Daewoo DMB-1822LH, DMB-1832LH, DMB-2122LH, DMB-2112LH User Manual

CONTENTS
1. SPECIFICATIONS.....................................................................................................2
2. CONFIGURATION.....................................................................................................4
3. OUTLINE AND DIMENSIONS .................................................................................5
4. INSTALLATION SECTION......................................................................................10
5. OPERATION ............................................................................................................26
6. WIRING DIAGRAM .................................................................................................41
7. REFRIGERANT CYCLE.........................................................................................45
8. CONTROL BLOCK DIAGRAM...............................................................................46
10. PCB DRIVING DESCRIPTION ............................................................................54
11. KEY COMPONENTS OF ELECTRONIC CIRCUIT ...........................................76
12. DISASSEMBLY INSTRUCTIONS........................................................................80
1) Indoor Unit ........................................................................................................80
2) Outdoor Unit .....................................................................................................83
3) Exploded Diagram (Indoor Unit)......................................................................84
4) Exploded Diagram (Outdoor Unit)...................................................................92
5) Control Box Assembly......................................................................................96
6) Control Panel Assembly.................................................................................102
Contents
2
1. SPECIFICA
TIONS
MODEL
DMB-1822/1832LH (9K) DMB-1822/1832LH (9K) DMB-1822/1832LH (9K+9K)
Function
Class T
Power AC 220-240V, 50Hz
Capacity
Dehumidification 1.15 1.15 2.3
Running Current
Power Input
Starting Current 49 A
Type Rotary (DAEWOO : China)
Model RBB095M011
Capacitor 25uF/370VAC 25uF/370VAC
Type
Capacitor
Motor Model Number
Control Capillary
Charge Quality 750 g 750 g
Type Flare
OD (Liquid/Suction) 1/4" (6.35mm) / 3/8" (9.52mm)
Indoor Unit Dimension (W x H x D) 750 x 245 x 174
Outdoor Unit Dimensions (W x H x D) 800 x 615 x 325
Net Weight
Indoor Unit (kg) 7.00 7.00
Outdoor Unit (kg) 62.0
Electrical
Data
Compressor
Fan
Motor
Refrigerant
(R-22)
Connection
DSB-1822/1832LH
W
Btu/h
l/h
A
W
A
Cooling Heating Cooling Heating Cooling Heating
2637.6
9000
2637.6
9000
2637.6
9000
2637.6
9000
5275.3
18000
5275.3
18000
4.6
990
4.6
990
4.6
990
4.6
990
8.6
1880
8.5
1840
Indoor Unit
Cross flow fan
1.0uF 400VAC
YDK-8-4B(Xiangming)
Outdoor Unit
Propeller
fan
5+25uF 400VAC
A2919BA010(DMI)
Indoor Unit
Cross flow fan
1.0uF 400VAC
YDK-8-4B(Xiangming)
Outdoor Unit
Propeller
fan
5+25uF 400VAC
A2919BA010(DMI)
-
-
-
-
-
-
-
RBB095M011
-
3
MODEL
DMB-2112/2122LH (9K) DMB-2112/2122LH (12K) DMB-2112/2122LH (9K+12K)
Function
Class T
Power AC 220-240V, 50Hz
Capacity
Dehumidification 1.15 2.10 3.25
Running Current
Power Input
Starting Current 49 A
Type Rotary (DAEWOO : China)
Model RCB120M001
Capacitor 25uF/370VAC 25uF/370VAC
Type
Capacitor
Motor Model Number
Control Capillary
Charge Quality 750 g 1150 g
Type Flare
OD (Liquid/Suction) 1/4" (6.35mm) / 3/8" (9.52mm)
Indoor Unit Dimension (W x H x D) 750 x 245 x 174
Outdoor Unit Dimensions (W x H x D) 800 x 615 x 325
Net Weight
Indoor Unit (kg) 7.00 9.3
Outdoor Unit (kg) 65.0
Electrical
Data
Compressor
Fan
Motor
Refrigerant
(R-22)
Connection
DSB-2112/2122LH
W
Btu/h
l/h
A
W
A
Cooling Heating Cooling Heating Cooling Heating
2637.6
9000
2637.6
9000
3516.8
12000
3516.8
12000
6154.4
21000
6154.4
21000
4.6
990
4.6
990
6.0
1300
6.0
1300
10.1
2200
10.1
2200
Indoor Unit
Cross flow fan
1.0uF 400VAC
YDK-8-4B(Xiangming)
Outdoor Unit
Propeller
fan
5+25uF 400VAC
A2919BA010(DMI)
Indoor Unit
Cross flow fan
1.0uF 400VAC
YDK-8-4B/A(Xiangming)
Outdoor Unit
Propeller
fan
5+25uF 400VAC
A2919BA010(DMI)
925 x 285 x 194 (815 x 285 x 195)
RBB095M011
-
-
-
-
-
-
-
-
2. CONFIGURATION
4
* You should individually install and operate each A and B units in DMB-2112LH and DMB-2122LH. * You can exchangeably install and operate each A and B unit in DMB-1822LH and DMB-1832LH.
