CyberPower Systems CPS3000PIE User Manual

CPS3000PIE
USER MANUAL
K01-0000010-00
CPS3000PIE
TABLE OF CONTENTS
SAFETY AND EMC INSTRUCTIONS………….……………………………………….………1
INSTALLING YOUR EPS………………………….…………………………… …….……3
BASIC OPERATION…………………………………………...................................................4
REPLACING THE BATTERY…………………….……………………………………….…...….6
DEFINITIONS FOR ILLUMINATED LCD………….……………………………………7
EPS STATUS INQUIRY AND FUNCTIONS SETUP…….……………………………………8
FAULT WARNING DISPLAY AND ALARM……………………………………….………10
TROUBLESHOOTING…………………………………………………….............................11
TECHNICAL SPECIFICATIONS…………………………………………………….………..…12
1
CPS3000PIE
K01-0000010-00
SAFETY AND EMC IN STRUCTIONS
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your Emergency Power System (EPS).
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and
humidity controlled indoor area free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover. CAUTION! EPS must be connected to an AC power outlet with circuit breaker
protection. Do not plug into an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the unit.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power
source before servicing EPS, replacing the external battery or installing equipment.
CAUTION! To reduce the risk of fire, only connect the EPS to a circuit with 25 amperes
maximum branch circuit over-current protection in accordance with the CE requirement.
CAUTION! The building wiring socket outlet (shockproof socket outlet) must be easily
accessible and close to the EPS.

(SAVE THESE INSTRUCTIONS)

CAUTION! Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable
of your equipment) to connect the EPS to the building wiring socket outlet (shockproof socket outlet).
CAUTION! Please use only VDE-tested, CE-marked power cables to connect the loads
to the EPS.
CAUTION! When installing the equipment, ensure that the sum of the leakage current of
the EPS and the connected equipment does not exceed 3.5mA.
CAUTION! This is permanently connected equipment and only qualified maintenance
personnel may carry out installations.
CAUTION! Do not disconnect the mains cable on the EPS or the building wiring socket
outlet (shockproof socket outlet) during operations since this would remove the protective ground of the EPS and of all connected loads.
2
CPS3000PIE
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT!
DO NOT use in any circumstance that would affect operation or safety of any life support equipment or with any medical applications or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or
electric shock, do not use with or near an aquarium. Condensation from the aquarium can cause the unit to short out.
DO NOT USE WITH LASER PRINTERS! The power demands of these devices
will overload and possibly damage the unit.
DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR HEAT!
DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS’S HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO EPS OUTPUT SOCKETS.
SAFETY:
EN62040-1-1
EMI:
Conducted Emission: IEC/EN 62040-2…Category C2 Radiated Emission: IEC/EN 62040-2……Category C2 Harmonic Current: IEC/EN61000-3-2 Voltage Fluctuations and Flicker: IEC/EN61000-3-3
EMS:
IEC/EN61000-4-2(ESD) IEC/EN61000-4-3(RS) IEC/EN61000-4-4(EFT) IEC/EN61000-4-5(lightning surge) IEC/EN61000-2-2 (Immunity to low frequency signals)
3
CPS3000PIE

INST ALLING YOUR EPS

UNPACKING

Inspect the EPS upon receipt. The box should contain the following: EPS unit x1; Installation Guide x1; User manual x1; Warranty card x1.
AUTOMATIC VOLTAGE REGULATOR
Utility power is inconsistent. The EPS increases low voltage to computer safe 220 volts. The EPS automatically provides battery backup (External battery connection required) if the voltage drops below 140 volts or exceeds 300 volts.

HARDWARE INSTALLATION GUIDE

1 . Your new EPS may be used immediately upon receipt. However , recharging the exte rna l
battery for at least 8 hours is recommended to ensure that the battery’s maximum
charge capacity is achieved (Charging time varies with capacity and a 100Ah or great battery is recommended). To recharge the external battery, simply leave the unit plugged into an AC outlet. Your EPS is equipped with an auto-charge feature. When the EPS is plugged into an AC outlet, the external battery will automatically recharge. The unit will charge in both the ON and OFF positions.
2. DO NOT plug a laser printer, paper shredder , copier, space heater, vacuum or other
large electrical device into the EPS. The power demand of these devices may overload and damage the unit. DO NOT use with medical or life support equipment. DO NOT use with or near aquariums as condensation may cause the unit to short.
3. After connecting the hard wires, plug the EPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. refrigerator, copier, etc…). The warranty prohibits the use of extension cords, outlet strips, and surge strips.
4. Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will beep once.
5. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the EPS off and unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker is depressed and then turn the EPS on.
6. To maintain optimal battery charge, leave the EPS plugged into an AC outlet at all times. UPS will not function if the Bypass For Charge Only switch is enabled. Enabling the switch provides the bypass for charge only.
4
CPS3000PIE

