CYCLONE NA330R36, PTB8636, CY917R30SS, PTB5630MB, PTB8624 Installation guide

...
Self-Cleaning Range Hoods
Undermount Range Hoods
CYB919R
PTB56
CY917R / CY919R
PTB8 Series
Installation and Operation Instructions
Please read all instructions before installing and operating.
All wiring and installation must be in accordance with CEC, NEC and local electrical codes.
READ AND SAVE THESE INSTRUCTIONS
2 Cyclone Undermount Installation - English
IMPORTANT SAFETY INSTRUCTIONS
WARNING
is appliance must be installed by a qualied technician.
e manufacturer declines all responsibilities in the event of failure to observe the instructions given here for installation, maintenance and suitable use of the product.
e manufacturer further declines all responsibility for injury due to negligence, and the warranty of the unit automatically expires due to improper installation and maintenance.
CAUTION
Suitable for use in household cooking area.
For residential cooking use only. Do not use to exhaust hazardous or explosive materials or vapors.
Two installers are recommended because of the size and weight of this hood.
Do not use more than 60 watts incandescent light bulbs for any model. Do not use round shaped light bulb for models CY1000C, CY1000R, NA930C, NA930R, and NA940D. Recommended use 23W orescent tube (equivalent to a 90 watts incandescent light bulb).
Do not use more than 20 watts per halogen bulb for models CYS1000R, and CY1011R. Light bulbs combined are not to exceed 40 watts.
Use LED bulb, 1.4W maximum per bulb, for CY3000R.
Use LED puck light, 1.4W maximum per light, for NA330R, PTB56 and PTB8 series.
*Bulb & socket may change.
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer.
2. Before servicing or cleaning the unit, switch power o at service panel and lock service panel to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device to the service panel.
3. Installation work and electrical wiring must be done by qualied persons in accordance with all applicable codes and standards, including re-rated construction.
4. Sucient air is needed for proper combustion and exhausting of gases through the ue of fuel burning equipment to prevent back draing. Follow the heating equipment manufacturer’s guideline and safety standards as published by the local code authorities.
5. When cutting or drilling into walls or ceilings, be careful not to damage existing electrical wiring and other hidden utilities.
6. To reduce the risk of re, electric shock and to properly exhaust air, ducted fans must always be vented outdoors. Do not vent exhaust air into spaces within walls, ceilings, attics, crawl spaces, or garages. Do not connect this fan with any solid-state speed control device.
7. Always keep the duct clear to maintain proper airow for venting.
8. e bottom of the hood MUST NOT BE LESS than 28” and at a suggested maximum of 36” above cooktop for best capture of cooking impurities. For a gas range, the bottom of the hood MUST NOT BE LESS than 30” above cooktop.
WARNING
TO REDUCE THE RISK OF RANGE TOP GREASE FIRE:
1. Never leave the range unattended at high settings.
2. Always turn hood ON when cooking at high heat or when aming food.
3. Use proper pan size. Always use cookware appropriate for the size of the surface element.
4. Keep fan, lters and grease laden surfaces clean. Clean ventilating fans frequently. Do not allow grease to accumulate on fan or lter.
5. Use HIGH setting on hood only when necessary.
6. Don’t leave hood unattended when cooking.
7. To reduce the risk of re, use only metal ductwork.
8. is unit must be grounded.
9. Not for outdoor use.
WARNING
Do not repair or replace any part of this appliance unless specically recommended in this book. All other service should be performed by a qualied technician.
e hood motor has a thermal overload that will automatically shut o the motor if it becomes overheated. e motor will restart. If the motor continually shuts o and restarts, contact the Cyclone service department. Ensure that the hood is mounted at the recommended mounting height.
is product may have sharp edges. Be careful to avoid cuts and abrasions during installation and cleaning.
3Cyclone Undermount Installation - English
Contents
Important Safety Instructions 3
Damage Inspection 5
Ducting 5
Mounting Heights and Clearance 6
Wiring Installation 6
Undermount Installation - Tools and Materials Required 7
Undermount Installation - Parts supplied 7
Undermount Hood Installation 8
PTB8 Series Installation 10
Undermount Hoods Specications 12
Troubleshooting 13
Maintenance 14
Control Panel 15
Cyclone Range Hoods Limited Warranty 16
4 Cyclone Undermount Installation - English
DAMAGE INSPECTION
Please fully inspect unit for damage before installation.
