CyberPower OLS1000ERT2U, OLS1000ERTXL2U, OLS1500ERTXL2U, OLS2000ERTXL2U, OLS3000ERTXL2U User Manual

...
Page 1
User’s Manual
OLS1000ERT(XL)2U OLS1500ERT(XL)2U OLS2000ERT(XL)2U OLS3000ERT(XL)2U
CyberPower Systems Inc. www.cpsww.com
Page 2
Copyright © 2013 CyberPower Systems, Inc.
IMPORTANT SAFETY INSTRUCTIONS
1
This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit.
CAUTION! The battery can power hazardous components inside the unit, even when the AC input power is disconnected.
CAUTION! The UPS should be placed near the connected equipment and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
CAUTION! (Non-Isolated Battery Supply): Risk of electric shock, battery circuit is not isolated from AC power source; hazardous voltage may exist between battery terminals and ground. Test before touching.
CAUTION! To reduce the risk of fire, connect the UPS to a branch circuit with 10 amperes (OLS1000 / OLS1500) / 16 amperes (OLS2000/ OLS3000) maximum over-current protection in accordance to CE requirement.
CAUTION! The AC outlet where the UPS is connected should be close to the unit and easily accessible.
CAUTION! Please use only VDE-tested, CE-marked mains cable, (e.g. the mains cable of your equipment), to connect the UPS to the AC outlet.
CAUTION! Please use only VDE-tested, CE-marked power cables to connect any equipment to the UPS.
CAUTION! When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected equipment does not exceed 3.5mA.
CAUTION! The OLS1000 / OLS1500 / OLS2000 / OLS3000 / Battery module models are only qualified maintenance personnel may carry out installations.
CAUTION! Do not unplug the unit from AC Power during operation, as this will invalidate the protective ground insulation.
CAUTION! To avoid electric shock, turn off and unplug the unit before installing the input/output power cord with a ground wire. Connect the ground wire prior to connecting the line wires!
CAUTION! Do not use an improper size power cord as it may
cause damage to your equipment and cause fire hazards.
CAUTION! Wiring must be done by qualified personnel.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances this unit
should be used for medical applications involving life support equipment and/or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
CAUTION! Do not dispose of batteries in fire as the battery may explode.
CAUTION! Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes.
CAUTION! A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handles.
CAUTION! The unit has a dangerous amount of voltage. When the UPS indicators is on, the units may continue to supply power thus the unit’s outlets may have a dangerous amount of voltage even when it’s not plugged in to the wall outlet.
CAUTION! Make sure everything is turned off and disconnected completely before conducting any maintenance, repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety conductor before any other cables are connected.
WARNING! (Fuses): To reduce the risk of fire, replace only with the same type and rating of fuse.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
Page 3
Copyright © 2013 CyberPower Systems, Inc .
HARDWARE INSTALLATION
2 2
UPS
User’s manual
Phone line
USB communication cable
Input power cord
Output power cords x2pcs
PowerPanel® Business Edition software CD
Flat head screws: M4X8L (12)
Pan head screws: M5X12L (12)
Plastic washers (8)
Screw hole dust covers (8)
Handles (2)
Rackmount left rail Rackmount right rail Rackmount ears (Stands) (2)
Page 4
Copyright © 2013 CyberPower Systems, Inc.
3
HARDWARE INSTALLATION
HARDWARE INSTALLATION
These versatile UPS systems can be mounted in a
rackmount or vertical tower orientation. This versatility is
especially important to growing organizations with changing
needs that value having the option to position a UPS on a
floor or in a rackmount system. Please follow the instructions
below for the respective mounting methods.
SAFETY PRECAUTIONS
CAUTION! To prevent the risk of fire or electric shock, only
use the supplied hardware to attach the mounting brackets.
RACKMOUNT INSTALLATION
Step 1: Rackmount ears installation
1) Attach the two handles to the Rackmount ear using the
provided screws M4X8L*4pcs.
