dab water technology S4A, S4D, S4B, S4E, S4F Installation And Operating Manual

...
INSTALLATION AND OPERATING MANUAL
FOR DAB 4” SUBMERSIBLE PUMPS
S4A – S4B – S4C – S4D – S4E – S4F
DAB Submersible Pump Installation Instructions 2013 rev 1 2
DAB 4” SUBMERSIBLE PUMP INSTALLATION
AND OPERATING INSTRUCTIONS
These instructions supply the necessary information for the installation and operation of 4” submersible pumps,
and should be thoroughly read and understood before installation is attempted.
GUARANTEE
The following Guarantee conditions shall apply to borehole submersible pump installation. White International shall not be held responsible for damage caused by improper installation, use of cable and control boxes, level controls or magnetic starters which are not approved by White International, negligent or careless handling, lightning, improper voltage supply, corrosion due to impure water, wear caused by sand, gravel or other abrasives in the water being pumped.
IMPORTANT PRECAUTIONS
1. Damage to pump or motor caused by abrasive or corrosive water is not covered by the
Guarantee; however, to guard against installing a pump in aggressive water, it is suggested that an analysis of the bore water be submitted to the Department of Agriculture prior to installation to ensure pump suitability.
2. The bore should be clean before installation. The submersible pump must not be used to bail a
new bore. Guarantee does not cover failure or wear due to abrasives in the water.
3. Be sure voltage and frequency as shown on the nameplate of the control box and motor are the
same as the voltage and frequency on the line to which the motor is to be connected. Minimum voltage at the motor must be 240 volts for single phase and 415 volts for three phase.
4. Do not allow pump to run single phase unless it is properly connected to the correct control box.
5. Do not allow pumps to run dry, against a closed discharge or full open discharge. Refer to table
showing minimum and maximum flow conditions.
6. In addition to the check valve built into the pump, it may be necessary to install an additional check
valve. This is mandatory for heads greater than 80 metres, or on pressure systems. This will reduce water hammer shocks to the pump.
7. Know the total depth of the bore and ensure that the pump does not rest on the bottom or in
sand. Ensure 2 metres (6 feet) clear below the pump to the bottom of the bore.
8. Know the pumping level of the bore and ensure that the pump remains submerged at all times.
Use of level controller is recommended. If probe type is used, the probe should be located to switch the pump off when the bore water level drops within 1 metre of the pump suction. Alternatively a probeless control such as TESLA GUARDIAN can be used.
9. A Flow Inducer Sleeve or shroud which ensures that the water is drawn into the pump from
below the motor is required when the pump is in open water (i.e. water tank, river or dam), is in a rock well, below casing or set in screens, or well diameter is too large.
10. Do not install borehole submersibles in a crooked bore without gauging first. Lower a gauge which
is the same diameter and length as the pump to be used into the bore. If the gauge does not bind, it is safe to install the pump.
11. Never support the weight of the pump by the drop (power) cable or by the safety rope. Refer
instructions in section PUMP DROP PIPE.
DAB Submersible Pump Installation Instructions 2013 rev 1 3
TYPICAL SUBMERSIBLE INSTALLATION
Pump connected for Submersible water pressure system manual operation incorporating 100 litre pressure tank
DEPTH OF INSTALLATION
Make sure that the unit is at least one metre above any gravel layer and one metre below the minimum drawdown level. If during the initial operation, the pump lowers the well water level until suction is discontinued, then lower the pump where feasible, or install a protection device, or reduce the flow rate of the pump to prevent over-pumping.
DAB Submersible Pump Installation Instructions 2013 rev 1 4
PUMP DROP PIPE (Pipe Down The Bore)
Polythene drop pipe may be used, provided the pressures and depths indicated in the tables below are not exceeded.