If the unit is damaged in shipment, return the unit to the store in which it was bought for repair or replacement.
If the unit is damaged by the customer, repair or replacement is the responsibility of the customer.
If the unit is damaged by the installer (if other than the customer), repair of replacement must be made by arrangement between customer and installer.
Once installed, all damages will be assumed the responsibility of the installer.
DUCTING
WARNING
To reduce the risk of re, use only metal ductwork.
To reduce risk of re and to properly exhaust air, be sure to duct air outside – do not vent exhaust air into spaces within walls, ceilings, attics, crawl spaces, or garages.
CAUTION
Best to use rigid type metal ducts. Flexible ducts can restrict airow by more than 50%.
Reduce the number of transitions and turns as much as possible. If a reducer is used, install a long reducer instead of a pancake reducer. If turns and transitions are required, install them as far away from the opening as possible and as far apart between two as possible.
WARNING
6” round ductwork must be used to maintain maximum air ow eciency with motors of 450 CFM or greater. If the use of any size ducting is less than 6”, the warranty is automatically voided.
e venting duct must go horizontally or vertically up to the outside wall or the roof. If it is turned downward anywhere in the venting system, the warranty is automatica lly voided.
Examples of dierent types of ventilation for undermounts:
Roof Pitch with Cap and Flashing
Soffit or Crawl Space
Side Wall Cap with Gravity Damper
Fasten all connections with sheet metal screws and tape all joints with certied aluminum foil tape or duct. Do not cut a joist or stud unless absolutely necessary. If a joist or stud must be cut then a supporting frame must be constructed. Before making cutouts make sure there is proper clearance within the ceiling or wall for the exhaust vent.
Additional parts not provided.
Side Wall Cap with Gravity Damper
5Cyclone Undermount Installation - English
MOUNTING HEIGHTS AND CLEARANCE
WARNING
e hood should be installed at 28” minimum above the cooking surface. If pairing your range hood with a gas stove minimum mounting height must be 30” above the cooking surface.
Minimum mount height between range top to hood bottom should be no less than 28” for electric or ceramic stoves, and no less than 30” for gas stoves. e maximum mount height should be no more than 36”. e hood must be installed at the correct mounting height. Hoods mounted too low could result in heat damage. Hoods mounted too high, on the other hand, will be less eective and performance may suer.
Check your ceiling height and the hood height maximum before you select your hood.
Hood installation height above cook top is the user’s preference. e lower the hood is above the cook top the more ecient it will be in drawing out cooking odors, grease and smoke.
Max:
Max: Min:
Min:
Gas 30”
Gas 30”
Ceramic/Electric
Ceramic/Electric 28”
36”
36”
36”
28”
WIRING INSTALLATION
is appliance requires 120V 60Hz electrical supply and connection to an individual properly grounded branch circuit protected by a circuit breaker or time delay fuse.
Grounding Instructions
is appliance must be grounded. is appliance is equipped with a cord having a grounding wire or with a plug having grounding wire. e grounding wire must be grounded properly in the junction box or the plug must be plugged into an outlet that is properly installed and grounded.
1. Connect the power line ground wire to the green ground wire supplied with the hood.
2. Connect the black power wire to the black wire supplied with the hood.
3. Connect the white neutral wire to the white wire supplied with the hood.
Black: Power
White: Neutral
Install the Electrical Power Supply (PTB8 series only)
Position the outlet or junction box within the space covered by the upper cabinet or optional chimney ue. Place the outlet or junction box at a maximum distance of 36” above from where the cord exits from the hood. e center of the outlet or junction box should be positioned at no less than 2 ¾” away from the center of the damper. Make sure this does not interfere with the mounting area, ducting or chimney ue.
