CyberPower SM30KPMX, SM180KMFX, SM300KMFX, SM600KMFX User Manual

Page 1
User’s Manual
SM30KPMX SM180KMFX SM300KMFX SM600KMFX
Page 2
Ver 1.0.2
Page 3
Safety Precautions
Safety Precautions
This manual contains information concerning the installation and operation of Modular UPS. Please carefully read this manual prior to installation. The Modular UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent). Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty.
Safety Message Definition
Danger: Serious human injury or even death may be caused, if this requirement is ignored. Warning: Human injury or equipment damage may be caused, if this requirement is ignored. Attention: Equipment damage, loss of data or poor performance may be caused, if this requirement is ignored. Commissioning Engineer: The engineer who installs or operates the equipment should be well trained in electricity and safety and familiar with the operation, debug, and maintenance of the equipment.
Warning Label
The warning label indicates the possibility of human injury or equipment damage, and advises the proper step to avoid the danger. In this manual, there are three types of warning labels as below.
Labels
Description
Danger
Serious human injury or even death may be caused, if this requirement is ignored.
Warning
Human injury or equipment damage may be caused, if this requirement is ignored.
Attention
Equipment damage, loss of data or poor performance may be caused, if this requirement is ignored.
Safety Instruction
Danger
Performed only by commissioning engineers. This UPS is designed for commercial and industrial
applications only, and is not intended for any use in life-support devices or system.
Warning
Read all the warning labels carefully before operation, and
follow the instructions.
When the system is running, do not touch the surface with
this label, to avoid any hurt of scald.
ESD sensitive components inside the UPS, anti-ESD
measure should be taken before handling.
Page 4
Safety Precautions
Move & Install
Danger
Keep the equipment away from heat source or air outlets. In case of fire, use dry powder extinguisher only, any liquid
extinguisher can result in electric shock.
Warning
Do not start the system if any damage or abnormal parts
founded.
Contacting the UPS with wet material or hands may be
subject to electric shock.
Attention
Use proper facilities to handle and install the UPS. Shielding
shoes, protective clothes and other protective facilities are necessary to avoid injury.
During positioning, keep the UPS way from shock or
vibration.
Install the UPS in proper environment, more detail in section
3.3.
Debug & Operate
Danger
Make sure the grounding cable is well connected before
connecting the power cables, the grounding cable and neutral cable must be in accordance with the local and national codes practice.
Before moving or re-connecting the cables, make sure to
cut off all the input power sources, and wait for at least 10 minutes for internal discharge. Use a multi-meter to measure the voltage on terminals and ensure the voltage is lower than 36V before operation.
Attention
The earth leakage current of load will be carried by RCCB or
RCD.
Initial check and inspection should be performed after long
time storing of UPS.
Maintenance & Replacement
Danger
All the equipment maintenance and servicing procedures
involving internal access need special tools and should be carried out only by trained personnel. The components that can only be accessed by opening the protective cover with tools cannot be maintained by user.
This UPS full complies with “IEC62040-1-1-General and
safety requirements for use in operator access area UPS”.
Dangerous voltages are present within the battery box. However, the risk of contact with these high voltages is minimized for non-service personnel. Since the component with dangerous voltage can only be touched by opening the protective cover with a tool, the possibility of touching high voltage component is minimized. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures
Page 5
Safety Precautions
in this manual.
Battery Safety
Danger
All the battery maintenance and servicing procedures
involving internal access need special tools or keys and should be carried out only by trained personnel.
When connected together, the battery terminal voltage will
exceed 400Vdc and is potentially lethal.
Battery manufacturers supply details of the necessary
precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times. Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.
Ambient temperature is a major factor in determining the
battery capacity and life. The nominal operating temperature of battery is 20°C. Operating above this temperature will reduce the battery life. Periodically charge the battery according to the battery user manuals to ensure the back-up time of UPS.
Replace the batteries only with the same type and the same
number, or it may cause explosion or poor performance.
When connecting the battery, follow the precautions for
high-voltage operation before accepting and using the battery, check the appearance the battery. If the package is damaged, or the battery terminal is dirty, corroded or rusted or the shell is broken, deformed or has leakage, replace it with new product. Otherwise, battery capacity reduction, electric leakage or fire may be caused. Before operating the battery, remove the finger ring,
watch, necklace, bracelet and any other metal jewelry
Wear rubber gloves.  Eye protection should be worn to prevent injury from
accidental electrical arcs.
Only use tools (e.g. wrench) with insulated handles.  The batteries are very heavy. Please handle and lift the
battery with proper method to prevent any human injury or damage to the battery terminal.
Do not decompose, modify or damage the battery.
Otherwise, battery short circuit, leakage or even human injury may be caused.
The battery contains sulfuric acid. In normal operation,
all the sulfuric acid is attached to the separation board and plate in the battery. However, when the battery case is broken, the acid will leak from the battery. Therefore, be sure to wear a pair of protective glasses, rubber gloves and skirt when operating the battery. Otherwise, you may become blind if acid enters your
Page 6
Safety Precautions
eyes and your skin may be damaged by the acid.
At the end of battery life, the battery may have internal
short circuit, drain of electrolytic and erosion of positive/negative plates. If this condition continues, the battery may have temperature out of control, swell or leak. Be sure to replace the battery before these phenomena happen.
If a battery leaks electrolyte, or is otherwise physically
damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the
affected area should be washed immediately with water.
Disposal
Warning
Dispose of used battery according to the local instructions
Page 7
Contents
Contents
Chapter 1 Product Introduction ............................................................................................ 1
1.1 System Configuration ............................................................................................ 1
1.2 Power Module ........................................................................................................ 2
1.3 Operation Mode ..................................................................................................... 2
1.3.1 Normal Mode ...................................................................................................... 2
1.3.2 Battery Mode ...................................................................................................... 2
1.3.3 Bypass Mode ...................................................................................................... 3
1.3.4 Maintenance Mode (Manual Bypass) ................................................................ 3
1.3.5 ECO Mode .......................................................................................................... 4
1.3.6 Auto-restart Mode ............................................................................................... 4
1.3.7 Frequency Converter Mode ............................................................................... 5
1.4 UPS Structure ........................................................................................................ 5
1.4.1 UPS Configuration .............................................................................................. 5
1.4.2 UPS Outlook ....................................................................................................... 5
Chapter 2 Installation Instruction ......................................................................................... 9
2.1 Location ................................................................................................................. 9
2.1.1 Installation Environment ..................................................................................... 9
2.1.2 Site Selection...................................................................................................... 9
2.1.3 Size and Weight ................................................................................................. 9
2.2 Unloading and Unpacking ................................................................................... 11
2.2.1 Moving and Unpacking of the Cabinet ............................................................. 11
2.2.2 Unpacking Power Module ................................................................................ 11
2.3 Positioning ........................................................................................................... 13
2.3.1 Positioning Cabinet .......................................................................................... 13
2.3.2 Installing Power Module ................................................................................... 11
2.4 Battery ................................................................................................................. 16
2.5 Cable Entry .......................................................................................................... 16
2.6 Power Cables ...................................................................................................... 19
2.6.1 Specifications ................................................................................................... 19
2.6.2 Specifications for Power Cables Terminal ....................................................... 19
2.6.3 Circuit Breaker .................................................................................................. 20
2.6.4 Connecting Power Cables ................................................................................ 20
2.7 Control and Communication Cables ................................................................... 22
2.7.1 Dry Contact Interface ....................................................................................... 23
2.7.2 Communication Interface ................................................................................. 28
Chapter 3 UPS and Module Control Panel ........................................................................ 29
3.1 Introduction .......................................................................................................... 29
3.2 LCD panel for Power Module .............................................................................. 29
3.2.1 LED Indicator .................................................................................................... 29
3.2.2 Control and Operation Keys ............................................................................. 30
3.2.3 LCD Display ...................................................................................................... 30
3.3 UPS operator panel ............................................................................................. 32
3.3.1 LED Indicator .................................................................................................... 32
3.3.2 Control and Operation Keys ............................................................................. 33
3.3.3 LCD touch Screen ............................................................................................ 34
3.4 Main Menu ........................................................................................................... 35
3.4.1 Cabinet ............................................................................................................. 35
3.4.2 Module .............................................................................................................. 37
Page 8
Contents
3.4.3 Setting .............................................................................................................. 39
3.4.4 Log .................................................................................................................... 41
3.4.5 Operate ............................................................................................................. 45
3.4.6 Scope ............................................................................................................... 46
Chapter 4 Operations ........................................................................................................ 48
4.1 UPS Start-up ....................................................................................................... 48
4.1.1 Start in Normal Mode ....................................................................................... 48
4.1.2 Start from Battery ............................................................................................. 49
4.2 Procedure for Switching between Operation Modes .......................................... 49
4.2.1 Switching the UPS from Normal Mode into Battery Mode ............................... 49
4.2.2 Switching the UPS from Normal Mode into Bypass Mode .............................. 49
4.2.3 Switching the UPS into Normal Mode from Bypass Mode .............................. 50
4.2.4 Switching the UPS from Normal Mode into Maintenance Bypass Mode......... 50
4.2.5 Switching the UPS into Normal Mode from Maintenance Bypass Mode ......... 51
4.3 Battery Maintenance ........................................................................................... 51
4.4 EPO ..................................................................................................................... 52
4.5 Installation of Parallel Operation System ............................................................ 53
Chapter 5 Maintenance ..................................................................................................... 55
5.1 Precautions .......................................................................................................... 55
5.2 Instruction for Maintaining Power Module ........................................................... 55
5.3 Instruction for Maintaining ................................................................................... 55
5.3.1 Maintaining Bypass Module for 6-slot and 10-slot Cabinet ............................. 55
5.3.2 Maintaining Static Bypass Unit for 20-slot Cabinet .......................................... 56
5.3.3 Maintenance for the Air-drawing fans .............................................................. 56
5.3.4 Battery Maintenance ........................................................................................ 56
5.3.5 Disconnect the Inner Control Neutral cable ..................................................... 57
5.4 Battery Setting ..................................................................................................... 57
5.4.1 Battery Setting .................................................................................................. 58
5.4.2 Setting of Battery Number ................................................................................ 58
5.4.3 Battery Capacity Setting ................................................................................... 58
5.4.4 Float and Boost Charge Setting ....................................................................... 58
5.4.5 EOD Voltage Setting ........................................................................................ 59
5.4.6 Charging Current Percent Limit ........................................................................ 59
5.4.7 Battery Temperature Compensate ................................................................... 59
5.4.8 Boost Charge Time Limit .................................................................................. 59
5.4.9 Auto Boost Period ............................................................................................. 59
5.4.10 Auto maintenance Discharge Period .............................................................. 59
5.4.11 Warnings for Battery and Environment Temperature Overheat ..................... 60
5.5 Replacing Dust Filter (optional) ........................................................................... 60
Chapter 6 Product Specification ........................................................................................ 61
6.1 Applicable Standards .......................................................................................... 61
6.2 Environmental Characteristics ............................................................................ 61
6.3 Mechanical Characteristic ................................................................................... 61
6.4 Electrical Characteristics ..................................................................................... 62
6.4.1 Electrical Characteristics (Input Rectifier) ........................................................ 63
6.4.2 Electrical Characteristics (Intermediate DC Link) ............................................ 63
6.4.3 Electrical Characteristics (Inverter Output) ...................................................... 63
6.4.4 Electrical Characteristics (Bypass Mains Input) ............................................... 64
6.5 Efficiency ............................................................................................................. 64
6.6 Display and Interface ........................................................................................... 64
Page 9
Chapter 1 Product Introduction
1
SM 180-600 KMFX User Manual
Chapter 1 Product Introduction
1.1 System Configuration
The Modular UPS is configured by the following part: Power modules, Bypass & Monitoring module, and cabinet with manual Bypass switch. One or several battery strings should be installed to provide backup energy once the utility fails. The UPS structure is shown in Fig. 1-1.