PN
RATING
MAX PUMP
HEAD (M) BY
CURVE
MAX KPA
AT TOP
OF BORE
MAX PSI
AT TOP
OF BORE
MAX
DEPTH
(M)
MAX
DEPTH
(FT)
6.3
63 0 0
63
207
6.3
63
138
20
49
161
6.3
63
276
40
35
114
6.3
63
414
60
21
68
6.3
63
552
80 7 22 8 80 0 0
80
262
8
80
138
20
66
216 8 80
276
40
52
170 8 80
414
60
38
124
8
80
552
80
24
78 8 80
689
100
10
32
10
100 0 0
100
328
10
100
138
20
86
282
10
100
276
40
72
236
10
100
414
60
58
190
10
100
552
80
44
144
10
100
689
100
30
97
10
100
827
120
16
51
10
100
965
140 2 5
12.5
125 0 0
125
410
12.5
125
138
20
111
364
12.5
125
276
40
97
318
12.5
125
414
60
83
272
12.5
125
552
80
69
226
12.5
125
689
100
55
179
12.5
125
827
120
41
133
12.5
125
965
140
27
87
12.5
125
1103
160
13
41
12.5
125
1172
170 5 18
16
160 0 0
160
525
16
160
138
20
146
479
16
160
276
40
132
433
16
160
414
60
118
387
16
160
552
80
104
340
16
160
689
100
90
294
16
160
827
120
76
248
16
160
965
140
62
202
16
160
1103
160
48
156
16
160
1172
170
40
133
16
160
1241
180
33
110
16
160
1379
200
19
64
16
160
1517
220 5 17
DAB Submersible Pump Installation Instructions 2013 rev 1 5
PN
RATING
MAX PUMP
HEAD (M) BY
CURVE
MAX KPA
AT TOP
OF BORE
MAX PSI
AT TOP
OF BORE
MAX
DEPTH
(M)
MAX
DEPTH
(FT)
20
200 0 0
200
656
20
200
138
20
186
610
20
200
276
40
172
564
20
200
414
60
158
518
20
200
552
80
144
472
20
200
689
100
130
426
20
200
827
120
116
379
20
200
965
140
102
333
20
200
1103
160
88
287
20
200
1172
170
80
264
20
200
1241
180
73
241
20
200
1379
200
59
195
20
200
1517
220
45
149
20
200
1655
240
31
103
20
200
1793
260
17
56
20
200
1931
280 3 10
Polythene drop pipe can be selected by reference to the pump curve and its suitability can be checked on site by checking the maximum pressure read at the top of the bore reference to the maximum depth allowed.
An unstrained safety rope must be connected to all pumps suspended on polythene pipe. This line should be fastened to the lifting hook of the pump. The other end should be fastened at the top of the bore casing or bore cap. The safety rope should be affixed at three metre intervals by a suitable underwater tape with the rope having some slackness between each interval to compensate for the expansion of the polythene pipe when under load.
Care should be exercised to ensure that the polythene pipe is securely fastened to reliable fittings.
If galvanized steel drop pipe is used, it is best installed in three meter lengths to enable easy handling and all threads should be treated against corrosion.
It may be necessary, as a safety precaution to install a non-return valve at the top of the bore. This is in addition to the non-return valve fitted in the pump. This will assure a break down of the water hammer and consequently a reduction of shocks on the hydraulic components (which occurs in any pump system) immediately after each shutdown.
This non-return valve is mandatory where the pump heads (pressure at the top of the bore plus pump depth) exceed 80 m (785 kPa or 262 ft) or where the pump is part of an automatic pressure system.
WIRING
Wiring should conform to the requirements of local and national electrical codes. If in any doubt, contact your Electricity Supply Authority.
CAUTION
The use of smaller cable than specified below may cause premature motor failure and will void the warranty. Larger sized cables may be used.
The use of old drop cable or white flat is not recommended. Use water-proof cable only, i.e, Aquaflex AQM rated for immersion to 100 m (500m immersion rated also available) obtainable from White International.
The tables on the next page indicate the correct size electrical drop cable and maximum lengths to be used.
