CyberPower SM20KPM, SM200KMF, SM060KMF, SM120KMF User Manual

Page 1
User’s Manual
SM20KPM SM200KMF SM120KMF SM060KMF
www.cpsww.com
Page 2
Safety Precautions
Modular UPS SM series User Manual - 1 -
Safety Precautions
This manual contains information concerning the installation and operation of Modular UPS . Please carefully read this manual prior to installation. The Modular UPS cannot be put into operation until it is commissioned by engineers approved by the manufacturer (or its agent). Not doing so could result in personnel safety risk, equipment malfunction and invalidation of warranty. The UPS has been designed for commercial or industrial use only, and is not intended for use in any life support application. This is a CLASS C Uninterruptible Power Supply (UPS) product. In a domestic environment, this product may cause radio interference, in which case, the user may be required to take additional measures.
Conformity and standards
This product complies with
CE73/23 & 93/68 (low voltage safety) and 89/336 (EMC), and the following UPS product standards:
*IEC62040-1-1-General and safety requirements for use in operator access area *IEC/EN62040-2 EMC requirements CLASS C *IEC62040-3 Performance requirements and test methods For more details, refer to Chapter 9. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approved accessories only.
WARNING: high earth leakage current
Earth connection is critical before connecting the input supply (include both utility supply and battery). "Earth leakage current introduced by the UPS, in any configuration from 10kW to 200kW, exceeds 3.5 mA and is less than 1000 mA and complies with the requirements of IEC/EN 62040-1 / IEC/EN 60950-1" Transient and steady-state earth leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous RCCB or RCD devices. Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional pulses (class A) and insensitive to transient current pulses. Note also that the earth leakage currents of the load will be carried by this RCCB or RCD. This equipment must be earthed in accordance with local electrical authority codes of practice.
WARNING: back-feeding protection
This system has a control signal available for use with an automatic device, externally located, to protect against back-feeding voltage through the mains Static Bypass circuit. If this protection is not used with the switchgear that is used to isolate the bypass circuit, a label must be added to the switchgear to advise service personnel that the circuit is connected to a UPS system. The text has the following meaning or is equivalent to: Isolate the UPS before working on the circuit of this UPS.
Components that can be maintained by user
All the equipment maintenance and servicing procedures involving internal access need special tools and should be carried
out only by trained
personnel. The components that can only be accessed by opening the protective cover with tools cannot be maintained by user. This UPS full complies with “IEC62040-1-1-General and safety requirements for use in operator access area UPS”. Dangerous voltages are present within the battery box. However, the risk of contact with these high voltages is minimized for non-service personnel. Since the component with dangerous voltage can only be touched by opening the protective cover with a tool, the possibility of touching high voltage component is minimized. No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures in this manual.
Page 3
Safety Precautions
Modular UPS SM series User Manual - 2 -
Battery voltage higher than 400Vdc
All the battery maintenance and servicing procedures involving internal access need special tools or keys and should be carried out only by trained personnel.
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH THIS EQUIPMENT. WHEN CONNECTED TOGETHER, THE BATTERY TERMINAL VOLTAGE WILL EXCEED 400Vdc AND IS POTENTIALLY LEATHAL.
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times. Particular attention should be paid to the recommendations concerning local environmental conditions and the provision of protective clothing, first aid and fire-fighting facilities.
Page 4
Contents
Modular UPS SM series User Manual 3
Contents
ContentsContents
Contents
Safety Precautions .......................................................................................................... - 1 -
Chapter 1 Installation ......................................................................................................... 8
1.1 Introduction ........................................................................................................... 8
1.2 Initial Checking ....................................................................................................... 8
1.3 Location .................................................................................................................. 8
1.3.1 UPS Location ................................................................................................ 8
1.3.2 External Battery Room ................................................................................. 9
1.3.3 Storing .......................................................................................................... 9
1.4 Positioning .............................................................................................................. 9
1.4.1 System Cabinet ............................................................................................. 9
1.4.2 Moving the Cabinets .................................................................................... 9
1.4.3 Clearances Required for Operating ............................................................ 10
1.4.4 Front Access ............................................................................................... 10
1.4.5 Final Positioning ......................................................................................... 10
1.4.6 Installation of Adjustable Feet ................................................................... 10
1.4.7 UPS Composition........................................................................................ 10
1.4.8 Installing Power Modules ........................................................................... 11
1.4.9 Cable Entry ................................................................................................. 12
1.5 External Protective Devices.................................................................................. 12
1.5.1 Rectifier and Bypass Input Supply of the UPS ............................................ 12
1.5.2 External Battery ......................................................................................... 13
1.5.3 UPS Output................................................................................................. 13
1.6 Power Cables ........................................................................................................ 13
1.6.1 Cable Connections ..................................................................................... 14
1.7 Control Cabling and Communication ................................................................... 14
1.7.1 UPS Dry Contact and Monitoring Board Features ..................................... 14
1.7.2 Dry Contact Interface: Battery and Environmental Temperature Detection
(J2 / J3) ................................................................................................................ 15
1.7.3 Dry Contact Interface: Remote EPO Input Port (J4) ................................... 15
1.7.4 Dry Contact Interface: Generator Input (J5) .............................................. 16
1.7.5 Dry Contact Interface: Battery Circuit Beaker Input Port (J6 / J7) ............. 17
1.7.6 Dry Contact Interface: Battery Warning Output (J8) ................................. 18
1.7.7 Dry Contact Interface: Integrated Warning Output (J9) ............................ 18
1.7.8 Dry Contact Interface: Mains Failure Warning Output (J10) ..................... 19
Chapter 2 Battery Installation .......................................................................................... 20
2.1 General Recommendations.................................................................................. 20
2.2 Battery Typologies ................................................................................................ 21
2.2.1 Battery Installation ..................................................................................... 21
2.2 Battery Maintenance ........................................................................................... 22
Page 5
Contents
Modular UPS SM series User Manual 4
Chapter 3 Installation of UPS Rack System and Parallel System .................................... 23
3.1 Overview .............................................................................................................. 23
3.2 UPS Rack Modules in Parallel System .................................................................. 23
3.2.1 Installation of Cabinet ................................................................................ 23
3.2.2 External Protective Devices ....................................................................... 23
3.2.3 Power Cables .............................................................................................. 24
3.2.4 Parallel Signal Board ................................................................................... 24
3.2.5 Control Cables ............................................................................................ 24
Chapter 4 Installation Drawing ........................................................................................ 25
Chapter 5 Operation ......................................................................................................... 31
5.1 Introduction ......................................................................................................... 31
5.1.1 Split-Bypass Input....................................................................................... 31
5.1.2 Static Transfer Switch ................................................................................. 32
5.2 1+1 Parallel System .............................................................................................. 32
5.2.1 Features of Parallel System ........................................................................ 32
5.2.2 Parallel Requirements of UPS Modules ..................................................... 32
5.3 Operating Mode ................................................................................................... 33
5.3.1 Normal Mode ............................................................................................. 33
5.3.2 Battery Mode ............................................................................................. 33
5.3.3 Auto-Restart Mode .................................................................................... 33
5.3.4 Bypass Mode .............................................................................................. 33
5.3.5 Cold Start Mode ......................................................................................... 33
5.3.6 Maintenance Mode (Manual Bypass) ........................................................ 33
5.3.7 Parallel Redundancy Mode (System Expansion) ........................................ 33
5.3.8 Eco Mode ................................................................................................... 34
5.4 Battery Management—Set During Commissioning ............................................. 34
5.4.1 Normal Function ........................................................................................ 34
5.4.2 Advanced Functions (Software Settings Performed by the Commissioning
Engineer) ............................................................................................................. 34
5.5 Battery Protection (Settings by Commissioning Engineer) .................................. 34
Chapter 6 Operating Instructions .................................................................................... 35
6.1 Introduction ......................................................................................................... 35
6.1.1 Power Switches .......................................................................................... 35
6.2 UPS Startup .......................................................................................................... 35
6.2.1 Start-Up Procedure .................................................................................... 35
6.2.2 Procedures for Switching Between Operation Modes............................... 36
6.3 Procedure for Switching the UPS between Maintenance Bypass and Normal
Mode .......................................................................................................................... 37
6.3.1 Procedure for Switching from Normal Mode to Maintenance Bypass Mode
............................................................................................................................. 37
6.3.2 Procedure for Switching from Maintenance Mode to Normal Mode ....... 37
6.4 Procedure for Completely Powering Down a UPS ............................................... 38
6.5 Emergency Power Off (EPO) Procedure ............................................................... 38
6.6 Auto Start ............................................................................................................. 38
Page 6
Contents
Modular UPS SM series User Manual 5
6.7 UPS Reset Procedure ............................................................................................ 38
6.8 Operation Instruction for Power Module Maintenance ...................................... 38
6.9 Language Selection .............................................................................................. 39
6.10 Changing the Current Date and Time ................................................................ 39
6.11 Control Password 1 ............................................................................................ 39
Chapter 7 Operator Control and Display Panel ............................................................... 40
7.1 Introduction ......................................................................................................... 40
7.1.1 Mimic Current Path .................................................................................... 41
7.1.2 Audible Alarm (buzzer) .............................................................................. 41
7.1.3 Functional Keys .......................................................................................... 41
7.2 LCD Display Type .................................................................................................. 42
7.3 Detailed Description of Menu Items .................................................................... 43
7.4 UPS Event Log ....................................................................................................... 44
Chapter 8 Optional Parts .................................................................................................. 48
8.1 Replacing Dust Filters ........................................................................................... 48
Chapter 9 Product Specification ...................................................................................... 49
9.1 Applicable Standards............................................................................................ 49
9.2 Environmental Characteristics ............................................................................. 49
9.3 Mechanical Characteristics .................................................................................. 49
9.4 Electrical Characteristics (Input Rectifier) ............................................................ 50
9.5 Electrical Characteristics (Intermediate DC Link) ................................................. 50
9.6 Electrical Characteristics (Inverter Output) ......................................................... 50
9.7 Electrical Characteristics (Bypass Input) .............................................................. 51
9.8 Efficiency .............................................................................................................. 52
Page 7
Table of Figures
Modular UPS SM series User Manual 6
Table of Figures
Fig.1- 1: UPS structure................................................................................................ 11
Fig.1- 2: Power Module Installation Diagram ............................................................ 12
Fig.1- 3: The Symbols of RCCB .................................................................................... 12
Fig.1- 4: Front Panel of Bypass Module(Interface of Dry Contact / Monitoring Board)
............................................................................................................................. 15
Fig.1- 5: Diagram of J2 and J3 Dry Contact of Temperature Detection ...................... 15
Fig.1- 6: Diagram of input dry contact for remote EPO ............................................. 16
Fig.1- 7: Connection of Generator ............................................................................. 17
Fig.1- 8: BCB Interface ................................................................................................ 17
Fig.1- 9: Battery Low Warning Dry Contact ................................................................ 18
Fig.1- 10: Integrated warning dry contact .................................................................. 18
Fig.1- 11: Utility Failure Warning Dry Contact ........................................................... 19
Fig.3- 1: Circuit ram of EPO ........................................................................................ 23
Fig.3- 2: Installation of Parallel Signal Board BJ ......................................................... 24
Fig.3- 3: Connection of Parallel Control Cables of “1+N” System .............................. 24
Fig.4- 1: Wiring Diagram ............................................................................................ 25
Fig.4- 2: External Battery Connection ........................................................................ 25
Fig.4- 3: 200KVA UPS Module System, Front View and Rear View without Door ..... 26
Fig.4- 4: 120KVA UPS Module System, Front View and Rear View without Door ..... 26
Fig.4- 5: 60KVA UPS Module System, Front View and Rear View without Door ....... 27
Fig.4- 6: 200KVA UPS External Dimensions ................................................................ 27
Fig.4- 7: 120KVA UPS External Dimensions ................................................................ 28
Fig.4- 8: 60KVA UPS External Dimensions .................................................................. 28
Fig.4- 9: Power Connection of Module System UPS .................................................. 29
Fig.4- 10: Power Module ............................................................................................ 29
Fig.4- 11: Static Bypass Module ................................................................................. 30
Fig.5- 1: Single Unit Block Diagram ............................................................................ 31
Fig.6- 1: Location of Battery Cold Start Button .......................................................... 37
Fig.7- 1: UPS operator control and display panel ....................................................... 40
Fig.7- 2: Main LCD Display .......................................................................................... 42
Fig.8- 1: Dust Filter ..................................................................................................... 48
Page 8
Table of Tables
Modular UPS SM series User Manual 7
Table of Tables
Table.1- 1: UPS Configuration List .............................................................................. 11
Table.1- 2: Maximum Steady State AC and DC Current ............................................. 13
Table.1- 3: Description of Input Dry Contact ............................................................. 15
Table.1- 4: Description of Input Dry Contact for Remote EPO ................................... 16
Table.1- 5: Description of Status Interface and Connection of Generator ................ 17
Table.1- 6: Description of BCB Interface .................................................................... 17
Table.1- 7: Battery warning dry contact interface description .................................. 18
Table.1- 8: Integrated warning dry contact interface description ............................. 19
Table.1- 9: Description of Mains failure warning dry contact .................................... 19
Table.7- 1: Description of UPS Operator Control and Display Panel .......................... 40
Table.7- 2: Status Description of Indicator ................................................................. 41
Table.7- 3: Description of Audible Alarm ................................................................... 41
Table.7- 4: Functions of Functional Keys .................................................................... 41
Table.7- 5: Description of LCD Icons .......................................................................... 42
Table.7- 6: Description of Items in UPS System Information Window....................... 43
Table.7- 7: Item Description of UPS Menu ................................................................. 43
Table.7- 8: UPS Event List ........................................................................................... 44
Table.9- 1: Compliance with European and International Standards ........................ 49
Table.9- 2: Environmental Properties ........................................................................ 49
Table.9- 3: Mechanical Properties ............................................................................. 49
Table.9- 4: Rectifier AC Input (mains) ........................................................................ 50
Table.9- 5: Battery Information .................................................................................. 50
Table.9- 6: Inverter Output (to Critical Load) ............................................................. 50
Table.9- 7: Bypass Input ............................................................................................. 51
Table.9- 8: Efficiency, Air Exchange ............................................................................ 52
Page 9
Chapter 1 Installation
Modular UPS SM series User Manual 8
Chapter 1 Installation
1.1 Introduction
This chapter introduces the relevant requirements for positioning and cabling of the Modular UPS and related equipment. Because each site has its requirements, it is not the aim of this chapter to provide step-by-step installation instructions, but to act as a guide for the general procedures and practices that should be observed by the installing engineer.