BASIC OPERA TIO N

DESCRIPTION

1. AC Outlets The unit has two Schuko outlets and one terminal for connected equipment which ensures temporary uninterrupted operation of your equipment during a power failure. Max. output of 1a is 20A; Max. output of 1b is 15A; Max. output wattage of (1a+1b) is 2250W
Note:Maximum cord length is 10 meters and the cable O.D. must be 12AWG or greater.
2. AC Inlet
AC input terminals
NoteThe O.D. of the distribution cables must be 12AWG or greater.
3.DC Inlet
Battery input terminals
NoteMaximum battery wiring cable length is 2 meters and the cable O.D. must be 2AWG or greater.
4. DC Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
5. AC Output Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection. The breaker only works on 1b.
6. AC Input Circuit Breaker
Located on the side of the EPS, the circuit breaker serves to provide overload and fault protection.
7. Battery Input Wiring Fault LED
Battery input wiring fault LED will illuminate to indicate the wiring polarity is reversed.
8. Bypass Switch
Enabling this switch provides the bypass for charge only. UPS will not function if the switch is enabled.
9. Power Switch
Used as the master on/off switch for equipment connected to the battery power supplied outlets.
5
CPS3000PIE
10. Power On Indicator
This LED is above the power switch. It illuminates when the utility condition is normal and the EPS outlets are providing power, free of surges and spikes.
11. LCD Module Display
High resolution and intelligent LCD display shows all the EPS information with icons and messages. For more information please check the DEFINITIONS FOR ILLUMINATED LCD INDICATORS section.
12. LCD Display Toggle / Selected Switch
Users can monitor EPS status and set up functions using the toggle.
Installation Guide
Note: The installation must be done by professionals.
1. Remove the cover from the back of the machine.
2. Make sure both the POWER SW. and the BATTERY SW. are turned off. (Step1)
3. Connect the AC OUTPUT connections (AC
4. Connect the AC power source to AC INPUT
5. Connect the batteries to the BATTERY INPUT. (Step4)
UPS will not function if the switch is enabled. the bypass for charge only.
plugs or terminal connections). (Step2)
(Make sure AC power is off first). (Step3)
WIRING FAULT LED will illuminate to indicate the wiring polarity is reversed.
Enabling this switch provides
Step 1
Step 2
Step 3
Step 4
6
6. If the battery box or the battery
connection has a switch, please turn it on first.
7. Turn on the BATTERY SW. on the back of the machine (Step 5)
CPS3000PIE
8. Make the AC input connection and turn on the Power Switch on the front panel. The Power On Indicator and the LCD Module Display will blink 4 times. Press the Display toggle (Selected Switch) once. The output voltage showing on the LCD Module Display should be 220V. This completes the start-up process. (Step 6)
9. Press and hold the Display toggle switch for 4 seconds. The machine will begin a self test and enter Battery Mode for 6 seconds before returning to Line Mode. Correct any issues that may be present before continuing. See the Definitions for illuminated LCD on page 7 for a list of alarm code definitions.
10. After ensuring the machine works normally, reassemble the back cover. The installation
is now complete.
11. When the external battery needs to be maintained or replaced remember to turn the
machine off. Once off, remove the AC power source and switch off the BATTERY SW. before maintenance or replacing the batteries. When the work is complete, please start from Step 3 to re-install the machine.
Step 5 Step 6

REPLACING THE BA TTERY

CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before
servicing the battery. Battery service should only be done by qualified professionals.
CAUTION! Use only the specified type and number of external batteries. Please see the
technical specifications for replacement batteries.
CAUTION! The battery may present a risk of electrical shock. Do not dispose of
battery in a fire as it may explode. Follow all local ordinances regarding proper disposal of batteries. Most retailers that sell lead-acid batteries collect used batteries for recycling.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to skin
and eyes and may be toxic.
7
CPS3000PIE
CAUTION! A battery can present a high risk of short circuit current and electrical shock.
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. Do not lay tools or metal parts on top of battery or any terminals.
4. Wear rubber gloves and boots.
5. Determine if the external battery is inadvertently grounded. If grounded, remove the source of ground. CONTACT WITH GROUNDED BATTERY CAN RESULT IN
ELECTRICAL SHOCK!