Rectifier
AC/DC
Main
Static Bypass
Manual Bypass
Inverter
DC/AC
Charge/
Discharge
Output
Battery
Bypass
Fig.1-1 6-slot and 10-slot UPS Configuration
Fig.1-2 20-slot UPS Configuration
Page 10
Chapter 1 Product Introduction
2
SM 180-600 KMFX User Manual
1.2 Power Module
The power module structure is shown as Fig.1-3. The power module contains a rectifier, an inverter, and a DC/DC converter for charge and discharge of the external batteries.
Rectifier
AC/DC
Inverter
DC/AC
DC/DC
Input
Battery
Output
Fig 1-3 Power module structure
1.3 Operation Mode
The Modular UPS is an on-line, double-conversion UPS that permits operation in the
following modes:
Normal mode Battery mode Bypass mode Maintenance mode (manual bypass) ECO mode Auto-restart mode Frequency Converter mode
1.3.1 Normal Mode
The inverter of power modules continuously supply the critical AC load. The
rectifier/charger derives power from the AC mains input source and supplies DC power to the inverter while simultaneously FLOAT or BOOST charging its associated backup battery.
Rectifier
AC/DC
Main
Static Bypass
Manual Bypass
Inverter
DC/AC
Charger
DC/DC
Output
Battery
Bypass
Fig.1-4 Normal mode operation diagram
1.3.2 Battery Mode
Upon failure of the AC mains input power, the inverter of power modules, which obtain power from the battery, supply the critical AC load. There is no interruption in power to
the critical load upon failure. After restoration of the AC mains input power, the” Normal
mode” operation will continue automatically without the necessity of user intervention.
Page 11
Chapter 1 Product Introduction
3
SM 180-600 KMFX User Manual
Rectifier
AC/DC
Main
Static Bypass
Manual Bypass
Inverter
DC/AC
Discharge
DC/DC
Output
Battery
Bypass
Fig.1-5 Battery mode operation diagram
1.3.3 Bypass Mode
If the inverter overload capacity is exceeded under Normal mode, or if the inverter
becomes unavailable for any reason, the static transfer switch will perform a transfer of the load from the inverter to the bypass source, with no interruption in power to the critical AC load. Should the inverter be asynchronous with the bypass, the static switch will perform a transfer of the load from the inverter to the bypass with power interruption to the load. This is to avoid large cross currents due to the paralleling of unsynchronized AC sources. This interruption is programmable but typically set to be less than 3/4 of an electrical cycle, e.g., less than 15ms (50Hz) or less than 12.5ms (60Hz). The action of transfer/re-transfer can also be done by the command through monitor.
Rectifier
AC/DC
Main
Static Bypass
Manual Bypass
Inverter
DC/AC
Charger
DC/DC
Output
Battery
Bypass
Fig.1-6 Bypass mode operation diagram
1.3.4 Maintenance Mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load
when the UPS becomes unavailable e.g. during a maintenance procedure. (See Fig.1-7).
Page 12
Chapter 1 Product Introduction
4
SM 180-600 KMFX User Manual
Rectifier
AC/DC
Main
Static Bypass
Manual Bypass
Inverter
DC/AC
Charger
DC/DC
Output
Battery
Bypass
Fig.1-7 Maintenance mode operation diagram
Danger
During Maintenance mode, dangerous voltages are present on the terminal of input, output and neutral, even with all the modules and the LCD turned off.
1.3.5 ECO Mode
To improve system efficiency, UPS rack system works in Bypass mode at normal time,
and inverter is standby. When the utility fails, the UPS transfers to Battery Mode and the inverter provide powers to the loads.
Rectifier
AC/DC
Main
Static Bypass
Manual Bypass
Inverter
DC/AC
Charger
DC/DC
Output
Battery
Bypass
Fig.1-8 ECO Mode operation diagram
Note There is a short interruption time (less than 10ms) when transfer from ECO mode to battery mode, it must be sure that the interruption has no effect on loads.
1.3.6 Auto-restart Mode
The battery may become exhausted following an extended AC mains failure. The
inverter shuts down when the battery reaches the End of Discharge Voltage (EOD). The
UPS may be programmed to “System Auto Start Mode after EOD”. The system starts
Page 13
Chapter 1 Product Introduction
5
SM 180-600 KMFX User Manual
after a delay time when the AC main recovers. The mode and the delay time are programmed by the commissioning engineer.
1.3.7 Frequency Converter Mode
By setting the UPS to Frequency Converter mode, the UPS could present a stable
output of fixed frequency (50 or 60Hz), and the bypass static switch is not available.
1.4 UPS Structure
1.4.1 UPS Configuration
The UPS configuration is provided in Table 1.1
Table1.1 UPS Configuration
Item
Components
Quantity/
pcs
Remark
6-slot Cabinet
Manual Bypass
1
Requisite, factory installed
Bypass & Monitoring module
1
Requisite, factory installed
Dust filter
1
Optional.
10-slot Cabinet
Manual Bypass
Requisite, factory installed
Bypass & Monitoring module
1
Requisite, factory installed
Dust filter
1
Optional.
20-slot Cabinet
Power distribution cabinet (CB of Input, Bypass Input,
Output and Manual Bypass)
1
Requisite, factory installed
Monitoring unit
1
Requisite, factory installed
Bypass unit
1
Requisite, factory installed
Dust filter
1
Optional
30 kVA
Power module
Power module
1-20
Requisite, installed on site.
1.4.2 UPS Outlook
The UPS outlook is shown as Fig.1-9 to Fig.1-11.
Page 14
Chapter 1 Product Introduction
6
SM 180-600 KMFX User Manual
Fig.1-9 Outlook of 6-slot UPS
Fig.1-10 Outlook of 10-slot UPS
Fig.1-11 Outlook of 20-slot UPS
The UPS front view are shown in Fig.1-12 to Fig. 1-14
Page 15
Chapter 1 Product Introduction
7
SM 180-600 KMFX User Manual
Fig.1-12 Front view of 6-slot UPS Fig. 1-13 Front view of 10-slot UPS
Fig. 1-14 Front view of 20-slot UPS
①LCD control panel; ②SPD; ③Manual Bypass switch ④Battery cold start;
⑤Monitoring &static bypass module; ⑥Monitoring unit; ⑦Static Bypass unit;
⑧Output switch of 20-slot cabinet Q3; ⑨Input switch of 20-slot cabinet Q1
The UPS back view are shown in Fig.2-15 to Fig.2-17.
Page 16
Chapter 1 Product Introduction
8
SM 180-600 KMFX User Manual
.
Fig. 1-15 Back view of 6-slot UPS Fig. 1-16 Back view of 10-slot UPS
Fig. 1-17 Back view of 20-slot UPS
①PDU; ②Bypass Input switch of 20-slot cabinet Q3;
Manual bypass switch of 20-slot cabinet Q3
Page 17
Chapter 2 Installation Instruction
9
SM 180-600 KMFX User Manual
Chapter 2 Installation Instruction
2.1 Location
As each site has its requirements, the installation instructions in this section are to act as a guide for the general procedures and practices that should be observed by the installing engineer.
2.1.1 Installation Environment
The UPS is intended for indoor installation and uses forced convection cooling by internal fans. Please make sure there is enough space for the UPS ventilation and cooling. Keep the UPS far away from water, heat and inflammable and explosive, corrosive material. Avoid installing the UPS in the environment with direct sunlight, dust, volatile gases, corrosive material and high salinity. Avoid installing the UPS in the environment with conductive dirt. The operating environment temperature for battery is 20 to -25. Operating above 25
will reduce the battery life, and operation below 20 will reduce the battery capacity. The battery will generate a little amount of hydrogen and oxygen at the end of charging;
ensure the fresh air volume of the battery installation environment must meet EN50272-2001 requirements. If external batteries are to be used, the battery circuit breakers (or fuses) must be mounted as close as possible to the batteries, and the connecting cables should be as short as possible.
2.1.2 Site Selection
Ensure the ground or installation platform can bear the weight of the UPS cabinet ,batteries and battery rack. No vibration and less than 5 degree inclination horizontally. The equipment should be stored in a room so as to protect it against excessive humidity and heat sources. The battery needs to be stored in dry and cool place with good ventilation. The most suitable storage temperature is 20 to 25.
2.1.3 Size and Weight
Ensure there is enough space for the placement of the UPS. The room reserved for the UPS cabinet is shown in 2-1.
Attention
Ensure the following space margin: at least 0.8m before the front of the 6-slot or the 10-slot cabinet, at least 1 m for the 20-slot cabinet, so as to easily maintain the power module with the front door fully open; at least 0.5m at behind of 6-slot or the 10-slot cabinet, at least 0.6 m for 20-slot cabinet for ventilation and cooling. The space reserved for the cabinet is shown in Fig.3-2.
Page 18
Chapter 2 Installation Instruction
10
SM 180-600 KMFX User Manual
(a.) 6-slot cabinet (b.) 10-slot cabinet
(c.) 20-slot cabinet
Fig.2-1 Space reserved for the cabinetUnitmm
The dimension and weight for the UPS cabinet is shown in Table 2.1
Table 2.1 Weight for the cabinet
Configuration
Dimension(W×D×H)(mm)
Weight(Kg)
6-slot Cabinet
(with bypass module)
600×1100×1600
170
Page 19
Chapter 2 Installation Instruction
11
SM 180-600 KMFX User Manual
10-slot Cabinet
(with bypass module)
600×1100×2000
220
20-slot Cabinet
(with bypass module)
2000×1100×2000
620
30KVA power module
460×790×133
34
2.2 Unloading and Unpacking
2.2.1 Moving and Unpacking of the Cabinet
The steps to move and unpack the cabinet are as follows
1. Check if any damages to the packing. (If any, contact to the carrier)
2. Transport the equipment to the designated site by forklift, as shown in Fig.2-2.
Fig.2-2 Transport to the designated site
3. Open the top plate of the steel-edged wooden case with slotted awl and pier, followed by side boards (see Fig.2-3)..
Fig.2-3 Disassemble the case
Page 20
Chapter 2 Installation Instruction
12
SM 180-600 KMFX User Manual
4. Remove the protective foam around the cabinet.
Fig.2-4 Remove the protective foam
5. Check the UPS. (a) Visually examine if there are any damages to UPS during transportation. If any, contact to the carrier. (b) Check the UPS with the list of the goods. If any items are not included in the list, contact to our company or the local office.
6. Dismantle the bolt that connects the cabinet and wooden pallet after disassembly.
7. Move the cabinet to the installation position.
Attention
Be careful while removing to avoid scratching the equipment.
2.2.2 Unpacking Power Module
1. The steps to move and unpack the power module are as follows
2. The packing case must be placed on the platform smoothly, as is shown in Fig.3-5
Fig.2-5 Place on platform smoothly
3. Cut the plastic packing belt and scotch tape to open the carton.
Page 21
Chapter 2 Installation Instruction
13
SM 180-600 KMFX User Manual
(see Fig.2-6.
Fig.2-6 Open the carton
4. Remove the foam cover (See Fig.2-7).
Fig.2-7 Remove the foam cover
5. Take out the UPS with plastic package and dismantle the packaging materials.
Attention
The waste materials of unpacking should be disposed to meet the demand for environmental protection.
2.3 Positioning
2.3.1 Positioning Cabinet
The UPS cabinet has two way of supporting itself: One is to support itself temporarily by the
4 wheels at the bottom(12 for the 20-slot)making it convenient to adjust the position of the cabinetThe other is by anchor bolts to support the cabinet permanently after adjusting the position of the cabinet. The supporting structure is shown in Fig. 2-8..
