CyberPower OLS6000E, OLS6000EXL, OLS10000EXL, OLS10000E User Manual

Userˊs Manual
CyberPower Systems Inc.
www.cyberpower.com
OLS6000E(XL)
OLS10000E(XL)
CONTENT
1. Safety .................................................................................................................1
1.1. Installation ..................................................................................................1
1.2. Operation ....................................................................................................1
1.3. Maintenance, Servicing and Faults .............................................................2
1.4. Transport ....................................................................................................3
1.5. Storage .......................................................................................................3
1.6. Standards ...................................................................................................3
2. Description of Commonly Used Symbols .......................................................4
3. Introduction .......................................................................................................4
3.1. Feature .......................................................................................................5
3.2. Electrical Specifications ..............................................................................6
3.3. Operating Environment ...............................................................................7
3.4. Dimensions and Weights ............................................................................7
4. Installation .........................................................................................................8
4.1. Unpacking ...................................................................................................8
4.2. Power Wires Installation .............................................................................8
4.3. External Battery Pack Connecting Procedure ......................................... 11
4.4. EPO Connection ....................................................................................... 12
5. Operation ......................................................................................................... 13
5.1. Display Panel ............................................................................................ 13
5.2. Turning On and Turning Off UPS .............................................................. 15
5.3. LCD Operation .......................................................................................... 16
6. Special Function ............................................................................................. 21
6.1. ECO Function ........................................................................................... 21
6.2. Converter Function ................................................................................... 21
6.3. Parallel Function ....................................................................................... 22
7. Trouble Shooting ............................................................................................ 26
7.1. Trouble Shooting According to Warning Indication ................................... 26
7.2. Trouble Shooting According to Fault Indication ........................................ 28
7.3. Trouble Shooting in Else Cases................................................................ 29
8. Battery Maintenance ....................................................................................... 30
9. Communication Port ....................................................................................... 31
9.1. USB Interface ........................................................................................... 31
9.2. Dry contact Interface(optional) ................................................................. 31
9.3. RS232 Interface ........................................................................................ 31
9.4. Intelligent slot ............................................................................................ 31
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1. Safety
1.1. Installation
This is permanently connected equipment, and it must be installed by qualified
maintenance personnel.
Condensation may occur if the UPS is moved directly from a cold to a warm
environment. The UPS must be absolutely dry before being installed. Please
allow an acclimatization time of at least two hours.
Do not install the UPS near water or in damp environment.
Do not install the UPS where it would be exposed to direct sunlight or near heat.
Do not connect appliances or items of equipment which would overload the UPS
(e.g. laser printers, etc.) to the UPS output.
Do not block ventilation openings in the UPS’s housing. Ensure allow at least
0.5m of space on front and rear of the UPS.
Place cables in such a way that no one can step on or trip over them.
Connect UPS with the earth reliably before connecting to the building wiring
terminal, and external battery source must also be earthed.
An integral single emergency switching device which prevents further supply to
the load by the UPS in any mode of operation should be provided in the building
wiring installation.
An appropriate disconnect device as short-circuit backup protection should be
provided in the building wiring installation.
The equipment is powered by two sources: the mains source, the internal
battery or the external battery source.
With the installation of the equipment, the sum of the leakage current of the UPS
and the connected load does not exceed 5% of rated value of input current.
1.2. Operation
Do not disconnect the main cable on the UPS or the building wiring terminals
during operation since this would remove the protective earth from the UPS and
all connected loads.
The UPS output terminal block may still be electrically lived even if the UPS is
1
not connected to the building wiring terminal, for there is internal current source
(batteries).
In order to fully disconnect the UPS, first turn the input breaker in the "OFF"
position, then disconnect the mains lead.
Indiscriminate operation of switches may cause output loss or damage to
equipment. Refer to instruction before conducting any control.
While the UPS work as a parallel system, the external parallel cable should be
reinforced insulation.
Ensure that no liquid or other foreign objects can enter the UPS.
1.3. Maintenance, Servicing and Faults
Do not remove the enclosure since the UPS operates with hazardous voltages.
It is to be serviced only by qualified maintenance personnel.
Caution! Risk of electric shock. Even after the unit is disconnected from the
mains power supply (building wiring terminal) components inside the UPS are
still connected to the battery which are potentially dangerous.
Before carrying out any kind of service or maintenance, isolate UPS and
disconnect the batteries. Verify that no current is present and no hazardous
voltage exists in the capacitor or BUS capacitor.
Batteries must be replaced only by qualified personnel.
Batteries have a high short-circuit current and pose a risk of shock. Take all
precautionary measures specified below and any other necessary measures
when working with batteries:
─ remove all jewellery, wristwatches, rings and other metal objects
─ use only tools with insulated grips and handles.
When changing batteries, replace with the same quantity and the same type of
batteries.
Do not attempt to dispose of batteries by burning them. It could cause explosion.
The UPS may be connected to external battery package. Proper disposal of
batteries is required. Refer to your local codes for disposal requirements.
Do not open or destroy batteries. Effluent electrolyte can cause injury to the skin
and eyes. It may be toxic.
Replace the fuse only by a fuse of the same type and of the same spec in order
to avoid fire hazards.
