90
91.74 27.96
234.87 71.59
70
34.89 10.64
54.52 16.62
85.19 25.97
218.09 66.47
75
32.57 9.93
50.89 15.51
79.51 24.24
203.55 62.04
80
30.53 9.31
47.71 14.54
74.54 22.72
190.83 58.16
85
28.74 8.76
44.90 13.69
70.16 21.38
179.60 54.74
90
27.14 8.27
42.41 12.93
66.26 20.20
169.62 51.70
95
25.71 7.84
40.17 12.25
62.77 19.13
160.70 48.98
100
24.43 7.45
38.17 11.63
59.63 18.18
152.66 46.53
Page 30
24
9 APPENDIX Ⅳ12V AC WIRE GAUGE AND
TRANSMISSION DISTANCE RELATION TABLE
It is to recommend max transmission distance when the cable diameter is fixed and the DC 12V voltage loss rate is lower than 10%. For the DC power supply devices, the max allowed voltage
loss rate is 10%. The cable listed in the table below is copper wire (the resistivity of copper is ρ
=0.0175Ω*mm²/m).
Feet (m) mm
w
0.8000
1.000
1.250
2.000 5
122.1337.23
190.83 58.16
298.17 90.88
763.31 232.66
10
61.0618.61
95.4129.08
149.08 45.44
381.66 116.33
15
40.7112.41
63.6119.39
99.3930.29
254.44 77.55
20
30.539.31
47.7114.54
74.5422.72
190.83 58.16
25
24.437.45
38.1711.63
59.6318.18
152.66 46.53
30
20.356.20
31.809.69
49.6915.15
127.22 38.78
35
17.455.32
27.268.31
42.6012.98
109.04 33.24
40
15.274.65
23.857.27
37.2711.36
95.41 29.08
45
13.574.14
21.206.46
33.1310.10
84.81 28.85
50
12.213.72
19.085.82
29.829.09
76.33 23.27
55
11.103.38
17.355.29
27.118.26
69.39 21.15
60
10.183.10
15.904.85
24.857.57
63.61 19.39
65
9.392.86
14.684.47
22.946.99
58.72 17.90
70
8.722.66
13.634.15
21.306.49
54.52 16.62
75
8.142.48
12.723.88
19.886.06
50.89 15.51
80
7.632.33
11.933.64
18.645.68
47.71 14.54
85
7.182.19
11.233.42
17.545.35
44.90 13.69
90
6.782.07
10.603.23
16.565.05
42.41 12.93
95
6.431.96
10.043.06
15.694.78
40.17 12.25
100
6.111.86
9.542.91
14.914.54
38.17
Page 31
25
Feet (m) mm
w
0.8000
1.000
1.250
2.000 11.63
Page 32
26
10 APPENDIX V WIRE GAUGE REFERENCE TABLE
Metric bare wire
diameter
mm
AWG
SWG
Bare wire cross
section
mm2)
0.050
43
47
0.00196
0.060
42
46
0.00283
0.070
41
45
0.00385
0.080
40
44
0.00503
0.090
39
43
0.00636
0.100
38
42
0.00785
0.110
37
41
0.00950
0.130
36
39
0.01327
0.140
35
0.01539
0.160
34
37
0.02011
0.180
33
0.02545
0.200
32
35
0.03142
0.230
31
0.04115
0.250
30
33
0.04909
0.290
29
31
0.06605
0.330
28
30
0.08553
0.350
27
29
0.09621
0.400
26
28
0.1257
0.450
25
0.1602
0.560
24
24
0.2463
0.600
23
23
0.2827
0.710
22
22
0.3958
0.750
21
0.4417
0.800
20
21
0.5027
0.900
19
20
0.6362
1.000
18
19
0.7854
1.250
16
18
1.2266
1.500
15
1.7663
2.000
12
14
3.1420
2.500
4.9080
3.000
7.0683
Note
This manual is for reference only. Slight difference may be found in the user interface. All the designs and software here are subject to change without prior written notice. All trademarks and registered trademarks are the properties of their respective owners. If there is any uncertainty or controversy, please refer to the final explanation of us. Please visit our website or contact your local service engineer for more information.
Loading...