Model
DMB-1822LH DMB-1832LH
DMB-2112LH DMB-2122LH
Indoor Unit Items
Unit Capacity
A 9000 Btu/h
B 9000 Btu/h
A 12000 Btu/h
B 9000 Btu/h
Reference
A & B units are the same
A & B units are different
A
B
A
B
(DMB-1822LH)
9K
9K
A
B
(DMB-2112LH)
12K
9K
A
B
(DMB-2122LH)
12K
9K
A
B
(DMB-1832LH)
9K
9K
5
750
Plate Mounting
REMOCON
Connecting Pipe
Grille Insert
174
245
REMOTE CONTROLLER
Frame Grille
Body
Plate Mounting
3. OUTLINE AND DIMENSIONS
1
INDOOR UNIT
DMB-1822LH unit A & B, DMB-2112LH unit B (9000 BTU/h)
6
750
750
Plate Mounting
REMOCON
Connecting Pipe
Grille Insert
174
245
REMOTE CONTROLLER
Frame Grille
Body
Plate Mounting
DMB-1832LH unit A & B, DMB-2122LH unit B (9000 BTU/h)
DMB-2112LH unit A (12000BTU/h)
7
REMOCON
Filter - L Filter - R
Grille Insert
Frame Grille
Body
Plate Mounting
Connecting Pipe
Plate Mounting
406
194
285
925
REMOTE CONTROLLER
8
DMB-2122LH unit A (12000BTU/h)
9
2
OUTDOOR UNIT
DMB-1822LH/1832LH/2112LH/2122LH
Inlet
Outlet
Outlet
Foot Cushion
800
Cabinet Front
Service Cover
Service Valve
Cabinet Side
Panel Top
Guide Support
Foot
325
10
This Installation section explains how and where to connect this new air conditioner. Please read make sure all acces­sories are included as shown below and read manual thoroughly. This Installation section is provided to assist the per­son knowledgeable in air conditioner installation and should not be installed by anybody who is not thoroughly familiar with this type of installation. Please contact a professional installer if necessary.
ACCESSORIES SUPPLIED WITH THE UNIT:
COPPER TUBING:
Copper tubing supplied is available at most dealers or A/C shops. Make sure the new copper tubing has the same specifications and diameter as the original copper tubing and is as short as possible.
Note:
The remainders except for No. 2, 7, 11 are contained in the indoor boxes.
BASIC ACCESSORIES
1
2
8
6
7
9
3
10 11
4
No. Description Qty.
1 Wall Bracket 2
2 Outdoor Unit Cover 1
3 Remote Controller
4 Deodorizing Filter
5 Electrostatic Filter
2
2
2
6 Remote Holder 2
No. Description Qty.