Page 22
Chapter 2 Installation Instruction
14
SM 180-600 KMFX User Manual
(a.) 6&10-slot cabinet
(b.) 20-slot cabinet
①Adjustable anchor bolt ②L-shape corner fittings ③ supporting wheels
Fig.2-8 Supporting structureBottom view
The steps to position the cabinet are as follows
1. Ensure the supporting structure is in good condition and the mounting floor is smooth and strong.
2. Retract the anchor bolts by turning them counterclockwise using wrench, the cabinet is then supported by the four wheels.
3. Adjust the cabinet to the right position by the supporting wheels.
4. Put down the anchor bolts by turning them clockwise using wrench, the cabinet is then supported by the four anchor bolts.
5. Ensure the four anchor bolts are in the same height and the cabinet is fixed and immovable.
6. Positioning done.
Page 23
Chapter 2 Installation Instruction
15
SM 180-600 KMFX User Manual
Attention
Auxiliary equipment is needed when the mounting floor is not solid enough to support the cabinet, which helps distribute the weight over a larger area. For instance, cover the floor with iron plate or increase the supporting area of the anchor bolts.
2.3.2 Installing Power Module
The installation position of power module is shown in Fig.2-10 .Please install the power modules following the principle of from bottom to top to prevent inclination of the cabinet due to high center of gravity. The steps of installing power module are as follows (Take the 10-slot cabinet as example):
1. Ensure the cabinet is fixed and no damage to the body and inserting port of the power module.
2. Hold the handler and the body of the power module by two persons at each side.
3. Insert the module in the installation position, and push it into the cabinet smoothly.
4. Fix the module to the cabinet though the mounting holes on two sides of the front plate of the module (See Fig.2-9 at right).
5. Installing Power Module done.
Fig.2-9 Installing power module
Note The installing method of bypass module for 6-slot and 10-slot is the same as the power module. The installing of Static Bypass Unit and Monitoring Unit for 20-slot cabinet needs to be split the inner cable and copper bars.
Page 24
Chapter 2 Installation Instruction
16
SM 180-600 KMFX User Manual
Attention
Do not place the module on the floor by rear side with connectors; All installation works for bypass module and power module should be done by 2
persons together, for its heavy weight.
2.4 Battery
Three terminals(positive,neutral,negative)are drawn from the battery unit and connected
to UPS system. The neutral line is drawn from the middle of the batteries in series (See Fig.2-9).
+
-
N
N
40 batteries in series
403921
Fig.2-9 Battery string wiring diagram
Danger
The battery terminal voltage is of more than 400Vdc, please follow the safety instructions to avoid electric shock hazard. Ensure the positive, negative, neutral electrode is correctly connected from the battery unit terminals to the breaker and from the breaker to the UPS system.
2.5 Cable Entry
For the 6-slot and 20-slot cabinet, both bottom and top cable entry are available. For the 10-slot cabinet, the top cable entry is available. However, if bottom cable entry is
required, optional parts should be added. The cable entry are shown in Fig.3-10, Fig.3-11 and Fig.3-12
Page 25
Chapter 2 Installation Instruction
17
SM 180-600 KMFX User Manual
(a.) Bottom entry (b.) Top entry
Fig.2-10 Cable entry for 6-slot cabinet
Fig.3-11 Top entry for 10-slot cabinet
Page 26
Chapter 2 Installation Instruction
18
SM 180-600 KMFX User Manual
Bottom entry
Top entry
Fig.3-12 Cable entry for 20-slot cabinet
Page 27
Chapter 2 Installation Instruction
19
SM 180-600 KMFX User Manual
2.6 Power Cables
2.6.1 Specifications
The UPS power cables are recommended in Table 2.2.
Table 2.2 Recommended cables for power cables
Contents
150/25
180/30
250/25
300/30
500/25
600/30
Main Input
Cable
(mm²)
A
70
95
150
185
2*150
2*185 B 70
95
150
185
2*150
2*185 C 70
95
150
185
2*150
2*185 N 70
95
150
185
2*150
2*185
Output
Cable
(mm²)
A
70
70
120
150
2*120
2*150 B 70
70
120
150
2*120
2*150 C 70
70
120
150
2*120
2*150
N
70
70
120
150
2*120
2*150
Bypass
Input
(Optional)
Cable
(mm²)
A
70
70
120
150
2*120
2*150
B
70
70
120
150
2*120
2*150 C 70
70
120
150
2*120
2*150 N 70
70
120
150
2*120
2*150
Battery
Cable
(mm²)
+
95
95
185
240
2*185
2*240
-
95
95
185
240
2*185
2*240 N 95
95
185
240
2*185
2*240
PE
Cable
(mm²)
PE
70
70
95
95
120
120
Note
The recommended cable section for power cables are only for situations described below
Ambient temperature30.  AC loss less than 3%DC loss less than 1%The length of the AC power cables are no
longer than 50 m and the length of the DC power cables are no longer than 30 m.
Currents listed in the table are based on the 380V system (Line-to-line voltage) .For 400 V
system, the currents is 0.95 times and for the 415V system the current is 0.92 times.
The size of neutral lines should be 1.5~1.7 times the value listed above when the
predominant load is non-linear.
2.6.2 Specifications for Power Cables Terminal
Specifications for power cables connector are listed as Table 2.3.
Table 2.3 Requirements for power module terminal
Model
Terminal
Connection
Bolt
Bolt Aperture
Torque
6-slot cabinet
Main Input
Cables crimped
OT terminal
M10 / 15Nm
Bypass Input
Cables crimped
OT terminal
M10 / 15Nm
Battery
Cables crimped
OT terminal
M10 / 15Nm
Output
Cables crimped
OT terminal
M10 / 15Nm
PE
Cables crimped
OT terminal
M10 / 15Nm
10-slot cabinet
Main Input
Cables crimped
OT terminal
M12
13mm
22Nm
Bypass Input
Cables crimped
OT terminal
M12
13mm
22Nm
Page 28
Chapter 2 Installation Instruction
20
SM 180-600 KMFX User Manual
Battery
Cables crimped
OT terminal
M12
13mm
22Nm
Output
Cables crimped
OT terminal
M12
13mm
22Nm
PE
Cables crimped
OT terminal
M12
13mm
22Nm
20-slot cabinet
Main Input
Cables crimped
OT terminal
M16
17mm
96Nm
Bypass Input
Cables crimped
OT terminal
M16
17mm
96Nm
Battery
Cables crimped
OT terminal
M16
17mm
96Nm
Output
Cables crimped
OT terminal
M16
17mm
96Nm
PE
Cables crimped
OT terminal
M12
13mm
22Nm
2.6.3 Circuit Breaker
The circuit breakers (CB) for the system are recommended in Table 2.4.
Table 2.4 Recommended CB
Installed position
6-slot cabinet
10-slot cabinet
20-slot cabinet
Input CB
300A/3P
600A/3P
/
Bypass Input CB
250A/3P
500A/3P
/
Output CB
250A/3P
500A/3P
/
Battery CB
400A,500Vdc
800A,500Vdc
1250A,500Vdc
For the 20-slot cabinet, the Main Input, Bypass Input and Output CB are installed in the Cabinet.
Attention
The CB with RCD (Residual Current Device) is not suggested for the system.
2.6.4 Connecting Power Cables
The steps of connecting power cables are as follows:
1. Verify that all the switches of the UPS are completely open and the UPS internal maintenance bypass switch is open. Attach necessary warning signs to these switches to prevent unauthorized operation.
2. Open the back door of the cabinet, remove the plastic cover. The input and output terminal, battery terminal and protective earth terminal are shown in Fig.2-11 &Fig 2.13.
Page 29
Chapter 2 Installation Instruction
21
SM 180-600 KMFX User Manual
Fig.2-13 6-slot connections terminals
Fig.2-14 10-slot connections terminals
Fig.2-15 20-slot connections terminals
3. Connect the protective earth wire to protective earth terminal (PE).
4. Connect the AC input supply cables to the Input terminal and AC output supply cables to the Output terminal.
5. Connect the Battery cables to the Battery terminal.
6. Check to make sure there is no mistake and re-install all the protective covers.
Attention
The operations described in this section must be performed by authorized electricians or
Page 30
Chapter 2 Installation Instruction
22
SM 180-600 KMFX User Manual
qualified technical personnel. If you have any difficulties, contact the manufacturer or agency.
Warning
Tighten the connections terminals to enough torque moment, refer to Table 3.3, and
please ensure correct phase rotation.
Before connectionensure the input switch and the power supply are offattach warnings
label to warn not to operate by others
The grounding cable and neutral cable must be connected in accordance with local and
national codes.
2.7 Control and Communication Cables
The front panel of the bypass module provides dry contact interface (J2-J11) and communication interface (RS232RS485,SNMP ,Intelligent card interface and USB port)as it is shown in Fig.2-14.
Fig.2-16 Dry contact &communication interface for 6-slot and 10-slot cabinet
Dry Contact Interface
SNMP
Card
Intelligent
Slot
USB Port RS485
RS232
Dry
contact
SNMP
card
Intelligent
card
USB
RS485
RS232
Page 31
Chapter 2 Installation Instruction
23
SM 180-600 KMFX User Manual
Fig.2-17 Dry contact &communication interface for20-slot cabinet
The UPS accepts external signal from zero-voltage (dry) contacts connected through external dry contact terminals produced and phoenix terminals. Through software programming, these signals become active when these contacts connect to +24V to ground).The cables connected to DRY terminal must be separated from power cables. Moreover, these cables should be double insulated with a typical 0.5 to 1.5 mm2 cross-section area for a maximum connection length between 25 and 50 meters.
2.7.1 Dry Contact Interface
Dry contact interface includes port J2-J11 and the functions of the dry contact are shown in Table 2.5.
Table 2.5 Functions of the port
Port
Name
Function
J2-1
TEMP_BAT
Detection of battery temperature
J2-2
TEMP_COM
Common terminal for temperature detection
J3-1
ENV_TEMP
Detection of environmental temperature
J3-2
TEMP_COM
Common terminal for temperature detection
J4-1
REMOTE_EPO_NC
Trigger EPO when disconnect with J4-2
J4-2
+24V_DRY
+24V
J4-3
+24V_DRY
+24V
J4-4
REMOTE_EPO_NO
Trigger EPO when shorted with J4-3
J5-1
+24V_DRY
+24V
J5-2
GEN_CONNECTED
Input dry contact , function is settable , Default: interface for generator
J5-3
GND_DRY
Ground for +24V
J6-1
BCB Drive
Output dry contact, function is settable. Default: Battery trip signal
J6-2
BCB_Status
Input dry contact, function is settable. Default: BCB Status and BCB Online, (Alert no battery when BCB Status is invalid).
J7-1
GND_DRY
Ground for +24V
J7-2
BCB_Online
Input dry contact, function is settable. Default: BCB Status and BCB Online (Alert no battery when BCB Status is invalid).
J8-1
BAT_LOW_ALARM_NC
Output dry contact (Normally closed), function is settable.
Default: Low battery alarming
J8-2
BAT_LOW_ALARM_NO
Output dry contact (Normally open), function is settable. Default: Low battery alarming
J8-3
BAT_LOW_ALARM_GND
Common terminal for J8-1 and J8-2
J9-1
GENERAL_ALARM_NC
Output dry contact, (Normally closed) function is settable.
Default: Fault alarming
J9-2
GENERAL_ALARM_NO
Output dry contact, (Normally open) function is settable.
Default: Fault alarming
J9-3
GENERAL_ALARM_GND
Common terminal for J9-1 and J9-2
J10-1
UTILITY_FAIL_NC
Output dry contact, (Normally closed) function is settable.
Page 32
Chapter 2 Installation Instruction
24
SM 180-600 KMFX User Manual
Default: Utility abnormal alarming
J10-2
UTILITY_FAIL_NO
Output dry contact, (Normally open) function is settable.
