Cypress OSM-1000-BRD Quick Start Manual

DIP Switch Address Table
1 2 3 4
X
X
XX
X
XX
XX
XXX
X
XX
XX
XXX
XX
XXX
XXX
XXXX
Address #
Address 0
Address 1
Address 2
Address 3
Address 4
Address 5
Address 6
Address 7
Address 8
Address 9
X = ON
OSM-1000-BRD Quick Start Guide
OSDP-Wiegand Converter
Product Overview:
The OSM-1000-BRD (board only) OSDP-Wiegand Converter is a general purpose Wiegand / OSDP converter. The OSM unit has two operating modes, PD (Peripheral Device) mode and ACU (Access Control Unit) mode. In PD mode, the OSM unit connects a traditional Wiegand reader to an OSDP ACU. In ACU mode, the OSM unit connects an OSDP reader to a traditional Wiegand Access Controller. Additionally, two OSM-1000 units can be used together, one in ACU mode and the other in PD mode, to connect a Wiegand reader to a Wiegand Access Controller with an OSDP connection in between.
What is included:
OSM-1000-BRD (board only) Warranty Quick Start Guide
Pin Designations:
DIP Switch Settings:
DIP Switches 1-4: Set the OSDP Polling
Address in PD mode. Set the OSDP Address to be polled by the OSM unit in ACU mode. See the DIP Switch Address Table to the right.!
DIP Switch 5: When ON, enables the Beep on Read feature when in ACU mode.!
DIP Switch 6: When ON, enables Secure Channel communication. !
DIP Switch 7: When ON, inverts osdp_LED command sent to PD when in ACU mode; and inverts the state of the output pin based on
osdp_LED command received in PD mode. !
DIP Switch 8: When ON, the OSM-1000 is set to ACU mode. When OFF, the OSM-1000 is
set to PD mode.
Set OSDP Polling
Address (0-15)
Beep on
Read
(ACU Mode)
Enable Secure
Channel
Invert
LED
Mode
Select
ON
C & K
ON
OFF
OSDP Default Parameters:
Secure Channel Key: 303132333435363738393A3B3C3D3E3F!
Polling Address: 0!
Baud Rate: 9600
For more detailed information on the OSM-1000 visit CypressIntegration.com.
190815
RS-485 A RS-485 B Ground Strike N.O. Strike COM Strike N.C. Ground 8 - 16 VDC Input
8 - 16 VDC Input
Ground
Data 0 Data 1
LED
Digital Input
Ground
Buzzer / Output Control
ACU Mode Wiring Diagram
PD Mode Wiring Diagram
Status LED Behavior:!
The OSM-1000-BRD unit has a tri-color LED that can display red, green, blue, and white. The startup sequence lasts approximately 5 seconds and the LED will display red, blue, green, white or display red, green, blue, white. !
ACU Mode:! Communication with PD: the status LED will be blue with fast, green flashes or green with fast, blue flashes. The status LED will
briefly turn red when it receives reader data from the PD.! No Communication with PD: the status LED will be blue with slow, green flashes or green with slow, blue flashes. The status LED will briefly turn red when it receives reader data from the PD.
PD Mode:! Communication with ACU: the status LED will red with fast, blue flashes or red with fast, green flashes. !
No communication with ACU: the status LED will slowly fade from red to o, and back to red.
Bench Testing: Bench testing is recommended to avoid troubleshooting issues in the field.
ACU Mode:!
1. At the bench, connect the OSM unit to the PD and the Wiegand access controller by following the ACU Mode Wiring Diagram.!
2. Observe the OSM unit and PD communicating. Refer to the “Status LED Behavior” section to verify that the OSM unit is
communicating with the PD.!
3. If the devices do not communicate, make sure the the baud rate and polling ID match. In the OSDP spec, the default baud rate is 9600 and the default polling ID is 0.!
PD Mode:!
1. At the bench, connect the OSM unit to the Wiegand reader and ACU by following the PD Mode Wiring Diagram. !
2. Observe the OSM unit and ACU communicating. Refer to the “Status LED Behavior” section to verify that the OSM unit is
communicating with the ACU. !
3. If the devices do not communicate, make sure the the baud rate and polling ID match. In the OSDP spec, the default baud rate is 9600 and the default polling ID is 0.
12VDC
Power
Supply
Power
Ground
OSDP
Card
Reader
Power Ground RS485 A RS485 B
Wiegand
Access
Control Panel
Ground
Data 0 Data 1
LED Out
Beeper Out
12VDC
Power
Supply
Power Ground
8 - 16 VDC Input Ground Data 0 Data 1 LED I/O Ground Output Control Buzzer
RS485 A RS485 B
Ground
Strike N.O.
Strike COM
Strike N.C.
Ground
8 - 16 VDC Input
RS485 A RS485 B
OSDP Access
Control Panel
12VDC
Power
Supply
Power
Ground
Wiegand
Card
Reader
Power
Ground
LED IN
Data 0 Data 1
8 - 16 VDC Input Ground Data 0 Data 1 LED I/O Ground Digital Input Digital Input
RS485 A RS485 B
Ground
Strike N.O.
Strike COM
Strike N.C.
Ground
8 - 16 VDC Input