7 Foot Cushion 4
8 Concrete Nails 10
9 Remote Holder Screws 6
10 Wall Bracket Screws 16
11
12 Signal connection cord 2
Battery 4
5
12
4. INSTALLATION SECTION
11
OPTIONAL A CCESSORIES
1 2
4
3
5 6
ACCESSORIES NOT SUPPLIED WITH THE UNIT:
No. Description Part No. Qty Material Size Remark
1 Drain Hose Extension 3103200400 2 ID19.6 X 2m PVC Pipe 2 Tape 2TQ1007502 2 PVC 75W X 0.1T X 25m
3 Copper Tubing Extension
3104402600 2
1/4" Copper Tube X L5M
Wrapped with insulator tube
3104402910 2
3/8" Copper Tube X L5M 4 Insulator Plate 3103301010 2 F-US 225 X 120 X 5T 5 Putty 2221040001 2 80g 6 Connection Cord 3112716320 2 3P X 6m 7 Cable tie 3172400500 8 L200 x W4.08
8 Fixture tie mount 3112000300 8 L24.5 x W15.5 x H11.5 x ø6.6 9 Cap wall 3100900600 2 PP
97 8
12
INSTALLATION DIAGRAM
Below is an overview for the connection of the Indoor unit to the Outdoor unit. The pages following will give detailed instructions for full installation. Remember to read the complete Installation section and follow all the safety instructions fully when installing the Indoor and Outdoor units.
OVERVIEW
This appliance must be installed according to national power supply acquirement.
NOTES:
After installation it must be possible for the user to disconnect the power supply plug.
If the AC outlet is a 3-pronged type or other, have an electrician install a new outlet.
Contanct service man when replace the power cord set.
Drain Hose
Ground Wire (Not Supplied)
3/8" side piping
Signal Wire
1/4" side piping
Drain Hose
Wall
Wall Cap
Drain
Hose
Pipes
(Not Supplied)
Signal wire
Wrap with
Tape
Copper
12000 BTU/h
or
9000 BTU/h
(9000BTU/h)
Tubing
At least 30cm
(11.8in) from unit
Maximum Height 7M (21Ft)
Maximum Length 15M (49Ft)
Any tube length between 7 and 15 meters must
be precharged with freon using the following calulation: (Length – 5) x 30 grams
Adding additonal tubing will decrease efficiency
60
cm
23.6 inches
cm
10
cm
3.9 inches
60
23.6 inches
70
cm
27.6 inches
AC Outlet
and Plug
Plug into 220V~240V
AC Outlet
(Not supplied)
10cm (3.95in) from ceiling
30cm (11.8in) from
side wall
30cm (11.8in) from
side wall
10cm (3.95in) from
side wall
10cm (3.95in) from
side wall
Wall
Bracket
Connecting
cable
Connecting cable
(Not supplied)
13
INSTALLATION
1. Determine the type of wall (sheetrock, concrete, etc.) and make sure it is strong enough to hold indoor unit. Select an approximate position for the unit, taking the required distances away from walls/AC outlet into consideration.
INDOOR UNIT
Do not install the unit in an area with direct sunlight, near heat sources (radiator, etc.), or an area where leakage of flammable gas may be expected.
Select a position in the room, high on the wall, where the whole room can be uniformly cooled.
Select a location that can hold the weight of the unit and where the copper tubing, drain hose and Indoor to Outdoor Wire have the shortest distance to the Outdoor unit.
Make sure the Indoor unit is installed at least 10cm (3.95in) away from the top and left side wall and at least 30cm (11.8in) from AC outlet and right side wall (see Overview figure on previous page).
OUTDOOR UNIT
Do not install the unit in an area near heat sources, exhaust fans, or an area where leakage of flammable gas may be expected.
Do not install the unit in a humid, damp or uneven location.
Select a location that is well ventilated .
Leave enough room around the unit for air intake, exhaust
and possible maintenance.
2. Determine if the hole is to be made at the left or right hole location.
10 mm
10 mm
150 mm 60 mm
3. Using drill with hole-cutting attachment or equivalent, cut a hole 65mm (2.56") in diameter. The hole should be made at a slight downward slant to the outdoor side. Measure the thickness from the inside to outside edges and cut a PVC pipe at a slight angle 1/4" shorter than the thickness of the wall and insert pipe in wall.
4. For sheetrock, wooden or similar wall, measure down from the ceiling using a level or tape measure and attach the wall bracket to the wall using 4 screws. If you are not able to line up the holes with the beams, use toggle bolts. Make sure the wall bracket is even and flush against the wall.
Indoor Outdoor
Cut at slight angle
CAUTION
Before making hole, make sure there are no studs, pipes, electrical wiring or conduit directly behind the area to be cut.
