CyberPower PP1500, PP2200 User Manual

Professional Tower UPS
PP1500/PP2200
User Manual
SAFETY WARNINGS
K01-P1K50H0-01
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS. This equipment can be operated by any individuals with no previous training. The socket-outlet shall be installed near the equipment and easily accessible. During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3.5mA. Attention, hazardous through electric shock. Also with disconnection of this unit from the mains, hazardous voltage still may be accessible through suppl y from battery. The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the battery when maintenance or service work inside the UPS is necessary. Do not dispose of batteries in a fire, the battery may explode. Do not open or mutilate the battery or batteries, released electrolyte is harmful to the skin and eyes.
UNPACKING
Inspect the UPS upon receipt. The box should contain the following:
UPS Unit x1; PowerPanel Business Edition Software Disk x1; Serial Interface Cable (DB-9) x1; USB Device Cable x1;Telephone Cable x1;
User Manual x1
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Insure that the equipment plugged into the battery power-supplied outlets does not exceed the UPS unit’s rated capacity (1500VA/1000W for PP1500, 2200VA/1500W for PP2200). If rated unit capacities are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip.
2. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert Watts (W) or Amps (A) into VA by doing the calculations below. Note: The below equation only calculates the maximum amount of VA that the equipment can use, not what is typically used by the equipment at any one time. Users should expect usage requirements to be approximately 60% of below value.
TO ESTIMATE POWER REQUIREMENTS
1. W atts (W) x 2.0 = VA or Amps (A) x 120 = VA
2. Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual requirements. There are many factors that can affect the amount of power that your computer system will require. The total load that you will be placing on the battery-powered outlets should not exceed 80% of the unit’s capacity.
HARDWARE INSTALLATION GUIDE
1. Connect the equipment to your UPS outlets. Items such as copiers, laser printers, vacuums, space heaters, paper shredders, or other large electrical devices should not be connected to the UPS. Please assure that the total loads of your equipments must be less than the maximum total power load of your UPS.
2. Connect your UPS power cord into a two-pole, three-wire grounding receptacle only. Please avoid using extension cords and adapter plugs. (To maintain optimal battery charge, leave the UPS plugged in at all times.)
3. Press the UPS power button to turn it on. The “Power On” indicator will be illuminated in “Green”.
4. Install your optional software and accessories. To use the software, simply connect the enclosed serial interface cable to the serial port on the UPS and an open serial port on the computer.
FRONT PANEL DESCRIPTION
◆◆◆◆ Battery Indicators
BATTERY CAPACITY
◆◆◆◆ Load Level Indicators
LOAD CAPACITY
◆◆◆◆ Wiring Fault Indicator
◆◆◆◆ Using Battery Indicator
AVR Indicator
◆◆◆◆ Power On Indicator
These indicators show a visual i ndication of the illuminate and the UPS starts beeping.
These LED indicators show a visual depiction of the UPS load. The load indicator LED will turn orange if the load is between 80 and 100%. If the load is under 20%, no indicator LED will illuminate.
This LED indicator will ill ground or reversed wiring. If this is illuminated, the user is advised to disconnect all electrical equipment from the outlet and have an electrician check the outlet to insure proper wiring.
This illuminates during utility failure, indicating that the battery is supplying power to the battery-power supplied outlets.
This LED indicates that the UPS is operating in automatic voltage regulation mode. When the LED is ill uminated continuously, it indicates input over-voltage and the UPS unit bucks the voltage. When the LED is flashed in rotation, it indicates that the UPS unit is boosting input voltage.
This LED is illuminated when the utility condition is normal and the UPS outlets are providing “clean spikes.
INSTALLING YOUR UPS SYSTEM
BASIC OPERATION
◆◆◆◆ Power Switch
◆◆◆◆ Test Switch
Press the ON/OFF button to turn the UPS on or off.
