Table of Contents
Model List 1
PDU Naming Convention: 1
Package Contents 1
Safety Precautions 2
Installation 2
Horizontal Installation (1U models only) 2
Vertical Installation with Brackets 3
Vertical Installation with Brackets (0U models only) 3
Vertical Installation with Keyhole Mounts (0U Models) 4
Cord Retention Tray installation 4
Meter Configuration 4
Electrical Installation 5
Troubleshooting 5
Product Features 6
Basic Series ( 1U 20A ) 6
Basic Series ( 0U 10A ) 7
Basic Series ( 0U 20A ) 8
Meter Series ( 0U 20A ) 9

For more information on CyberPower products, visit www.CPSww.com
PDU Naming Convention:
1. Amperage: Amperage – 15A, 20A, 30A
2. Series: B: =Basic M: =Metered
SW: = Switched
3. Rack Space: NULL: =Horizontal V:= Vertical
4. Input Voltage: HV:= High Voltage – 200V to 240V
5. Plug Type: IEC:= (IEC 320 C14/C20)
6. Outlet Number Front: Number of Outlets followed by
F – Example 8F
7. Outlet Number Rear: Number of Outlets followed by
R – Example 8R
Basic Series:
PDU20BHVIEC8R
PDU20BHVIEC10R
PDU20BHVIEC12R
PDU20BHVIEC12Ra
Basic Series:(0U)
PDU10BVHVIEC16F
PDU10BVHVIEC20F
PDU20BVHVIEC16F
PDU20BVHVIEC20F
PDU20BVHVIEC24F
PDU20BVHVIEC32F
PDU20BVHVIEC38F
Metered Series:(0U)
PDU20MVHVIEC24F
PDU20MVHVIEC30F
PDU20MVHVIEC38F
Package Contents
Model List
PDU (1)
Ground Screw M5 X 6 (1 pcs)
Horizontal Installation
Used (1 set)
Bracket Mounting
Screws M4 X 8 (4pcs)
Cord Retention Tray
Mounting Screws
M3 X 6 (4/8/12/16 pcs varies by models)
Keyhole Mounting Pegs (2pcs)
with Screws M4 X 8 (2pcs)
(for 0U models only)
Cord Retainer Clips
(8/10/12/14/16/20/24/30/
32/38 pcs - varies by models)
for Cord Retention Tray
Vertical Installation
Used (1 set)
Vertical Mounting Brackets
(1 set)(for 0U models only)
Mounting Brackets
Cord Retention Tray
(1/2/3/4 pcs - varies by models)

For more information on CyberPower products, visit www.CPSww.com
Safety Precautions
Read the following before installing or operating the
Power Distribution Unit (PDU):
1. Use only the supplied hardware to attach the mounting brackets.
2. The PDU must only be plugged into a three-wire, grounded outlet
on a circuit protected by a fuse or circuit breaker. Connection to
any other type of power outlet may result in a shock hazard.
3. Do not use extension cords or adapters with this PDU.
4. Never install a PDU or associated wiring or equipment during a
lightning storm.
5. Check that the power cord, plug, and socket are in good condition.
6. The socket-outlet shall be installed near the equipment and shall
be easily accessible.
7. CAUTION! To prevent the risk of fire or electric shock, this PDU
should be installed in a temperature and humidity controlled
indoor area free of conductive contaminants. Do not install this
PDU where excessive moisture or heat is present.
User Manual
Documentation:
Before using, please check to ensure the package contains all
the items shown above. If there are any missing parts, please
contact CyberPower technical support at www.CPSww.com
Pow
er
D
istri
bution
Unit
User M
a
n
ual
Check
Installation
Horizontal Installation (1U models only)
Step 1 – Mounting bracket installation
Install the screws (M4 X 8) in holes diagonally from each other.
Step 2 – PDU Mounting
Install the PDU using fasteners compatible with the rack.

For more information on CyberPower products, visit www.CPSww.com
Vertical Installation with Brackets
Step 1 – Mounting bracket installation
Vertical Installation with Brackets (0U models only)
Step 1 – Mounting bracket installation
Install the screws (M4 X 8) in holes diagonally from each other.
Step 2 – PDU Mounting
Step 2 – PDU Mounting
Install the PDU using fasteners compatible with the rack.
Install the PDU using fasteners compatible with the rack.
Attach the Vertical Mounting Brackets to the PDU with the 4
supplied Bracket Mounting Screws (M4 X 8).