DEFINITIONS FOR ILLUMINATED LCD

The LCD Display indicates a variety of EPS operational conditions. All descriptions apply when the EPS is plugged into an AC outlet and turned on or when the EPS is on battery.
1. INPUT VOLTAGE Meter: This meter measures the
AC voltage that the EPS is receiving from the utility wall outlet. The EPS is designed, through the use of automatic voltage regulation, to continuously supply connected equipment with stable, 220 output voltages. In the event of a complete power loss, severe brownout or over-voltage the EPS will rely on its external battery
to supply consistent 220 output voltage. The Input
Voltage Meter can be used as a diagnostic tool to identify poor quality input power.
2. OUTPUT VOLTAGE Meter: This meter measures, the AC voltage that the EPS is
providing to the computer. It displays normal line mode, AVR mode, and battery backup mode.
3. NORMAL MODE Icon: This icon will illuminate when the EPS is working under normal
conditions.
4. ON BAT (On Battery) Icon: During a severe brownout or blackout, this icon illuminates
and an alarm sounds (2 short beeps followed by a pause) to indicate the EPS is operating from its external batteries. During a prolonged brownout or blackout, the alarm will sound continuously. When the BATTERY CAPACITY Meter shows one 20% capacity segment remaining it indicates the EPS's external batteries are nearly out of power. You should save files and shut down your equipment immediately.
5. AVR (Automatic Voltage Regulator) Ico n: This icon will illuminate whenever your EPS
is automatically correcting high or low AC line voltage. This is a normal, automatic operation of your EPS, and no action is required on your part.
8
CPS3000PIE
6. SILENT MODE Icon: This icon illuminates whenever the EPS is in silent mode. The
buzzer will not beep during the battery mode until the battery reaches low capacity.
7. OVER LOAD Icon: This icon will illuminate and an alarm will sound to indicate the battery
supplied outlets are overloaded. T o clear the overload, unplug some of your equipment from the battery supplied outlets until the icon is no longer illuminated and the alarm stops.
8. FAULT MODE Icon: This icon illuminates if there is a problem with the EPS. Please
contact CyberPower Systems for further help and support.
9. BATTERY CA PACITY Me t e r : This meter displays the approximate charge level (in 20%
increments) of the EPS's external battery. During a blackout or severe brownout, the EPS will switch to battery power, the ON BAT icon will be illuminated, and the charge level will decrease.
10. LOAD CAPACITY Meter:This meter displays the approximate output load level (in 20%
increments) of the EPS's battery outlets.

EPS Status Inquiry and Functions Setup

1. General Mode
a. Press the “Display” button to check the status of the EPS
Item Unit 1 Input Voltage V 2 Output Voltage V 3 Output Frequency Hz 4 Load Kw 5 Load Capacity % 6 Battery Capacity % 7 Centigrade 8 Fahrenheit
b. Press and hold the Display toggle for 4 seconds,
z If the machine is in the Battery Mode, it enters the
status of Mute.
z If the machine is in the Line Mode, it proceeds Self
Test.
c. If the Display toggle remains untouched for over 30
seconds, the LCD backlight will turn off automatically.
9
CPS3000PIE
2. Set-up Mode
Step 1 : The machine enters Set-Up Mode after holding the Display toggle for 10
seconds. Icon 4,5,6,7,8,9 lights to indicate Set-Up Mode.
Step 2 : By pressing the Display toggle, users can switch between setup functions. User
configurable functions are as follows:
a. Delay Time: The time delay between switching from Battery Mode to Line Mode.
There are 9 different settings. The default setting is 2.0 minutes. Function description: The machine will switch from Battery Mode to Line Mode after the AC power transmission reaches stability within the preset delay time.
b. Battery AH: The function adjusts the battery charging current according to the
capacity of the connected batteries. It can be configured for 50, 100, 150 and 200AH The default setting is 200AH.
c. Nominal Output Voltage: Configures the correct electricity/voltage supplied in the
area/country where the EPS will be used. 220V, 230V and 240V may be selected. The system default setting is 220V. Function description: AVR Dynamic Voltage Compensation works automatically based on the system voltage settings.
d. Static Frequency Tolerance: There are 6 settings. The default setting is +/-10%.
Function description: The settings may be adjusted to the quality of the electricity in use.
e. Slew Rate: Also called Dynamic Frequency Tolerance. There are 5 different settings.
The default value is 4Hz/sec. Function description: “Slew Rate” indicates the tolerance of a device in accepting frequency variances. The lower “Slew Rate” results in less tolerance but better protection for the connected loads.
f. Battery Shutdown Voltage: This function adjusts the UPS shutdown point according
to the battery voltage.
The settable items are sorted by unit as in the following table
Items Unit
Delay Time Min Battery AH A Nominal Output Voltage V Static Frequency Tolerance % Slew Rate Hz Battery Shutdown Voltage V
10
CPS3000PIE
Step 3: Press and hold the toggle for 4 seconds. When the icons blink, the value of each
item can be changed by slightly pressing the toggle.
Step 4: To save the value and return to general mode, press and hold the toggle for 4
seconds.
Note: If the machine is left idle for over 30 seconds during setup, it will turn off the
backlight and return to general mode automatically.
Note: If user wants to return to general mode without saving changes, there are
two methods:
1. Wait for the backlight to turn off
2. Press and hold the “Display” toggle for 10 seconds