Min. 2 ¾”
Max. 36”
Green: Ground
6 Cyclone Undermount Installation - English
PLEASE REFER TO PAGES 11-20 FOR YOUR MODEL’S SPECIFICATIONS
UNDERMOUNT INSTALLATION - TOOLS AND MATERIALS
REQUIRED
Electrical drill or ratchet driver
Phillips screwdriver #2 or driver bit
Straight blade screwdriver
Wire stripper or cutter
Tape measure
Electrical supplies for wiring (i.e. marrets, electrical tape)
UNDERMOUNT INSTALLATION - PARTS SUPPLIED
1 × Hood
Rectangular Opening Models ONLY:
1 × Rectangular Damper
Aluminum foil tape and/or duct tape
Hammer
Jigsaw or saber saw
Step ladder
All Units Except NA330R:
2 × Round Oil Saucers
CYS1000R ONLY:
1 × Round Oil Saucer
All Units Except NA330R:
2 × Rectangular Oil Cups
CYS1000R ONLY:
1 × Rectangular Oil Cups
CY3000R ONLY:
2 × Insertable Oil Cups
4 × Mounting Screws
INCLUDED IN UNIT
CYS1000R, CY1011R:
2 × Halogen Lights
(20W per bulb)
INCLUDED IN UNIT
CY3000R ONLY:
2 × Dimmable LED Lights
(1W per bulb)
HARDWARE PACKAGE
Rectangular Opening Models ONLY:
6 × Damper Screws
PRE-INSTALLED
NA330R ONLY:
2 × LED Lights
(1.5W per bulb)
*Bulb & socket may change.
NA330R ONLY:
1 × Oil Collector
7Cyclone Undermount Installation - English
UNDERMOUNT HOOD INSTALLATION
WARNING
Turn o power circuit at the service panel before wiring this unit.
All electrical work must be done by a qualied electrician in accordance with all applicable codes and standards. is range hood must be properly grounded.
Preparation for Installation
1. Unpack range hood and check contents. Note: Be cautious of sharp edges within the unit. Remove hood cover insert screws and li o cover to expose the inside (Figure 1). For NA330R/PTB56, to open the cover (bae lter) complete the following steps (Figure 1a): i. Pull the bae lter forwards toward the front of the hood
using the handle while pushing the back side upwards inside the hood.
ii. With the lter tilted upwards, push the lter backward
and then pull down the front to remove the bae lter.
Figure 1.
CAUTION
At least two installers are required due to the weight and size of the hood.
Bae Removal for NA330R/PTB56:
Figure 1a.
1. Forward 2. Upwards
3. Upwards
Figure 2. Figure 3a, 3b.
Electrical Knockout
4. Downwards
2. Remove either the top or rear electrical knockout depending on how you plan to run power leads to the hood through cabinet or wall (Figure 2). i. Insert a screwdriver into the knockout slot and bend the
knockout back and forth (Figure 3a & 3b). Pliers may be used to remove the loosened knockout.
3. For rectangular rear venting conguration (Figure 4): i. Cover the rectangular top cutout with the rectangular
cover plate and fasten with tapping screws. For optimal use, remove apper for top venting conguration.
ii. Place the rectangular damper onto the rear cutout and
fasten with tapping screws.
Important: Seal both the top cover plate and damper with aluminum foil tape (preferred) or duct tape.
4. For rectangular top venting conguration (Figure 5): i. Cover the rear cutout with the rectangular cover plate
and fasten with tapping screws.
ii. Place the rectangular damper onto the top rectangular
cutout and fasten with tapping screws.
Important: Seal both the rear cover plate and damper with aluminum foil tape (preferred) or duct tape.
5. For round top venting conguration: no rear cover or damper required.
Figure 4.
Figure 5.
Cover Plate
Tapping Screws
Damper
Damper
Cover Plate
Tapping Screws
8 Cyclone Undermount Installation - English
Preparation for Vent and Exhaust Duct Connection
Knockout Opening
1. To connect a rectangular vent to a round exhaust duct (or vice versa), use a connecting duct and adapter.
2. e round vent of a Cyclone Range Hood is 6” diameter. If the round exhaust duct is not 6” diameter, a connecting duct is necessary to accommodate the dierent size. If the exhaust duct is less than 6” diameter, the eciency of your Cyclone Range Hood will be reduced and the warranty may be voided.
3. If the rectangular vent is being connected to an existing rect angular duct, a connecting duct is not needed. However, a professional should be consulted to install the range hood properly.
Install the Undermount Hood
1. Place the range hood on the bottom of the cabinet. Route
the power supply cord through the access hole and through the knockout. is step will have to be accomplished while positioning the hood (Figure 6 & 7).