Warning: installation can only be done by authorized engineers
Do not apply electrical power to the
UPS equipment before the commissioning engineer arrives at installation site.
The UPS should be installed by a qualified engineer in accordance with the information contained in this chapter. All the equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation information.
Note: 3-Phase 4-Wire Input Power is required
The standard UPS system can be connected to TN, TT AC distribution system (IEC60364-3) of 3-phase 4-wire and a 3-wire to 4-wire conversion transformer is provided as an optional part.
WARNING: battery hazards
SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED WITH THIS EQUIPMENT.
When connecting the battery, the battery terminal voltage will exceed 400Vdc and is potentially lethal.
Eye protection should be worn to prevent injury from accidental electrical arcs.
Remove rings, watches and all metal objects.
Only use tools with insulated handles.
Wear rubber gloves.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.
1.2 Initial Checking
Perform the following checking operations prior to the UPS installation.
1. Visually examine if there is any damage inside and outside the UPS rack and battery equipment due to the transportation. Report any such damage to the shipper immediately.
2. Verify the product label and confirm the correctness of the equipment. The equipment label is attached on the back of front door. The UPS model, capacity and main parameters are marked on the label.
1.3 Location
1.3.1 UPS Location
The UPS is intended for indoor installation and should be located in a cool, dry and clean environment with adequate ventilation to keep the environmental parameters within the specified operating range (see Table.9-2).The Modular series UPS uses forced convection cooling by internal fans. Cooling air enters the module through ventilation grills located at the front part of the cabinet and exhausted through grills located in the rear part of the cabinet. Please do not block the ventilation holes. If necessary, a system of extractor fans should be installed to aid cooling-air flow. An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain airflow. The cooling capacity of air conditioner should be selected according to the power loss data of UPS specified in Table.9-8: Normal mode (VFI SS 111 double-conversion UPS)
Note: The UPS should be installed on a cement surface or other surface that is not combustible.
Page 10
Chapter 1 Installation
Modular UPS SM series User Manual 9
1.3.2 External Battery Room
The battery will generate some amount of hydrogen and oxygen at the end of charging, so the fresh air volume of the battery installation environment must meet EN50272-2001 requirements. The ambient temperature of the battery must be stable. Ambient temperature is a major factor in determining the battery capacity and life. The nominal operating temperature of battery is 20°C. Operating above this temperature will reduce the battery life, and operation below this temperature will reduce the battery capacity. If the average operating temperature of battery is increased from 20ºC to 30ºC, then the service life of the battery will be reduced by 50%. If the operating temperature of the battery is above 40ºC, then the battery service life will be decreased in exponent rate. In a normal installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries away from heat sources or air outlets. If external batteries are to be used, the battery circuit breakers (or fuses) must be mounted as close as possible to the batteries, and the connecting cables should be as short as possible.
1.3.3 Storing
Should the equipment not be installed immediately, it must be stored in a room so as to protect it against excessive humidity and heat sources (see Table.9-2).The battery needs to be stored in dry and cool place with good ventilation. The most suitable storage temperature is 20 ºC to 25ºC.
Preventing battery deep discharge
Should the UPS remains unpowered for a prolonged period of time while the battery are connected, the batteries may deeply discharge and being so permanently damaged .In such cases it is therefore recommended to leave the battery circuit breaker(s) open. During storage in any case, periodically charge the battery according to the battery user manuals.
1.4 Positioning
When the equipment has been finally positioned, ensure the UPS will remain stationary and stable. To prolong the service life, the place chosen must guarantee:
Space for easy operation on the UPS
Air sufficient enough to dispel heat produced by UPS
Against atmospheric agents
Against excessive humidity and heat sources
Against dust
With the current fire prevention requirements
The operating environment temperature is within +20°C to +25°C. The batteries are at maximum efficiency in this temperature range (for information about the battery storage and transportation as well as the environment, refer to Table.9-2 )
This equipment is of steel frame structure wrapped by removable panels. The top and side panels are fixed by screws.
After opening the UPS rack door, the auxiliary connections for external low voltage interface and the maintenance bypass can be accessed. The UPS rack has an operator and control panel located on its front door, which provides the basic operating status and alarm information. Batteries are external. The UPS provides air inlet port in the front and the air exhaust port in the rear part.
1.4.1 System Cabinet
A UPS system can comprise an UPS rack system, external battery cabinet, depending on the specific system requirement. All the UPS system cabinets used in the same installation site are of the same height and should be positioned side-by-side to achieve an aesthetically appealing effect. Refer to Chapter 7 Installation Drawing for the positioning of UPS cabinet.
1.4.2 Moving the Cabinets
Warning
Ensure that any lifting equipment used in moving the UPS cabinet has sufficient lifting capacity.
The UPS is fitted with castors
– take care to prevent
movement when unbolting the equipment from its shipping pallet. Ensure adequate personnel and lifting aids are available when removing the shipping pallet.
Ensure that the UPS weight is within the weight loading capacity range of any hoisting equipment. See Table.9-3 for UPS weight. UPS and optional cabinets can be handled by means of a fork lift or similar equipment. The UPS cabinet can also be moved by its castors when moving in a short distance. Note: Care must be taken when handling units fitted with batteries. Keep such moves to a minimum.
Page 11
Chapter 1 Installation
Modular UPS SM series User Manual 10
1.4.3 Clearances Required for Operating
As rack module UPS has no ventilation grills at either sides, no clearances are required for the sides. To enable routine tightening of power terminations within the UPS, it is recommended that clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 500mm in the rear side of the rack to permit adequate circulation of air coming out of the unit. If the UPS make use of internal modular battery sufficient clearing shall be given at the back site to allow personnel to operate the battery circuit breakers
1.4.4 Front Access
The component layout of the UPS rack system supports front access and repairing the UPS, thus reducing the space requirement for side access.
1.4.5 Final Positioning
When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS will remain stationary and stable.
1.4.6 Installation of Adjustable Feet
Installation diagrams in Chapter 4 of this manual identify the location of the holes in the base plate through which the equipment can be bolted to the floor. If the UPS is to be located on a raised floor, it should be mounted on a pedestal suitably designed to accept the UPS point loading (more than 800 kg).
1.4.7 UPS Composition
The UPS structure is shown in Fig. 1-1. The UPS configuration is provided in Table. 1-1
(a) 10 module cabinet
Page 12
Chapter 1 Installation
Modular UPS SM series User Manual 11
(b) 6 module cabinet
(c) 3 module cabinet
Fig.1- 1: UPS structure
Table.1- 1: UPS Configuration List
Item Component
Quantity
Remarks
1 System Display 1 Requisite, factory installed
2 Bypass module
1
Requisite, facto
ry installed
3 Input/output/maintenance
bypass breakers
1 Requisite, facto
ry
installed
4 Power module
1 ≤n ≤10
Requisite
1.4.8 Installing Power Modules
The number and possible installation positions of the Power Modules may vary according to the chosen factory configuration. Please install the power modules and from bottom to top, so as to avoid cabinet toppling due to high gravity center. Installation procedures of power modules When installing power modules always work from the lower available space upwards to prevent from raising the center of gravity. The default setting from the bottom space upwards is NO.1 to NO.10 (10 modules cabinet), NO.1 to NO.6 (6 modules cabinet), or NO.1 to NO.3 (3 modules cabinet). Insert the module in the installation position, and push it into the cabinet. Secure the module to the cabinet through the fixing holes on both sides of the front panel of the module.
Page 13
Chapter 1 Installation
Modular UPS SM series User Manual 12
Fig.1- 2: Power Module Installation Diagram
1.4.9 Cable Entry
Cables can enter the module UPS rack system and battery cabinet both from bottom and top. Cable entry is made possible through a blanking plate fitted at the bottom or top of the equipment. The recommended installation practice is to install glands to prevent foreign material or vermin entering the cabinet.
1.5 External Protective Devices
For safety concerns, it is necessary to install external circuit breakers or other protective devices for the input AC supply of the UPS system. This section provides generic practical information for qualified installation engineers. The installation engineers should have the knowledge of the regulatory wiring standards, and of the equipment to be installed.