This UPS performs a self-test automatically when power is on. If the UPS passes the test, it returns to on-line operation. If the UPS fails the self-test, please recharge the battery for 4 hours and perform another self-test. If it fails after recharging the battery, please replace the battery.
battery charge. If battery capacity is under 20%, no indicator LED will
uminate to warn the user that a wiring problem exits with the AC outlet, such as bad ground, miss
power”, free of surges and
REAR PANEL DESCRIPTION
◆◆◆◆ Circuit Breaker Reset for Overload Protection
◆◆◆◆ Communication Protection Ports
◆◆◆◆ Serial/ USB Ports
When power failure occurs, one of the following shutdown sequences will be executed:
1. If the Primary and Secondary serial ports are both in use: the Primary computer will start to count down (user controlled delay) for shutdown
2. If only the Secondary serial port is in use: the Secondary computer will shutdown following the user settings in PowerPanel Software.
Re-settable circuit breakers provide optimal overload protection.
Ethernet RJ-45 Network Protection Ports protect
The PP1500/PP2200 provides two serial and one USB ports to allow connection and communi cation between the UPS and two computers. This allows the simultaneous shutdown of two computer systems. These interfaces are also compatible with the UPS service provided by Windows 2000, Windows NT, Windows XP, Windows Server 2003.
(User Control delay can be set in the PowerPanel Business Edition Recommended time is 5 minutes). Once the Primary computer is shutdown,
UPS will signal the Secondary computer and initiate the Secondary to shutdown. The UPS default shutdown time is 2 minutes. Therefore,
the it is recommended that Secondary computer is set to shutdown within 1 minute in PowerPanel Software.
However, the Secondary computer will not able to signal the UPS to shutdown. Therefore, the UPS will only power off when it is in low battery.
◆◆◆◆ Backup Power for Critical Loads
The UPS provides 2 battery powered, surge protected outlets for the most critical connected equipments
and insures temporary uninterrupted operation of connected equipments during a power failure.
NOTE: When the UPS is overloaded, the UPS will interrupt power supply to the other 6 battery
outlets and leave these 2 outlets for critical loads uninterrupted.
◆◆◆◆ Battery Backup and Surge Protection Outlets
unit provides 6 battery-powered, surge-protected and AVR outlets for connected equipments and
This insures uninterrupted operation of connected equipment during a power failure.
your Phone, Fax and Modem from surges over the Ethernet/Phone line.
1. The Primary PC
ntrol the UPS and make any change to the operation of the UPS,
To co please install the PowerPanel Business Editon in your primary compu then connect it to the Serial Port I or USB port of the UPS.
2. The Secondary PC
The secondary computer with PowerPanel installed should be connected to the serial port II. This PC will shutdown following the user settings in PowerPanel Software when a power failure occurs but it is unable to exhibit any co
ntrol over the UPS.
Please go to www.cyberpowersystems.com for free download PowerPanel Software.
ter and
BATTERY REPLACEMENT AND STORAGE
Contact your dealer or call the number in this manual for information on battery replacement.
Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of personnel knowledgeable of batteries and their precautions. Keep
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries. CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as it may explode. Follow all local
ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to t CAUTION! A battery can present a high risk of short circuit current and electric shock. Take the following precautions before replacing the
battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit).
is inadvertently grounded. If inadvertently grounded, remove source of ground. CONTACT WITH A GROUNDED
BATTERY REPLACEMENT PROCEDURE:
1. Turn off and unplug all connected equipments.
2. Turn the UPS off and unplug it from the AC power source.
3. Carefully turn the UPS upside down. Remove the 6 retaining screws and the cover.
4. Disconnect the black and red wires from the battery set.
5. Remove the battery protection cover and take out the battery set from the compartment.
6. Slide a new battery pack into the unit. Assemble the battery protection cover, ca
ble, screws in the reverse sequence of above steps.
REMINDER: Recharge the unit for 4 – 8 hours to ensure the UPS performs expected runtime
STORAGE:
First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables connected to the UPS to avoid battery drain. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to insure battery life. If the battery remains uncharged for an extended period of time, it may suffer permanent loss of capacity.
unauthorized personnel away from batteries.
he skin and eyes and may be toxic.