For more information on CyberPower products, visit www.CPSww.com
Vertical Installation with Keyhole Mounts (0U Models)
Step 1 – Keyhole Mount installation
Meter Configuration
Cord Retention Tray installation
(Optional for both horizontal and vertical installations)
Attach the Keyhole Mounting Pegs to the PDU with the 2
supplied Bracket Mounting Screws (M4 X 8).
Align the the Keyhole Mounts to the Keyhole Slots on the rack.
Insert and slide down to lock firmly into place.
Step 2 – PDU Mounting
Depending on installation method (vertical or horizontal), the
LED Meter may need to be rotated, before installation, for
proper orientation.
Attach the Cord Retention Tray to the PDU with the 4 supplied
Cord Retention Tray Mounting Screws (M3 X 6).
Use a screw driver to gently remove the LED Meter. Rotate
the LED Meter 90 degrees, and insert back into the PDU.
!
Note

For more information on CyberPower products, visit www.CPSww.com
Electrical Installation
Step 1 – Receptacle evaluation
Ensure that the plug type of your PDU unit (e.g. NEMA 5-15P,
NEMA 5-20P, NEMA L5-30P) matches the wall receptacle type
that you are using.
Troubleshooting
PDU must be plugged into a three-wire, grounded
wall receptacle only. The wall receptacle must also be
connected to an appropriate branch circuit/main with fuse
or circuit breaker protection. Connection to any other type
of wall receptacle may result in a shock hazard.
Step 2 – Plug the PDU into the wall receptacle
Step 3 – Attach equipment
Before attaching equipment, it is important to calculate the total
load that will be placing on the PDU. It is extremely important
not to exceed the PDU's maximum current load (as outlined in
the Specifications section). In order to determine the total load,
simply add up the amperage of your devices and ensure that it
does not exceed the unit’s capacity.
Problem Possible Cause Solution
PDU outlets do
not provide power
to connected
equipment
1. Open breaker
2. Loose power cord
Reset breaker, check if plug
is completely connected.
If the problem remains,
contact tech support.
Amperage displayed
on Amperage Meter
exceeds the unit’s
capability
(Metered type only)
1. Overload
2. Amperage meter is
damaged
The meter will flash when
overloaded. Reduce the
load on the PDU until the
overload is gone.
If the problem remains,
contact tech support.
Circuit breaker
has tripped
1. Sustained overload
2. Excessive ambient
or internal
temperatures.
3. Faulty breaker
Reset breaker.
If the problem remains,
contact tech support.

For more information on CyberPower products, visit www.CPSww.com
A
R
A B C D E FF
Product Features
Front View
Technical Specifications
Model Name
PDU20BHVIEC8R
PDU20BHVIEC10R
PDU20BHVIEC12R
PDU20BHVIEC12Ra
Input
Voltage 200~240V
Max Current 20 A
Regulatory Derated
Input Current
16 A
Circuit Breaker 16 A
Plug Type IEC 320 C20
Power Cord Length 10 ft /3.05m
Output
Voltage 200~240V
Max Current 20 A
Outlet Type(Quantity)
IEC 320 C13(8)
IEC 320 C13(10)
IEC 320 C13(12)
IEC 320 C19(2)/C13(10)
Indicators
LED Indicators N/A
Meter Readout N/A
Physical
Dimension (WxDxH) 17.5" x 1.5" x 1.75" / 44.45 x 3.81 x 4.45 cm
Environmental
Humidity
Operating 0 to 95% Non-condensing
Non-Operating 0 to 95% Non-condensing
Altitude
Operating 0ft to 10,000ft/3048m
Non-Operating 0ft to 50,000ft/15240m
Temperature
Operating 32F/0
o
C to 95F/35oC
Non-Operating 5F/-15oC to 113F/45oC
Safety Approvals
Certifications UL60950_1 , CSA C22.2, CE, RoHS Compliant
A. Mounting Bracket
B. Rear Outlets (IEC 320 C13)
C. Circuit Breaker
D. External Site Ground
E. AC Inlet (IEC 320 C20)
F. Cord Retention Tray Screw Holes
Back View
Basic Series ( 1U 20A )

For more information on CyberPower products, visit www.CPSww.com
A. AC Inlet (IEC 320 C14)
B. Circuit Breaker
C. External Site Ground
D. Front Outlets
E. Cord Retention Tray
Screw Holes
A. Bracket Screw Hole
B. Keyhole Mount Peg
Screw Holes
Product Features
Front View
Technical Specifications
Model Name
PDU10BVHVIEC16F
PDU10BVHVIEC20F
Input
Voltage 200~240V
Max Current 10 A
Regulatory Derated
Input Current
10 A
Circuit Breaker 10A
Plug Type IEC 320 C14
Power Cord Length 10 ft /3.05m
Output
Voltage 200~240V
Max Current 10 A
Outlet Type(Quantity)
IEC 320 C13(16)
IEC 320 C19(4)/C13(16)
Indicators
LED Indicators N/A
Meter Readout N/A
Physical
Dimension (WxDxH)
1.75"x1.5"x24" / 4.45x3.81x60.96 cm
1.75"x1.5"x36" / 4.45x3.81x91.44 cm
Environmental
Humidity
Operating 0 to 95% Non-condensing
Non-Operating 0 to 95% Non-condensing
Altitude
Operating 0ft to 10,000ft/3048m
Non-Operating 0ft to 50,000ft/15240m
Temperature
Operating 32F/0
o
C to 95F/35oC
Non-Operating 5F/-15oC to 113F/45oC
Safety Approvals
Certifications UL60950_1 , CSA C22.2, CE, RoHS Compliant
Back View
A
B
C
E
E
D
B
A
B
A
Basic Series ( 0U 10A )

