SAFETY AND EMC IN STRUCTIONS
This manual contains important safety instructions. Please read and follow all instructions
carefully during installation and operation of the unit. Read this manual thoroughly before
attempting to unpack, install, or operate your Emergency Power System (EPS).
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and
humidity controlled indoor area free of conductive contaminants. (Please see specifications
for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover.
CAUTION! EPS must be connected to an AC power outlet with circuit breaker
protection. Do not plug into an outlet that is not grounded. If you need to de-energize this
equipment, turn off and unplug the unit.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power
source before servicing EPS, replacing the external battery or installing equipment.
CAUTION! To reduce the risk of fire, only connect the EPS to a circuit with 25 amperes
maximum branch circuit over-current protection in accordance with the CE requirement.
CAUTION! The building wiring socket outlet (shockproof socket outlet) must be easily
accessible and close to the EPS.
(SAVE THESE INSTRUCTIONS)
CAUTION! Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable
of your equipment) to connect the EPS to the building wiring socket outlet (shockproof
socket outlet).
CAUTION! Please use only VDE-tested, CE-marked power cables to connect the loads
to the EPS.
CAUTION! When installing the equipment, ensure that the sum of the leakage current of
the EPS and the connected equipment does not exceed 3.5mA.
CAUTION! This is permanently connected equipment and only qualified maintenance
personnel may carry out installations.
CAUTION! Do not disconnect the mains cable on the EPS or the building wiring socket
outlet (shockproof socket outlet) during operations since this would remove the protective
ground of the EPS and of all connected loads.
2
CPS3000PIE
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!
DO NOT use in any circumstance that would affect operation or safety of any life support
equipment or with any medical applications or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or
electric shock, do not use with or near an aquarium. Condensation from the aquarium can
cause the unit to short out.
DO NOT USE WITH LASER PRINTERS! The power demands of these devices
will overload and possibly damage the unit.
DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO
DIRECT SUNLIGHT OR NEAR HEAT!
DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS’S
HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR
DRYERS TO EPS OUTPUT SOCKETS.
SAFETY:
EN62040-1-1
EMI:
Conducted Emission: IEC/EN 62040-2…Category C2
Radiated Emission: IEC/EN 62040-2……Category C2
Harmonic Current: IEC/EN61000-3-2
Voltage Fluctuations and Flicker: IEC/EN61000-3-3
EMS:
IEC/EN61000-4-2(ESD)
IEC/EN61000-4-3(RS)
IEC/EN61000-4-4(EFT)
IEC/EN61000-4-5(lightning surge)
IEC/EN61000-2-2 (Immunity to low frequency signals)
3
CPS3000PIE
INST ALLING YOUR EPS
UNPACKING
Inspect the EPS upon receipt. The box should contain the following:
EPS unit x1; Installation Guide x1; User manual x1; Warranty card x1.
AUTOMATIC VOLTAGE REGULATOR
Utility power is inconsistent. The EPS increases low voltage to computer safe 220 volts. The
EPS automatically provides battery backup (External battery connection required) if the
voltage drops below 140 volts or exceeds 300 volts.
HARDWARE INSTALLATION GUIDE
1 . Your new EPS may be used immediately upon receipt. However , recharging the exte rna l
battery for at least 8 hours is recommended to ensure that the battery’s maximum
charge capacity is achieved (Charging time varies with capacity and a 100Ah or great
battery is recommended). To recharge the external battery, simply leave the unit plugged
into an AC outlet. Your EPS is equipped with an auto-charge feature. When the EPS is
plugged into an AC outlet, the external battery will automatically recharge. The unit will
charge in both the ON and OFF positions.
2. DO NOT plug a laser printer, paper shredder , copier, space heater, vacuum or other
large electrical device into the EPS. The power demand of these devices may
overload and damage the unit. DO NOT use with medical or life support
equipment. DO NOT use with or near aquariums as condensation may cause the
unit to short.
3. After connecting the hard wires, plug the EPS into a 2 pole, 3 wire grounded receptacle
(wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and
does not service equipment with large electrical demands (e.g. refrigerator, copier, etc…).
The warranty prohibits the use of extension cords, outlet strips, and surge strips.
4. Press the power switch to turn the unit on. The power on indicator light will illuminate and
the unit will beep once.
5. If an overload is detected, an audible alarm will sound and the unit will emit one long beep.
To correct this, turn the EPS off and unplug at least one piece of equipment from the
battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker is
depressed and then turn the EPS on.
6. To maintain optimal battery charge, leave the EPS plugged into an AC outlet at all times.
UPS will not function if the Bypass For Charge Only switch is enabled. Enabling the
switch provides the bypass for charge only.
4