![](/html/e3/e3b2/e3b238ea39dcdb821f4b5997c5efc6672b523ca3c63eba1d01a9b05b128f489b/bg1.png)
OL2200RTXL2U
SMART APP
ONLINE UPS
Prevent business interruptions and safeguard
mission-critical enterprise network equipment.
The CyberPower OL2200RTXL2U is a rack/tower UPS with double
conversion topology. It provides sine wave output to critical applications
and equipment that require seamless power correction. The Extended
Battery Module (EBM) expands runtime, and Fast Charge Technology
restores full backup power faster. This model comes with an extendable
LCD control panel, Smart Battery Management charging technology, and
energy-saving GreenPower UPS™ ECO Mode.
The OL2200RTXL2U oers generator compatibility and delivers clean
AC power with zero transfer time. Its sine wave output keeps sensitive
equipment working by preventing unnecessary shutdowns that can occur
with simulated sine wave output.
With a $400,000 lifetime connected equipment guarantee and a threeyear warranty, you can trust CyberPower’s commitment to high quality.
TYPICAL APPLICATIONS
• Corporate and Enterprise Servers
• Network and Storage Devices
• Edge Closets
• PBX and VoIP Installations
FE AT U R E S
• 2200 VA / 1800 W
• Double Conversion Topology
• Sine wave output, zero transfer time
• Configurable Output - 100, 110, 115, 120, 125 V,
50/60 Hz
• GreenPower UPS™ ECO Mode
• Expansion Slot
• 2U Rack Mount/Tower Convertible
• Outlets: (6) NEMA 5-20R, (1) NEMA L5-20R
• PowerPanel® Business Edition Management
Software
SPECIFICATIONS
GENERAL
UPS Topology Online Double Conversion
Energy Saving Yes, ECO Mode Eciency >95%
Energy Star Qualified Yes
INPUT
Nominal Voltage 100 V to 125 V
60 V to 69 V, 0% to 60% load
Voltage Range
Frequency Range 40 Hz to 70 Hz (auto-sensing)
Power Factor 0.99
Cold Start Yes
70 V to 79 V, 0% to 70% load
80 V to 89 V, 0% to 80% load
90 V to 95 V, 0% to 90% load
96 V to 150 V, 0% to 100% load
INPUT - CONT.
Plug Ty p e NEMA 5-20P
Cord Length (ft) 10
Cord Length (m) 3
OUTPUT
VA
Watts
Power Factor 0.82
Waveform (Battery Mode) Sine wave
Nominal Voltage
(Battery Mode)
2200 (2.2 kVA) at 120, 125 V
1980 (1.98 kVA) at 115, 110 V
1760 (1.76 kVA) at 100 V
1800 (1. 8 kW) at 120, 125 V
1620 (1.62 kW) at 115, 110 V
1440 (1.44 kW) at 100 V
100, 110, 115, 120, 125 V ±2%
(configurable)
![](/html/e3/e3b2/e3b238ea39dcdb821f4b5997c5efc6672b523ca3c63eba1d01a9b05b128f489b/bg2.png)
OL2200RTXL2U
SMART APP ONLINE UPS
SPECIFICATIONS CONT.
OUTPUT - CONT.
Frequency
ECO Mode Bypass
Voltage Range
Harmonic Distortion
(T HD)
Crest Factor 3:1
Outlets - Total 7
Outlet Type (6) NEMA 5-20R, (1) NEMA L5-20R
Overload Protection
Short Circuit Protection
Bypass
Maintenance Bypass Optional MBP20A6
Transfer Time 0ms
50/60 Hz ±0.25 Hz (auto-sensing/
configurable)
±10%, ±15% (configurable)
<3% at linear load, <5% at nonlinear load
Line Mode:
105% to 125% load for 1 min
126% to 150% load for 10 sec
Battery Mode:
105% to 130% load for 10 sec
131% to 150% load for 2 sec
UPS output cut o immediately
or input fuse / circuit breaker
protection
Internal bypass
(automatic and manual)
BAT TE RY
Runtime at Half Load 20 min
Runtime at Full Load 6.5 min
Batte r y Ty p e Sealed lead acid
Battery Size 12 V/9 Ah
Battery Quantity 6
Replaceable Ye s
Replacement Battery RB1290X6A
Hot Swappable Yes
Typical Recharge Time 4 h (0% to 90%)
Smart Battery
Management (SMB) Mode
Extended Battery Module
(EBM)
Yes
Optional BP72V60ART2U
SURGE PROTECTION & FILTERING
Surge Protection
Phone RJ-11 / Ethernet
Surge Protection RJ-45
EMI/RFI Filtration Yes
1335 Joules, per IEC 61000-4-5
Level 3
1-In / 1-Out (combo)
MANAGEMENT & COMMUNICATIONS
LCD Multifunction LCD
Rotatable LCD Control
Panel Option
Removable LCD Control
Panel Option
HID Compliant USB Port Yes
Serial Port Yes
Emergency Power O
(EPO) Port
Dry Contact Port Yes
Cables Included USB cable, Serial cable
LED Indicators
Audible Alarms
Software PowerPanel® Business Edition
Upgradeable Firmware Yes, requires RMCARD205
Expansion Slot
Yes
Yes, requires DB26 cable (not
included)
Yes
Power On (white)
Line Mode (green)
Battery Mode (yellow)
Bypass Mode (yellow)
Fault (red)
Replace Battery (red)
Battery Mode, Battery Low,
Overload, UPS Fault
Yes, for optional RMCARD205
or R E L AYIO500
PHYSICAL
Form Factor
Enclosure Construction Steel
Rack Mounting Hardware Included
Physical Dimensions (WxHxD) (cm)
Physical Dimensions (WxHxD) (in)
Physical Dimensions (WxHxD) (mm)
Weight (kg) 30.93
Weight (lb) 68.2
Rack Units 2U
Rack / Tower Convertible
(Rotatable LCD)
43.18 x 8.89 x 59.99 (cm)
17 x 3.5 x 23.62 (in)
432 x 89 x 600 (mm)