1.5.1 Rectifier and Bypass Input Supply of the UPS
Over currents
Install suitable protective devices in the distribution unit of the incoming mains supply, considering the power cable current-carrying capacity and overload capacity of the system (see Tab. 9-7). Generally, the magnetic circuit breaker with IEC60947-2 tripping curve C (normal) at the 125% of the current listed in Tab. 9-7 is recommended. Split bypass: In case a split bypass is used, separate protective devices should be installed for the rectifier input and bypass input in the incoming mains distribution panel. Note: The rectifier input and bypass input must use the same neutral line. Protection against earth faults (RCD devices): The RCD device installed upstream of the input supply should: Sensitive to DC unidirectional pulses (class A) in the network Insensitive to transient current pulses Have an average sensitivity that is adjustable between 0.3A and 1A.
Fig.1- 3: The Symbols of RCCB
When using the RCD in the split bypass system or parallel system, the RCD should be installed in the upstream of the input distribution to avoid wrong alarm. The residual current introduced by RFI filter in the UPS is between 3.5mA and 1000mA. It is recommended to confirm the sensitivity of each RCD of upstream input distribution and downstream distribution (to load).
Page 14
Chapter 1 Installation
Modular UPS SM series User Manual 13
1.5.2 External Battery
The DC compatible circuit breaker provides over current protection for UPS system and battery, which is provided by the external battery cabinet. See Appendix A for a selection guide.
1.5.3 UPS Output
In the eventuality that an external distribution panel is used for load distribution, the selection of protective devices must provide discrimination with those that are used at the input to the UPS (see Tab. 9-7).
1.6 Power Cables
Design the cables according to the descriptions in this section and local regulatory wiring standards, and the environmental conditions (temperature and physical support media) should be taken into consideration. Refer to IEC60950-1 Table 3B Cabling.
WARNING
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN EMI, ELECTRIC SHOCK HAZARD, OR
RISK OF FIRE,
SHOULD AN EARTH FAULT OCCUR.
Table.1- 2: Maximum Steady State AC and DC Current
UPS power(KVA)
Rated current (A)
Main input current at full load battery
charging12
Output current at full load2
Battery discharging current at E.O.D=1.67V/cell, no overload
380V 400V 415V 380V 400V 415V
36 Batt
ery
string
38 Batt
ery
string
40 Batt
ery
string
200 306 293 281 303 290 278 468 443 421
120 184 176 168 182 174 167 281 266 253
100 153 146 140 152 145 139 234 222 211
60 92 88 84 91 87 83 140 133 126
40 61 59 56 61 58 56 94 89 84
30 46 44 42 45 43 42 70 66 63
20 31 29 28 30 29 28 47 44 42
Note:
1. Input current of common input configurations of rectifier and bypass
2. Take special care when determining the size of the output and bypass neutral cable, as the current circulating on the neutral cable may be greater than nominal current in the case of non-linear loads, which is usually 1.732 times of rated currents.
3. The earth cable connecting the UPS to the main ground system must follow the most direct route possible. The earth conductor should be sized according to the fault rating, cable lengths, type of protection, etc. According to AS/IEC60950-1, the cross section area of the conductor is 90mm2 (200kVA), the cross section area of the conductor is 50mm2 (120KVA).
4. When sizing battery cables, a maximum volt drop of 4Vdc. is permissible at the current ratings given in Table.1-2. The load equipment is connected to a distribution network of individually protected bus-bars fed by the UPS output rather than connected directly to the UPS. In parallel multi-module systems, the output cable of each ups rack unit should be kept at equal length between the output of the ups rack output terminals and the parallel distribution bus-bars to avoid affecting the shared current. When laying the power cables, do not form coils, so as to avoid the formation of electromagnetic interference.
5. See Chapter 4 Installation Drawing for the positions of wiring terminals.
WARNING
FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN EMI, ELECTRIC SHOCK HAZARD OR RISK OF FIRE,
SHOULD AN EARTH FAULT OCCUR.
Page 15
Chapter 1 Installation
Modular UPS SM series User Manual 14
1.6.1 Cable Connections
Note
The operations described in this section must be performed by authorized electricians
or qualified technical personnel.. If you have any
difficulties, do not hesitate to contact our Customer Service & Support department.
After the equipment has been finally positioned and secured, refer to Chapter 4 Installation Drawing to connect the power cables as described in the following procedures:
1. Verify that all the external input distribution switches of the UPS are completely opened and the UPS internal maintenance bypass switch is opened. Attach necessary warning signs to these switches to prevent unauthorized operation.
2. Open rear panel of the UPS, and then the power connection terminals are visible.
3. Connect the protective earth and any necessary grounding cables to the PE terminal. The cabinet for the UPS must be connected to the user’s ground connection.
Note: The grounding cable and neutral cable must be connected in accordance with local and national codes practice. Identify and make power connections for incoming cables according to one of the two procedures below, depending on the type of installation:
Common Input Connections
4. For common bypass and rectifier inputs, connect the AC input supply cables to the UPS input terminals (mA-mB-mC-mN) Refer to Fig. 4-11 and tighten the connections to 5 Nm (M6 Bolt), 13Nm(M8 Bolt). ENSURE CORRECT PHASE ROTATION.
Split Bypass Connections
5. If a 'split-bypass' configuration is used, connect the AC input supply cables to the rectifier input terminals (mA-mB-mC-mN) Refer to Fig.4-11 and the AC bypass supply cables to the bypass input terminals (bA-bB-bC-bN) and tighten the connections to 5 Nm (M6 Bolt) or 13Nm (M8 Bolt) or 25Nm (M10 Bolt). ENSURE CORRECT PHASE ROTATION. Note: For split Bypass operation ensure that the bus-bars between Bypass and Rectifier inputs are removed. The neutral line of bypass input must be connected to that of the rectifier input.
Frequency Converter Mode
If the frequency converter configuration is used, connect the AC input cables to the rectifier input terminals (mA-mB-mC-mN) Refer to Fig.4-11 and tighten the connections to 5Nm (M6 bolt), or to 13Nm (M8 bolt), or to 25Nm (M10 bolt). ENSURE CORRECT PHASE ROTATION AND TIGHTEN CONNECTION TERMINALS. No need to connect the bypass input cables to bypass input terminals (bA-bB-bC-bN). Note: For the frequency converter operation mode, ensure that the bus-bars between Bypass and Rectifier inputs are removed.
Output System Connections
6. Connect the system output cables between the UPS output bus-bars (oA-oB-oC-N) Refer to Fig.4-11 and the critical load and tighten the connections to 5Nm (M6 Bolt) or to 13Nm (M8 Bolt) or to 25Nm(M10 Bolt). ENSURE CORRECT PHASE ROTATION.
WARNING
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, then ensure that the system output cables are safely isolated at their ends.
7. Re-install all the protective covers.
1.7 Control Cabling and Communication
1.7.1 UPS Dry Contact and Monitoring Board Features
According to the specific needs of the field, the UPS may need auxiliary connection to realize the management of the battery system (including external battery switch and battery temperature sensor), communicate with PC, provide alarm signal to external device, or realize remote EPO. These functions are realized through the UPS dry contact board and monitoring board at the front of bypass module. The boards provide the following interfaces:
EPO
Environment and battery temperature input interface
Generator input dry contact interface
Page 16
Chapter 1 Installation
Modular UPS SM series User Manual 15
Battery warning output dry contact interface
Battery circuit breaker interface
Mains failure warning output dry contact interface
Intelligent card interface
User communication interface
The UPS dry contact board provides input dry contacts and output dry contacts.
Fig.1- 4: Front Panel of Bypass Module (Include Interface of Dry Contact)
1.7.2 Dry Contact Interface: Battery and Environmental Temperature Detection (J2 / J3)
The input dry contact J2 and J3 detect the temperature of batteries and environment respectively, which can be used in environment monitoring and battery temperature compensation. J2 and J3 interfaces diagram are shown in fig.1-5, and the description of interface is in table.1-3.
Fig.1- 5: Diagram of J2 and J3 Dry Contact of Temperature Detection
Table.1- 3: Description of Input Dry Contact
Position
Name Purpose
J2.1 TEMP_BAT Battery temperature detection
J2.2 / Battery temperature detection
J3.1 TEMP_ENV
Environment temperature detection
J3.2 / Environment temperature detection
Note: Specified temperature sensor is required for temperature detection (R25=5Ohm, B25/50=3275), please confirm with the
manufacturer, or contact local maintenance engineers when placing an order.
1.7.3 Dry Contact Interface: Remote EPO Input Port (J4)
The UPS has an Emergency Power OFF (EPO) function. This function can be activated by pressing a button on the control panel of the UPS or through a remote contact provided by the user. The EPO pushbutton is protected by a hinged plastic cover. J4 is the input port for remote EPO. It requires shorting NC and +24v during normal operation, and the EPO is triggered when opening NC and +24v,
Page 17
Chapter 1 Installation
Modular UPS SM series User Manual 16
or shorting NO and +24v. The port diagram is shown in fig.1-6, and port description is shown in table.1-4.
Fig.1- 6: Diagram of input dry contact for remote EPO
Table.1- 4: Description of Input Dry Contact for Remote EPO
Position Name Purpose
J4.1 EPO_NC EPO is activated when disconnecting fromJ4.2
J4.2
24V
+24V, connect the common terminal of NC and NO
J4.3 EPO_NO EPO is activated when shorting with J4.2
The EPO is triggered when shorting pin 2 and 3 or opening pin 2 and 1 of J4. If an external emergency stop facility is required, it is connected via the reserved terminals of J4. The external emergency stop facility needs to use shielded cables to connect to the normally open/closed remote stop switch between these two pins. If this facility is not used, then pin 3 and pin 4 of J4 must be open, or pin 1 and pin 2 of J4 must be shorted.
Note
1. The emergency stop action within the UPS will shut down the rectifier, inverter and static bypass. However, it does not internally disconnect the mains input power supply. To disconnect ALL power to the UPS, open the upstream input circuit breaker(s) when the EPO is activated.
2. Pin 1 and 2 of J4 have been shorted before the UPS is delivered.
3. All auxiliary cables must be double insulated twisted cables with cross sectional area of 0.5mm2 ~ 1.5mm2 for maximum connection length between 25m and 50m.
1.7.4 Dry Contact Interface: Generator Input (J5)
J5 is the status interface for generator connection. Connect J5-2 with J5-1, and it indicates that the generator has been connected with the system. The interface diagram is shown in fig.1-7, and interface description is shown in table.1-5.
Page 18
Chapter 1 Installation
Modular UPS SM series User Manual 17
Fig.1- 7: Connection of Generator
Table.1- 5: Description of Status Interface and Connection of Generator
Position Name Purpose
J5.1 +24V Internal
+24V power supply
J5.2 GEN Connection status of generator
J5.3 GND Power ground
Note
All auxiliary cables must be double insulated twisted cables with cross sectional area of 0.5mm2 ~ 1.5mm2 for maximum connection length between 25m and 50m.
1.7.5 Dry Contact Interface: Battery Circuit Beaker Input Port (J6 / J7)
J6 and J7 are the ports of BCB. The diagram is shown in fig.1-8, and description is shown in table.1-6.
Fig.1- 8: BCB Interface
Table.1- 6: Description of BCB Interface
Position
Name Description
J6.1 BCB_DRV
BCB actuating signal, provide the actuating
signal of +24V, 20mA
J6.2 BCB_CONT BCB contact status, connect with the normally open signal of BCB
J7.1 GND Common connection
J7.2 BCB_ONL
BCB on
-
line–input (normally open) , BCB is on
-
line when the signal is connecting with GND
Page 19
Chapter 1 Installation
Modular UPS SM series User Manual 18
Note
All auxiliary cables must be double insulated twisted cables with cross sectional area of 0.5mm2 ~ 1.5mm2 for maximum connection length between 25m and 50m.