FAULT WARNING DISPLAY AND ALARM

1. Overheat Protection
z EPS overheatThe output of the machine is removed and the LCD display shows the
temperature exceeds 70 (157). FAULT Icon lights as well.
2. Over-voltage ProtectionThe output of the machine is removed. Over Load and FAULT Icon lights on the LCD display.
3. Battery MissingA long beep is heard and Battery Icon flashes
4. The following table shows each corresponding warning message on the LCD display and the alarm action when the machine output is off
Condition
Solution
LCD Warning
Display
Fault Icon
>70
Over Load Icon.
Fault Icon
Alarm
Rapid Beep High Temperature
Output-Off
Over 70
Long Beep Over Load Output-Off -
Load exceed the rating of EPS.
11
Check fans function and air vent clearances.
Check total load to confirm the rating of EPS.
Battery Icon Flash Beep Once Battery Missing- In Line
Mode Battery Missing.
Fault Icon 1. Rapid Beep
2. Recurring Beep
3. Long Beep
Can Not Start Up None 1. Line Input/Output
1. Low Battery
Output-Off
-- Insufficient battery
capacity.
2. Over Charge or AVR Error-- In Line Mode, battery is overcharged or AVR is faulty.
3. Short Output-Off -- Output Short Circuit Protection
Error Output-Off --
incorrect Input/Output connection
2. Cold Start Battery
High Voltage Output-Off -- the
battery voltage is too high during cold start.
CPS3000PIE
Turn the EPS off, check
battery wiring and presence of battery
1. Recharge the battery.
2. Inform service agents.
3. Check the EPS output to see if there is a short circuit.
1. Check Input/Output connection.
2. Check the reason for battery over-voltage.

TROUBLESHOOTING

Problem Possible Cause Solution
Full-time surge protection outlets stop providing power to equipment. Circuit breaker button is projecting from the side of the unit
The EPS will not turn on.
Circuit breaker has tripped due to an overload.
The on/off switch is designed to prevent damage by rapidly turning it off and on. Mechanical problem. Contact Cyberpower Systems via
Turn the EPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit breaker by depressing the button, and then turn the EPS on.
Turn the EPS off. Wa it 10 seconds and then turn the EPS on.
phone at +31 (0) 40 2348170 or visit our website at www.cyberpowersystems.com
12
CPS3000PIE

TECHNICAL SPECIFICATIONS

Model CPS3000PIE
Capacity (VA) 3000VA Capacity (Watts) 2250W Operation Technology AVR ( Single Boost & Single Buck ) AC Input Input Voltage Range 140Vac – 300Vac Input Frequency Range 50/60 Hz +/- 3 Hz (auto sensing) AC Output Number of Phase Single Phase On Battery Typical Output Voltage Pure Sine Wave at 220Vac +/- 10% Nominal Output Voltage Configuration Note Configurable for 220 : 230 : 240Vac On Battery Output Frequency 50 / 60 Hz +/- 1% Overload Protection On Utility: Circuit Breaker
On Battery: Internal Current Limiter Transfer Time < 10 ms ( Typical ) Output Receptacles Schuko * 2 + Terminal Block External Battery Voltage x Recommended Rating X Quantity 12V x 100Ah X 2 External Battery Voltage Rating 24V External Battery Type Sealed Maintenance Free Lead Acid Battery External Battery Protection DC Circuit Breaker Hot Swappable External Battery Yes Extended Runtime Yes Status Indication Indicators Power On, LCD Display Audible Alarms On Battery, Low Battery, Overload Environmental
Operating Temperature 32 to 95 ( 0 to 35℃)
Operating Relative Humidity 0 to 95% Non-Condensing Physical Dimensions (L*W*H)( mm ) 330*260*440 Weight (Kg) 36 Kg Agency Certificated CE
13