Default: Utility abnormal alarming
J10-3
UTILITY_FAIL_GND
Common terminal for J10-1 and J10-2
Note The settable functions for each port can be set by the monitor software. The default functions of each port are described as follows.
Battery Warning Output Dry Contact Interface
The input dry contact J2 and J3 can detect the temperature of batteries and environment respectively, which can be used in environment monitoring and battery temperature compensation. Interfaces diagram for J2 and J3 are shown in Fig.2-15, the description of interface is in Table
2.6.
J2
J3
TEMP_BAT
TEMP_ENV
Fig.2-15 J2 and J3 for temperature detecting
Table 2.6 Description of J2 and J3
Port
Name
Function
J2-1
TEMP_BAT
Detection of battery temperature
J2-2
TEMP_COM
Common terminal
J3-1
ENV_TEMP
Detection of environmental temperature
J3-2
TEMP_COM
Common terminal
Note Specified temperature sensor is required for temperature detection (R25=5Kohm, B25/50=3275), please confirm with the manufacturer, or contact the local maintenance engineers when placing an order.
Remote EPO Input Port
J4 is the input port for remote EPO. It requires shorting NC and +24V and disconnecting NO and +24V during normal operation, and the EPO is triggered when opening NC and +24V or shorting the NO and +24V. The port diagram is shown in Fig.2-16, and port description is shown in Table 2.7.
Page 33
Chapter 2 Installation Instruction
25
SM 180-600 KMFX User Manual
EPO_NC
+24V
+24V
J4
EPO_NO
+24V
+24V
+24V
Fig.2-16 Diagram of input port for remote EPO
Table 2.7 Description of input port for remote EPO
Port
Name
Function
J4-1
REMOTE_EPO_NC
Trigger EPO when disconnect with J4-2
J4-2
+24V_DRY
+24V
J4-3
+24V_DRY
+24V
J4-4
REMOTE_EPO_NO
Trigger EPO when connect with J4-3
Generator Input Dry Contact
The default function of J5 is the interface for generator J5 Connect pin 2 of J5 with +24V power supply; it indicates that the generator has been connected with the system. The interface diagram is shown in Fig.2-17, and interface description is shown in Table 2.8.
J5
GEN
+24V
AUX-N.O. AUX-N.O.
Generator
Fig.2-17 Diagram of status interface and connection of generator
Table 2.8 Description of status interface and connection of generator
Port
Name
Function
J5-1
+24V_DRY
+24V
J5-2
GEN_CONNECTED
Connection status of generator
J5-3
GND_DRY
Power ground for +24V
BCB Input Port
The default function of J6 and J7 are the ports of BCB. The port diagram is shown in Fig.2-18, and description is shown in Table 2.9.
Page 34
Chapter 2 Installation Instruction
26
SM 180-600 KMFX User Manual
BCB_DRV
BCB_CONT
J6
J7
BCB_ONL
+24V
+24V
+24V
Fig.2-18 BCB Port
Table 2.9 Description of BCB port
Port
Name
Function
J6-1
BCB_DRIV
BCB contact drive, provides +24V voltage,20mA drive signal
J6-2
BCB_Status
BCB contact status, connect with the normally open signal of BCB
J7-1
GND_DRY
Power ground for +24V
J7-2
BCB_Online
BCB on-line input (normally open) , BCB is on-line when the signal is connecting with J7-1
Battery Warning Output Dry Contact Interface
The default function of J8 is the output dry contact interface, which presents the battery warnings of low or excessive voltage, when the battery voltage is lower than set value, an auxiliary dry contact signal will be activated via the isolation of a relay. The interface diagram is shown in Fig.2-19, and description is shown in Table 2.10.
J8
BAT_LOW_NC
BAT_LOW_N
O
GND
Fig.2-19 Battery warning dry contact interface diagram
Table2.10 Battery warning dry contact interface description
Port
Name
Function
J8-1
BAT_LOW_ALARM_NC
Battery warning relay (normally closed) will be open during warning
J8-2
BAT_LOW_ALARM_NO
Battery warning relay (normally open) will be closed during warning
J8-3
BAT_LOW_ALARM_GND
Common terminal
Page 35
Chapter 2 Installation Instruction
27
SM 180-600 KMFX User Manual
General Alarm Output Dry Contact Interface
The default function of J9 is the general alarm output dry contact interface. When one or more warnings are triggered, an auxiliary dry contact signal will be active via the isolation of a relay. The interface diagram is shown in Fig.2-20, and description is shown in Table 2.11.
J9
ALARM_NC
ALARM_NO
GND
Fig.2-20 Integrated warning dry contact interface diagram
Table2.11 General alarm dry contact interface description
Port
Name
Function
J9-1
GENERAL_ALARM_NC
Integrated warning relay (normally closed) will be open during warning
J9-2
GENERAL_ALARM_NO
Integrated warning relay (normally open) will be closed during warning
J9-3
GENERAL_ALARM_GND
Common terminal
Utility Fail Warning Output Dry Contact Interface
The default function of J10 is the output dry contact interface for utility failure warning, when the utility fails, the system will send a utility failure warning information, and provide an auxiliary dry contact signal via the isolation of a relay. The interface diagram is shown in Fig.2-21, and description is shown in Table 2.12.
J10
UTI_FAIL_NC
UTI_FAIL_NO
GND
Fig.2-21 Utility failure warning dry contact interface diagram
Table 2.12 Utility failure warning dry contact interface description
Port
Name
Function
Page 36
Chapter 2 Installation Instruction
28
SM 180-600 KMFX User Manual
Port
Name
Function
J10-1
UTILITY_FAIL_NC
Mains failure warning relay(normally closed) will be open during warning
J10-2
UTILITY_FAIL_NO
Mains failure warning relay (normally open) will be closed during warning
J10-3
UTILITY_FAIL_GND
Common terminal
2.7.2 Communication Interface
RS232RS485 and USB portProvide serial data which can be used for commissioning and maintenance by authorized engineers or can be used for networking or integrated monitoring system in the service room. SNMP: Used on site installation for communication (Optional). Intelligent card interfaceExtension dry contact interface (Optional).
Page 37
29
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
Chapter 3 LCD Panel
3.1 Introduction
This chapter introduces the functions and operator instructions of the operator control and display panel in detail, and provides LCD display information, including LCD display types, detailed menu information, prompt window information and UPS alarm information.
3.2 LCD panel for Power Module
The structure of LCD panels for power module is shown in Fig.3-1.
1Status indicator 2LCD Display 3OFF Key 4FUNC Key
Fig.3-1 Control and display panel for power module
The operator control panel is divided into three functional areasStatus indicatorcontrol and operation keys and LCD display.
3.2.1 LED Indicator
The LED indicator has green and red colors to indicate the statuses and faults by combinations of different colors and the time it lasts. The combinations are listed in Table 3.1
Table 3.1 Statues and faults of different combinations
No.
LED combinations
Description
1
Green short-time flashing 1 (Green for 1SOff for 2S)
Rectifier soft starting
2
Green short-time flashing 2 (Green for 2SOff for 1S)
Inverter soft starting
3
Green medium-time flashing (Green for 1SOff for 5S)
Power module inverter standby
4
Green long-time flashing (Green for 2SOff for 10S)
Power module in deep sleep (shutdown)
5
Steady green
UPS is working normally
6
Red and Green Alternating (Red for 1S,Green for 5S)
The load powered by inverter with warnings No batterybattery discharging, overload etc.
7
Steady red
Power module shutdown by fault
8
Red medium-time flashing (Red for 1SOff for 5S)
Shutdown manually or by monitoring software
9
Red short-time flashing (Red for 1SOff for 1S)
Situation except above
1
2
3
4
Page 38
Chapter 3 LCD Panel
30
SM 180-600 KMFX User Manual
3.2.2 Control and Operation Keys
The control and operation keys include FUNC keys and OFF key that have different functions: (a) The FUNC key is used for turning the display pages; (b) The OFF key is mainly for turning off the power module, as the following procedures:
1) EnableLCD panel -> Menu Operate -> Enable Module “OFF” Key
2) Press the “OFF” key for 3 seconds,the power module will be excluded from the system.
(c) Pressing the “FUNC” keys resets the LCD display.
3.2.3 LCD Display
LCD is for displaying the information for the module and its structure is shown in Fig.4-2.
1Select triangle 2Energy bar 3Digit Display Area 4Unit
Fig.3-2 LCD display for Module
Users can browse the information of each power module by pressing the FUNC key to turn the pages.
Select triangle of highlighted
Input information is presented in the Digit Displays Area3-phase voltage and 3-phase current.
Select triangle of highlighted
Output information is presented in the Digit Displays Area3-phase voltage, 3-phase current and the 3-phase load percentage.
Select triangle of highlighted
Battery information is presented in the Digit Displays Area Battery positive voltage, battery positive charge/discharge current and bus positive voltage;
Select triangle of highlighted:
Battery information is presented in the Digit Displays Area: battery negative voltage, battery negative charge/discharge current and bus negative voltage.
Page 39
31
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
highlighted
Fault and warning codes are shown in Digit Displays Area in recycle (shown with short dash when less than 3).The meanings of the codes are listed in Table 3.2.
flashing
Indicating a fault occurs.
Energy bar of
(a) Flashing: Rectifier soft start; (b) Highlighted: The rectifier is working normally; (c) Off: Other situation.
Energy bar of
(a) Flashing: Inverter starting; (b) Highlighted: Load on inverter; (c) Off: Other situation.
Energy bar of
(a) Flashing: low battery voltage (b) Highlighted: Charging normally;
(c) Off: battery not connected.
Energy bar of :
(a) Lightened: Discharging mode; (b) Off: battery not connected or charging.
Unit: Voltage (V), Current (A), Percentage (%). When one power module is turning page, the other modules update within 2 seconds.
Table 3.2 codes for faults and warnings
Codes
Description
Codes
Description
16
Main voltage abnormal
67
Battery polarity reversed
18
Bypass phase sequence fault
69
Inverter protected
20
Bypass voltage abnormal
71
Neutral disconnected
28
Bypass Over-track frequency
74
Module shut down manual
30
Transfer times (from inverter to bypass) in 1 hour exceed the limit.
81
Battery or charger fail
32
Output shorted
83
Lost N+X redundancy
34
EOD of battery
85
EOD system inhibited
38
Battery test fail
93
Inverter IO CAN fail
41
Battery maintenance fail
95
Data CAN fail
Page 40
Chapter 3 LCD Panel
32
SM 180-600 KMFX User Manual
47
Rectifier fail
97
Power share fail
49
Inverter fail
109
Inverter bridge open
51
Rectifier over temperature
111
Temperature difference over limit
53
Fan fail
113
Input current unbalanced
55
Output overload
115
DC bus over voltage
57
Output overload time out
117
Rectifier soft start fail
59
Inverter over temperature
119
Relay open
61
UPS inverter Inhibited
121
Relay shorted
65
Low battery
127
Transfer to inverter manually
3.3 UPS operator panel
The structure of operator control and display panel for cabinet is shown in Fig.3-3.
1: LCD touch screen 2: EPO switch 3: Audible Alarm (Buzzer) 4: Status indicator 5: Bypass indicator 6: Rectifier indicator 7: Inverter indicator 8: Load indicator 9: Battery indicator 10: Bypass transfer 11: Inverter transfer 12: Mute
Fig.3-3 Control and display panel for cabinet
The LCD panel for cabinet is divided into three functional areasLED indicatorcontrol and operation keys and LCD touch screen.