DAB Submersible Pump Installation Instructions 2013 rev 1 6
SINGLE PHASE 240 VOLT CABLE SELECTION
TESLA 3.2
4.4
5.9
8.2
10.5
15.3
240V MOTOR PSC kW (HP)
0.37 (0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5
(2.0)
2.2
(3.0)
Metric
Cable
Stranding
Area mm2
metres
metres
metres
metres
metres
metres
7/0.50
1.5
94
67
49
36
29
19
7/0.67
2.5
174
123
91
67
53
36
7/0.85
4.0
279
197
146
106
85
58
7/1.04
6.0
417
296
218
159
126
87
7/1.35
10
701
496
366
268
213
147
7/1.70
16
1117
791
585
426
339
235
THREE PHASE 415 VOLT CABLE SELECTION
TESLA 1.5
1.8
2.3
3.3
4.2
5.7
8.0
9.6
13.5
16.8
415V MOTOR kW (HP)
0.37 (0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5
(2.0)
2.2
(3.0)
3.0
(4.0)
4.0
(5.5)
5.5
(7.5)
7.5
(10.5)
Metric
Cable
Stranding
Area mm2
metres
metres
metres
metres
metres
metres
metres
metres
metres
metres
7/0.50
1.5
267
240
185
133
104
77
55
46
33
27
7/0.67
2.5
491
442
340
245
192
142
101
84
61
49
7/0.85
4.0
789
710
546
395
308
229
161
135
98
79
7/1.04
6.0
1180
1062
817
590
462
342
241
202
147
118
7/1.35
10
1982
1784
1372
991
775
575
405
339
246
198
7/1.70
16
3158
2843
2186
1579
1236
917
646
541
392
315
DAB Submersible Pump Installation Instructions 2013 rev 1 7
MOTOR DATA
TESLA
240V PSC MOTORS
kW
HP
AMPS
AMPS
OHMS
OHMS
CAPACITOR
O/LOAD
Full Load
Locked Rotor
Run Winding
Start Winding
uF
A
Black to Blue/Grey*
Black to Brown*
0.37
0.5
3.4
9.2
8.8
18.8
16
4
0.55
0.75
4.8
15.8
5.6
13.5
20
5
0.75
1.0
6.5
20.8
3.5
6.7
25
7
1.1
1.5
8.9
32.0
2.5
5.4
35
10
1.5
2.0
11.2
41.4
1.9
5.0
40
13
2.2
3.0
16.2
50.2
1.6
3.7
60
20
TESLA
415VMOTORS
kW
HP
AMPS
AMPS
OHMS
Full Load
Locked Rotor
Across Any
Two Leads
0.37
0.5
1.8
6.8
35.0
0.55
0.75
2.0
8.4
25.6
0.75
1.0
2.6
13.0
17.3
1.1
1.5
3.6
14.8
13.0
1.5
2.0
4.6
19.8
8.9
2.2
3.0
6.2
27.3
6.0
3.0
4.0
8.8
40.5
4.2
4.0
5.5
10.5
58.8
3.3
5.5
7.5
14.5
79.8
2.35
7.5
10.0
18.1
86.9
2.0
* Resistances taken at motor leads.
CONNECTION TO THREE PHASE STARTERS
A direct on line starter incorporating thermal overload and fuses must be used with all three phase motors, otherwise warranty will be void. Use of non approved fuses may not protect your motor and void warranty.
CHECK ROTATION OF BOTH SINGLE AND THREE PHASE MOTORS
Both single and three phase motors connected to a supply for the first time may rotate in either direction. It is therefore necessary to find out if the motor is rotating in the correct direction. Motor shaft rotates anticlockwise viewed from the lead grommet end. Change rotation by reversing wires.
If rotation is to be checked on the surface, proceed as follows:
Pour clean water into discharge by holding the non-return valve open so that the shaft bearings and the impellers become wet.
Turn on the power switch and check the shaft rotation is correct.
WARNING: The dry running should not exceed 2 to 3 seconds, otherwise seizing may occur due to inadequate lubrication.