1.7.6 Dry Contact Interface: Battery Warning Output (J8)
J8 is the output dry contact interface, which outputs the battery warnings of low or excessive voltage, when the battery voltage is lower than set value, an auxiliary dry contact signal will be provided via the isolation of a relay. The interface diagram is shown in fig.1-9, and description is shown in table.1-7.
Fig.1- 9: Battery Low Warning Dry Contact
Table.1- 7: Battery warning dry contact interface description
Position
Name description
J8.1 BAT_LOW_NC Battery warning relay (normally closed) will be open during warning
J8.2 BAT_LOW_NO
Battery warning relay (normally open) will be closed during warning
J8.3 GND Commo
n connection
1.7.7 Dry Contact Interface: Integrated Warning Output (J9)
J9 is the integrated warning output dry contact interface, when one or more than one present warning is triggered, the system will send integrated warning information, and provide an auxiliary dry contact signal via the isolation of a relay. The interface diagram is shown in fig.1-10, and description is shown in table.1-8.
Fig.1- 10: Integrated warning dry contact
Page 20
Chapter 1 Installation
Modular UPS SM series User Manual 19
Table.1- 8: Integrated warning dry contact interface description
Position Name Purpose
J9.1 ALARM_NC Integrated warning relay (normally closed) will be open during warning
J9.2 ALARM_NO Integrated warning relay (normally open) will be closed during warning
J9.3 GND Common connection
Note
All auxiliary cables must be double insulated twisted cables with cross sectional area of 0.5mm2 ~ 1.5mm2 for maximum connection length between 25m and 50m.
1.7.8 Dry Contact Interface: Mains Failure Warning Output (J10)
J10 is the output dry contact interface for utility failure warning, when the utility fails, the system will send a utility failure warning information, and provide an auxiliary dry contact signal via the isolation of a relay. The interface diagram is shown in fig.1-11, and description is shown in table.1-9.
Fig.1- 11: Utility Failure Warning Dry Contact
Table.1- 9: Description of Mains failure warning dry contact
Position
Name Purpose
J10.1 UTI_FAIL_NC
Mains failure warning relay(normally closed) will be
open during warning
J10.2 UTI_FAIL_NO Mains failure warning relay (normally open) will be closed during warning
J10.3 GND
Common connection
Note
All auxiliary cables must be double insulated twisted cables with cross sectional area of 0.5mm2 ~ 1.5mm2
for maximum connection length
between 25m and 50m.
Page 21
Chapter 2 Battery Installation
Modular UPS SM series User Manual 20
Chapter 2 Battery Installation
2.1 General Recommendations
Take special care when operating the batteries of the Modular UPS system. When all the battery cells are connected, the battery voltage can exceed 400Vdc, which is potentially lethal.
Note
The precautions for battery installation, use and maintenance are to be provided by the batteries manufacturers. The precauti
ons in this section
include the key issues that must be considered during the installation design, which may be adjusted according to the specific local situations.
Battery Room Design
The battery shall be installed and stored in a clean, cool and dry environment.
Do not install the battery in a sealed battery chamber or sealed room. The battery room ventilation shall at least meet the requirement of EN50272-2001. Otherwise, battery bulging, fire and even human injury may be caused.
The battery shall be installed far away from the heating source (e.g. transformer). Do not use or store the battery in the place near the heating source or burn the battery or place it into fire. Otherwise, battery leakage, bulging, fire or explosion may be caused.
Batteries shall be placed in such a manner that two bare live parts with the potential difference of more than 150V shall not be contacted at the same time. If it is unavoidable, insulated terminal cover and insulated cables shall be used for connection.
If external batteries are to be used, the battery circuit breakers (or fuses) must be mounted as close as possible to the batteries, and the connecting cables should be as short as possible.
Battery Handling
When connecting the battery, follow the precautions for high-voltage operation
Before accepting and using the battery, check the appearance the battery. If the package is damaged, or the battery terminal is dirty, corroded or rusted or the shell is broken, deformed or has leakage, replace it with new product. Otherwise, battery capacity reduction, electric leakage or fire may be caused.
Before operating the battery, remove the finger ring, watch, necklace, bracelet and any other metal jewelry Wear rubber gloves. Eye protection should be worn to prevent injury from accidental electrical arcs. Only use tools (e.g. wrench) with insulated handles.
The batteries are very heavy. Please handle and lift the battery with proper method to prevent any human injury or damage to the battery terminal.
Do not decompose, modify or damage the battery. Otherwise, battery short circuit, leakage or even human injury may be caused.
The battery contains sulfuric acid. In normal operation, all the sulfuric acid is attached to the separation board and plate in the battery. However, when the battery case is broken, the acid will leak from the battery. Therefore, be sure to wear a pair of protective glasses, rubber gloves and skirt when operating the battery. Otherwise, you may become blind if acid enters your eyes and your skin may be damaged by the acid.
At the end of battery life, the battery may have internal short circuit, drain of electrolytic and erosion of positive/negative plates. If this condition continues, the battery may have temperature out of control, swell or leak. Be sure to replace the battery before these phenomena happen.
If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.
If electrolyte comes into contact with the skin, the affected area should be washed immediately with water.
Page 22
Chapter 2 Battery Installation
Modular UPS SM series User Manual 21
2.2 Battery Typologies
Traditional: consisting of one of more strings of battery blocks installed on shelves in a locked cabinet or dedicated battery room.
Note
The Traditional external battery cabinet can make use of each even number of battery per string between 36 and 44. The default factory setting, if the unit is ordered w/o internal battery is 40. The cabinet is only for valve regulated maintenance-free lead-acid battery. CAUTION: The lead acid battery may cause chemistry hazard
2.2.1 Battery Installation
Only the qualified engineers are allowed to install and maintain mounted in a traditional battery cabinet or shelf. To ensure safety, install the external battery in a locked cabinet or dedicated battery room accessible just to service qualified personnel. Please note that number of cells set via software must be consistent with the actual number of cells. A minimum space of 10mm must be reserved on all vertical sides of the battery block to permit free air movement around the cells. A certain clearance should be reserved between the top of the cells and the underside of the shelf above as this is necessary for monitoring and servicing the cells. When installing the batteries always work from the bottom shelf upwards to prevent raising the center of gravity. Install the batteries reliably and avoid vibration and mechanical bumping. The bending radius of cable should be more than 10D, where "D" is the outer diameter of cable. When connecting the cable, do not cross the battery cables and do not bind the battery cables together. The battery connection must be firm and reliable. After the connection, all the connections between the wiring terminals and the batteries must be corrected to meet the torque requirement provided in the specifications and user manuals of the battery manufacturers. Each battery terminal should be insulated after its connection has been made. Check if the battery is unexpectedly grounded. If the battery is unexpectedly grounded, remove the earth power supply. Contacting any part of the grounded earth may be subject to electric shock. Measure the battery voltage, and carry out battery voltage calibration after the UPS is started.
Warning: Battery connections
When using a
traditional battery solution, always comply with the following precautions:
Disconnect the charging power before connecting or disconnecting the cable of the battery terminals.
Do not connect the cables between the UPS battery terminals and the batteries before getting the approval from the commissioning engineer.
When connecting the cables between the battery terminals and the circuit breaker, always connect the circuit breaker end of the cable first.
Be sure to connect the positive/negative terminals of the batteries to circuit breakers and circuit breakers to the UPS respectively with reference to the markings of positive/negative terminals. Reverse connection of battery polarities will result in explosion, fire accident, the damage of batteries and UPS, and human injury.
The battery connecting terminal shall not subject to any external force, such as the pulling force or twisting force of the cable. Otherwise, the internal connection of the battery may be damaged, and in severe case, the battery may catch fire.
Do not connect power until the total voltage of the battery string is verified correct through measurement.
Do not connect any conductor between the positive and negative terminals of the battery.
Do not close the battery circuit breakers before getting the approval from the commissioning engineer.
Page 23
Chapter 2 Battery Installation
Modular UPS SM series User Manual 22
2.2 Battery Maintenance
For the battery maintenance and precautions, please refer to IEEE-Std-1188-2005 and the relevant manuals provided by the battery manufacturers.
Battery Maintenance Note
Check to ensure that all the safety devices are in place and function normally. Check if the battery management parameter setting is normal particularly.
Measure and record the air temperature in the battery room.
Check if the battery terminals are damaged or have the symptom of heating, and if the shell or cover is damaged.
Please fasten every bolt on the terminal according to the fastening torque specified in the table below.
After 1-2 months of service, recheck to make sure that each screw has been fastened according to the specified torque. Otherwise there is risk of fire.
CAUTION: Use the battery with the same capacity and type, if battery is replaced by an incorrect type, it can cause explosion.
CAUTION: Dispose of used battery according to the local instructions
Page 24
Chapter 3 Installation of UPS Rack System and Parallel System
Modular UPS SM series User Manual 23
Chapter 3 Installation of UPS Rack System and Parallel System
3.1 Overview
The single or parallel system should be installed according to the installation procedures of the UPS rack module system and the requirements in this Chapter. For single UPS rack module installation the EPO button on the front panel of the UPS rack controls the emergency stop of UPS modules and bypass static switch and also supports remote emergency power off function that can be used to shut down the UPS rack module remotely.
Note
1. The remote EPO switch must provide normally open or normally closed dry contact signals.
2. The open circuit voltage is 24Vdc, and the current is less than 20mA.
3. Normally closed EPO-J4 terminals: Pin 1 and pin 2 have been connected in factory and located on the dry contact board GJ.
UPS1
Dry contact board GJ
J4-2
J4-3
UPS1
Dry contact board GJ
J4-2
J4-3
UPS2
Dry contact board GJ
J4-2
J4-3
Fig.3- 1: Circuit ram of EPO
3.2 UPS Rack Modules in Parallel System
The basic installation procedures of parallel system are the same with those of the UPS rack module system. In this section, only the installation procedures related to the parallel system are introduced.
3.2.1 Installation of Cabinet
To make the maintenance and system test easier, an external maintenance bypass is recommended in the installation.
3.2.2 External Protective Devices
Refer to Chapter 1 Installation
Page 25
Chapter 3 Installation of UPS Rack System and Parallel System
Modular UPS SM series User Manual 24
3.2.3 Power Cables
The power cable connection of the parallel rack module system is similar to that of the single UPS rack module system. If the bypass input and rectifier input share the same neutral terminal and if an RCD protective device is installed at the input, then the RCD device must be installed before the input cables are connected to the neutral terminal. Refer to Chapter 1 Installation Note: The length and specification of the power cables of each UPS module should be the same, including the bypass input cables and UPS output cables, so that the load sharing effect can be achieved in bypass mode.
3.2.4 Parallel Signal Board
Installation of parallel signal board
The parallel signal board BJ is installed at the rear of the static switch power module. Refer to fig.3-2,
(a) (b)
Fig.3- 2: Installation of Parallel Signal Board BJ
Remove cable W102 as fig.3-2(a)
Install parallel signal board BJ as fig.3-2(b)
Connect cable 1 and cable 2 as fig.3-2(b)
3.2.5 Control Cables
Parallel control cable
The parallel control cables are designed to be shielded and double insulated, and are connected between the UPS rack modules to form a loop as shown below. The parallel signal board BJ is installed at the rear of the static switch power module. This close loop connection ensures the reliability of the parallel system control. Refer to fig. 3-3
Fig.3- 3: Connection of Parallel Control Cables of “1+N” System
Page 26
Chapter 4 Installation Drawing
Modular UPS SM series User Manual 25
Chapter 4 Installation Drawing
Input
Output
Bypass(Option)
External Batt.