2. Center the hood in place beneath the
cabinet and ush with the front of the cabinet. Outline the four keyhole mounting slots for the hood onto the bottom of the cabinet.
3. Partially screw in the four hood
mounting wood screws through the narrow ends of the marked keyholes.
4. Align the hood’s wider ends of the
keyholes mounting slots over the four partially installed screws. Push the hood against the wall so that the screws are now secured in the narrow end of the keyhole and that the front of the hood is aligned with the cabinet front (Figure 7).
5. Check to ensure the rear or top vent is tted and connected to
the duct properly. Use aluminum foil tape to cover all seams.
Figure 6.
4. An exhaust duct needs to be cut if there is not an existing duct in your home. Please consult/hire a professional to complete the work properly. In general, for rear venting, a rectangular hole needs to be cut into the wall to t the rectangular exhaust duct extended to the outside wall. For top venting, a rectangular or a 6” round hole needs to be cut through the ceiling or the back wall and the bottom of the cabinet to t the duct connection.
6. Tighten the hood mounting screws all the way into the cabinet so the hood is rmly attached.
7. Make the Electrical Connection i. Secure the electrical wire to the hood with the connector’s
“STAR” locknut.
ii. Strip about ½” of insulation from the ends of the electrical
power wires.
iii. Connect the power line ground wire to the green ground
wire supplied with the hood (Figure 8).
iv. Connect the black power wire to the black wire supplied
with the hood.
v. Complete the same step with the white wire.
8. Reinstall the hood cover plate with the insert screws. For NA330R, no screws are needed. Place bae lters back on.
9. Attach the rectangular and round oil collectors at the far back and under the fan guard respectively. For NA330R, oil collector is already installed.
10. Turn on the hood to check for any leaks in the ductwork and to ensure proper function.
Figure 7.
Mounted Strips
Width of
Range Hood
Keyhole
Slot Outline
Figure 8.
Range Hood Front
Junction Box
Range Hood Connection
Power Line Connection
Electrical Knockout
9Cyclone Undermount Installation - English
PTB8 SERIES INSTALLATION
WARNING
Turn o power circuit at the service panel before wiring this unit.
All electrical work must be done by a qualied electrician in accordance with all applicable codes and standards. is range hood must be properly grounded.
Preparation for Installation
1. Unpack range hood and check contents. Please inspect the product for damage and/or defects prior to installation. Note: Be cautious of sharp edges within the unit.
2. Conrm that all hardware and accessories are present in addition to the range hood;
1 - Package containing
◆ 5 x - ⅝” wo od screws for sec uring the top of the hood
to upper cabinet (if applicable)
◆ 4 x - 3” wood screws for securing the cleat
◆ 4 x - 1 ⅛” wood screws for securing the hood to the cleat
◆ 6 x - ⅝” screws for securing the damper
◆ 1 x - rubber damper seal/gasket
◆ 2 x - wall anchor
◆ 2 x - 1 ¼” screws for anchors
2 - Baffle filters (for 30” model, 3 filters for 36” model) 1 - Grease cup 1 - Wood mounting cleat (strip) - 28.5” x 2” x ¾” 1 - Damper
Wall Mount Installation Instructions
1. Determine mounting height of the hood. Cyclone recommends that the hood be mounted at a minimum height of:
◆ For gas stoves 30” - 36”
◆ For electric, induction, etc. stoves 28” - 36”
2. Conrm the location of the mounting cleat and check to make sure it is centered and level. Secure the cleat in place with the 3” wood screws provided. (Figure 1)
Note: make sure the wood cleat is secured and fastened
to all available wall studs (a minimum of 2 studs is ideal) where there is only one stud available, use drywall anchors or suitable substitute. Do not rely on drywall alone to support the hood.
Figure 1
15"
30"-36"
Mounting Cleat
Screws
Range Hood
Wall Studs
Stove
CAUTION
At least two installers are required due to the weight and size of the hood.
Preparation for Vent and Exhaust Duct Connection
1. e round vent of a Cyclone Range Hood is 6” (8” for PTB88) diameter. If the round exhaust duct is not 6” (8” for PTB88) diameter, a connecting duct is necessary to accommodate the dierent size. If the exhaust duct is less than 6” (8” for PTB88) diameter, the eciency of your Cyclone Range Hood will be reduced and the warranty may be voided.