(1)
(3)
(2)
(4)
TROUBLE SHOOTING
Problem Possible Cause Solution
The UPS does not perform expected runtime.
The UPS will not turn on. The on/off switch is designed to
Outlets do not provide power to equipment
PowerPanel Business Edition is inactive (all icons are gray).
Batteries are not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is slightly worn out. Contact CyberPower Systems at tech@cyberpowersystems.com.
prevent damage by rapidly turning it off and on.
The unit is not connected to an AC outlet.
The battery is worn out. Contact CyberPower Systems at tech@cyberpowersystems.com.
Mechanical problem. Contact CyberPower Systems at tech@cyberpowersystems.com.
Circuit breaker is tripped due to overload
Batteries are discharged Allow the unit to recharge for at least 4 hours.
Unit has been damaged by a surge or spike.
The serial cable is not connected.
The serial cable is connected to the wrong port.
The unit is not providing battery power.
The serial cable is not the cable that was provided with the unit.
Turn the UPS off. Wait 10 seconds and then turn the UPS on.
The unit must be connected to a 110/120v 60Hz outlet.
Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit breaker and then turn the UPS on.
Contact CyberPower Systems at tech@cyberpowersystems.com.
Connect the serial cable to the UPS unit and an open serial port on the back of the computer. You must use the cable that came with the unit.
Check the back of the computer for an additional serial port. Move the cable to this port.
Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the UPS back on. This should reset the unit.
You must use the cable that was included with the unit for the software and the unit to be able to communicate.
Limited Warranty and Connected Equipment Guarantee
TECHNICAL SPECIFICATIONS
Model PP1500 PP2200
Capacity (VA) AV0022 AV0051
Capacity (Watts) W0051 W0001
Input
Input Voltage Range 85Vac – 150Vac
Frequency Range 50/60 Hz +/- 3Hz
Output
On Battery Output Voltage Pure Sine Wave at 120Vac +/- 7%
On Battery Output Frequency 47-53Hz for 50Hz nominal, 57-63Hz for 60Hz nominal
Transfer Time (Typical) 4ms
Overload Protection
Lightning / Surge Protection Yes
Internet Ready
(DSL / Phone / FAX / Modem Protection)
Physical
Total # of UPS Receptacles
Dimensions (cm) 42.0*18.0*23.5
Weight (kg) 25.4 31.1
Battery
Sealed Maintenance Free Lead Acid Battery
Hot Swappable Battery Yes
Typical Recharge Time 8 Hours
Warning Diagnostics
Indicators
Audible Alarms On Battery, Low Battery, Overload
Environmental
Operating Temperature +32°F to 95°F ( 0°C to 35°C )
Operating Relative Humidity 0% to 95% Non Condensing
Communication
PowerPanel Business Edition Software
Management
Self-Test Manual Self-Test
Auto-Charger/ Auto-Restart/USB Yes
SNMP/ HTTP Network Card Optional
On Utility: Circuit Breaker, On Battery: Internal Current Limiting
RJ11/RJ45 (One In/One Out)
(8) NEMA 5-15R
Power On, Using Battery, AVR, Wiring Fault, Load Level, Battery Level
gniretliF dna noitcetorP egruS
(2) NEMA 5-20R
(6) NEMA 5-15R
aM ,3002 revreS ,PX/0002/TN/EM/89/59 swodniW c OSX, Linux
DEFINITIONS FOR ILLUMINATED LED INDICATORS
Power On
On Slow flash Off Set Off
On Rapid flash Off Set Off
AVR
Using
Battery
Circuit
Breaker
Alarm
Condition
lamroN ffO teS ffO ffO nO
AVR- Max. boost 13% of input voltage for output regulation while input voltage is from 5% to 14% under nominal.
AVR- Max. boost 26% of input voltage for output regulation while input voltage is from 15% to 29% under nominal.
Who Pays For Shipping? We pay when we send items to you; you pay when you send items to us.
What Are Some Things This Warranty Does Not Cover?