2) Attach the two rackmount ears to the UPS using the
provided screws M4X8L*8pcs.
Step 2: Rackmount rails Installation
1) The rails adjust to mount in 48-cm (19-inch) panel racks
from 52 to 91.5cm (20.5 to 36 inches) deep. Select the
proper holes in the rack for positioning the UPS in the
rack. The UPS takes up position 1 through position 6.
2) Attach the rackmount rail to your rack with two M5X12L
screws and two plastic washers at the front of the rack.
(Located in position 1 & position 6) Do not tighten the
screws. Adjust the rail size on the rail assembly of your
rack. Secure the rail to the rear of the rack with two
M5X12L screws and two plastic washers. Tighten all
screws at the front and rear of the rail. Once completed,
perform the same steps for assembling the other
rackmount trail.
Page 5
Copyright © 2013 CyberPower Systems, Inc.
HARDWARE INSTALLATION
4
Step 3: Install the UPS on the rack
Place the UPS on a flat stable surface with the front of the
unit facing toward you. Secure the UPS to your rack with
four M5X12L screws at the front of the rack. (Located in
position 2 & position 5).
Step 2: Attach the base stands
Tighten the screws (M5X12*4pcs) of the base stands
(rackmount ears) onto the bottom of the UPS.
VERTICAL/TOWER INSTALLATION
Step 1: Rotate the Multifunction LCD Module
1 Unscrew the right panel of the UPS. Separate the right
panel from the UPS.
2Unscrew the LCD plate , Gently lift the LCD module out.
Rotate it to the tower orientation. Reinstall it for a tower
configuration .Attach the LCD plate and LCD module to the
right panel using the provided screws.
Step 3: Attach dust covers
Insert dust cover into the rackmount ear screw holes that are
not being used.
Page 6
Copyright © 2013 CyberPower Systems, Inc.
HARDWARE INSTALLATION
5
ELECTRICAL INSTALLATION
After completing the hardware installation of the UPS, you are now ready to plug in the UPS and connect your equipment.
SAFETY PRECAUTIONS
CAUTION! Installation environment should be in a temperature and humidity controlled indoor area free of conductive
contaminants. Do not install this UPS where excessive moisture or heat is present (Please see specifications for acceptable
temperature and humidity range).
CAUTION! Never install a UPS, or associated wiring or equipment, during a lightning storm.
CAUTION! Do not work alone under hazardous conditions.
CAUTION! In case of the risk of electric shock, do not remove the top cover.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
Page 7
Copyright © 2013 CyberPower Systems, Inc.
INSTALLING YOUR UPS SYSTEM
6
SYSTEM BLOCK DIAGRAM
Output
Input Filter
PFC
AC/DC
BUS
Inverter
DC/AC
INV
RY
Charger
AC/DC
Bypass
Battery
Output
Filter
Input
Line Mode Battery Mode Bypass Mode
Control
&
Monitoring
LCD Module
USB & DB9
SNMP Slot
DC/DC
HARDWARE INSTALLATION GUIDE
1. Battery charge loss may occur during shipping and storage.
Before using the UPS, it’s strongly recommended to charge batteries for four hours to ensure the batteries’ maximum charge capacity. To recharge the batteries, simply plug the UPS into an AC outlet.
2. When using the included software, connect either the serial
or the USB cable between the computer and the corresponding port on the UPS. Note: If the USB port is used, the serial port will be disabled. They cannot be used simultaneously.
3. Connect your computer, monitor, and any
externally-powered data storage device (Hard drive, Tape drive, etc.) into the outlets only when the UPS is off and unplugged. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage the unit.
4. To protect a fax machine, telephone, modem line or network
cable, connect the telephone or network cable from the wall jack outlet to the jack marked “IN” on the UPS and connect a telephone cable or network cable from the jack marked “OUT” on the UPS to the modem, computer, telephone, fax machine, or network device.