3. Rest the hood on the wood cleat with one person holding the hood. Score the drywall through at least 2 of the 3 holes located on the rear panel of the hood for placement of screws and/or drywall and anchors. Remove the hood and drill pilot holes into the marks transferred on the wall and add anchors if there is no stud(s) available.
Figure 2
Wall Anchor
10 Cyclone Undermount Installation - English
4. Install the plastic damper using the rubber seal and the 6 x ⅝” screws provided. (Figure 3)
Figure 3
5. Once anchors are installed, secure the hood to the wood cleat using the 1 ⅛” screws provided. Use the 1 ¼” screws to secure the back panel of the hood to the anchors in the wall. (Figure 4)
Figure 4
Mounting
Cleat
Wall Anchor
Screws
Under Mount Installation Instructions
*FOLLOW THE STEPS FOR WALL MOUNT INSTALLATION
In Addition:
1. Cut an access hole in your cabinet for the damper and ducting. Note: e damper should be installed at the end when connecting the duct. (Figure 5)
Figure 5
Access Hole
2. ere are 5 pilot holes located at the top of the hood. Use the 5 x ⅝” screws provided to secure the hood to the cabinet. (Figure 6)
Figure 6
Mounting
Cleat
Screws
Wall Anchor
11Cyclone Undermount Installation - English
UNDERMOUNT HOODS SPECIFICATIONS
SIZE
MAX.
CUBIC FEET/
METER (CFM)
MAX. SONES
MOTOR
FINISH
CONTROLS
SPEED
LEVELS
NA940D CY1011R CY3000R CYS1000R NA330R
30” 30” 30” 24”/30” 30”/36”
PTB8 Series PTB56
24” (PTB83)
30”/36” (PTB83/86/88)
30”/36”
300 (PTB83)
680 680 680 300 680
600 (PTB86)
680
880 (PTB88)
4 (PTB83)
7 7 7 4 7
6 (PTB86)
7
TBD (PTB88)
DOUBLE DOUBLE DOUBLE SINGLE DOUBLE SINGLE DOUBLE
WHT/BLK/SS WHT/BLK/SS WHT/BLK/SS WHT/BLK/SS SS SS MB/SS
ROCKER SWITCH
ROCKER SWITCH
DIGITAL TOUCH
SWITCH
ROCKER SWITCH
DIGITAL
TOUCH
SWITCH
PUSH BUTTON
PUSH
BUTTON
2 2 6 2 6 3 4
TIME
DELAY OFF
FILTERS
DUCT
LIGHTING
AC INPUT
MOUNTING
HEIGHT
NO NO YES NO YES YES YES
NO NO NO NO BAFFLE BAFFLE BAFFLE
NA940D - 6”
ROUND TOP/ 3
¼” × 10”
RECTANGULAR
TOP OR REAR
Florescent Florescent
120V 60Hz
28”-36” 28”-36” 28”-36” 28”-36” 28”-36” 28”-36” 28”-36”
*Bulb & socket may change.
CY1011R - 3 ¼”
× 10”
RECTANGULAR
TOP OR REAR
120V 60Hz
3 ¼” × 10”
RECTANGULAR
TOP OR REAR
2 × 1.4W
LED Light Bulb
120V 60Hz
3 ¼” × 10” RECTANGU­LAR TOP OR
REAR
2 × 20W
Halogen Lights
120V 60Hz
q
3 ¼” × 10” RECTANGU­LAR TOP OR
REAR
2 × 1.4W
LED Puck Light
120V 60Hz
PTB83/PTB86 - 6”
ROUND TOP/
PTB88 - 8” ROUND
TOP
3 × 1.4W
LED Puck Light
120V 60Hz
3 ¼” × 10” RECTAN-
GULAR
TOP OR
REAR
2 × 1.4W
LED Puck
Light
120V 60Hz
12 Cyclone Undermount Installation - English
TROUBLESHOOTING
For additional service inquiries, contact Cyclone servicing department at 1-888-293-5662 or Service@CycloneRangeHoods.com
ISSUE CAUSE SOLUTION
Unit doesn’t work aer installation.