For Concrete, or similar type wall, make holes into the wall and insert concrete nails instead of screws.
INST ALLING THE WALL BRACKET :
To install the wall bracket, follow the procedures below. One hole is required for the tubing and may be either on the left or right side.
SELECTING A SITE:
DMB-1812LH (9000BTU/h)
DMB-1812LH (12000BTU/h)
10 mm
10 mm
150 mm 60 mm
9000 Btu/h Class
12000 Btu/h Class
14
INSTALLING THE AC CONNECTION WIRE T O THE INDOOR UNIT FOR A C POWER SUPPLY
The AC Connection wire is used to supply AC from the outdoor unit to the indoor units. To install AC connection wire, follow the procedures below.
NOTE:
This appliance must be installed according to National power supply requirement.
If the supply cord is damaged, it must be replaced by the manufacuturer or its service agent or a similarly
qualified person in order to avoid a hazard.
Make sure the outdoor units AC cord is not connected to AC connection wire.
When connecting wires, make sure they are fully inserted and minimum copper wire is exposed. If they are
not, shorting, overheating, no operation, etc. may occur.
Be sure to comply with local codes on running a wire from the indoor to the outdoor unit.
1. Open the connection cover on the indoor unit to access the connection area. Remove the Connection Cover.
Loosen the screw fixed at the Connection Cover.
Remove the Connection Cover.
2. Fish the AC connection wire from the rear of the indoor unit through the front of the unit. For easier connection, make sure enough wire is pulled through the front. Use the wire as shown below:
3. To connect wires, loosen the screw in the Terminal Block and insert the correct wires like following figure. Connect the Brown wire to the “L” connection,
Yellow/Green wire to the “” connection and the Blue wire to “N” connection.
Screw
Screw (Special screw)
Blue Yellow/Green Brown
L
N
Brown Blue
Yellow/Green
15
4. Connect the wires to the housing and terminals on the control board individually according to the outdoor uint connection.
indoor terminal
Connection
Cable
Connection
Cable
not insert
plug
Unit A
LN
indoor terminal
Unit B
LN
L1 N1
Outdoor terminal
Outdoor
L2 N2
Unit A Unit B
Brn
Y/G Brn Blu Brn Blu Y/G Brn Blu Y/G
Y/G Blu Brn Y/G Blu
LN
Power
Terminals
Signal
++
<INDOOR UNIT (Control Box)><INDOOR UNIT (Control Box)>
(9000 Btu/h) (12000 Btu/h)
Terminals
Signal
++
NOTE: We want you to observe bellow recommended specifications.
Part Name
Power plug Power cable Circuit breaker Connection cable
Recommended specifications
250V 10/16A Flexible, H05RN-F above 2.0mm
2
15A H05RN-F 0.5 or 0.75mm2 x 3P x 6m
16
Left
Tubing
2. Make sure the drain hose and copper tubing are wrapped with the rubber insulation. Using the tape, wrap the AC connection wire, copper tubing and drain hose together.
MOUNTING (INDOOR UNIT)
The Indoor unit must be mounted before connecting the AC connection wire, drain hose and copper tubing. To mount, follow the procedures below:
1. The tubing can be extended in 4 directions as shown below. No cutting is necessary for left/rear and right/rear tubing connections. If using left or right tub­ing connections, remove the plastic area with a hack­saw so pipes can go through.
CAUTION:
Make sure the outdoor units AC cord is not
connected to AC power when performing these procedures.
Be sure to comply with local codes on running a wire from the indoor to the outdoor unit.
DO NOT LET THE AC CONNECTION WIRE COME IN DIRECT CONTACT WITH THE TUBING OR HOSE!
3. Shape the tubing so it can easily go through the hole in the wall. Push the AC connection wire, copper tub­ing and drain hose through the hole in the wall angling downward. Situate the indoor unit on the wall bracket by lifting the indoor unit slightly above the wall bracket and then down so it is securely locked in place.
Wall Bracket
Insert Putty
Drain Hose
CAUTION:
When using the tube reamer, hold the tube downward and make sure no copper scraps fall into the tubing.