3.3.1 LED Indicator
There are 6 LEDs on the panel to indicate the operating status and fault. (See Fig. 3-3). The description of indicators is shown in Table 3.3
Table 3.3 Status description of indicator
Indicator
State
Description
Rectifier
indicator
Steady green
Rectifier normal for all modules
Flashing green
Rectifier normal for at least one module, mains normal
Steady red
Rectifier fault
Flashing red
Mains abnormal for at least one module
1
2
3
4
6
7
8
9
5
BYP INV MUTE
10
11
12
Page 41
33
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
Indicator
State
Description
Off
Rectifier not operating
Battery
indicator
Steady green
Battery charging
Flashing green
Battery discharging
Steady red
Battery abnormal (battery failure, no battery or battery reversed) or battery converter abnormal (failure, over current or over temperature) , EOD
Flashing red
Battery low voltage
Off
Battery and battery converter normal, battery not charging
Bypass
indicator
Steady green
Load supplied by bypass
Steady red
Bypass abnormal or out of normal range, or static bypass switch fault
Flashing red
Bypass voltage abnormal
Off
Bypass normal
Inverter
indicator
Steady green
Load supplied by inverter
Flashing green
Inverter on, start, synchronization or standby (ECO mode) for at least one module
Steady red
System output not supplied by inverter, inverter fault for at least one module.
Flashing red
System output supplied by inverter, inverter fault for at least one module.
Off
Inverter not operating for all modules
Load
indicator
Steady green
UPS output ON and normal
Steady red
UPS overload time is out, or output short, or output no power supply
Flashing red
Overload output of UPS
Off
No output of UPS
Status
indicator
Steady green
Normal operation
Steady red
Failure
There are two different types of audible alarm during UPS operation, as shown in Table 3.4.
Table 3.4 Description of audible alarm
Alarm
Description
Two short alarm with a long one
when system has general alarm (for example: AC fault),
Continuous alarm
When system has serious faults (for example: fuse blown or hardware failure)
3.3.2 Control and Operation Keys
Control and operation keys include four keys of 2, 10, 11 and 12(See Fig.3-3), which are used together with LCD touch screen. The functions description is shown in Table 3.5.
Table 3.5 Functions of Control and operation keys
Function Key
Description
EPO
Long press,cut off the load power (shut down the rectifier, inverter, static bypass and battery)
BYP
Long press,transfer to the bypass (Push the button up in the back of the door to enable , see Fig.5.2)
Page 42
Chapter 3 LCD Panel
34
SM 180-600 KMFX User Manual
INV
Long press, transfer to the inverter
MUTE
Long press to switch between turning off and on the buzzing
Attention
When bypass frequency is over track, there is interruption time(less than 10ms) for transferring from bypass to inverter.
3.3.3 LCD touch Screen
Users can easily browse the information, operate the UPS, and set the parameters through the LCD touch screen, which is friendly for users. After the monitoring system starts self-test, the system enters the home page, following the welcome window. The home page is shown in Fig.3-4.
System
information
Power path
Current
warning
messages
Main menu
Fig.3-4 Home page
Home page consists of Status bar, Information display, warning information and main menu. Status bar
The Status bar contains the model of the product, capacity, operational mode , and the number of the power module and the time of the system.
Warning Information
Display the warning information of the cabinet.
Information Display
Users can check the information of the cabinet in this area. The bypass voltage, main input voltage, battery voltage, and output voltages are presented in the form of gauge. The loads are displayed in the form of bar chart in percentage. The green area stands for a load of less than 60%, yellow area for a load of 60%-100% and red area for a load of more than 100%. The energy flow mimics the flow of the power.
Main Menu
The main menu includes Cabinet, Module, Setting, log, Operate and Scope. Users can operate and control the UPS, and browse all measured parameters through main menu. The structure of the main menu tree is shown in Fig.3-5.
Page 43
35
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
Fig.3-5 Structure of menu tree
3.4 Main Menu
The main menu includes Cabinet, Module, Setting, Log, Operate and Scope and it is described in details below.
3.4.1 Cabinet
Touch the icon , (At the bottom left of the screen), and the system enters the page of the Cabinet, as it is shown in Fig.3-6.
Operating
status
Version
information
Title
Operating information
Sub menu
Fig.3-6 Cabinet
Page 44
Chapter 3 LCD Panel
36
SM 180-600 KMFX User Manual
The Cabinet comprises sectors of title, information display, version running status, information display and submenu. The sectors are described as follows. Title
Display the information of the selected submenu.
Running status
The squares shown on the mini current path represent the various UPS power paths and show the current UPS operating status. (The green square indicating the block working normally, the white indicating the absent of the block and red indicating the absence of the block or in fault).
Version Information
The version information for LCD of the cabinet and monitor.
Submenu
It includes the submenu of Bypass, Main, Output, load and battery.
Information display
Display information of each submenu. The interface of each submenu is shown in Fig.3-7.
(a.) Interface of Main (b.) Interface of Output
(c.) Interface of Load (d.) Interface of Battery
Fig.3-7 Submenu interface of Cabinet
The submenu of Cabinet is described in details below in Table 3.6.
Table 3.6 Description of each submenu of Cabinet
Submenu Name
Contents
Meaning
Main
V
Phase voltage
A
Phase current
Hz
Input frequency
PF
Power factor
Page 45
37
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
Submenu Name
Contents
Meaning
Bypass
V
Phase voltage
A
Phase current
Hz
Bypass frequency
PF
Power factor
Output
V
Phase voltage
A
Phase current
Hz
Output frequency
PF
Power factor
Load
kVA
Sout: Apparent Power
kW
Pout: Active Power
kVar
Qout: Reactive power
Load (The percentage of the UPS load)
Battery
V
Battery positive/negative Voltage
A
Battery positive/negative Current
Capacity (%)
The percentage compared with new battery capacity
Remain T(Min)
Remaining battery backup time
Battery(℃)
Battery Temp
Ambient(℃)
Environmental Temp
Total Work T
Total work time
Total Discharge T
Total discharging time
3.4.2 Module
Touch the icon , (At the bottom left of the screen), and the system enters the page of
the Module, as is shown in Fig.3-8.
Power module
informatuion
Version
information
Title
Operating information
Sub menu
Fig.3.8 Module
The Module comprises sectors of title, information display, power module
information, version information and submenu. The sectors are described as follows. Title
Present the title of submenu of the selected power module.
Page 46
Chapter 3 LCD Panel
38
SM 180-600 KMFX User Manual
Information display
Display information of each submenu.
Power module information
The users can choose the power module to browse the information in the “Information
display” sector.
Colors of the square on the mimic current path represent the various power module paths and show the current operating status. (a) The green square indicating the module working normally, (b) The black indicating module in invalid (c) The red indicating the absence of the module or in fault
Take the 5#module for example. It indicates that UPS is in Normal mode and the rectifier and inverter are working normally .The battery is not connected.
Version Information
The version information for rectifier and inverter of the selected module.
Submenu
The submenu includes Input, Output, Load, INFO and S-CODE. Users can enter the interface of each submenu by directly touching the icon .Each interface of the submenu is shown in Fig.3-9.
(a)Interface of Output (b)Interface of Load
(c)Interface of Information (d)Interface of S-Code
Fig.3-9 Module menu
The submenus of Module are described below in details in Table 3.7.
Table 3.7 Description of each submenu of Module
Submenu Name
Contents
Meaning
Input
V
Input phase voltage of selected module
A
Input phase current of selected module
Hz
Input frequency of selected module
PF
Input power factor of selected module
Page 47
39
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
Submenu Name
Contents
Meaning
Output
V
Output phase voltage of selected module
A
Output phase current of selected module
Hz
Output frequency of selected module
PF
Output power factor of selected module
Load
V
Load voltage of selected module
%
Load (The percentage of the power module selected)
KW
Pout: Active Power
KVA
Sout: Apparent Power
Information
BATT+(V)
Battery Voltage (positive)
BATT-(V)
Battery Voltage (negative)
BUS(V)
Bus Voltage(Positive & Negative)
Charger(V)
Charger Voltage(Positive & Negative)
Fan Time
Total Fan’s Running time of the selected power
module
Inlet Temperature(°C)
Inlet Temperature of the selected power module
Outlet Temperature(°C)
Outlet Temperature of the selected power module
S-code
Fault Code
3.4.3 Setting
Touch the icon , (At the bottom of the screen), and the system enters the page of the Setting, as it is shown in Fig.3-10.
Fig.3-10 Setting menu
The submenus are listed on the right side of the Setting page. Users can enter each of the setting interfaces by touching the relevant icon. The submenus are described in details below in Table 3.8.
Table 3.8 Description of each submenu of Setting
Page 48
Chapter 3 LCD Panel
40
SM 180-600 KMFX User Manual
Submenu
Name
Contents
Meaning
Date&Time
Date format setting
Three formats: (a) year/month/day, (b) month/date/year,(c) date/month/year
Time setting
Setting time
Language
Current language
Language in use
Language selection
Simplified Chinese and English selectable
The setting taking action immediately
after touching the language icon)
COMM.
Device Address
Setting the communication address
RS232 Protocol Selection
SNT Protocol, ModBus Protocol, YD/T Protocol and Dwin(For factory use)
Baudrate
Setting the baudrate of SNT, ModBus and YD/T
Modbus Mode
Setting mode for Modbus:ASCII and RTU selectable
Modbus parity
Setting the parity for Modbus
USER
Output voltage Adjustment
Setting the Output Voltage
Bypass Voltage Up Limited
Up limited working Voltage for Bypass
settable:+10%,+15%,+20%,+25%
Bypass Voltage Down Limited
Down limited working Voltage for Bypass, settable:-10%,-15%,-20%,-30%,-40%
Bypass Frequency Limited
Permitted working Frequency for Bypass Settable:+-1Hz,+-3Hz,+-5Hz
Dust Filter Maintenance Period
Setting Dust Filter Maintenance Period
BATTERY
Battery Number
Setting the number of the battery(12V)
Battery Capacity
Setting of the AH of the battery
Float Charge Voltage/Cell
Setting the floating Voltage for battery cell
(2V)
Boost Charge Voltage/Cell
Setting the boost Voltage for battery cell
(2V)
EOD(End of discharge) Voltage/Cell,@0.6C Current
EOD voltage for cell battery,@0.6C current
EOD(End of charge) Voltage/Cell,@0.15C Current
EOD voltage for cell battery,@0.15C current
Charge Current Percent Limit
Charge current (percentage of the rated current)
Battery Temperature Compensate
Coefficient for battery temperature compensation
Boost Charge Time Limit
Setting boost charging time
Auto Boost Period
Setting the auto boost period
Auto Maintenance Discharge Period
Setting the period for auto maintenance discharge
SERVICE
System Mode
Setting the system mode: Single , parallel,
Page 49
41
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
Submenu
Name
Contents
Meaning
Single ECO, parallel ECO,LBS, parallel LBS
RATE
Configure the rated Parameter
For the factory use CONFIGURE
Configure the system
For the factory use
Note
Users have various permissions to the configuration of the Setting :( a) for the Date &Time,
LANGUAGE and COMM, user can set on their own without password. (b)For the USER, a one-level password is needed and the setting must be done by commissioning engineer (c) For the Battery and SERVICE, a Two-level password is needed and it is set by the after-service personal. (d)For the RATE and CONFIGURE, a Three-level password is needed and it is set only by the factory.
The C stands for Ampere number. For instance, if the battery is 100AHthen C=100A.
Warning
Ensure the number of the battery, set via the menu or the monitoring software, is completely equal to the real installed number. Otherwise it will cause serious damage to the batteries or the equipment.
3.4.4 Log
Touch the icon , (At the bottom of the screen), and the system enters the interface of the Log, as it is shown in Fig.3-11.The log is listed in reverse chronological order(i.e. the first on the screen with #1 is the most new), which displays the events ,warnings and faults information and the data and time they occur and disappear.
Fig.3-11 Log menu
Every event recorded in the table includes the sequence number, the content of the event and
Page 50
Chapter 3 LCD Panel
42
SM 180-600 KMFX User Manual
the time stamp when it occurs, as is marked in the red box.
Sequence number
The serial number for the event.