Light indicates power ON but motor doesn’t turn.
e unit vibrates. 1. e motor is not secured. 1. Tighten the motor in place.
Motor works but lights do not turn on.
1. e power source is not turned ON. 1. Ensure power is ON for the circuit breaker and unit.
2. e power line and the cable locking connector
are not connected properly.
3. e control panel or motherboard is defective
(CY3000R/NA330R).
1. e motor is defective, possibly seized. 1. Change the motor. Servicing may be required.
2. e control panel or motherboard is defective. 2. Change defective part. Servicing may be
2. Damaged blower wheel. 2. Replace the blower wheel. Servicing may be
3. e hood is not secured in place. 3. Check the installation of the hood. Screws may
4. Venting duct too small or blockage in the duct
opening or ductwork.
1. Defective light bulb. 1. Change the light bulb.
2. e light bulb is loose. 2. Tighten the light bulb.
2. Check the power connection with the unit is connected properly.
3. Change the control panel or motherboard.
required.
required.
require tightening
4. Check the venting duct and the wall cap or roof cap.
e hood is not venting out properly.
3. e control panel or motherboard is defective (CY3000R/NA330R).
1. e hood might be hanging too high from the cook top.
2. Blockage in the duct opening or ductwork. 2. Remove all the blocking from the duct work or
3. Using the wrong size of ducting. 3. Use at least 6” duct work.
3. Change the control panel or motherboard.
1. Adjust the distance between the cook top and the bottom of the hood within 28” - 36” above the range.
duct opening.
13Cyclone Undermount Installation - English
MAINTENANCE
For a complete description of our maintenance and operating instructions you may visit us online at www.CycloneRangeHoods.com to download your model’s Use and Care Guide.
Due to the fact that we are always striving to improve our products and take advantage of advances in technology, there may be slight variations in your product.
WARNING
Always switch o power and unplug before cleaning and maintenance.
Surface and Filter Cleaning:
Clean with warm soapy water and a clean cloth. Do not use corrosive or abrasive detergent or steel wool pads that can scratch the surface of the machine.
Use non-abrasive stainless steel polish to bu out the luster and grain. Scrub lightly.
e stainless steel lters trap residue and grease from cooking. e lters should never have to be replaced but should be cleaned thoroughly every 30 to 60 days depending on cooking habits. Filters may be placed on the top rack of the dishwasher or soaked in warm, soapy water. Spray degrease detergent and leave to soak if heavily soiled.
Replacing Lightbulbs:
WARNING
Always switch o electrical supply before carrying out any operation on the appliance.
In order to prevent the risk of personal injury, the halogen lamps must be cooled before removal.
Do not use more than 60W incandescent light bulbs for any model. Do not use round shaped light bulb for models NA940D. Recommended use 23W orescent tube (equivalent to a 90W incandescent light bulb).
*Bulb & socket may change.
Please use 23W or 15W orescent tube light bulbs for NA940D. Use 120V 20W halogen light bulbs for CY1011R/ CYS1000R. Use LED bulb, 1.4W maximum per bulb, for CY3000R. Use LED puck light, 1.4W maximum per light, for NA330R. To change bulbs for CYS1000R and CY3000R:
1. Firmly press ngers against the light bulb and twist counter­clockwise until bulb is loosened
14 Cyclone Undermount Installation - English
is range hood requires LED bulbs. (1.4W maximum per bulb) To change the light bulb, remove light case from the light socket. e light case can be accessed from the inside of the body of the machine. i. Disconnect the connecting wires of the light socket from the
motherboard wires.
ii. Remove grease lters and push light case outward away from
the machine.
iii. Replace with a new case.
CONTROL PANEL
Model: NA330R (above) CY3000R (below)
e unit is controlled by a digital touch switch.
Light Power
Power
LOW
speed
Timer/24 Hour Clock
HIGH
speed
Light
To Set the Time
e time will appear on the digital display panel. Simply press and hold the power button for about three seconds and use the LOW button to set the hour and the HIGH button to set the minutes.
To Engage Time-Delay O Functions:
Simply press the power button while the machine is running, and use the LOW and HIGH power buttons to set the number of minutes you would like the fan to run before automatically shutting o.