2. Make a flare at the end of the copper tube with a flare tool.
Make sure the inside surface and edges are smooth and the sides are uniform length.
1. Cut the copper tube extension to the desired length with a tube cutter. It is highly recommended that 1 foot is added to the requested length. After cutting, debur­ring may be necessary (see below diagram). Perform this with a tube reamer.
BEFORE AFTER
PREPARING THE COPPER TUBING (NOT INCLUDED)
A copper tubing extension (not included) may need to be cut. If this is the case, it will also have to be deburred and flared as shown below:
Flare tool
Flare nut
Connection
pipe
Right Tubing
Right/Rear
Tubing
Left/Rear
Tubing
17
1. Remove the flare nut stoppers from the inside unit. Determine the location of the copper tubing and where the bends will be. Gently bend the copper tub­ing, making sure to use big angles so no crimping will occur. Try to do this on the first try as repeated bend­ing may break or crimp the tubing.
2. Remove the plastic stoppers from the tubing. Connect the large and small copper tubing to the respective extension and rotate the flare nut with your finger until a smooth match is made. Make sure the copper extension has foam rubber (insulation) on it.
Flare Nutcoupler
CONNECTING COPPER TUBES
To connect the copper tubes, follow the procedures below:
NOTE:
When removing the flare nut stopper from the inside unit, confirm Ping, sounds because the mixed gas is charged in the inside unit,
3. Once a smooth match is made, tighten the flare nut using a wrench. Be very careful not to strip the threads or flare nut. Repeat this process for the small and large tubing. When tightening the flare nut, use another wrench to securely hold the coupler from twisting and possibly damaging the tubing.
4. Remove the flare nut stoppers from the outdoor unit’s valves. Connect the larger copper tubing to the larger valve on the outdoor unit. Connect the smaller copper tubing to the smaller valve on the outdoor unit.
5. Perform a leak test on all copper tube connections. To prevent heat loss and damage to walls from conden­sation, the copper tube connections coming from the wall must be insulated. Do this by wrapping foam rub­ber or equivalent around the connection approximate­ly 8mm thick so no copper tubing is exposed.
NOTES:
As with all wiring and hookups on this unit, make sure the AC plug on the the outdoor units are unplugged.
Be very careful not to strip the threads or flare nut.
When insulating the connections, use foam rubber or
equivalent.
1. Connect the drain hose extension to the drain hose coming from the indoor unit by loosing the clamp on the extension using a phillips screwdriver, attaching the hoses together and then tightening the clamp.
2. Run the drain hose, slanted downward, outside. If the drain pipe is exposed indoors, make sure it is thoroughly insulated so condensation does not ruin walls or furniture or come in contact with the AC connection or exten­sion. Also, do not crease or form a trap in the tub­ing.
Wall Bracket
Insert Putty
Drain Hose
CONNECTING THE DRAIN HOSE
To connect the drain hose, follow the procedures below:
18
1. Remove the screw holding on the connection cover. Remove the connection cover on the outdoor unit to access the connection area.
3. Connect the wires to the housing and terminals on the control board individually as the following.
INSTALLING THE AC CONNECTION WIRE TO THE OUTDOOR UNIT FOR AC POWER SUPPLY
The AC connection wire is used to supply AC from the Indoor unit to the Outdoor unit. To install the AC connection wire, follow the procedures below.
2. Route the AC connection wire into the opening on the outdoor unit and through the wire holder. To connect to the wire holder, loosen the screw on the wire hold­er, insert the wires through, then tighten the screw.
NOTES:
Make sure the outdoor units AC cord is not connected to AC power when connecting the indoor/outdoor wire.
When connecting wires, make sure they are fully inserted and minimum copper wire is exposed. If they are not,
shorting, overheating, no operation, etc. may occur.
Be sure to comply with local codes on running a wire from the indoor to the outdoor unit.
Yellow/Green Blue
Brown
indoor terminal
Connection
Cable
Connection
Cable
not insert
plug
Unit A
LN
indoor terminal
Unit B
LN
L1 N1
Outdoor terminal
Outdoor
L2 N2
Unit A Unit B
Brn
Y/G Brn Blu Brn Blu Y/G Brn Blu Y/G
Y/G Blu Brn Y/G Blu
LN
Power
Connection Cover
19
4. To connect wires, loosen the screw in the Terminal Block and insert the correct wires like following figure. Connect the Brown wire to the L connection, the
Yellow/Green wire to the “” connection, the Blue wire to the N connection.