Content of the event
Display the information of events, warnings and faults. (0# means the event happens to the cabinet, n# means the information is sent by the nth power module.)
Time for the Event
The time the event occurs.
Total Log Items
Display the total number of events. The system can record 895 events. If the number exceeds 895, the system will delete the earliest events.
Turn the list page up/down to check the information of the events. The Table 3.9 below displays all the events and gives a brief explanation
Table 3.9 List for events
String
Sequence
LCD Display
Explanation
1
Load On UPS-Set
Load On UPS
2
Load On Bypass-Set
Load On Bypass
3
No Load-Set
No Load (Output Power Lost)
4
Battery Boost-Set
Charger is Boosting Battery Voltage
5
Battery Float-Set
Charger is Floating Battery Voltage
6
Battery Discharge-Set
Battery is Discharging
7
Battery Connected-Set
Battery cables Connected
8
Battery Not Connected-Set
Battery cables Disconnected.
9
Maintenance CB Closed-Set
Maintenance CB is Closed
10
Maintenance CB Open-Set
Maintenance CB is Open
11
EPO-Set
Emergency Power Off
12
Module On Less-Set
Valid Inverter capacity is less than the load capacity
13
Module On Less-Clear
Event above disappears
14
Generator Input-Set
Generator as the Ac Input Source
15
Generator Input-Clear
Event above disappears
16
Utility Abnormal-Set
Utility (Grid) Abnormal
17
Utility Abnormal-Clear
Event above disappears
18
Bypass Sequence Error-Set
Bypass voltage Sequence is reverse
19
Bypass Sequence Error-Clear
Event above disappears
20
Bypass Volt Abnormal-Set
Bypass Voltage Abnormal
21
Bypass Volt Abnormal-Clear
Event above disappears
22
Bypass Module Fail-Set
Bypass Module Fail
23
Bypass Module Fail-Clear
Event above disappears
24
Bypass Overload-Set
Bypass Over load
25
Bypass Overload-Clear
Event above disappears
26
Bypass Overload Tout-Set
Bypass Over Load Timeout
27
Byp Overload Tout-Clear
Event above disappears
Page 51
43
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
28
Byp Freq Over Track-Set
Bypass Frequency Over Track Range
29
Byp Freq Over Track-Clear
Event above disappears
30
Exceed Tx Times Lmt-Set
Transfer times (from inverter to bypass) in 1 hour exceed the limit.
31
Exceed Tx Times Lmt-Clear
Event above disappears
32
Output Short Circuit-Set
Output shorted Circuit
33
Output Short Circuit-Clear
Event above disappears
34
Battery EOD-Set
Battery End Of Discharge
35
Battery EOD-Clear
Event above disappears
36
Battery Test-Set
Battery Test Starts
37
Battery Test OK-Set
Battery Test OK
38
Battery Test Fail-Set
Battery Test fails
39
Battery Maintenance-Set
Battery Maintenance Starts
40
Batt Maintenance OK-Set
Battery maintenance succeeds
41
Batt Maintenance Fail-Set
Battery maintenance fails
42
Module Inserted-Set
N# Power Module joins the system
43
Module Exit-Set
N# Power Module quits the system.
44
Rectifier Fail-Set
N# Power Module Rectifier Fails
45
Rectifier Fail-Clear
Event above disappears
46
Inverter Fail-Set
N# Power Module Inverter Fail
47
Inverter Fail-Clear
Event above disappears
48
Rectifier Over Temp.-Set
N# Power Module Rectifier Over Temperature
49
Rectifier Over Temp.-Clear
Event above disappears
50
Fan Fail-Set
N# Power Module Fan Fail
51
Fan Fail-Clear
Event above disappears
52
Output Overload-Set
N# Power Module Output Over Load
53
Output Overload-Clear
Event above disappears
54
Inverter Overload Tout-Set
N# Power Module Inverter Over Load Timeout
55
INV Overload Tout-Clear
Event above disappears
56
Inverter Over Temp.-Set
N# Power Module Inverter Over Temperature
57
Inverter Over Temp.-Clear
Event above disappears
58
On UPS Inhibited-Set
Inhibit system transfer from bypass to UPS (inverter)
59
On UPS Inhibited-Clear
Event above disappears
60
Manual Transfer Byp-Set
Transfer to bypass manually
61
Manual Transfer Byp-Set
Cancel to bypass manually
62
Esc Manual Bypass-Set
Escape transfer to bypass manually command
63
Battery Volt Low-Set
Battery Voltage Low
64
Battery Volt Low-Clear
Event above disappears
65
Battery Reverse-Set
Battery pole (positive and negative) are reverse
66
Battery Reverse-Clear
Event above disappears
67
Inverter Protect-Set
N# Power Module Inverter Protect ( Inverter Voltage Abnormal or Power Back feed to DC Bus)
Page 52
Chapter 3 LCD Panel
44
SM 180-600 KMFX User Manual
68
Inverter Protect-Clear
Event above disappears
69
Input Neutral Lost-Set
Input Grid Neutral Lost
70
Bypass Fan Fail-Set
Bypass Module Fan Fail
71
Bypass Fan Fail-Clear
Event above disappears
72
Manual Shutdown-Set
N# Power Module Manually Shutdown
73
Manual Boost Charge-Set
Manually Battery Boost Charge
74
Manual Float Charge-Set
Manually Battery Float Charge
75
UPS Locked-Set
Inhibit to shut down the UPS
76
Parallel Cable Error-Set
Parallel cable in error
77
Parallel Cable Error-Clear
Event above disappears
78
Lost N+X Redundant
Lost N+X Redundant
79
N+X Redundant Lost-Clear
Event above disappears
80
EOD Sys Inhibited
System is inhibited to supply after the battery is EOD (end of discharging)
81
Power Share Fail-Set
Power share is not in balance
82
Power Share Fail-Clear
Event above disappears
83
Input Volt Detect Fail-Set
Input Voltage is abnormal
84
Input Volt Detect Fail-Clear
Event above disappears
85
Battery Volt Detect Fail-Set
Battery Voltage is abnormal
86
Batt Volt Detect Fail-Clear
Event above disappears
87
Output Volt Fail-Set
Output Voltage is abnormal
88
Output Volt Fail-Clear
Event above disappears
89
Outlet Temp. Error-Set
Outlet Temperature is abnormal
90
Outlet Temp. Error-Clear
Event above disappears
91
Input Curr Unbalance-Set
Input current is not balance
92
Input Curr Unbalance-Clear
Event above disappears
93
DC Bus Over Volt-Set
DC bus over Voltage
94
DC Bus Over Volt-Clear
Event above disappears
95
REC Soft Start Fail-Set
Rectifier soft start fails
96
REC Soft Start Fail-Clear
Event above disappears
97
Relay Connect Fail-Set
Relay in open circuit
98
Relay Connect Fail-Clear
Event above disappears
99
Relay Short Circuit-Set
Relay shorted
100
Relay Short Circuit-Clear
Event above disappears
101
No Inlet Temp. Sensor-Set
The inlet temperature sensor is not connected or abnormal
102
No Inlet Temp Sensor-Clear
Event above disappears
103
No Outlet Temp. Sensor-Set
The Outlet temperature sensor is not connected or abnormal
104
No Outlet TmpSensor-Clear
Event above disappears
105
Inlet Over Temp.-Set
Inlet over temperature
106
Inlet Over Temp.-Clear
Event above disappears
Page 53
45
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
Note
Different colors of the words represent different level of events: (a)Green, an event occurs (b)Grey, the event occurs then clears
(c)Yellow, warning occurs (d) Red, faults happen.
3.4.5 Operate
Touch the icon (At the bottom of the screen), and the system enters the page of the “Operate”, as it is shown in Fig.3-12.
Fig.3-12 Operate menu
The “Operate” menu includes FUNCTION BUTTON and TEST COMMAND. The contents are
described in details below.
FUNTION BUTTON
Clear/Restore Buzzing
Mute or Restore buzzing of the system by touching the icon or .
Fault Clear
Clear the faults by touching the icon .
Transfer to and ESC Bypass
Transfer to bypass mode or cancel this command by touching the icon or .
Transfer to Inverter
Transfer the bypass mode to Inverter Mode by touching the icon .
Enable Module “OFF” Button
Page 54
Chapter 3 LCD Panel
46
SM 180-600 KMFX User Manual
Enable the switch for powering off the Power Module by touching the icon .
Reset Battery History Data
Reset the battery history data by touching the icon , the history data includes the
times of discharge, days for running and hours of discharging.
Reset Dust filter Using Time
Reset the time of dust filter using by touching the icon , it includes the days of using and maintenance period.
TEST COMMAND
Battery Test
By touching the icon the system transfer to the Battery mode to test the condition of the battery. Ensure the bypass is working normally and the capacity of the battery is no
less than 25%.
Battery Maintenance
By touching the icon , the system transfers to the Battery mode. This function is used for maintaining the battery, which requires the normality of the bypass and minimum capacity of 25% for the battery.
Battery Boost
By touching the icon , the system starts boost charging.
Battery Float
By touching the icon , the system starts float charging.
Stop Test
By touching the icon , the system stops battery test or battery maintenance.
3.4.6 Scope
Touch the icon , (At the bottom right of the screen), and the system enters the page of the Scope, as it is shown in Fig.3-13.
Page 55
47
SM 180-600 KMFX User Manual
Chapter 3 LCD Panel
Fig.3-13 Scope Menu
Users can view the waves for output voltage, output current and bypass voltage by touching the corresponding icon in the left side of the interface. The waves can be zoomed in and zoom out.
Touch the icon to display the 3 phase output voltage.
Touch the icon to display the 3 phase output current.
Touch the icon to display the 3 phase bypass voltage.
Touch the icon to zoom in the wave.
Touch the icon to zoom out wave.
Page 56
Chapter 4 Operations
48
SM 180-600 KMFX User Manual
Chapter 4 Operations
4.1 UPS Start-up
4.1.1 Start in Normal Mode
The UPS must be started up by commissioning engineer after the completeness of installation. The steps below must be followed
1. Ensure all the external circuit breakers are open.
2. Close the input external circuit breakers and the system starts initializing. If the system has
dual inputs close both of the breakers.
3. The LCD in front of the cabinet is lit up. The system enters the home page, as shown in
Fig.4-4.
4. Notice the energy bar in the home page, and pay attention to the LED indicators. The
rectifier flashes indicating the rectifier is starting up. The LED indicators are listed below in Table 4.1.
Table 4.1 Rectifier starting up
Indicator
Status
Indicator
Status
Rectifier
green flashing
Inverter
off
Battery
red
Load
off
Bypass
off
Status
red
5. After 30S, the rectifier indicator goes steady green, presenting the finishing of rectification
and bypass static switch closes then the inverter is starting up. The LED indicators are listed below in Table.4.2.
Table 4.2 Inverter starting up
Indicator
Status
Indicator
Status
Rectifier
green
Inverter
green flashing
Battery
red
Load
green
Bypass
green
Status
red
6. The UPS transfers from the bypass to inverter after the inverter goes normal. The LED indicators
are listed below in Table 4.3.
Table 4.3 Supplying the load
Indicator
Status
Indicator
Status
Rectifier
green
Inverter
green
Battery
red
Load
green
Bypass
off
Status
red
7. The UPS is in Normal Mode. Close the battery circuit breakers and the UPS starts charging the
battery. The LED indicators are listed below in Table 4.4.
Table 4.4 Normal mode
Indicator
Status
Indicator
Status
Rectifier
green
Inverter
green
Battery
green
Load
green
Bypass
off
Status
green
8. Close the output circuit breaker for the load and it finishes the starting up for the UPS.
Note
When the system starts, the stored setting will be loaded.
Users can browse all events during the process of the starting up by checking the
Page 57
Chapter 4 Operations
49
SM 180-600 KMFX User Manual
menu Log.