Model: NA940D/CY1011R
e unit is controlled by rocker switches.
e fan and light are each controlled by a rocker switch. e
fan switch has three positions: HIGH, LOW and OFF. e light switch has two positions, ON and OFF. For CY1011R the light switch has three positions for HIGH, LOW and OFF.
HIGH
speed
LOW
speed
Fan Controls
OFF
OFF
ON
Light
Model: CYS1000R
e unit is controlled by rocker switches.
e fan and light are each controlled by a rocker switch. e fan switch has three positions: HIGH, LOW and OFF. e light switch has three positions for HIGH, LOW and OFF.
HIGH
speed
OFF
LOW
speed
OFF
HIGH LOW
Model: PTB8 Series
e unit is controlled by push buttons
Timer
Fan Speed Levels
Light
To Engage Time-Delay O Functions:
Simply press the timer button while the machine is running to engage the timer for three minutes. Press the timer button again, and the fan will turn o.
Fan Controls
Light
Model: PTB56
e unit is controlled by push buttons
Timer
Fan Speed Levels
Light
To Engage Time-Delay O Functions:
Simply press the timer button while the machine is running to engage the timer for three minutes. Press the timer button again, and the fan will turn o.
15Cyclone Undermount Installation - English
CYCLONE RANGE HOODS LIMITED WARRANTY
Cyclone Range Hoods Inc. (hereunder called “e Company”) provides a warranty that its products are free from defects in workmanship and materials for a period of two (2) years from the date of purchase. is warranty includes in-home service (where applicable) for the rst year and workshop service for the second year. During that time period, e Company will, at the Company’s option, repair or replace without charge any parts or complete unit found to be defective. Further, the warranty for the motor extends for an additional eight (8) years, with labor costs extra. is warranty is not transferrable from the original purchaser. e company reserves the right to use functionally equivalent reconditioned parts or products as warranty replacement or as part of warranty service.
THE COMPANY WILL NOT BE HELD RESPONSIBLE FOR ANY CLAIMS OVER THE ORIGINAL PURCHASE PRICE OF THE PRODUCTS NOR BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES ARISING OUT OF OR IN CONNECTION WITH PRODUCT USE OR PERFORMANCE.
Some provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
In-home service will be made available only in areas where a contracted service provider oers services. If customer outside the service area, additional charges may apply for shipping costs for warranty repair or replacement. e unit removal and reinstallation works are under the customer responsibility.
is warranty does not cover any costs related to the products including but not limited to:
a) Normal maintenance service required for the products; b) light bulbs, plastic grease collector cups, lters, ducts, roof caps, wall caps and other accessories for ducting; c) natural wear of the nish of the products or wear caused by improper maintenance, use of corrosive and abrasive cleaning products; d) products or parts which have been subject to freight damage, misuse, negligence, accident or any other circumstances beyond the control of e Company.
e warranty will be automatically void if any of the following apply:
i. Commercial use of the products or use otherwise inconsistent with its intended purpose;
ii. e function of part or the complete assembly has been modied or repaired by unauthorized person;
iii. Faulty installation or installation contrary to recommended installation instructions:
e hood installed at less than 28” minimum above the range surface;
Ventilation system has not been vented to the outside or ventilation system stuck;
Less than 6” round or equivalent ductwork has been used anywhere in the venting system for models with 550 CFM or more CFM;
e venting duct turned downward anywhere in the venting system;
Wrong electrical wire connection for the fan.
To qualify for warranty service you must: (a) notify us at the address telephone number stated below within 2 days of the discovery of the defect; (b) provide the model number and serial number; and (c) describe the nature of any defect in the product or part. At the time of requesting for service, you must present evidence of your proof of purchase and proof of the original purchase date. If we determine that the warranty exclusions listed above apply or if you fail to provide the necessary documentation to obtain service, customer will be responsible for all shipping, travel, labor and other costs related to the service For warranty services or repair, please contact the dealer from whom you purchased the product or the address shown below.
North America Range Hoods Inc.
1361 Huntingwood Drive, Unit 16
Tel: 1-866-293-5662 or (416) 293-0933 Fax (416) 293-4793
Email: Info@CycloneRangeHoods.com
Website: www.CycloneRangeHoods.com
16 Cyclone Undermount Installation - English
Scarborough, ON M1S 3J1
Loading...