+ N -
Dry Contact Board GJ
Fig.4- 1: Wiring Diagram
BCB_DRV
BCB_CONT
J6
J7
BCB_ONL
+24V
+24V
+24V
Fig.4- 2: External Battery Connection
Page 27
Chapter 4 Installation Drawing
Modular UPS SM series User Manual 26
External BCB interface:
BCB DRV: J6-1 BCB drive signal BCB STATUS: J6-2 BCB contactor status, normally opened. Shorted to GND when activated GND: J7-1 ground
Fig.4- 3: 200KVA UPS Module System, Front View and Rear View without Door
Fig.4- 4: 120KVA UPS Module System, Front View and Rear View without Door
Page 28
Chapter 4 Installation Drawing
Modular UPS SM series User Manual 27
Fig.4- 5: 60KVA UPS Module System, Front View and Rear View without Door
Fig.4- 6: 200KVA UPS External Dimensions
Top view
Page 29
Chapter 4 Installation Drawing
Modular UPS SM series User Manual 28
Fig.4- 7: 120KVA UPS External Dimensions
Fig.4- 8: 60KVA UPS External Dimensions
Page 30
Chapter 4 Installation Drawing
Modular UPS SM series User Manual 29
(a) 200KVA UPS power connection
(b) 120KVA UPS power connection
(c) 60KVA UPS power connection
Fig.4- 9: Power Connection of Module System UPS
Fig.4- 10: Power Module
Page 31
Chapter 4 Installation Drawing
Modular UPS SM series User Manual 30
Fig.4- 11: Static Bypass Module
Notes for installing modules:
1. When installing the modules, install the modules from bottom to top. When removing the modules, remove the modules from top to bottom. The purpose is to maintain the stable center of gravity.
2. After inserting the module, tighten all the screws.
3. When removing the modules, turn off modules first, remove the screws and then remove the modules.
4. Wait for 5 minutes before inserting the removed modules.
Page 32
Chapter 5 Operation
Modular UPS SM series User Manual 31
Chapter 5 Operation
Warning: Hazardous mains voltage and/or battery voltage present(s) behind the protective cover
The components
that can only be accessed by opening the protective cover with tools cannot be operated by user. Only qualified service
personnel are authorized to remove such covers.
5.1 Introduction
The Modular UPS rack system provides the critical load (such as communication and data processing equipment) with high quality uninterruptible AC power. The power from the UPS is free from voltage and frequency variations and disturbances (interruption and spike) experienced at the Mains AC input supply. This is achieved through high frequency double conversion power pulse width modulation (PWM) associated with fully digital signal processing control (DSP), which features high reliability and convenience for use. As shown in fig.5-1, the AC input mains source is supplied at UPS input and converted into a DC source. This DC source feeds the Inverter that converts the DC source into a clean and input independent AC source. The battery powers the load through the inverter in case of an AC input mains power failure. The utility source can also power the load through the static bypass. When the UPS needs maintenance or repair, the load can be transferred to maintenance bypass without interruption and the power module and bypass module can be removed for maintenance.
REC INV
BAT
CHARGER
REC INV
BAT
CHARGER
BCB
Battery Module
BCB
bA bB bC
Optional
mA mB mC mN
Batt+
BattN
Batt-
oA oB oC oN
Power Module 1#
Power Module 10#
Bypass Module
Maintenance Bypass
Fig.5- 1: Single Unit Block Diagram
5.1.1 Split-Bypass Input
Fig. 5-1 illustrates the Modular UPS in what is known as the split-bypass configuration (that is, the bypass uses a separate AC source). In this configuration, the static bypass and maintenance bypass share the same independent bypass power supply and connect to the power supply
Page 33
Chapter 5 Operation
Modular UPS SM series User Manual 32
through a separate switch. Where a separate power source is not available, the bypass and rectifier input supply connections are linked.
Note
Split-Bypass Input function is optional.
Default of factory is single input.
5.1.2 Static Transfer Switch
The circuit blocks labeled Static Switch in fig.5-1 contain electronically controlled switching circuits that enable the critical load to be connected to either the inverter output or to a bypass power source via the static bypass line. During normal system operation the load is connected to the inverter; but in the event of a UPS overload or inverter failure, the load is automatically transferred to the static bypass line. To provide a clean (no-break) load transfer between the inverter output and static bypass line, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics, which makes the inverter frequency track that of the static bypass supply, provided that the bypass remains within an acceptable frequency window. A manually controlled maintenance bypass supply is incorporated into the UPS design. It enables the critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine maintenance.
Note
When the UPS is
operating in bypass mode or on maintenance bypass, the connected equipment is not protected from power failures or surges
and sags.
5.2 1+1 Parallel System
Several “single unit” UPS modules may constitute a “1+1” system, where up to two single units operate together for the purpose of providing additional power or reliability or both. The load is equally shared between any paralleled UPSs. In addition, two UPS modules or 1+1 groups may be configured as “distributed redundant” systems. Each UPS module or system has independent outputs that nevertheless are synchronized through a Load Bus Synchronizer (LBS) so that critical loads can be seamlessly transferred from one system to another. See 5.3 Operating Mode for more information.
5.2.1 Features of Parallel System
1. The hardware and firmware of single module UPS units are completely compatible with the requirements of a parallel system. Parallel configuration can be achieved merely through settings in configuration software. The parameters settings for the modules in parallel system shall be consistent.
2. Parallel control cables are connected in a ring, providing both performance and redundancy. Dual-bus control cables are connected between any two UPS modules of each bus. The intelligent paralleling logic provides the user with maximum flexibility. For example, shutting down or starting up UPS modules in a parallel system can be done in any sequence. Transfers between Normal and Bypass modes of operation are synchronized and self–recovering e.g. following overloads and their clearance.
3. The total load of the parallel system can be queried from each module’s LCD.
5.2.2 Parallel Requirements of UPS Modules
A group of paralleled modules behave as if it were one large UPS with the advantage of presenting higher reliability. In order to assure that all modules are equally utilized and to comply with relevant wiring rules, the following requirements apply:
1. All UPS modules shall be of the same rating and must be connected to the same bypass source.
2. The bypass and the main input sources must be referenced to the same neutral potential.
3. Any RCD (Residual Current detecting device), if installed, must be of an appropriate setting and located upstream of the common neutral bonding point. Alternatively, the device must monitor the protective earth currents of the system. Refer to the High Leakage Current Warning in the first part of this manual.
4. The outputs of all UPS modules must be connected to a common output bus.
5. It is strongly recommended that each paralleled UPS install at least a redundant power module
Page 34
Chapter 5 Operation
Modular UPS SM series User Manual 33
Note
Optional isolation transformers are available for applications where sources do not share the same neutral reference or where
the neutral is not
available.
5.3 Operating Mode
The Modular UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these modes:
Normal mode
Battery Mode
Auto-restart mode
Bypass mode
Cold start mode
Maintenance mode (manual bypass)
Parallel redundancy mode
Eco Mode
5.3.1 Normal Mode
The UPS inverter power modules continuously supplies the critical AC load. The rectifier/charger derives power from the AC mains input source and supplies DC power to the inverter while simultaneously FLOAT or BOOST charging its associated backup battery.
5.3.2 Battery Mode
Upon failure of the AC mains input power; the inverter power modules, which obtains power from the battery, supplies the critical AC load. There is no interruption in power to the critical load upon failure. After restoration of the AC mains input power, the “Normal Mode” operation will continue automatically without the necessity of user intervention.
5.3.3 Auto-Restart Mode
The battery may become exhausted following an extended AC mains failure. The inverter shuts down when the battery reaches the End of Discharge voltage (EOD). The UPS may be programmed to “Auto Recovery after EOD” after a delay time if the AC mains input recovers. This mode and any delay time are programmed by the commissioning engineer.
5.3.4 Bypass Mode
If the inverter overload capacity is exceeded under normal mode, or if the inverter becomes unavailable for any reason, the static transfer switch will perform a transfer of the load from the inverter to the bypass source, with no interruption in power to the critical AC load. Should the inverter be asynchronous with the bypass, the static switch will perform a transfer of the load from the inverter to the bypass with power interruption to the load. This is to avoid large cross currents due to the paralleling of unsynchronized AC sources. This interruption is programmable but typically set to be less than 3/4 of an electrical cycle, e.g., less than 15ms (50Hz) or less than 12.5ms (60Hz).
5.3.5 Cold Start Mode
If there is no utility input and want UPS to start from battery mode, UPS can start up from Cold start mode
5.3.6 Maintenance Mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS becomes unavailable e.g. during a maintenance procedure.
5.3.7 Parallel Redundancy Mode (System Expansion)
For higher capacity or higher reliability or both, the outputs of several UPS modules can be programmed for direct parallel while a built-in parallel controller in each UPS ensures automatic load sharing. A parallel system can be composed of up to two UPS modules.
Page 35
Chapter 5 Operation
Modular UPS SM series User Manual 34
5.3.8 Eco Mode
To improve system efficiency, UPS rack system works in bypass mode at normal time, and inverter is standby. When utility fails, UPS transfer to battery mode, and inverter power the loads. The efficiency of ECO system can be up to 98%. NOTE: There is a short interruption time (lower than 10ms) when transfer from ECO mode to battery mode, it must be sure that the time has no effect on loads.
5.4 Battery Management—Set During Commissioning
5.4.1 Normal Function
1. Constant Current Boost Charging
Current can be set up as 0%~20%, default setting is 10%.
2. Constant Voltage Boost Charging
Voltage of boost charging can be set as required by the type of battery. For Valve Regulated Lead Acid (VRLA) batteries, maximum boost charge voltage should not exceed 2.4V / cell.
3. Float Charge
Voltage of float charging can be set as required by the type of battery. For VRLA, float charge voltage should be between 2.2V to 2.3V, default setting is 2.25V.
4. Float Charge Temperature Compensation (optional)
A coefficient of temperature compensation can be set as required by the type of battery.
5. End of Discharge (EOD) Protection
If the battery voltage is lower than the EOD, the battery converter will shut down and the battery is isolated to avoid further battery discharge. EOD is adjustable from 1.6V to 1.75V per cell (VRLA).
5.4.2 Advanced Functions (Software Settings Performed by the Commissioning Engineer)
Battery self-test and self-service
At periodic intervals, 25% of the rated capacity of the battery will be discharged automatically, and the actual load must exceed 25% of the rated UPS (kVA) capacity. If the load is less than 25%, auto-discharge cannot be executed. The periodic interval can be set from 720 to 3000 hours. Conditions: Battery at float charge for at least 5 hours, load equal to 25~100% of rated UPS capacity Trigger—Manually through the command of Battery Maintenance Test in LCD panel or automatically Battery self-test interval.
5.5 Battery Protection (Settings by Commissioning Engineer)
Battery Low Pre-warning
The battery under-voltage pre-warning occurs before the end of discharge. After this pre-warning, the battery should have the capacity for 3 remaining minutes discharging with full load. And the
End of discharge (EOD) protection
If the battery voltage is lower than the EOD, the battery converter will be shut down. EOD is adjustable from 1.6V to 1.75V per cell (VRLA).
Battery Disconnect Devices Alarm
The alarm occurs when the battery disconnect device disconnects. The external battery connects to the UPS through the external battery circuit breaker. The circuit breaker is manually closed and tripped by the UPS control circuit.