Users can check the information of the power module by the keys in the front of it.
4.1.2 Start from Battery
The start from battery is referring to battery cold start. Take the 10-slot UPS as example, the steps for the start-up are as follows
1. Confirm the battery is correctly connected; close the external battery circuit breakers.
2. Press the red button for the battery cold startSee Fig.4-1.The system is then powered
by the battery. For the 20-slot UPS, there are 2 battery cold star button, for each of the button, it can only start the power modules of its cabinet(See Fig.4-2).
Fig.4-1The position of the battery cold start button for 10-slot cabinet
Fig.4-2 the position of the battery cold start button for 20-slot cabinet
3. After that, the system is starting up following steps 3 in section 5.1.1 and the system
transfers to battery mode in 30S.
4. Close the external output power supply isolation to supply the load, and the system is
working on battery mode.
4.2 Procedure for Switching between Operation Modes
4.2.1 Switching the UPS from Normal Mode into Battery Mode
The UPS transfers to Battery model immediately after the utility (mains voltage) is failed or
drops down below the predefined limit.
4.2.2 Switching the UPS from Normal Mode into Bypass Mode
Two ways to transfer the UPS into Bypass mode from Normal mode (a) Enter the menu Operate, touch the icon “transfer to bypass” and the system
transfers to bypass mode ;
Page 58
Chapter 4 Operations
50
SM 180-600 KMFX User Manual
(b) Press and hold the BYP key on the operator control panel for longer than two seconds and
the system transfers to bypass mode. This needs to enable the switch behind the front door. See Fig.4-3.
Fig.4-3 Enable the switch
Warning
Ensure the bypass is working normally before transferring to bypass mode. Or it may cause failure.
4.2.3 Switching the UPS into Normal Mode from Bypass Mode
Two ways to transfer the UPS into Normal mode from Bypass Mode
(a) Enter the menu Operate, touch the icon transfer to inverter and the system transfers to bypass mode (b) Press and hold the INV key on the operator control panel for longer than two seconds and the system transfers to Normal mode.
Note Normally, the system will transfer to the Normal mode automatically. This function is used when the frequency of the bypass is over track and when the system needs to transfer to Normal mode by manual.
4.2.4 Switching the UPS from Normal Mode into Maintenance Bypass Mode
These following procedures can transfer the load from the UPS inverter output to the maintenance bypass supply, which is used for maintaining the bypass module (for 6-slot and 10-slot cabinet) and monitoring, static bypass unit (for 20-slot cabinet).
1. Transfer the UPS into Bypass mode following section 4.2.2.
2. Open the battery breaker and close the maintenance bypass. And the load is powered
through maintenance bypass and static bypass.
3. Pull out the bypass module (for 6-slot and 10-slot cabinet) , and dismantle monitoring,
static bypass unit (for 20-slot cabinet) and the load is powered through maintenance bypass.
Page 59
Chapter 4 Operations
51
SM 180-600 KMFX User Manual
Warning
Before making this operation, read messages on LCD display to be sure that bypass supply is regular and the inverter is synchronous with it, so as not to risk a short interruption in powering the load.
Danger
If you need to maintain the power module, wait for 10 minutes to let the DC bus capacitor fully discharge before removing the cover.
4.2.5 Switching the UPS into Normal Mode from Maintenance Bypass Mode
These following procedures can transfer the load from the Maintenance Bypass mode to inverter output.
1. The bypass turns on 30S after the LED touch screen goes on, the bypass indicator goes
green and the load is powered through maintenance bypass and static bypass.
2. Turn off the maintenance bypass switch and the load is powered through bypass. The
rectifier starts followed by the inverter.
3. After 60S, the system transfers to Normal mode.
4.3 Battery Maintenance
If the battery is not in use for a long time, it is necessary to test the condition of the battery. Two methods are provided:
1. Manual Discharging test. Enter the menu Operateas is shown in Fig.5-4 and touch the
icon “Battery maintenance” ,the system transfers into the Battery mode for
discharging. The system will stop discharging when the battery will have 20% of capacity or
in low voltage. Users can stop the discharging by touching the “Stop Test” icon .
Fig.4-4 Battery maintenance
Page 60
Chapter 4 Operations
52
SM 180-600 KMFX User Manual
2. Auto discharging. The system can maintenance the battery automatically when the setting
is done. The setting procedures are as follows.
(a) Enable battery auto discharge. Enter the “CONFIGURE” page of the menu Setting, tick
the “Battery Auto Discharge” and confirm (This needs to be done by factory).
(b) Setting period for battery auto discharge. Enter the “BATTERY “page of the Setting (See
Fig.5-5), Set the period time in the item “Auto Maintenance Discharge Period” and confirm.
Fig.4-5 Setting period for battery auto discharge
Warning
The load for the auto maintenance discharge should be 20%-100%,if not, the system will not start the process automatically.
4.4 EPO
The EPO button located in the operator control and display panel (with cover to avoid disoperation, see Fig.5-6) is designed to switch off the UPS in emergency conditions (e.g., fire, flood, etc.).To achieve this, just press the EPO button, and the system will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS control circuit will remain active; however, the output will be turned off. To completely isolate the UPS, users need to open the external mains input supply to the UPS. Users can restart the UPS by powering the UPS again.
Warning
When the EPO is triggered, the load is not powered by the UPS. Be careful to use the EPO function.
Page 61
Chapter 4 Operations
53
SM 180-600 KMFX User Manual
Fig .4-6 EPO Button
4.5 Installation of Parallel Operation System
For the 6-slot and 10-slot system ,it can have three UPS cabinets in parallelwhich can extend to a capacity of total 900KVA.Howerever, for the 20-slot system, parallel is not supported at present. Two UPS cabinets are connected as is shown in Fig.4-6.
Fig. 4-6 Parallel diagram
The parallel board is located at the back of the UPS cabinet, whose name is PS1203-TF4 as is shown in Fig.4-7.
Page 62
Chapter 4 Operations
54
SM 180-600 KMFX User Manual
Fig.4-7 Location of the Parallel board
The control cables for the parallel operation must be connected with all single devices to form a closed loop, as is shown in Fig.4-8.
Fig.4-8 Parallel connection
For more details of parallel operation, please refer to the “Instruction for Parallel Operation
of Modular UPS”.
Page 63
55
SM 180-600 KMFX User Manual
Chapter 5 Maintenance
Chapter 5 Maintenance
This chapter introduces UPS maintenance, including the maintenance instructions of power module and monitoring bypass module and the replacement method of dust filter.
5.1 Precautions
1. Only certified engineers are authorized to maintain the UPS.
2. The components or PCBs should be disassembled from top to bottom, so as to prevent any
inclination from high gravity center of the cabinet.
3. To ensure the safety before maintaining, measure the voltage between operating parts and
the earth with multi-meter to ensure the voltage is lower than hazardous voltage, i.e. DC
voltage is lower than 60Vdc, and AC maximum voltage is lower than 42.4Vac.
4. Wait 10 minutes before opening the cover of the power module or the bypass after pulling
out from the Cabinet.
5.2 Instruction for Maintaining Power Module
Confirm the UPS is operating in Normal Mode and the bypass is working normally before pulling out the power module needed to be repaired.
1. Ensure the remaining power module will not be overloaded.
2. Power off the module.1)Enable.LCD panel -> Menu Operate -> Enable Module
“OFF” Key 2)Press the “OFF” key for 3 seconds,the power module quits from
the system.
3. Remove the mounting screw on the two front sides of the power module (See Fig.3-10) and
pull out the module by two persons.
4. Wait 10 mins before opening the cover for repairing.
5. After the repairing is done, push the power module into the cabinet following the steps in
section 3.3.2 and the power module will automatically join the system.
5.3 Instruction for Maintaining
5.3.1 Maintaining Bypass Module for 6-slot and 10-slot Cabinet
Confirm the UPS is operating in Normal mode and the bypass is working normally before pulling out the bypassing module needed to be repaired. Follow the steps below to maintain the bypass module.
1. Transfer the system to bypass mode through the LCD control panel(Refer to section 4.5.5)
2. Open the battery switch, close maintenance bypass switch; the UPS power will be supplied
by maintenance bypass.
3. Pull out the bypass module and the load is powered through maintenance bypass.
4. Remove the mounting screw on the two front sides of the bypass module (See Fig.3-10)
and the front signal cable connects to the bypass module.
5. Pull out the bypass module and the LCD touch screen goes off.
6. Wait 10 mins before opening the cover for repairing.
7. After the repairing is done, push the bypass module into the cabinet following the steps in
section 3.3.2 and the LED touch screen goes on.
8. The bypass turns on 30S after the LED touch screen goes on and the bypass indicator
goes green and the load is powered through maintenance bypass and static bypass.
9. Turn off the maintenance bypass switch and the load is powered through bypass. The
rectifier starts followed by the inverter.
10. After 60S, the system transfers to Normal mode.
Page 64
Chapter 5 Maintenance
56
SM 180-600 KMFX User Manual
5.3.2 Maintaining Static Bypass Unit for 20-slot Cabinet
1. Transfer the system to bypass mode through the LCD control panel (Refer to section4.5.5);
2. Open the battery switch, Close maintenance bypass switch; the UPS power will be supplied by maintenance bypass;
3. Open the Main Input switch, Input Bypass switch and UPS output switch;
4. Disconnect Inner Control Neutral cable as Fig.6-1;
5. Take out the screws fixed on the fan panel and dismantle the fan panel;
6. Take out the two sets of control signal cables (in DB9 type);
7. Take out the fan units and remove the cables for the fans;
8. Dismantle the screws that fix the static bypass unit and copper bars;
9. Pull the static bypass unit to an extent which can make the maintenance possible(the static bypass unit can be repaired without taking out);
10. After the maintenance is done, push the static bypass inside;
11. Fix the static bypass and inner copper bars from the back of the cabinet;
12. Connect the cables for the fans and restore the fan units;
13. Connect two sets of control signal cables (in DB9 type);
14. Install the fan panel, fix the screws;
15. Close the UPS bypass input switch, output switch, main input switch in order;
16. Connect Inner Control Neutral cable as Fig.6-1
17. 2 minutes after the power on, there is energy flow in the LCD panel showing that the load is supplied by static bypass and manual bypass
18. Open the manual bypass switch, the Inverter will start automatically. After 60s, the UPS
will run in Normal mode, which indicates the maintenance is done successfully.
Note: If it needs to take out the static bypass unit to do the repair, a forklift is suggested. (The
weight of the static bypass unit can be 55kg).
5.3.3 Maintenance for the Air-drawing fans
1. Take out the fan unit panel
2. Push the button of the fans to turn off the fans
3. Change the fans
4. Push the button to turn on the fans again
5. Install the fan panel
5.3.4 Battery Maintenance
For the Lead-Acid maintenance free battery, when maintenance the battery according to requirements, battery life can be prolonged. The battery life is mainly determined by the following factors:
1. Installation. The battery should be placed in dry and cool place with good ventilation. Avoid
direct sunlight and keep away from heat source. When installing, ensure the correct connection to the batteries with same specification.
2. Temperature. The most suitable storage temperature is 20 ºC to 25ºC.
3. Charging/discharging current. The best charging current for the lead-acid battery is
0.1C .The maximum current for the battery can not 0.3C.The suggested current is
0.05C-3C.
4. Charging voltage. In most of the time, the battery is in standby state. When the utility is
normal, the system will charge the battery in boost mode (Constant voltage with maximum limited) to full and then transfers to the state of float charge.
5. Discharge depth. Avoid deep discharging, which will greatly reduce the life time of the
battery. When the UPS runs in battery mode with light load or no load for a long time, it will cause the battery to deep discharge.
6. Check periodically. Observe if any abnormality of the battery measure if the voltage of
each battery are in balance. Discharge the battery periodically.