DAB Submersible Pump Installation Instructions 2013 rev 1 8
If the unit is installed in the bore, then the correct direction of rotation is the one that will give maximum head (pressure) at the same capacity.
To correct a reversed rotation, change any two leads (except earth) from the three phase supply at the motor starter. Mark the leads so that the wires will in future be reconnected to the correct terminals of the starter. Single phase motors wired incorrectly can also operate in reverse. Check wiring.
EARTHING SINGLE AND THREE PHASE PUMPS
All Pump motors are equipped with an earth lead which must be connected to the earth of the incoming power supply. Further, control boxes and starters must also be earthed. If Testing or used outside a well, the motor must be connected to the power supply earth lead to prevent a lethal shock hazard.
ELECTRICAL CHECK LIST
It is recommended that where possible, all electrical connections be carried out before delivery to site.
Always check that the motor gland is tight.
Check control boxes, motors and pumps are as ordered and correctly matched.
Check the motor resistances before and after crimping the drop cable to the motor lead, using the charts supplied, and before the water proof heat shrink is applied.
Make sure that the water proof heat shrink is heated sufficiently to cause resin to flow to create a water tight seal.
If possible, it is good to practice run the pump briefly in a container of water (water must be over the suction inlet) to check on operation before installation in the bore.
Drop cable should be affixed at three metre intervals by a suitable underwater tape with the cable having some slackness between each interval to compensate for the expansion of the polythene pipe when under load.
DELIVERY PIPING
Large diameter pipe should be used for long runs to compensate for pressure losses due to friction. Long pipe runs can cause water hammer and damage to pumping systems. Consult your local borehole specialist as additional check valve and water hammer arrestor (pressure tank) may need to be fitted.
PUMP SWITCHING
By Float Switches, Pressure Switches, Timers etc.
(See also section headed “Pressure System Installation”
Provided the switching device used has an adequate current rating, it may be connected directly into the supply line to 240 volt motor control boxes. If the current rating of the switch is not adequate, a starter contactor must be wired into the supply, and the switching device connected to the control circuit of the starter contactor.
In the case of three phase motors, all switching devices should be wired to the control circuit of a suitable starter contactor, and on no account should they be used to directly break the supply circuit to the pump.
NOTE: Any automatic switching of the pump greater than 20 starts per hour will shorten the motor life and may void warranty.
DAB Submersible Pump Installation Instructions 2013 rev 1 9
INITIAL STARTING
Before connecting the pump outlet pipe from the bore, bend and gate valve should be screwed into the top of the bore cap as a pump valve.
With the gate valve just slightly open, start the pump.
NEVER START THE PUMP AT FULL FLOW FOR THE FIRST TIME
Immediately the pump has been started, catch some of the discharge water in a large container and allow the solids to settle out. If little or no sand appears, open the gate valve to 1/3 and pump until the water is clean.
For the first 10 to 20 minutes of operation, it is suggested to keep the gate valve only partially open, to maintain a low flow which will prevent turbulence in the well near the pump and possible seizing of the pump due to excessive sand in the water.
If excessive amounts of sand or other solids are being pumped, shut the pump down, and have the bore attended to before restarting the pump.
Submersible pumps are not guaranteed against failure due to pumping sand. Pumping of sand of even very fine small quantities will shorten the effective life of any pump.
NEVER OPEN THE GATE VALVE ABRUPTLY
as this may raise sand and deposits.
The pump should be run for a period of 30 minutes to check that it does not pump the bore dry. This would be obvious by large fluctuations on the pressure gauge and the ammeter as the pump flow surges. Continuing operation in this manner could cause serious damage to the pump and motor due to shock pressures as the pump alternately takes up and loses the hydraulic load. This effect is generally referred to as “snoring”.