5. Press the ON switch to turn the UPS on. If an overload is
detected, an audible alarm will sound and the UPS will continuously emit one beep per second. For resetting the unit, unplug some equipment from the outlets. Make sure your equipment carries a load current within the unit’s safe range, (refer to the technical specifications).
6. This UPS is equipped with an auto-charge feature. When the
UPS is plugged into an AC outlet, the battery will automatically charge, even when the unit is switched off.
7. To maintain an optimal battery charge, leave the UPS
plugged into an AC outlet at all times.
8. Before storing the UPS for an extended period of time, turn
the unit OFF. Then cover it and store it with the batteries fully charged. Recharge the batteries every three months to ensure good battery capacity and long battery life. Maintaining a good battery charge will help prevent possible damage to the unit from battery leakage.
9. The UPS has one USB port (default) and one Serial port that
allows connection and communication between the UPS and any attached computer running the PowerPanel
®
Business Edition Agent software. The UPS can control the computer’s shutdown during a power outage through the connection while the computer can monitor the UPS and alter various programmable parameters. Note: Only one communication port can be used at a time. The port not in use will automatically become disabled or the serial port will be disabled if both ports are attached.
10. EPO (Emergency Power Off) / ROO(Remote on/off) Port:
EPO/ROO ports allow administrators the capability to connect the UPS unit to customer-supplied EPO/ROO switches. If EPO is enabled, these installations give operators a single access point to immediately power-off all equipment connected to the UPS during an emergency. If ROO is enabled, these installations give operators a access point to turn on/off UPS remotely.
11. To avoid electric shock, turn the unit OFF and disconnect
the unit from utility power before hardwiring the UPS (in/out power cord). The in/out power cord MUST be grounded.
Page 8
Copyright © 2013 CyberPower Systems, Inc.
BASIC OPERATION
8 7
POWER MODULE FRONT/REAR PANEL DESCRIPTION
1. Power On/Off Button
Master ON/OFF for the UPS.
2. Function Buttons
Scroll up, scroll down, select and cancel LCD menu.
3. Multifunction LCD Readout
Indicate status information, settings and events.
4. Input Circuit Breaker
Provide input overload and fault protection.
5. Battery Backup & Surge Protected Outlets
Provide battery backup and surge protection. They ensure power is provided to connected equipment over a period of time during a power failure.
6. Serial Port
Serial port provides communication between the UPS and the computer. The UPS can control the computer’s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters.
7. USB port
This is a connectivity port which allows communication and control between the UPS and the connected computer. It is recommended to install the PowerPanel® Business Edition Agent software on the PC/Server connected with the USB cord.
8. Surge Protected Communication Ports RJ-45/RJ-11
These ports are used to protect standard RJ-45/RJ-11 based products (ADSL, LAN, Phone/ Modem-Lines) and cabling systems from surges.
9. SNMP/HTTP Network slot
Slot to install the optional SNMP card for remote network control and monitoring.
10. Extended Runtime Battery Module Connector
Connect to additional external battery modules.
11. EPO (Emergency Power Off) Connector
Enable Power-Off in emergency from a remote location.
12. AC Input Inlet
Connect the AC Power cord to a properly wired and grounded outlet.
OLS1000ERT(XL)2U, OLS1500ERT(XL)2U
OLS2000ERT(XL)2U
OLS3000ERT/ERTXL2U
Page 9
Copyright © 2013 CyberPower Systems, Inc.
BASIC OPERATION
8
BATTERY MODULE FRONT/REAR PANEL DESCRIPTION
1. Input Connector
Use this input connector to daisy chain the next Battery module.
Remove the connector cover for access.
2. On-board Replaceable Fuse Cover
Replaceable fuse is accessible from the rear panel.
It must be done by qualified personnel.
3. Output Connector
Use this output Connector to connect the Battery module to
the Power module or to the next Battery module.
BPSE36V45ART2U, BPSE72V45ART2U
CONNECTION 1 : POWER MODULE WITH ONE BATTERY MODULE
Step 1: Loosen the two screws to remove the
battery cable retention bracket of the power module.