Page 65
57
SM 180-600 KMFX User Manual
Chapter 5 Maintenance
5.3.5 Disconnect the Inner Control Neutral cable
Inner control Neutral cable can be disconnected by turning off the Neutral Cable Switch. By doing this, the Auxiliary power supply is cut off from the utility. 6-slot cabinet and 10-slot cabinet doesn’t need to disconnect the inner control neutral cable. The Inner Control Neutral Cable is located in the right of the maintenance bypass and is protected by the protective board, as is shown in Fig.5-1.
Fig.5-1 the position of Inner Control Neutral cable
5.4 Battery Setting
The setting of battery needs to be done after the first time of powering off or any changes done on the batteries. The battery configuration can be done through the LCD control panel (Fig.5-2) or though monitoring software (Fig.5-3).
Fig.5-2 Configuration through LCD control panel
Page 66
Chapter 5 Maintenance
58
SM 180-600 KMFX User Manual
Fig.5-3 Configuration through monitoring software
5.4.1 Setting of Battery Type
The battery type can be only set through the monitoring software. The system at present supports lead acid battery and Lithium iron phosphate battery (LFPB).
5.4.2 Setting of Battery Number
1) Setting battery number for Lead- Acid battery
The nominal voltage of one block battery is 12V and for each block of battery, it consists of 6 cells (each cell of 2V).For the setting, as is shown in Fig.5-2, if the battery is 40, it means that there are 40 blocks of batteries and both the positive and negative are 20 blocks of batteries. In the case of cell battery of 2V (usually with large capacity) is used, battery number should be the same as the block battery. The cell battery actually in use should be 240 cells (6*40), with both and positive and negative of 120 cells. The battery number setting range is 36-44
2) Setting battery number for LFPB
For the cell of each LFPB, the cell voltage is 3.2V; each battery block consists of 1 cell. In total, if 40 blocks of Lead- Acid battery are used, for the LFPB, the number will be 150. Both the positive and negative are 75 cells. The battery number setting range is 140-180.The lowest EOD voltage for the LFPB will be 360V and highest voltage can be 620V.
5.4.3 Battery Capacity Setting
Battery Capacity Setting sets the capacity value of the battery block .For example, if the system uses 40 blocks of 12V/100AH batteries, the Battery Capacity Setting should set to 100 Ah. If 240 cells of 2V/1000AH are used, the Battery Capacity Setting should be set to 1000 Ah. In case of there are more than one strings of battery in parallel, the battery capacity setting value will be the times of the single string. For instance, if the configuration is two strings of 40 blocks of 12V/100AH batteries, the battery capacity setting should be set to 200AH. The system sets current limits according to the battery capacity set. For the Lead-Acid battery, the current limit is 0.2C, and for the LIPB, the current is 0.3C. For instance, the 20-slot UPS is configured to 40 blocks of 12V/500AH batteries, which can provides total max charging current of 192A.Due to the current limits(0.2C) , the max charging current will be 100A(0.2*500A).
5.4.4 Float and Boost Charge Setting
In boos charging, the system charges the batteries with constant current. After the period, the system will enter the float charging. For the Lead-Acid battery ,the default float charge voltage per cell is 2.25V, boost charge voltage is 2.35V
For the LFPB, the default float and boost charge voltage per cell is 3.45V
Page 67
59
SM 180-600 KMFX User Manual
Chapter 5 Maintenance
5.4.5 EOD Voltage Setting
The EOD voltage 0.6C is the EOD voltage when the discharging current is larger than 0.6C; EOD voltage 0.15C is the EOD voltage when the discharging current is less than 0.15C.EOD voltage decreases linearly as the EOD voltage Current increases from 0.15C to 0.6C, as shown in Fig.6-4.
Fig.5-4 EOD voltage
For Lead-Acid battery, the cell voltage is suggested to set to 1.65V/cell at 0.6C, and set to
1.75V at 0.15C
For the LFPB battery, the cell voltage is suggested to set to 2.7V/cell at both 0.6C and 0.15C.
5.4.6 Charging Current Percent Limit
This setting is for limiting the charging power, max current limit can be20% of the rated active power. The actual charging current is also limited to the battery capacity.
5.4.7 Battery Temperature Compensate
This is for setting the temperature compensate coefficient. Based on 25when the temperature is higher than that, the discharging voltage goes lower; When the temperature is
lower than that, the discharging voltage goes higher.
5.4.8 Boost Charge Time Limit
This is for setting the Boost Charge time. When the set time is up, the system transfers to float charge. The setting range can be 1-48h.
5.4.9 Auto Boost Period
This is for setting the Auto boost period time. When the set time is up, the system boost charges the battery. It is suggested to boost charge the battery every three month, set the period to 4320h.
5.4.10 Auto maintenance Discharge Period
When the Auto maintenance Discharge period is reached, the system discharges the battery. This function should be enabled by checking the AutoMaint (RateSetting->SysCodeSetting1) through the monitoring software, as shown in Fig.5-5.
Page 68
Chapter 5 Maintenance
60
SM 180-600 KMFX User Manual
Fig.5-5 Enable the Auto maintenance Discharge period
The EOD voltage of Auto maintenance Discharge is 1.05 times of the normal EOD voltage.
5.4.11 Warnings for Battery and Environment Temperature Overheat
This function can be set through the monitoring software. The system will read the temperature information of the battery and environment and give warning of overheat. The set range is 25-70 .
The temperature sensor should be placed through the Dry Contact.
5.5 Replacing Dust Filter (optional)
As shown in Fig.5-6, there are 3~4 dust filters on the back of UPS’ front door, each filter is held in place by a bracket on either side of each filter. The procedure of replacing each filter is as follows:
1. Open the front door and locate the filters on the back side of the front door.
2. Remove one bracket.
3. Remove the dust filter to be replaced and insert the clean one.
4. Reinstall the bracket.
Fig. 5-6 Dust filter on the back side of front door
Page 69
61
SM 180-600 KMFX User Manual
Chapter 6 Product Specification
Chapter 6 Product Specification
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics.
6.1 Applicable Standards
The UPS has been designed to conform to the following European and international
standards:
Table 6.1 Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS used in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC) requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2(C3)
Method of specifying the performance and test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111)
Note The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60950).
6.2 Environmental Characteristics
Table 6.2 Environmental Characteristics
Item
Unit
Requirements
180kVA
300kVA
600kVA
Acoustic noise level
at 1 meter
dB
65dB @ 100% load, 62dB @ 45% load
≤70dB
Altitude of Operation
m
≤1000,load derated 1% per 100m from 1000m to 2000m
Relative Humidity
%
0-95,non condensing
Operating Temperature
0-40(for UPS only),Battery life is halved for every 10°C increase above 20°C
UPS Storage Temperature
-40-70
6.3 Mechanical Characteristic
Table 6.3 Mechanical Characteristics for Cabinet
Item
Unit
180kVA
300kVA
600kVA
Mechanical
Dimension (W*D*H)
mm
600*1100*1600
600*1100*2000
2000*1100*2000
Weight
kg
170
220
660
Color
N/A
Black
Protection Level
IEC60529
N/A
IP20
Page 70
Chapter 6 Product Specification
62
SM 180-600 KMFX User Manual
Table 6.4 Mechanical Characteristics for Power Module
Item
Unit
30KVA
Mechanical Dimension
W*D*H
mm
460*790*134
Weight
kg
34
6.4 Electrical Characteristics
6.4.1 Electrical Characteristics (Input Rectifier)
Table 6.5 Rectifier AC input Mains
Item
Unit
Parameter
Grid System
\
3 Phases + Neutral + Ground
Rated AC Input Voltage
Vac
380/400/415 (three-phase and sharing neutral
with the bypass input)
Rated Frequency
Vac
50/60Hz
Input voltage range
Vac
304~478Vac (Line-Line),full load
228V~304Vac (Line-Line),load decrease linearly
according to the min phase voltage
Input Frequency range
Hz
40~70
Input Power factor
PF
>0.99
THDI
THDI%
<3% (full Linear Load)
Page 71
63
SM 180-600 KMFX User Manual
Chapter 6 Product Specification
6.4.2 Electrical Characteristics (Intermediate DC Link)
Table 6.6 Battery
Items
Unit
Parameters
Battery bus voltage
Vdc
Rated:±240V
Quantity of
lead-acid cells
Nominal
40=[1 battery(12V)] ,240=[1 battery(2V)]
Float charge
voltage
V/cell
VRLA)
2.25V/cell(selectable from 2.2V/cell~2.35V/cell) Constant current and constant voltage charge mode
Temperature
compensation
mV/℃/cl
3.0(selectable:0~5.0) Ripple voltage
≤1
Ripple current
≤5
Equalized
charge voltage
VRLA
2.4V/cell(selectable from : 2.30V/cell~2.45V/cell)
Constant current and constant voltage charge mode
Final
discharging voltage
V/cell
VRLA)
1.65V/cell(selectable from: 1.60V/cell~1.750V/cell)
@0.6C discharge current
1.75V/cell (selectable from: 1.65V/cell~1.8V/cell)
@0.15C discharge current (EOD voltage changes linearly within the set range according to discharge current)
Battery Charge
V/cell
2.4V/cell(selectable from : 2.3V/cell~2.45V/cell)
Constant current and constant voltage charge mode
Battery Charging
Power Max Current
kW
10%* UPS capacity (selectable from : 1~20% * UPS capacity)
6.4.3 Electrical Characteristics (Inverter Output)
Table 6.7 Inverter Output (To critical load)
Item
Unit
Value
Rated capacity
kVA
180/300/600
Rated AC voltage
Vac
380/400/415 (Line-Line)
Rated Frequency
Hz
50/60
Frequency Regulation
Hz
50/60Hz±0.1%
Voltage precision
%
±1.5(0~100% linear load)
Overload
\
110%, 60min;
125%,10min;
150%,1min;
>150%,200ms
Synchronized
Range
Hz
Settable, ±0.5Hz ~ ±5Hz, default ±3Hz
Synchronized Slew
Rate
Hz
Settable, 0.5Hz/S ~ 3Hz/S, default 0.5Hz/S
Output Power
Factor
PF
0.9
Transient
Response
%
<5% for step load (20% - 80% -20%)
Transient recovery
< 30ms for step load (20% - 100% -20%)
Output Voltage
THDu
<1% from 0% to 100% linear load
<6% full non-linear load according to IEC/EN62040-3
Page 72
Chapter 6 Product Specification
64
SM 180-600 KMFX User Manual
6.4.4 Electrical Characteristics (Bypass Mains Input)
Table 6.8 Bypass Mains Input
Item
Unit
180
300
600
Rated AC voltage
Vac
380/400/415
(three-phase four-wire)
Rated AC Current
A
273
454
909
Overload
%
110% Long term operation
110%~125% for 5min 125%~150% for 1min
150%~400% for 1s
>400% ,less than 200ms
Current rating of
neutral cable
A
1.7×In
Rated frequency
Hz
50/60
Switch time
(between bypass
and inverter)
ms
Synchronized transfer: 0ms
Bypass voltage
range
%\
Settable, default -20%~+15%
Up limited: +10%, +15%, +20%, +25%
Down limited: -10%, -15%, -20%, -30%, -40%
Bypass frequency
range
%Hz
Settable, ±1Hz, ±3Hz, ±5Hz
Synchronized
Range
Hz
Settable ±0.5Hz~±5Hz, default ±3Hz
6.5 Efficiency
Table 6.9 Efficiency
System Efficiency
Normal mode(dual conversion)
%
>95
Battery discharging efficiency (battery at nominal voltage 480Vdc and full-rated linear load)
battery mode
%
>95
6.6 Display and Interface
Table 6.10 Display and Interface
Display
LED + LCD +Color touch screen
Interface
Standard:RS232, RS485, USB, Dry Contact Option: SNMP,AS/400
Loading...