2
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission................................:IEC/EN 62040-2
Category C3
Radiated Emission...................................:IEC/EN 62040-2
Category C3
*EMS
ESD....................................................... ..:IEC/EN 61000-4-2
Level 3
RS............................................................:IEC/EN 61000-4-3
Level 3
EFT..........................................................:IEC/EN 61000-4-4
Level 4
SURGE....................................................:IEC/EN 61000-4-5
Level 4
Low Frequency Signals............................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the
second environment-installation restrictions or additional measures may be
needed to prevent disturbances.
1.4. Transport
Please transport the UPS only in the original packaging to protect against shock
and impact.
1.5. Storage
The UPS must be stockpiled in the room where is ventilated and dry.
1.6. Standards
3
Symbol and Explanation
Symbol
Explanation
Symbol
Explanation
Alert you to pay special attention
Caution of high voltage
Alternating current source(AC)
Direct current source(DC)
Turn on or turn off the UPS
Protective ground
Recycle
Do not dispose with ordinary trash
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to
familiarize yourself with them and understand their meaning:
3. Introduction
This On-Line series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically for computer
equipments, communication servers, and data centers.
The double-converter principle eliminates all mains power disturbances. A rectifier
converts the alternating current from the mains power to direct current. On the
basis of this DC voltage, the inverter generates an AC sinusoidal voltage, which
constantly supplies the loads. In the event of power failure, the maintenance-free
batteries power the inverter.
This manual covers the UPS listed as follows. Please confirm whether it is the
model you intend to purchase by performing a visual inspection of the Model No. on
the rear panel of the UPS.
4
Model NO.
Type
Model NO.
Type
OLS6000E
Standard
OLS6000EXL
Extended backup time
OLS10000E
OLS10000EXL
" XL" Model: Extended backup time.
3.1. Feature
This series UPS is a new generation of UPS, which provides the outstanding
reliability, and most cost-performance ratio in the industrial. Following benefit the
product has:
True online double-conversion technology with high power density, frequency
independence and generator compatibility.
High input power factor 0.99,overall high efficiency 92%, save power
and wiring expense. Low input current distortion, avoid power pollution.
Output power factor is 0.9, perfect output sine waveform, suitable almost all
critical equipment.
Outstanding adaptability to the worst mains input condition. Extra wide input
voltage, frequency range and waveform, avoid excessive dissipating limited
5
OLS6000E(XL) OLS10000E(XL)
Fig.3-1 The rear view of OLS6000E(XL)/OLS10000E(XL)
Input
Model NO.
OLS6000E(XL)
OLS10000E(XL)
Phase
Single
Voltage Range
110~276Vac(Depends on load level)
Frequency Range
(45~55)/(54~66)Hz
Rated Current
31(36)A
50(55)A
Power Factor
0.99 @ full load
Battery
Rated Voltage
240Vdc
Rated Current
28A
47A
Output
Model NO.
OLS6000E(XL)
OLS10000E(XL)
Power Rating
6kVA/5.4kW
10kVA/9kW
Voltage*
208/220/230/240Vac
Frequency
Synchronized 50/60×(1±10%)Hz @Line mode
50/60×(1±0.1%)Hz @Battery mode
Wave Form
sine
battery energy.
Internal charger of XL model could be up to 4Amps to decrease recharging
time of battery.
N+X parallel redundancy to increase the reliability and flexibility. Number of
parallel operating UPS is up to 4.
ECO mode with high efficiency 96%, save power expense for user.
Start-able without battery.
3.2. Electrical Specifications
6
Load Type
PF 0.5~1, lagging
THDV
2% @ full linear load
≤5% @ full nonlinear load
Overload**
In Line mode:
10 min 105~125%
1 min 125~150%
10 s >150%
100 ms >170%
In Battery mode:
2 min 105~125%
30 s 125~150%
100 ms >150%
Temperature
Humidity
Altitude
Storage temperature
0~40
<95%
<1000m
-15~50
Model NO.
Dimensions W×H×D(mm)
Net Weight (kg)
OlS6000E
260×708×550
70
OLS6000EXL
260×708×550
25
OLS10000E
260×708×550
86
OLS10000EXL
260×708×550
28
*The load capacity would be derated to 90% automatically when the output voltage
is adjusted to 208Vac.
**The overload capacity would be derated automatically in Line mode while the
circumstance temperature is larger than 35 degree.
3.3. Operating Environment
Note: The load capacity should be derated 1% every 100m heightened on the
basis of 1000m.
3.4. Dimensions and Weights
7
The system must be installed and wired only by qualified electricians in
accordance with applicable safety regulations!
For safety, please cut off the mains power switch before installation!
When installing the electrical wiring, please note the nominal amperage of your
incoming feeder.
4. Installation
4.1. Unpacking
A UPS
A users manual
A USB cable
A RS232 cable (optional)
A parallel cable
A parallel port cover plate
Terminal splices 12pcs (using for the wire connection on input terminal)
*PowerPanel® Business Edition software is available on our website. Please
visit www.cyberpower.com and go to the Software Section for free download.
CAUTION! Inspect the appearance of the UPS to see if there is any damage during
transportation. Do not turn on the unit and notify the carrier and dealer immediately
if there is any damage or lacking of some parts.
4.2. Power Wires Installation
4.2.1. Notes for installation:
1) The UPS must be installed in a location with good ventilation, far away from
water, inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not blocked. Allow at
least 0.5m of space on each side.
3) Condensation to water drops may occur if the UPS is unpacked in a very low
temperature environment. In this case it is necessary to wait until the UPS is fully
dried inside out before proceeding installation and use. Otherwise there are
hazards of electric shock.
8