Page 36
Chapter 6 Operating Instructions
Modular UPS SM series User Manual 35
Chapter 6 Operating Instructions
Warning-Hazardous mains voltage and/or battery voltage present(s) behind the protective cover
The components that can only be accessed by opening the protective cover with tools cannot be operated by user. Only qualifie
d service
personnel are authorized to remove such covers.
6.1 Introduction
The Modular UPS operates in the following 3 modes listed in table.6-1. This section describes various kinds of operating procedures under each operating mode, including transfer between operating modes, UPS setting and procedures for turning on/off inverter.
Tab.6-1: UPS Operating mode
Operating mode Descriptions
Normal mode
UPS powers the load
Bypass mode
The load power supply is provided by the static bypass. This mode can be regarded as a temporary transition
mode
between the normal mode and maintenance bypass mode, or a temporary abnormal operating status
Maintenance mode
UPS Shuts down, the load is connected to the mains vie Maintenance bypass. NOTE: in this mode the load is not
protected against abnormal mains
Note:
1. Refer to Chapter 7 Operator Control and Display Panel, for all the user operating keys and LED displays.
2. The audible alarm may annunciate at various points in these procedures.
3. The UPS function can be set via maintenance software. However, the setting and commissioning must be done by maintenance engineers trained.
6.1.1 Power Switches
The UPS rack system has a maintenance bypass breaker, a main input breaker and output breaker, and all the other transfers are processed automatically by internal control logics.
6.2 UPS Startup
Do not start the UPS until the installation is completed, the system has been commissioned by authorized personnel and the external power isolators are closed.
6.2.1 Start-Up Procedure
This procedure must be followed when turning on the UPS from a fully powered down condition. The operating procedures are as follows:
1. Open the external power switch. Open the internal power switch. Open the UPS door, connect the power supply cables and ensure the correct
phase rotation.
Warning
During this procedure the UPS output terminals are live. If any load equipment are connected to the UPS output terminals please check with the load user that it is safe to apply power: If the load is not ready to receive power then ensure that it is safely isolated from the UPS output terminals.
2. Close the output circuit breaker (Q3). Close the mains input circuit breaker (Q1) and connect the mains power. The LCD starts up at
this time. The Rectifier indicator flashes during the startup of rectifier. The rectifier enters normal operation state, and after about 20s, the rectifier indicator goes steady green. After initialization, the bypass static switch closes. The UPS Mimic LEDs will indicate as following:
Page 37
Chapter 6 Operating Instructions
Modular UPS SM series User Manual 36
LED Status
Rectifier indicator Green
Battery indicator Red
Bypass indicator Green
Inverter Indicator Off
Load indicator Green
Status indicator Green
Note
The output circuit breaker (Q3) must be closed first, followed by input circuit breaker (Q1), or the rectifier cannot
be started.
3. The inverter starts up automatically. The inverter indicator flashes during the startup of inverter. After about 1minute, the inverter is ready,
the UPS transfers from bypass to inverter, the bypass indicator turns off, and the inverter and load indicators turn on. The UPS is in normal mode. The UPS Mimic LEDs will indicate as following:
LED St
atus
Rectifier indicator Green
Battery indicator Red
Bypass indicator Off
Inverter Indicator Green
Load indicator Green
Status indicator Green
4. Close external battery switch, battery indicator turns off, a few minutes later the battery will be charged by UPS. The UPS Mimic LEDs will
indicates as following:
LED Status
Rectifier indicator Green
Battery indicator Green
Bypass indicator Off
Inverter Indicator Green
Load indicator Green
Status indicator Green
6.2.2 Procedures for Switching Between Operation Modes
Switch from normal mode to bypass mode
Press “Transfer bypass” menu in menu to switch to bypass mode.
Note
In bypass mode, the load is directly fed by the mains power instead of the pure AC power from the inverter.
Switch from bypass mode to normal mode
Press “Escape bypass” menu in bypass mode. After inverter enters normal operation, UPS transfers to normal mode.
Battery Start
Verify that the battery is properly connected.
Press the cold start-up button (see as fig.6-1) under the rectifier input circuit breaker for 1 seconds
At this point, the LCD displays the start screen, press cold start-up button again. And the battery indicator flashes green. It stops flashing and becomes solid green about 10 seconds after the rectifiers enter normal operation.
The inverter starts up automatically, the green inverter indicator flashes. The UPS works in battery mode after 60 seconds.
Page 38
Chapter 6 Operating Instructions
Modular UPS SM series User Manual 37
Fig.6- 1: Location of Battery Cold Start Button
6.3 Procedure for Switching the UPS between Maintenance Bypass and Normal Mode
6.3.1 Procedure for Switching from Normal Mode to Maintenance Bypass Mode
This procedure can transfer the load from the UPS inverter output to the maintenance bypass supply, but the precondition is that the UPS is in normal mode before the transfer.
Caution
Before making this operation, read messages on display to be sure that bypass supply is regular and the inverter is synchrono
us with it, so as not
to risk a short interruption in powering the load.
1. Press the “Transfer Bypass” menu in on the right side of the LCD. The UPS Mimic indicator Inverter will green flash and also the Status
Indicator will turn red and will be accompanied by an audible alarm. The load transfers to static bypass, and the inverter standby.
Note
Pressing the Alarm Silence button cancels the audible alarm but leaves the warning message displayed until the alarm condition is rectified.
2. Open the UPS front door, and close the maintenance bypass breaker (Q2) from OFF to ON position. The load power supply is provided by the
manual maintenance bypass.
3. Press EPO to make sure the charge current is 0. Open the mains input breaker (Q1) and output breaker (Q3), open the external battery
breaker.
Warning
If you need to maintain the module, wait for 10 minutes to let the DC bus capacitor fully discharge before removing corresponding module. When the maintenance bypass switch is on position of ON, some part of the UPS circuit still has hazardous voltage. Therefore, only qualified person can maintain the UPS.
Note
When the UPS is in maintenance bypass mode, the load is not protected against abnormal mains supply.
6.3.2 Procedure for Switching from Maintenance Mode to Normal Mode
1. Close output breaker (Q3). Close mains input breaker (Q1). The LCD starts up at this time. The Rectifier indicator flashes during the startup
of rectifier. The rectifier enters normal operation state, and after about 20s, the rectifier indicator goes steady green. After initialization, the bypass static switch closes.
2. Open the manual maintenance breaker (Q2).
Page 39
Chapter 6 Operating Instructions
Modular UPS SM series User Manual 38
Warning
Before opening the maintenance breaker (Q2), make sure that static bypass switch is working according power flow displayed on
LCD.
3. After about 60s, UPS transfers to inverter. Close external battery breaker.
6.4 Procedure for Completely Powering Down a UPS
If you need to power down the UPS completely, follow the procedures as:
Press EPO button on the right side of operation panel
Open external battery breaker and internal battery breaker
Open mains input breaker (Q1) and output breaker (Q3)
If you need to isolate the UPS from the AC power supply, you should open the external input power supply isolation first (if the rectifier and bypass use different power supply, you need to open these two input isolation respectively).
6.5 Emergency Power Off (EPO) Procedure
The EPO button is designed to switch off the UPS in emergency conditions (e.g., fire, flood, etc.).To achieve this, just press the EPO button, and the system will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging. If the input utility is present, the UPS control circuit will remain active; however, the output will be turned off. To completely isolate the UPS, you need to open the mains input breaker and battery breaker.
6.6 Auto Start
Commonly, the UPS rack is start up on static bypass. When the mains power fails, the UPS draws power from the battery system to supply the load until the battery voltage reaches the end of discharge (EOD) voltage, and the UPS will shut down. The UPS will automatically restart and enable output power:
After the mains power is restored
If the Auto Recovery after EOD Enabling feature is enabled
6.7 UPS Reset Procedure
After using EPO to shut down the UPS, operates as following to restore UPS:
Shutdown UPS completely
Start UPS as section 6.2.1
After the UPS is shut down due to inverter over temperature, or overload, or too many switching times, UPS will reset the fault automatically when fault is cleared.
Note
The rectifier will be turned on automatically when the over temperature fault disappears after the disappearance of over temperature signals.
After pressing the EPO button, if the UPS mains input has been disconnected, the UPS is completely powered down. When the UPS mains input is restored, the EPO condition will be cleared and the UPS system will enable static bypass mode to restore the output.
Warning
If the maintenance bypass breaker is put to ON and the UPS has mains input
, then the UPS output is energiz
ed.
6.8 Operation Instruction for Power Module Maintenance
Only a trained operator can perform the following procedures
Page 40
Chapter 6 Operating Instructions
Modular UPS SM series User Manual 39
Maintenance guidance for power modules
If the system is normal mode and the bypass is normal, the redundant number of power module is at least 1:
1. Press “off” button on the front panel of power module to manually power off power module.
2. Loosen the screws of the main power module and remove the module after 2 minutes. If there are no redundant power modules:
1. Transfer to bypass mode.
2. Loosen the screws of the main power module and remove the module after 2 minutes.
Note
To ensure the safety, be sure to use a multi-meter to measure the DC bus capacitor voltage and ensure the voltage is below 60V before operation.
3. After finishing the maintenance of the power module, insert the main power module (the inserting interval for each module is longer than 10s),
the power module will automatically join the system operation, and then tighten the screws at the two sides of the power module.
Maintenance guidance for bypass power module
Note
The bypass power mo
dule cannot be maintained in battery mode.
If the system is in normal mode and the bypass is normal:
1. Manually shut down the inverter, and the UPS transfers to bypass. Close the maintenance bypass breaker and the UPS transfer to
maintenance bypass mode.
2. Press EPO button to ensure the battery current is 0. Open the battery circuit breaker or disconnect battery terminals.
3. Open mains input breaker and output breaker.
4. Remove the bypass power modules that need maintenance or repair, wait for 5 minutes and then maintain the bypass power modules. After
finishing the maintenance of the bypass power modules, insert the modules.
5. Transfer to normal mode as section 6.3.2.
Note
The terminal of bypass power module is big, and it need more power when inserting bypass
module to make sure tighten connection.
6.9 Language Selection
The LCD menus and data display are available in 4 languages: English, French, Simple Chinese, English, and Traditional Chinese. Perform the following procedure to select a language needed:
1. In main menu, press in to enter in function setting menu in the LCD screen.
2. Select “Language” setting menu.
3. Select the language and make sure. At this time, all the words in the LCD will be displayed in the selected language.
6.10 Changing the Current Date and Time
To change system date and time:
1. In main menu, press to enter in function setting menu in the LCD screen.
2. Select “Time Set“.
3. Enter new date and time, then enter to confirm it.
6.11 Control Password 1
The system is password protected to limit the operator’s operating and control authorities. You can only operate and test the UPS and battery after entering correct password 1. The default password 1 is 12345678.
Page 41
Chapter 7 Operator Control and Display Panel
Modular UPS SM series User Manual 40
Chapter 7 Operator Control and Display Panel
This chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail, and provides LCD display information, including LCD display types, detailed menu information, prompt window information and UPS alarm list.
7.1 Introduction
The operator control and display panel is located on the front panel of the UPS. Through the LCD panel, the operator can operate and control the UPS, and check all measured parameters, UPS and battery status and event and alarm logs. The operator control panel is divided into three functional areas as shown in fig.7-1: mimic current path, LCD display & Menu keys, and Control and Operation Keys. The detailed description of parts on operator control and display panel is shown in table.7-1.