1. This Warranty is lost as a result of the failure or the restoration of data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums, medical or life support devices, etc.
What are the Limitations?
1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded outlets (including other connectors.
2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected to the Product and not “daisy-chained” together in serial fashion with any extension cords, another Product or device similar to the Produc
t, surge suppressor, or power tap. Any such installation voids the Limited Warranty.
3. The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any license, instruction manual, or warnings provided with the Product and the equipment connected to it.
4. The Product must have been used at all times within the limitations on the Product’s VA capacity.
Where Can I Get More Information?
For further information please feel free to contact CyberPower at Cyber Power Systems (USA), Inc. 4241 12th Ave E., STE 400, Shakopee, MN 55379; call us at (877) 297-6937; or send us an e-mail message at claims@cpsww.com.
4xHA0.9 / V21 4xHA0.7 / V21
WARNING!! This equipment has been tested and found to comply with the limits for a Class B Digital Device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful i nterference in residential installation. This equipment generates
, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the foll owing measures: (1) Reorient or relocate the receiving antenna. (2) Increase the separation between the equipment and receiver. (3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. (4) Consult the dealer or an experienced radio/TV technician for help. Any special accessories needed for compliance must be specified in the instruction.
The Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulation. Cet appareil numerique de la class B respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada
does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any data that
compliance with electrical and safety codes of the most current electrical code), without the use of any adapters or
FCC Notice
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)This device may not cause harmful interferenc that may cause undesired operation.
e, and (2) this device must accept any interference received, including interference
ON On Off Set Off
Off Off On Set Two Beeps
Off Off On Set Rapid Beeps
On/Off
Off Off On Up Long Beep
Off Off Off Set Off
On/ Off
/Flash
On/Off Set Long Beep
AVR- Max. buck 11% of input voltage for output regulation while input voltage is from 8% to 25% over nominal.
Utility Failure- The UPS is providing battery power to the Battery-Power Supplied outlets.
Utility Failure- The UPS is providing battery power. Rapid beeps indicate the battery will run out of charge within a few minutes.
Overload- Turn the UPS off and unplug at least one piece of equipment from the UPS. Wait 5 seconds, reset the circuit breaker and restart the UPS.
Overload- Turn the UPS off and unplug at least one piece of equipment from the UPS. Wait 5 seconds, reset the circuit breaker and restart the UPS.
Surge Protection Malfunction- Power surge has damaged the unit. Please contact CyberPower Systems.
Read the following terms and conditions carefully before using the CyberPower UPS (the “Product”). By using the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and Connected Equipment Guarantee (together referred to as this “Warranty”). If you do not agree to the terms and conditions of this Warranty, you should return the Product for a full refund prior to using it.
Who Is Providing This Warranty? CyberPower Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
What Does This Warranty Cover? This warranty covers defects in materials and workmanship in the Product under normal use and conditions. It also covers equipment that was connected to the Product and damaged because of the failure of the Product.
What Is The Period of Coverage? This warranty covers the Product for three y
Who Is Covered? This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.
How Do You Get Service?
1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379 or send us an e-mail message at claims@cpsww.com for instructions.
2. W hen you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on all applicable insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number.
3. You must provide a purchase receipt (or other proof of the original purchase) and provide a description of the defect.
4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and shipment, and you must pay the cost of the repair estimate.
How Long Do I Have To Make A Claim? All c
laims must be made within ten days of the occurrence.
What Will We Do To Correct Problems? CyberPower will inspect and examine the Product.
If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full pu you paid for the Product (purchase receipt showing price paid is required).
If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the connected equipment. We will repair or replace the equipment that was damaged because of the failure of our Product or pay you the fair market value (NOT REPLACEMENT COST) of the equipment at of the guide, or eBay, craigslist, or other source to establish that amount. Our liability is limited to the Connected Equipment Guarantee amount as stated in the Technical Specifications section.
ears and connected equipment for as long as you own the Product.
rchase price
time of the damage. W e will use Orion Blue Book, or another a third-party valuation