Step 2: Use the battery cable of the Battery
module to connect the Battery module to the Power module.
Step 3: Rotate the battery cable retention racket
and tighten the two screws to fix battery cable.
CONNECTION 2 : POWER MODULE WITH MULTIPLE BATTERY MODULES
Step 1: Connect the 1st Battery module to the Power
module using battery cable.
Step 2: Loosen the two screws to remove the battery
cable retention bracket of the 1
st
battery module.
Step 3: Use the battery cable to connect the 2
nd
Battery
module to the 1
st
Battery module.
Step 4: Rotate the battery cable retention bracket and
tighten the two screws to fix battery cable.
Page 10
Copyright © 2013 CyberPower Systems, Inc.
9
BASIC OPERATION
LCD SCREEN – UPS STATUS
LCD Screen
UPS Status Description
UPS is operating in Line Mode.
UPS is operating in Battery Mode.
UPS is operating in Bypass Mode.
UPS is operating in ECO (Economy) Mode.*
UPS is operating in Converter Mode when this icon blinking**.
*) When operating in ECO Mode, the efficiency of UPS is higher than that in online mode, but transfer time should not be 0ms
**) When operating in Converter Mode, the frequency of output should be always 50Hz or 60Hz, but load capacity will be
derated.
DEFINITIONS FOR OTHER ICONS
LCD Screen Description
LOAD capacity: This meter displays the approximate output
load level (in 20% increments) of the UPS outlets.
BATTERY capacity: This meter displays the approximate charge level (in 20% increments) of the UPS’s internal
battery. During a blackout or severe brownout,
the UPS switches to battery power, the BATTERY icon appears, and the charge level decreases.
MUTE:
This icon appears whenever the UPS is in silent
mode. The alarm does not beep during silent mode until the
battery reaches low capacity.
SCHEDULE: Users can setup the schedule to turn on and shut down the computer and UPS through PowerPanel® Personal Edition software. The LCD display will show how much time is left before the UPS will turn back on or shut down.
OVER LOAD: This icon appears and an alarm sounds to indicate the outlets are overloaded. To clear the overload,
unplug some of your equipment from the battery-supplied
outlets until the icon turns off and the alarm stops.
FAULT: This icon appears if there is a problem with the UPS. Please refer to “Event ID Descriptions”.
Page 11
Copyright © 2013 CyberPower Systems, Inc.
BASIC OPERATION
10
REPLACE: This icon appears if
the batteries need to be
replaced.
Event ID Descriptions
Event ID
Description of Cause
1
Bus Start Fail: DC-DC converter or bus sensing circuit failed.
2
Bus Volt High: DC-DC converter failed.
3
Bus Volt Low: DC-DC converter failed.
4
Bus Unbalanced: DC-DC converter failed.
5
INV Start Fail: Inverter circuit failed.
6
INV Volt High: Inverter circuit or output voltage sensing
circuit failed.
7
INV Volt Low: The load may be too heavy or inverter circuit
failed.
8
INV Short: The inverter circuit failed.
9
Bat Volt High: The external battery module connection is
wrong, or the charger failed.
10
Bat Volt Low: Batteries failed.
11
Over Temperature: High ambient temperature, or the
ventilation hole has been covered.
12
Over Load: UPS is overloaded.
54
High Temperature: High ambient temperature, or the
ventilation hole has been covered. This is shown only when
start up UPS.
55
Bat Low: Battery voltage is too low to DC start UPS.
57
EPO Off: Missing the EPO connection
58
Fan Fail: The ventilation hole has been covered, or the fans can’t work.
59
Bat Bad: Battery failed.
BUTTON OPERATION
Button
Operation Description
ON
Press this button to turn on UPS.
OFF
Press this button to turn off UPS.*
ENTER/
Press this button to scroll up in the LCD menu. Press this button simultaneously for 5 seconds to disable or enable the alarm system while in battery mode. Press this button simultaneously for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode. In setting mode, press this button to confirm selection, or press this button for long time to exit setting mode and saving
changes.