If in doubt about the draw down level of the bore, the use of level controller is recommended. If probe type is used, the probe should be located to switch the pump off when the bore water level drops within 1 metre of the pump suction. The use of a high level probe to automatically turn the pump on is not desired, as a rapid cycling of the pump could occur causing severe damage to the unit. Time clock or manual restart is recommended. Alternatively a probeless control such as TESLA GUARDIAN can be used.
MINIMUM FLOW CONDITIONS
Premature pump failure may result if pumps are continuously run at flow rates less than the following:
MINIMUM FLOW RATE MODEL
LPM
GPM
S4A 6 1.3
S4B
10
2.2
S4C
20
4.4
S4D
33
7.3
S4E
66
14.5
S4F
150
33.0
DAB Submersible Pump Installation Instructions 2013 rev 1 10
MAXIMUM FLOW CONDITIONS
Premature pump failure may result if pumps are run for more than a short period at flow rates greater than the following:
MAXIMUM FLOW RATE
MODEL
LPM
GPM
S4A
25
5.5
S4B
40
8.8
S4C
72
15.8
S4D
100
22.0
S4E
190
41.8
S4F
440
96.8
PRESSURE SYSTEM INSTALLATION
When a submersible pump is to be used as a pressure system, the following items are required.
A pressure tank of at least 30 litres draw off. A pressure switch, which is available from White International in a kit complete with pressure gauge and 3 way tee piece which allows plumbing to the pressure tank. A non­return valve at the top of the bore in addition to the pump’s in-built non-return valve is required for pressure system application. It is recommended to install an additional gate valve (isolating valve) to allow blow down of the pressure tank to facilitate pressure pre-charge checking.
The 2 pole pressure switch supplied with the kit may be used to break the supply to the control box on single phase pumps up to 1.5 hp. A starter contactor must be used in addition to the control box for single phase pumps above 1.5 hp, and all three phase pumps. One pole of the pressure switch supplied should be used to switch the control circuit of the starter contactor.
The pressure tank connected must be large enough to provide the storage capacity and draw off to limit pump starts to 5 per hour. Use more than one tank if necessary. Do not use “air volume control” tanks from old model pressure systems or primitive non-diaphragm type tanks.
CAUTION: If the available pump pressure at the bore head can exceed the pressure tank’s maximum working pressure should there be a pressure switch failure, then a pressure relief valve should be fitted in the delivery line to prevent the tank being over pressurised. Use only nominal 30 litre draw off tanks or larger. Do not at any time use smaller tanks. If cut out pressures exceed 5 bar (500 kPa, 73 psi) fit a 12 bar switch. Pressure switches operated outside their design working range can fatigue and cause pump and fittings failures and void warranty.
DAB Submersible Pump Installation Instructions 2013 rev 1 11
PUMP SERVICE CHART
THE TROUBLE IS?
WHAT TO LOOK FOR
Overload protector trips
Faulty pressure switch
Control box in sun or near heat source
Wrong control box being used
Defective control box
Hydraulic overload
Water logged pressure tank
Low voltage supply to motor
Excessive motor starts
No water delivered
Broken pump shaft or coupling
Check valve installed backwards
Check valve stuck closed
Inlet screen clogged
Water level too low in well
Hole in delivery pipe below top of bore
Low water delivery
Fittings stopping check valve opening fully
Pump rotation backwards
Water level too low in well
Discharge pipe clogged, corroded or ruptured
Pump installed too low in well and covered with sand or other solids
Inlet screen partial clogged
Worn pump
Leak in outlet pipe below top of bore
Check valve stuck partially closed
Pump doesn't shut off
Pipe ruptured
Defective or improperly adjusted pressure switch
Water level too deep for pump. Check selection Pump is air or gas bound
Worn pump
Pipe obstruction
Pump needs adjusting
Pump starts and stops too often (i.e. more than 5 per hour)
Incorrect pressure switch, see pressure system installation
Defective air valve or tank diaphragm
Pressure switch differential adjustment failure
Pressure tank is too small
DAB Submersible Pump Installation Instructions 2013 rev 1 12
PUMP SERVICE CHART con’t.