Fig.7- 1: UPS operator control and display panel
Table.7- 1: Description of UPS Operator Control and Display Panel
Indicator
Function
Button
Function
REC I/P Rectifier indicator
EPO EPO (emergency power off)
BATT. Battery indicator SELECT Select
BYP IP Bypass indicator ENTER Confirm
INV Inverter indicator ESC Exit
O/P LOAD Load indicator
UPS STATUS Status indicator
Page 42
Chapter 7 Operator Control and Display Panel
Modular UPS SM series User Manual 41
7.1.1 Mimic Current Path
The LEDs shown on the mimic current path represent the various UPS power paths and show the current UPS operating status. The status description of indicators is shown in table.7-2.
Table.7- 2: Status Description of Indicator
Indicator State Purpose
Rectifier indicator
Steady green
Rectifier normal for all modules
Flashing green
Rectifier for at least on module normal, mains normal
Steady red Rectifier fault
Flashing red
Mains abnormal for at least one module
Off Rectifier not operating
Battery indicator
Steady green Battery charging
Flashing green
Battery discharging
Steady red
Battery abnormal (battery failure, no battery or battery reverse) or battery converter abnormal
(failure, over current or over temperature) , EOD
Flashing
red Battery low voltage
Off Battery and battery converter normal, battery not charging
Bypass indicator
Steady green Load power supplied by bypass
Steady red
Bypass power abnormal or out of normal range, or static bypass switch fault
Flashing red Bypass voltage abnormal
Off Bypass normal
Inverter indicator
Steady green
Load power supplied by inverter
Flashing green Inverter On, start, synchronization of standby (ECO mode) for at least one module
Steady red
System power not supplied by inverter, inverter fault for at least one module.
Flashing red
System power supplied by inverter, inverter fault for at least one module.
Off Inverter not operating for all modules
O/P Load indicator
Steady green
UPS output ON and normal
Steady red
UPS output overload and overtime, or output short, or output no power supply
Flashing red Overload output of UPS
Off No output of UPS
Status indicator
Steady green
Normal operation
Steady red Failure
7.1.2 Audible Alarm (buzzer)
There are two different types of audible alarm during UPS operation as shown in table.7-3.
Table.7- 3: Description of Audible Alarm
Alarm Purpose
Two short alarm with a long one
when system has general alarm (for example: AC fault), this audible alarm can be heard
Continuous alarm
When system has serious faults (for example: fuse or hardware fault), this audible alarm can be heard
7.1.3 Functional Keys
There are 4 functional keys on operator control and display panel, which are used together with LCD. The functions description is shown in table.7-4.
Table.7- 4: Functions of Functional Keys
Functional key Functions
EPO To cut off the load power to shut down the rectifier,
inverter, static bypass and battery
SELECT
Select
ENTER Confirm
ESC E
xit
Page 43
Chapter 7 Operator Control and Display Panel
Modular UPS SM series User Manual 42
7.2 LCD Display Type
Following the self-check of UPS LCD display, the main LCD display is shown as fig.7-2, which can be divided into three display windows: system information, data command and current record.
Fig.7- 2: Main LCD Display
The description of LCD icon is shown in table.7-5:
Table.7- 5: Description of LCD Icons
Icon Description
Bypass parameter
Main input parameter
History file, system information
Function setting (display calibration, password setting, time setting, date format, communication protocol and language setting), system setting (used by product maintainers)
Battery data, battery parameter setting (used by service staff)
Test (battery self-test, battery maintenance)
Functional keys used by service staff (fault clearing, history file clearing, noise clearing, manual switch of bypass),
user’s setting (system mode, machine number, system ID, output voltage adjustment, frequency tracing speed, frequency tracing limit)
Output parameter
Load condition
Noise clearing, noise clearing cancel
Page 44
Chapter 7 Operator Control and Display Panel
Modular UPS SM series User Manual 43
7.3 Detailed Description of Menu Items
The LCD main display shown in fig.7-3 is described in details below.
UPS information window
UPS information window: display the current time and UPS name. The information of the window is not necessary for the user to operate. The information of this window is given in table.7-6.
Table.7- 6: Description of Items in UPS System Information Window
Display contents Meaning
SM200/20
Rated information. 3 phases in 3 phases out, 200KVA cabinet and 20KVA power
module
N=03(P-1/2)
3 power modules in system, UPS works in parallel mode, 2 units in system, this is the
1# unit (S mean single unit)
12:00 Current Time (format: 24 hours, hour : minute)
(Status) Normal, alarm, fault
Normal: UPS in normal condition
Alarm: UPS has general alarm, such as AC input fault Fault: UPS fuse or hardware fault
UPS menu and data window
UPS menu window displays the menu name of data window, while the data window displays the related contents of selected menu in menu window. Select UPS menu and data window to browse related parameters of UPS and set related functions. The details are given in table.7-7.
Table.7- 7: Item Description of UPS Menu
Menu name Menu item Meaning
Main input
V phase(V) Phase voltage
I phase(A) Phase current
Freq.(Hz) Input frequency
PF Power factor
Bypass input
V phase(V) Phase voltage
Freq. (Hz) Bypass frequency
I phase(A) Phase current
PF Power factor
AC output
V phase(V) Phase voltage
I phase(A) Phase current
Freq. (Hz) Output frequency
PF Power factor
UPS system load
Sout (kVA) Sout: Apparent Power
Pout (kW) Pout: Active Power
Qout (kVAR) Qout: Reactive Power
Load ()
Load (The percentage of the UPS rating load)
Battery data
Environmental Temp Environmental Temp
Battery voltage(V) Battery bus voltage
Battery current A) Battery bus current
Battery Temp() Battery Temp
Remaining Time (Min.) Remaining battery backup time
Battery capacity ()
The percentage compared with new battery capacity
battery equalized
charging
Battery is equalized charging
battery float charging Battery is float charging
Battery disconnected Battery is not connected
Current record (current alarm) Display all current alarm. The alarm list displayed on LCD of UPS operator control and
Page 45
Chapter 7 Operator Control and Display Panel
Modular UPS SM series User Manual 44
Menu name Menu item Meaning
display panel please refer to table 4
-8
History record (history alarm)
Display all history alarm. The alarm list displayed on LCD of UPS operator control and display panel please refer to table 4-9
Menu Language (language option) 4 languages can be selected
Settings
Display calibration Adjust the accuracy of LCD display
Date format set MONTH-DATE-YEAR and YEAR-MONTH-DATE formats can be selected
Date & Time Date/Time set
Language set User can set the language (Chinese, English and a kind of optional language)
Communication mode
Set communication
mode, MODBUS, Power protocol and company custom protocol
modes can be selected. Power protocol mode can be divided into equipment address,
baud rate set; MODBUS protocol mode can be divided into communication, mode (RTU
ASC), equipment address, baud rate and check-bit set; Company custom protocol
mode is the customer protocol of the company, no option is available.
Control password set User can modify control password 1
Test Command (Battery Test Control / System Test Control / Forced equalized charging)
Battery maintenance test
This test will lead to the battery being partly discharged to activate battery, at the same
time; the approximate battery capacity will be obtained. Bypass must be in normal condition, the battery capacity should be above 25%.
Battery self-check test
UPS switches to battery discharge for discharging to test if the battery is normal. Bypass must be in normal condition, the battery capacity should be above 25%.
Stop testing Manually Stop the test including maintenance test, capacity test
UPS system
information
Monitoring software
version
Provide monitoring software version
Rectified software
version
Provide rectified software version
Inverted software version
Provide inverted software version
Serial No. The serial no set when delivery from the factory
Rated information Network setting of system operating
Module type Type of the module
7.4 UPS Event Log
The follow table.7-8 gives the complete list of all the UPS events displayed by history record window and current record window.
Table.7- 8: UPS Event List
NO. UPS events Meaning
1 Fault Clear Manually clear fault
2 Log Clear Manually clear History log
3 Load on UPS Inverter powers load
4 Load on Bypass Bypass powers load
5 No Load There is no output power for load.
6 Battery Boost Charger is working in boost charge mode
7 Battery Float Charger is working in float charge mode
8 Battery Discharge Battery is discharging
9 Battery Connected Battery is connected already
10 Battery Not Connected Battery is disconnected.
11 Maintenance CB Closed Manual maintenance breaker is closed
12 Maintenance CB Open Manual maintenance breaker is opened
Page 46
Chapter 7 Operator Control and Display Panel
Modular UPS SM series User Manual 45
13 EPO Emergency Power Off
14 Inverter on Less
Available power module
capacity is less th
a
n the load capacity
. Please reduce the load capacity or
add extra power module to make sure that the UPS capacity is big enough.
15 Generator Input Generator is connected and a signal is sent to the UPS.
16 Utility Abnormal
Utility (Grid) is abnormal. Mains voltage or frequency exceeds the upper or lower limit and results in rectifier shutdown. Check the input phase voltage of rectifier.
17 Bypass Sequence Error Bypass voltage Sequence is reverse. Check if input power cables are connected correctly.
18 Bypass Voltage Abnormal
This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass
voltage exceeds the limit. The alarm will automatically reset if the bypass voltage becomes normal. First check if relevant alarm exists, such as “bypass circuit breaker open”, “Byp Sequence Err” and “Ip Neutral Lost”. If there is any relevant alarm, first clear this alarm.
1. Then check and confirm if the bypass voltage and frequency displayed on the LCD are within the setting range. Note that the rated voltage and frequency are respectively specified by “Output Voltage” and “Output Frequency”.
2. If the displayed voltage is abnormal, measure the actual bypass voltage and frequency. If the measurement is abnormal, check the external bypass power supply. If the alarm occurs frequently, use the configuration software to increase the bypass high limit set point according to the user’s suggestions
19 Bypass Module Fail Bypass Module Fails. This fault is locked until power off. Or bypass fans fail.
20 Bypass Over Load
Bypass current is over the limitation. If bypass current is under 135% of the rated current. The UPS alarms but has no action.
21 Bypass Over Load Tout The bypass overload status continues and the overload times out.
22 Bypass Freq. Over Track
This alarm is triggered by an inverter software routine when the frequency of bypass voltage
exceeds the limit. The alarm will automatically reset if the bypass voltage becomes normal. First check if relevant alarm exists, such as “bypass circuit breaker open”, “Bypass Sequence Error” and “IP Neutral Lost”. If there is any relevant alarm, first clear this alarm.
1. Then check and confirm if the bypass frequency displayed on the LCD are within the setting range. Note that the rated frequency is respectively specified by “Output Frequency”.
2. If the displayed voltage is abnormal, measure the actual bypass frequency. If the measurement is abnormal, check the external bypass power supply. If the alarm occurs frequently, use the configuration software to increase the bypass high limit set point according to the user’s suggestions
23 Exceed Tx Times Limit
The load is on bypass because the output overload transfer and re-transfer is fixed to the set times during the current hour. The system can recover automatically and will transfer back to the inverter with 1 hour
24 Output Shorted
Output shorted Circuit. Fist check and confirm if loads have something wrong. Then check and confirm if there is something wrong with terminals, sockets or some other power distribution unit. If the fault is solved, press “Fault Clear” to restart UPS.
25 Battery EOD
Inverter turned off due to low battery voltage. C
heck the mains power failure status and recover
the mains power in time
26
Battery Test OK Battery Test OK
27
Batt
ery Maint
enance OK Battery maintenance succeed
28
N# Comm Node Join
The N# Power Module is i
nserted in system
.
29
N# Comm Node Exit
The
N# Power Module is pull
ed out from system
.
30
N# REC Fail The N# Power Module Rectifier Fail, The rectifier has faulted and results in rectifier shutdown and
battery discharging.
31
N# INV Fail
The
N# Power Module Inverter Fail
. The inverter output
voltage is abnormal and the load transfers
to bypass.