ESC/
Press this button to scroll down in the LCD menu.
Press this button for long time to get into setting mode In setting mode, press this button to display next selection, or press this button for long time to exit setting mode without
saving changes.
ENTER/ + ESC/
Switch to bypass mode: When the main power is normal, press these two buttons simultaneously for 5 seconds, then UPS will enter to bypass mode.
*) If utility power is connected,UPS will keep charging but cut off output.
Page 12
Copyright © 2013 CyberPower Systems, Inc.
LCD SETUP FUNCTIONS
11
LCD INFORMATION READOUT
There are 12 types of UPS information available for display on digit area.
Information Submenu
Description
OUTPUT XXX V
Displays the Output Voltage
OUTPUT XX.XHz
Displays the Output Frequency
OUTPUT XXX (k)VA
Displays the Output VA
OUTPUT XXX% VA
Displays the Output Load Percentage of Maximum Apparent Power
OUTPUT XXX (k)W
Displays the Output Wattage
OUTPUT XXX% W
Displays the Output Load Percentage of Maximum Active Power
INPUT XXX V
Displays the Input Voltage
EVENT XXX
Displays the Event ID
ESTIMATED RUN TIME %
Displays the Estimated Percentage of Battery Capacity
ESTIMATED RUN TIME XX(.)X [Min][Hr]
Displays the Estimated Run Time with battery
TIME TO SHUT DOWN XX(.)X [Min][Hr]
Displays the Time Delay to Shutdown UPS
TIME TO TURN ON XX(.)X [Min][Hr]
Displays the Time Delay to Restart UPS
LCD SETTINGS CONFIGURATION
There are 8 UPS settings that can be configured by the user.
1. Press the “ESC” button simultaneously for 5 seconds to activate the setting mode.
The first configuration parameter will be displayed on the LCD screen.
Note: The manual settings programming mode can ONLY be invoked while UPS is in Bypass mode or Standby mode. To make UPS on Standby mode or Bypass mode, connect utility power to UPS and do not turn on UPS.
2. Press the “ENTER” button to select the setting you want to configure.
3. Press the “” buttons to scroll through the different parameters.
Press the “ENTER” button to select the parameter you want.
4. Press the “ESC” button simultaneously for 5 seconds to cancel and exit setting mode. Press the “ENTER” button
simultaneously for 5 seconds to save all the settings you just do and exit setting mode.
Page 13
Copyright © 2013 CyberPower Systems, Inc.
LCD SETUP FUNCTIONS
12
Configure Submenu
Available Settings
Default Setting
Output Voltage
= [208V] [220V] [230V] [240V] 230V
Output Frequency
= [50Hz][60Hz] 50Hz
ECO Mode *
[0%] (Disable) [10%][15%] (Enable) 0%
Bypass Mode **
[DIS] (Disable) [ENA] (Enable) Enable
Converter Mode
[DIS] (Disable) [ENA] (Enable) Disable
EPO/ROO***
[EPo] [Roo] EPO
EBM Number****
[0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10](for –E models, the maximum number is 3 )
0(for –E models) / 1 (for –EXL models)
Bypass when UPS is Off
[F1d](Disable)[F1E](Enable) Disable
*) This function would be set as 0% when Converter Mode is enabled. **) UPS has no bypass when Converter Mode is enabled. *** ROO (Remote On/Off): If ROO is enabled, UPS can be turn on/off by the ROO port. If ROO port is disconnected, UPS will be turned off. If ROO port is connected, UPS will be turned on when the utility is normal ****) UPS cannot detect the numbers of external battery automatically, so manual input from user is necessary.
SILENCING AUDIBLE ALARMS
Press the “ENTER” button on simultaneously for 5 seconds to disable or enable the alarm system while in battery mode. Note: Some audible alarms (Over Temperature, Fan Fail, etc.) can’t be silenced.
MANUAL BATTERY TEST
Press the “ENTER” button simultaneously for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode.