For more information on CyberPower products, visit www.CPSww.com
Product Features
Front View
Technical Specifications
Model Name
PDU20BVHVIEC16F
PDU20BVHVIEC20F
PDU20BVHVIEC24F
PDU20BVHVIEC32F
PDU20BVHVIEC38F
Input
Voltage 200~240V
Max Current 20 A
Regulatory Derated
Input Current
16 A
Circuit Breaker 16 A
Plug Type IEC 320 C20
Power Cord Length 10 ft /3.05m
Output
Voltage 200~240V
Max Current 20 A
Outlet Type(Quantity)
IEC 320 C13(16)
IEC 320 C19(4)/C13(16)
IEC 320 C19(4)/C13(20)
IEC 320 C19(4)/C13(24)
IEC 320 C19(4)/C13(30)
Indicators
LED Indicators N/A
Meter Readout N/A
Physical
Dimension (WxDxH)
1.75" x 1.5" x 24" / 4.45 x 3.81 x 60.96 cm
1.75" x 1.5" x 36" / 4.45 x 3.81 x 91.44 cm
1.75" x 1.5" x 48" / 4.45 x 3.81 x 121.92cm
1.75" x 1.5" x 60" / 4.45 x 3.81 x 152.40 cm
1.75" x 1.5" x 70" / 4.45 x 3.81 x 177.80 cm
Environmental
Humidity
Operating 0 to 95% Non-condensing
Non-Operating 0 to 95% Non-condensing
Altitude
Operating 0ft to 10,000ft/3048m
Non-Operating 0ft to 50,000ft/15240m
Temperature
Operating 32F/0
o
C to 95F/35oC
Non-Operating 5F/-15oC to 113F/45oC
Safety Approvals
Certifications UL60950_1 , CSA C22.2, CE, RoHS Compliant
B
A
A
B
Back View
High Voltage Type:
A. AC Inlet (IEC 320 C20)
B. Circuit Breaker
C. External Site Ground
D. Front Outlets
E. Front Outlets
F. Cord Retention Tray
Screw Holes
A. Bracket Screw Hole
B. Keyhole Mount Peg
Screw Holes
A
B
C
D
E
F
F
F
F
Basic Series ( 0U 20A )

For more information on CyberPower products, visit www.CPSww.com
Product Features
Front View
Technical Specifications
Model Name
PDU20MVHVIEC24F
PDU20MVHVIEC30F
PDU20MVHVIEC38F
Input
Voltage 200~240V
Max Current 20 A
Regulatory Derated
Input Current
16 A
Circuit Breaker 16 A
Plug Type IEC 320 C20
Power Cord Length 10 ft /3.05m
Output
Voltage 200~240V
Max Current 20 A
Outlet Type(Quantity)
IEC 320 C19(4)/C13(20)
IEC 320 C19(6)/C13(24)
IEC 320 C19(8)/C13(30)
Indicators
LED Indicators N/A
Meter Readout Amperage
Physical
Dimension (WxDxH)
1.75" x 1.5" x 48" / 4.45 x 3.81 x 121.92 cm
1.75" x 1.5" x 60" / 4.45 x 3.81 x 152.40 cm
1.75" x 1.5" x 70" / 4.45 x 3.81 x 177.80 cm
Environmental
Humidity
Operating 0 to 95% Non-condensing
Non-Operating 0 to 95% Non-condensing
Altitude
Operating 0ft to 10,000ft/3048m
Non-Operating 0ft to 50,000ft/15240m
Temperature
Operating 32F/0
o
C to 95F/35oC
Non-Operating 5F/-15oC to 113F/45oC
Safety Approvals
Certifications UL60950_1 , CSA C22.2, CE, RoHS Compliant
Back View
High Voltage Type:
A. AC Inlet (IEC 320 C20)
B. Circuit Breaker
C. External Site Ground
D. Front Outlets
E. Meter Readout
F. Front Outlets
G. Cord Retention Tray
Screw Holes
A. Bracket Screw Hole
B. Keyhole Mount Peg
Screw Holes
A
B
C
D
F
E
G
G
G
G
B
A
A
B
Meter Series ( 0U 20A )