32
N# REC OV Temp.
The
N# Power Module Rectifier Over Temperature
. The temperature of the rectifier IGBTs is too
high to keep rectifier running. This alarm is triggered by the signal from the temperature monitoring device mounted in the rectifier IGBTs. The UPS recovers automatically after the over temperature
Page 47
Chapter 7 Operator Control and Display Panel
Modular UPS SM series User Manual 46
signal disappears.
If over temperature exists, check:
1. Whether the ambient temperature is too high.
2. Whether the ventilation channel is blocked.
3. Whether fan fault happens.
4. Whether the input voltage is too low.
33
N# Fan Fail
At least one fan fails in the N# power module.
34
N# Output Over Load The N# Power Module Output Over Load. This alarm appears when the load rises above 100% of
nominal rating. The alarm automatically resets once the overload condition is removed.
1. Check which phase has overload through the load (%) displayed in LCD so as to confirm if this alarm is true.
2. If this alarm is true, measure the actual output current to confirm if the displayed value is correct. Disconnect non-critical load. In parallel system, this alarm will be triggered if the load is severely imbalanced.
35
N# INV Over Load Tout N# Power Module Inverter Over Load Timeout. The UPS overload status continues and the
overload times out. Note: The highest loaded phase will indicate overload timing-out first. When the timer is active, then the alarm “unit over load” should also be active as the load is above nominal. When the time has expired, the inverter Switch is opened and the load transferred to bypass. If the load decreases to lower than 95%, after 2 minutes, the system will transfer back to inverter mode. Check the load (%) displayed in LCD so as to confirm if this alarm is true. If LCD displays that overload happens, then check the actual load and confirm if the UPS has over load before alarm happens.
36
N# INV Ov
er Temp. The
N# Power Module Inverter Over Temperature
.
The temperature of the inverter heat sink is too high to keep inverter running. This alarm is triggered by the signal from the temperature monitoring device mounted in the inverter IGBTs. The UPS recovers automatically after the over temperature signal disappears. If over temperature exists, check: Whether the ambient temperature is too high. Whether the ventilation channel is blocked. Whether fan fault happens. Whether inverter overload time is out.
37 On UPS Inhibited
Inhibit system transfer from bypass to UPS (inverter)
. Check:
Whether the power module’s capacity is big enough for load. Whether the rectifier is ready. Whether the bypass voltage is normal.
38 Manual Transfer Bypass Transfer to bypass manually
39 Esc Manual Bypass
Escape from “transfer to bypass manually” command. If UPS has been transferred to bypass manually, this command enable UPS to transfer to inverter.
40 Battery Volt Low
Battery Voltage is Low. Before the end of discharging, battery voltage is low warning should occur. After this pre-warning, battery should have the capacity for 3 minutes discharging with full load.
41 Battery Reverse Battery cables are connected not correctly.
42 N# INV Protect
The
N# Power Module Inverter Protect
. Check:
Whether inverter voltage is abnormal Whether inverter voltage is much different from other modules, if yes, please adjust inverter voltage of the power module separately.
43 IP Neutral Lost
The mains neutral wire is lost or not detected. For 3 phases UPS, it’s recommended that user use a 3-poles breaker or switch between input power and UPS.
44 Bypass Fan Fail At least one of bypass module Fans Fails
45 N# Manual Shutdown
The
N# Power Module
is manually s
hutdown
. The power module shuts down rectifier and inverter,
and there’s on inverter output.
46 ManBoost Manually force the Charger work in boost charge mode.
Page 48
Chapter 7 Operator Control and Display Panel
Modular UPS SM series User Manual 47
47 ManFloat Manually force the charger work in float charge mode.
48 Arrears Shutdown Reserved.
49 Lost N+X Redundant Lost N+X Redundant. There is no X redundant powers module in system.
50 EOD Sys Inhibited System is inhibited to supply after the battery is EOD (end of discharging)
Page 49
Chapter 8 Optional Parts
Modular UPS SM series User Manual 48
Chapter 8 Optional Parts
8.1 Replacing Dust Filters
Each filter is held in place by a bracket on either side of each filter. To replace each filter:
1. Open the UPS front door and locate the filters on the back side of the front door (see Fig. 8-1).
2. Remove one bracket and loosen the screw on the second bracket. The second bracket need not be removed
3. Remove the dust filter to be replaced.
4. Insert the clean filter.
5. Reinstall the bracket, tightening the screw securely.
6. Tighten the screw on the second bracket.
Fig.8- 1: Dust Filter
Page 50
Chapter 9 Product Specification
Modular UPS SM series User Manual 49
Chapter 9 Product Specification
This chapter provides UPS product specification.
9.1 Applicable Standards
The UPS has been designed to conform to the following European and international standards:
Table.9- 1: Compliance with European and International Standards
Item Normative reference
General safety requirements for UPS used in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic compatibility (EMC) requirements for
UPS
EN50091-2/IEC62040-2/AS 62040-2 (C3)
Method of specifying the performance and test
requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3 (VFI SS 111)
Note: The above mentioned product standards incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and
60950).
9.2 Environmental Characteristics
Table.9- 2: Environmental Properties
Items Unit Requirements
Acoustic noise level at 1 meter dB 55.0
Altitude of Operation m
≤1000m above sea level, de
-
rat
ing power by 1% per 100m between 1000m and
2000m
Relative Humidity %RH 0 to 95%, non-condensing
Operating Temperature °C 0 to 40 degree, Battery life is halved for every 10°C increase above 20°C
UPS Storage-Transport Temperature °C -20~70
Recommended
Battery Storage
Temperature
°C -20~25 (20°C for optimum battery storage)
9.3 Mechanical Characteristics
Table.9- 3: Mechanical Properties
Cabinet Specification Unit SM60/20 SM120/20 200/20
Mechanical Dimension, W×D×H mm 600×900×1100 600×900×1600 600×900×2000
Weight kg 120 151 182
Color N/A Black
Protection Level, IEC(60529) N/A IP20
Module type Unit PM20
Mechanical Dimension, W×D×H mm 440×590×134
Weight kg 22.5
Color N/A Black(front), no color (other sides)
Page 51
Chapter 9 Product Specification
Modular UPS SM series User Manual 50
9.4 Electrical Characteristics (Input Rectifier)
Table.9- 4: Rectifier AC Input (mains)
Items Unit Parameter
Rated AC Input Voltage Vac 380/400/415 (three-phase and sharing neutral with the bypass input)
Input voltage range Vac -40%~+25%
Frequency
1
Hz
50/60 (range: 40Hz70Hz)
Power factor kW/kVA, full load 0.99
THD THDI% 3
9.5 Electrical Characteristics (Intermediate DC Link)
Table.9- 5: Battery Information
Items Unit Parameters
Battery bus voltage Vdc Nominal: ±240V, one-side range: 198V~288V
Quantity of lead
-
acid
cells
Nominal 480V=40*6cell (12V)
Float charge voltage V/cell(VRLA)
2.25V/cell (selectable from 2.2V/cell~2.35V/cell) Constant current and constant voltage charge mode
Temperature
compensation
mV/°C /cl -3.0(selectable from : 0~-5.0, 25°C or 30°C, or inhibit)
Ripple voltage %V float ≤1
Ripple current %C10 ≤5
Equalized charge voltage
VRLA
2.4V/cell(selectable from : 2.30V/cell2.45V/cell)
Constant current and constant voltage charge mode
Final discharging voltage
V/cell(VRLA)
1.65V/cell (selectable from : 1.60V/cell1.750V/cell) @0.6C discharge current
1.75V/cell (selectable from : 1.65V/cell1.8V/cell) @0.15C discharge current
(EOD voltage changes linearly within the set range according to discharge current)
Battery Charge V/cell
2.4V/cell (selectable from : 2.3V/cell~2.45V/cell) Constant current and constant voltage charge mode
Battery Charging Power Max Current
kW 10%* UPS capacity (selectable from : 0~20%* UPS capacity)
9.6 Electrical Characteristics (Inverter Output)
Table.9- 6: Inverter Output (to Critical Load)
Rated capacity (kVA) Unit 20~200
Rated AC voltage
1
Vac 380/400/415 (three-phase four-wire and sharing neutral with the bypass)
Freqency
2
Hz 50/60
overload %
110% load, 1 hour 125% load, 10min 150% load, 1min >150% load, 200ms
Fault current % 340% short current limitation for 200ms
Non-linear load
Capability
3
% 100%
Neutral current capability % 170%
Page 52
Chapter 9 Product Specification
Modular UPS SM series User Manual 51
Rated capacity (kVA) Unit 20~200
Steady state voltage stability %
±1 (balanced load)
±1.5 (100% imbalance load)
Transient voltage response2 % ±5
THD %
<1.5 (linear load) , <5 (non-linear load3)
Synchronization Window - Rated frequency ±2Hz (selectable: ±1~±5Hz)
Max change rate of synch
frequency
Hz/s 1: selectable: 0.1~5
Inverter voltage range %V(ac) ±5
Note:
1. Factory setting is 380V. Commissioning engineers can set to 400V or 415V.
2. Factory setting is 50Hz. Commissioning engineers can set to 60Hz.
3. EN50091-3(1.4.58) crest ratio is 3: 1.
4. IEC62040-3/EN50091-3 including 0%~100%~0% load transient, the recovery time is half circle to within 5% of stable output voltage.
9.7 Electrical Characteristics (Bypass Input)
Table.9- 7: Bypass Input
Rated capacity(kVA) Unit
40 60 80 100 120 140 160 200
Rated AC Voltage Vac
380/400/415
three-phase four-wire, sharing neutral with the rectifier input and providing neutral reference for the output
Rated current A
60
@380V
91
@380V
121
@380V
152
@380V
182
@380V
212
@380V
242
@380V
303
@380V
58
@400V
87
@400V
116
@400V
145
@400V
174
@400V
203
@400V
232
@400V
290
@400V
56
@415V
83
@415V
111
@415V
139
@415V
167
@415V
194
@415V
222
@415V
278
@415V
Overload %
125% load, long term
130% load, 1 hour
150% load, 6min
1000% load, 100ms
Superior protection bypass line N/A Thermal-magnetic breaker, the capacity is 125% of rated current output. IEC60947-2 curve C
Current rating of
neutral cable A 1.7×In
Frequency Hz 50/60
Switch time
(between bypass and inverter) ms Synchronized switch: ≤1ms
Bypass voltage tolerance
% Vac
Upper limit: +10,+15 or +20, default: +20
Lower limit: -10, -20, -30 or -40, default:-20
(acceptable stable bypass voltage delay: 10s)
Bypass frequency
tolerance % ±2.5, ±5, ±10 or ±20, default: ±10
Synchronization
-
Wi
ndow Hz
Rated frequency±2Hz (selectable from ±0.5Hz±5Hz)
Page 53
Chapter 9 Product Specification
Modular UPS SM series User Manual 52
Note:
1. Factory setting is 400V. Commissioning engineers can set to 380V or 415V.
2. Commissioning engineers can set to 50Hz or 60Hz. For example, UPS is set to frequency inverter mode, and then bypass status will
be neglected.
9.8 Efficiency
Table.9- 8: Efficiency, Air Exchange
Rated Efficiency (kVA) Unit
20200kVA
Efficiency
Normal mode(dual conversion) % 95
ECO mode
% 98
Battery discharging efficiency (DC/AC) (battery at nominal voltage 480Vdc and full
-
rated linear
load)
Battery mode % 95
Maximum air exchange
m3 /min 6.04/power module, 4.53/bypass module
Loading...