THE TROUBLE IS?
WHAT TO LOOK FOR
Fuses blow but overload doesn't trip
Supply cable too small
Hydraulic overload
Fuses too small
Fuse receptacle dirty or corroded
Power spike
Loose connection in fuse box
Defective incoming power leads
Excessive motor starts per hour
Earth wire connected to wrong control box terminal
Cable insulation failure
Voltage too high or low
Electric shock from water pipe
Defective (grounded) incoming power leads
Defective control box
Note: A motor down to earth or defective cable will not cause a shock.
Earth wire connected to wrong control box terminal
Pressure gauge oscillates, flow surges (snoring)
Water level too low in the well. (Flow through pump greater than flow into well)
Electrolysis on motor and pump
Insufficient earth / earth leakage
Broken earth wire
NOTE: Always install borehole submersibles with ON/OFF switches and approved circuit breaker to protect against motor damage and electrocution.
DAB Submersible Pump Installation Instructions 2013 rev 1 13
SERVICING AND MAINTENANCE INSTRUCTIONS S4 SERIES
DISMANTLING
REMOVAL OF THE VALVE BODY (117): Unscrew the four screws (52), which hold the strainer and cable guard. Remove the strainer (42) and cable guard (39). Loosen and remove the nuts and washers that attach the pump to the motor and separate the pump and motor. Using an oil filter wrench grip the liner (69) and secure the wrench in a vice. Use a spanner to unscrew the valve body (117) from the liner (69). N.B. The thread is left hand. Take care to unscrew the components in the correct direction.
REMOVAL OF THE PUMP LINER (69): Grip the pump support (3) in a vice taking care not to damage the support. Using an oil filter wrench, unscrew the liner (69) from the pump support (3). N.B. The thread is left hand. Take care to unscrew the components in the correct direction.
DISMANTLING THE STAGES: Remove the upper support (57) complete with pilot bush (270), unscrew and remove the nut (18) and the washer (66). Slide off each stage comprising of diffuser (6), impeller (4), wear ring (191) and diffuser body (98). N.B. Some models have one or two intermediate supports (57) complete with pilot bush (271) and shaft sleeve (58). With a texta mark these supports as the intermediate support and note their position with respect to the pump stages. When all stages have been removed, the spacer bush (55) can be slid from the shaft.
ASSEMBLY OF THE STAGES
Fit the pump shaft (7) onto the motor and ensure that the coupling engages fully. Fit the spacer bush (55) and the support (3) over the shaft. Secure the support with the motor nuts and washers. Fit the first diffuser body (98) on to the support, followed by the first wear ring (191) and the first impeller (4). Ensure that the impeller
metal neck ring fits inside the wear ring. Fit the first diffuser with the conical section of the diffuser’s internal
wear ring facing up. Repeat this for all stages taking care that impellers fit inside wear ring. Some models will require their intermediate supports (57) complete with pilot bush (271) and shaft sleeve (58) to be fitted at the locations that were previously marked. Fit the washer (66) and tighten the nut (18), and fit the upper support (57) complete with pilot bush (270).
FITTING OF THE PUMP LINER (69): Grip the pump support (3) in a vice taking care not to damage the support. Using an oil filter wrench, screw the liner (69) onto the pump support (3). N.B. The thread is left hand. Take care to tighten the components in the correct direction.
FITTING OF THE VALVE BODY (117): Using an oil filter wrench, grip the liner (69) and secure the wrench in a vice. Use a spanner to screw the valve body (117) into the liner (69). N.B. The thread is left hand. Take care to tighten the components in the correct direction. Fit the strainer (42) and cable guard (39) using the four screws (52).
DAB Submersible Pump Installation Instructions 2013 rev 1 14
S4A-S4B-S4C-S4D- S4E-S4F
117
52 39
69 57
270
18 66
6 4
191
98 58
57
6 4
191
55 98
7
3 42 52 54
271
DAB Submersible Pump Installation Instructions 2013 rev 1 15
Loading...