Page 14
Copyright © 2013 CyberPower Systems, Inc.
MAINTENANCE
13
Storage
To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to ensure battery life.
Safety Precautions
CAUTION! Only use replacement batteries which are certified by CyberPower Systems. Use of incorrect battery type is an electrical hazard that could lead to explosion, fire, electric shock, or short circuit. CAUTION! Batteries contain an electrical charge that can cause severe burns. Before servicing batteries, please remove any conductive materials such as jewelry, chains, wrist watches, and rings.
CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is harmful to the skin/eyes and may be toxic.
CAUTION! To avoid electric shock, turn off and unplug the UPS from the wall receptacle before servicing the battery. CAUTION! Only use tools with insulated handles. Do not lay tools or metal parts on top of the UPS or battery terminals.
Replacement Batteries
Please refer to the front side of the UPS for the model number of the correct replacement batteries. For battery procurement, log onto www.CPSww.com, or contact your local dealer.
Battery Disposal
Batteries are considered hazardous waste and must be disposed of properly. Contact your local government for more information about proper disposal and recycling of batteries. Do not dispose of batteries in fire.
Battery Installation and replacement
Step 1: Remove the front panel. Remove the retaining screws from the battery bracket and then remove the cover itself. undraw the connectors.
Step 2: Pull the battery tray out slowly. Put the new battery tray back into the compartment after that.
Step 3: Fasten the battery bracket and then insert the connectors. Place the connectors in the bracket.
Step 4: Tighten the screws of the battery bracket and front panel .
Page 15
Copyright © 2013 CyberPower Systems, Inc.
14
TECHNICAL SPECIFICATIONS
Model
OLS1000ERT
(XL)2U
OLS1500ERT
(XL)2U
OLS2000ERT
(XL)2U
OLS3000ERT
(XL)2U
Configuration
Capacity (VA)
1000VA
1500VA
2000VA
3000VA
Capacity (Watts)
800W
1200W
1600W
2400W
Form Factor
Rack
Energy-saving Technology
Yes, ECO Mode Efficiency ≧95%
Input
Input Voltage Range
110~130Vac± 5% for 1000 / 1500 / 2000 VA model
110~140Vac± 5% for 3000 VA only
@ 0~50% Load ± 5%
120~140Vac± 5% for 1000 / 1500 / 2000 VA model
140~160Vac± 5% for 3000 VA only
@ 0~60% Load± 5%
140~160Vac± 5% for 1000 / 1500 / 2000 VA model
160~190Vac± 5% for 3000 VA only
@ 0~80% Load± 5%
160~300Vac± 5% for 1000 / 1500 / 2000 VA model
190~300Vac± 5% for 3000 VA only
@ 0~100% Load± 5%
Input Frequency Range
40~70Hz
Input Power Factor
0.98
Cold Start
Yes
Output
Output Waveform
Pure Sine Wave
Output Voltage
208, 220, 230, 240Vac ±1%
Output Frequency
50 / 60Hz (Auto-Sensing or Configurable) ±0. 5Hz
Transfer Time (Typically)
0ms
Rated Power Factor
0.8
Harmonic Distortion
THD < 3% at Linear Load, < 5% at Non-linear Load @ Nominal Input
Crest Factor
3 : 1
ECO Mode Voltage
Regulation
±10%, ±15% (Configurable)
UPS Outlets
(3+3) IEC C13 (4+4) IEC C13
(4+4) IEC C13
(1) IEC C19
Protection
Surge Protection
IEC 61000-4-5 Level 4
Phone / Network Protection
RJ11/RJ45 (One In/One Out)
Overload Protection
Line Mode: 105~110% Overload warning only (No shutdown)
, 110~120% Warning, transfer to bypass after 60s >120% Transfer to bypass immediately
Battery Mode105~110%
Overload warning only (No shutdown)
, 110~120% Warning, shutdown after 10s >120% Shutdown immediately
Bypass Mode
Warning only @ 130%>Load>105%, Shutdown immediately @
Load>130%
Short Circuit Protection
UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
Battery
Specifications
(3) 12V/7AH
(3) 12V/8.5AH
(6) 12V/7AH
(6) 12V/8.5AH
For XL Models, NO Battery Inside.