DMB-1822/1832/2112/2122LH
20
CONNECTING SIGNAL WIRES BETWEEN INDOOR UNITS AND OUTDOOR UNIT
The signal wires are used to inter-communicate indoor and outdoors signal, and attached to the indoor unit at first. To install the signal wires to outdoor unit, follow the procedures below.
NOTE:
Make sure the indoor & outdoor units AC cord is not connected to AC power when connecting the signal
wires.
When connecting wires, make sure they are fully inserted and minimum copper wire is exposed. If they are
not, shorting, overheating, no operation, etc. may occur.
Be sure to comply with local codes on running a wire from the indoor to the outdoor unit.
Must be careful to insert signal wire connectors where like color is like color.
1. Remove the screw holding on the connection cover. Remove the connection cover on the outdoor unit to access the connection area.
3. Insert the indoor connector into the outdoor connector from the PCB Board individually as the following.
2. Route the indoor signal wire into the opening on the outdoor unit and through the wire connector, and insert the indoor connector into the outdoor connector.
Connection Cover
Indoor Unit A
White
Unit A
(White)
Unit B
(Red)
Outdoor PCB ASS'Y
White
Red
Red
Indoor Unit B
indoor unit A White – White indoor unit B Red – Red
21
1. Tape the two copper tubes, drain hose (and the electrical wiring if local codes permit) together with the supplied tape. Make sure the electrical wiring does not come in direct contact with the copper tub­ing or drain hose. Approximately 1 foot outside the hole, let the drain hose out and separate from the copper tubing and wiring.
Wall braket
Introduceti chit
Drain hose
2. Begin wrapping from the point the tubing comes out of the outdoor unit and continue to the hole in the wall. Leave no gaps or breaks and cover the entire length of the tubing. As you wrap, overlap the previous turn by half the width of the tape.
TAPING UP THE WIRE/TUBES/HOSE
After running the wire, hose and tubing outside, tape them up as shown below to insulate.
1. Apply the putty to any area on the outside hole that air or rain can get into.
Apply Putty
Here
Tubing
2. After applying putty, insert the wall Cap at Indoor side and Outdoor side.
Wall Bracket
Insert Putty
Wall Cap
(For DS-110R)
Drain Hose
APPLYING PUTTY AND INSERTING WALL CAP
After running the wires and tubing outside, putty should be inserted around the opening on the outside to protect against rain, wind, etc. To apply putty, see below:
Indoor side Wall
Outdoor side
3. Wrap the piping joints with the insulator plate and fas­ten it with vinyl tape.
pipe
Insulator Plate
vinyl tape
4. After wrapping the connection pipe with tape, fasten it to the outside wall with saddles, etc.
Saddle
(Not supplied)
Wall cap
Pipe
Tape
3/8" side piping
Connecting cable
Signal Wire
1/4" side piping
Drain Hose
22
AIR PURGING
Air and moisture remaining in the refrigerant system may create adverse conditions as indicated below:
pressure in the system rises.
operating current rises.
cooling efficiency drops.
moisture in the refrigerant circuit may freeze and block capil
-
lary tubing.
water may lead to corrosion of parts in the refrigerant system. Therefore, the indoor unit and tubing between the indoor and
outdoor unit must be evacuated to remove moisture from the system.
AIR PURGING WITH VA CUUM PUMP (TEST R UN)
Confirm each tube (narrow and wide tubes) between the indoor and outdoor units has been properly connected and all wiring for the test run has been completed. Remove the valve caps from the wide and narrow service valves on the outdoor unit. Note that both narrow and wide tube service valves on the out­door unit are kept closed at this stage (shipping position).
Leak Test
1. With the service valves on the outdoor unit remaining closed, remove the threaded cover on the wide tube service port. (Save for reuse.)
2. Attach a manifold valve (with pressure gauge) and dry nitro­gen gas cylinder to this service port with charge hoses.
CAUTION:
Be sure to use a manifold valve for air purging. If it is not avail
-
able, use a stop valve for this purpose. The Hi knob of the manifold valve must always be kept closed.
3. Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 150 P.S.I.G. Next, test for leaks with liquid soap.
Lo Hi
Pressure Gauge
Manifold Valve
Outdoor Unit
Indoor Unit
Charge Hose
Nitrogen Gas Cylinder (Vertical Position)
Evacuation
1. Attach the charge hose end described in the leak test area to a vacuum pump to evacuate the air remaining at the tubing and indoor unit. Confirm the ÒLoÓ knob of the manifold valve is open. Then, run the vacuum pump. The operation time for evacuation varies with the tubing length and capacity of the pump. The following table shows the amount of time for evacuation:
2. When the desired vacuum is reached, close the ÒLoÓ knob of the manifold valve and stop the vacuum pump.
Finishing the job
1. With a hex wrench, turn the narrow tube service valve stem counter-clockwise to fully open the valve.
2. Turn the wide tube service valve stem counter-clockwise to fully open the valve.
To avoid gas from leaking when removing the charge hose, make sure the wide tube service valve is fully open and
Model
DMB-1822LH
DMB-1832LH
DMB-2112LH
DMB-2122LH
STANDARD
LENGTH(m)
INDOOR
UNIT
Change am't(g)
per 1m
5
A15
15 15 15 15 15
6
15
B A B A B A B
5
5
5
turned all the way out.
3. Loosen the charge hose connected to the wide tube ser
-
vice port slightly to release the pressure, then remove the hose.
4. Replace the threaded cover on the wide tube service port and fasten it securely. This process is very important to prevent gas from leaking from the system.
5. Replace the valve caps at both wide and narrow service valves and fasten them securely.
This completes air purging with a vacuum pump. The air conditioner is now ready to test run..
If tubing length is less than
33 ft. (10 m)
10 min. or more
If tubing length is longer than
33 ft. (10 m)
15 min. or more
Required time for evacuation when 30 gal/h vacuum
pump is used
CAUTION:
CAUTION:
Freon Extra Charge
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the nitrogen gas cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
4. Do a leak test of all joints of the tubing (both indoor and outdoor) and both wide and narrow service valves. Bubbles
indicate a leak. Be sure to wipe off the soap with a clean cloth.
5. After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at
the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Lo Hi
Pressure Gauge
Manifold Valve
Outdoor Unit
Indoor Unit
Charge Hose
Vacuum Pump
23
24
TEST RUN
Check that all tubing and wiring have been completed correctly. Check again that the wide and narrow tube service valves are fully opened. Turn on the power and run the system.
Service Valve Construction
Valve Position Closed
The valve systems of both the wide and narrow tubes are turned all the way in. The unit is shipped from the factory in this position and it is also used for Pump Down and Air Purging.
Valve Position Fully Open
The valve stems of both the wide and narrow tubes are turned all the way out. This is normal operating and Test Run position.
Valve Position Half Open
With the narrow tube valve stem is turned to the halfway-down position. This position is used for pressure measure­ment and gas charging.
CAUTION:
When opening or closing the service valve stem, be sure to use a hex wrench.
PUMP DOWN
Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas. This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure (execute the pump down of the unit A and unit B respectively)
1. Connect a low-pressure gauge manifold hose to the charge port on the wide tube service valve.
2. Open the wide tube service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3. Close the narrow tube service valve (all the way in).
4. Turn on the units operating switch and start the cooling operation.
5. When the low-pressure gauge reading becomes 1 to 0.5 kg/cm2 (14.2 to 7.1 psi), fully close the wide tube valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit.
3-W ay V alve
3-way valve(Liquid Side) 3-way valve(Gas Side)
Works Shaft position Shaft position Service port
Shipping Closed Closed Closed
(with valve cap) (with valve cap) (with cap)
1 Air purging Open Closed Open
(Installation) (counter-clockwise) (clockwise) (push-pin or with
vacuum pump)
Operation Open Open Closed
(with valve cap) (with valve cap) (with cap)
2 Pumping down Closed Open Open (connected
(Transfering) (clockwise) (counter-clockwise) manifold gauge)
3 Evacuation Open Open Open
(Servicing) (with charging cylinder)
4 Gas charging Open Open Open
(Servicing) (with charging cylinder)
5 Pressure check Open Open Open
(Servicing) (with charging cylinder)
6 Gas releasing Open Open Open
(Servicing) (with charging cylinder)
25
26
1
NAME AND FUNCTION OF PARTS
Indoor Unit
5. OPERA
TION
9000 BTU/h Class (DMB-1822LH unit A & B, DMB-2112LH unit B)
Electrostatic Filter
removes dust and particles from the air
Deodorizing Filter
removes bad smells from the air
Air Inlet
Remote Controller Receiver
Signal wire
Remote Controller
Fan Direction (Up, Down)
Air Outlet
Antibacterial Filter
removes dust and
prohibits germs.
Lamp
9000 BTU/h Class (DMB-1832LH unit A & B, DMB-2122LH unit B)
Electrostatic Filter
removes dust and particles from the air
Deodorizing Filter
removes bad smells from the air
Air Inlet
Remote Controller Receiver
Signal wire
Remote Controller
Fan Direction (Up, Down)
Air Outlet
Antibacterial Filter
removes dust and
prohibits germs.
Lamp
27
1 2 0 0 0 B TU / h Cla s s (DM B -2 1 1 2 LH u n it A )
Lamp
Electrostatic Filter
removes dust and particles from the air
Deodorizing Filter
removes bad smells from the air
Air Inlet
Remote Controller Receiver
Signal wire
Remote Controller
Fan Direction (Up, Down)
Air Outlet
Antibacterial Filter
removes dust and prohibits
germs.
1 2 0 0 0 B TU / h Cla s s (DM B -2 1 2 2 LH u n it A )
Electrostatic Filter
removes dust and particles from the air
Deodorizing Filter
removes bad smells from the air
Air Inlet
Remote Controller Receiver
Signal wire
Remote Controller
Fan Direction (Up, Down)
Air Outlet
Antibacterial Filter
removes dust and
prohibits germs.
Lamp
28
INDOOR UNIT (DMB-2112LH unit A (12000BTU/h))
Remote Control Signal Receiver
This place is the part to receive the signal if it receives the signal, you can hear the signal “beep”.
When the remote controller is lost or out­of-order, push the emergency button
(EMERGENCY) to operate by hand.
Open the front panel on emergency operating. Remocon switch is usually used with remote
controller.
Indoor Unit Display Switch Panel
Timer (Yellow)
Lights-on during the time of reservation mode.
Quick (Red)
Lights-on during the time of Quick Mode.
ON (Red)
Lights-on
during the operation
Air clean (Green)
Lights-on
during the operation
ON AIR
CLEAN
QUICK TIMER
EMERGENCY REMOTE
EMERGENCY REMOTE
29
Remote Control Signal Receiver
This place is the part to receive the signal if it receives the signal, you can hear the signal “beep”.
When the remote controller is lost or out­of-order, push the emergency button
(EMR.) to operate by hand.
Open the front panel on emergency operating. Remocon switch is usually used with remote
controller.
Indoor Unit Display Switch Panel
Timer (Yellow)
Lights-on during the time of reservation mode.
Quick (Red)
Lights-on during the time of Quick Mode.
ON (Red)
Lights-on
during the operation
Air clean (Green)
Lights-on
during the operation
EMR. REMOCON
INDOOR UNIT (DMB-2122LH unit A (12000BTU/h))
30
Remote Control Signal Receiver
This place is the part to receive the signal if it receives the signal, you can hear the signal “beep”.
When the remote controller is lost or out­of-order, push the emergency button
(EMR.) to operate by hand.
Open the front panel on emergency operating. Remocon switch is usually used with remote
controller.
Indoor Unit Display Switch Panel
Timer (Yellow)
Lights-on during the time of reservation mode.
Quick (Red)
Lights-on during the time of Quick Mode.
ON (Red)
Lights-on
during the operation
Air clean (Green)
Lights-on
during the operation
EMR. REMOCON
INDOOR UNIT (DMB-1822LH unit A or B, DMB-2112LH unit B (9000BTU/h))
Loading...
+ 78 hidden pages