Recharge Time (Typically)
4 Hours (inside batteries)
Sealed, Maintenance Free
Yes
Status Indicators
LCD Screen
Graphic LCD
Audible Alarms
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery, Bypass Mode
Charger Failure /Over Charged, Fan failure, EPO active
Environment
Operating Temperature
32℉ to 104℉ ( 0℃ to 40℃)
Operating Relative Humidity
20 to 90% Non-Condensing
Page 16
Copyright © 2013 CyberPower Systems, Inc.
TECHNICAL SPECIFICATIONS
15
*) Within 50/60Hz±8% by default, the output frequency is synchronization with input mains. User can adjust the acceptable range for output frequency (±1, 2, 3, 4, 5, 6, 7, 8, 9, 10%). When input frequency is out of synchronization window but within 40-70Hz, UPS can stay in line mode and output frequency is regulated at 50/60Hz+0.5% with load derating by 40%.
Management
On-Device Features
Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
Connectivity Ports
(1) Serial Port (RS232), (1) USB Port,
SNMP/HTTP Capable
(1) Expansion Port (With optional RMCARD 302)
Software
Power Management
Software
PowerPanel® Business Edition
Physical
Dimensions (H x W x D)
3.46x 17.24x15.75 in.
88×438×400 mm
3.46x 17.24x22.83 in. 88×438×580 mm
Net Weight
384.2(18.6)lbs
13.2(8.4)Kg
32.2(18.8)lbs
14.6(8.5)Kg
46.8(25.6)lbs
21.2(11. 6)Kg
60.9(26.5)lbs
27.6(12)Kg
Safety
Conformance Approvals
CE
Page 17
Copyright © 2013 CyberPower Systems, Inc.
16
TROUBLE SHOOTING
Problem Possible Cause Solution
Warning
O/P Overload
Your equipment requires more power than the
UPS can provide. If the UPS is in Line Mode
then it will transfer to Bypass Mode; if the UPS is
in Battery Mode it will shutdown.
Shut off non-essential equipment. If this solves
the
overload problem, the UPS will transfer to
normal operation.
Battery Mode UPS is operating on battery power.
Save your data and perform a controlled-
shutdown.
Battery Low
UPS is operating on battery power and will be
shutting down soon due to extremely low battery
voltage.
UPS will restart automatically when acceptable
utility power returns.
BAT Disconnected/
Battery Replace
Missing battery power.
Check battery connector
when use battery
packages.
UPS has failed in Battery Test. Contact technical support to replace the battery.
Charger Failure Charger has failed.
1. Shut down UPS and turn off AC input.
2. Contact CyberPower for repair.
EPO OFF Missing the EPO connection. Check the EPO connection.
Fault
Over Temperature High ambient temperature.
1. Shut down UPS. Restart UPS to Check the
fan for operation and if the ventilation hole has
been covered
2. Contact CyberPower for repair.
Output Short Output short circuit.
1. Shut down UPS
2. Your attached equipment may have problems,
please remove them and check again.
High O/P V Output voltage is too high.
1. Shut down UPS
2. Contact CyberPower for repair.
Low O/P V Output voltage is too low.
Bus Fault Internal DC bus voltage is too high or too low.
Other
Startup fail
High temperature, or fan fail, or battery low, or
EPO off..
1. Restart UPS and press the “▼” button to
view the warning event. Then refer to the solution
for the warning.
2. Contact CyberPower for repair.
Page 18
Copyright © 2013 CyberPower Systems, Inc.
TROUBLE SHOOTING
17
CyberPower Systems Inc.
www.cpsww.com
Entire contents copyright
©
2013 CyberPower Systems Inc., All rights reserved. Reproduction in whole or in part without