This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries.
The Smart App Online 5-6kVA UPS models that are covered in this manual are intended for
installation in an environment within 32°F to 104°F (0°C to 40°C), free of conductive contaminants.
SPECIAL SYMBOLS
Warning: High voltage – Risk of Electric Shock
Caution - Important Instructions: Must always be followed.
Do Not Discard: The UPS or UPS batteries in trash. The batteries
contain lead acid. For more information, contact your local recycling
or hazardous waste facility.
To reduce the risk of fire, connect the UPS to a branch circuit with 50 amperes
(5,000/6,000 VA) maximum over-current protection in accordance with the
National Electric Code, ANSI/NFPA 70.
The AC electrical service where the UPS is connected should be close to the unit
and easily accessible.
Please use only UL-marked mains cable, (e.g. the mains cable of your equipment),
to connect the UPS to the AC outlet.
Please use only UL-marked power cables to connect any equipment to the UPS.
When installing the equipment, ensure that the sum of the leakage current of the
UPS and the connected equipment does not exceed 3.5mA.
Do not unplug the unit from AC power during operation, as this will disconnect the
protective ground insulation.
Do not use an improper size power cord as it may cause damage to your
equipment and cause fire hazards.
Make sure everything is turned off and disconnected completely before conducting
any maintenance, repairs or shipment.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT
SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS
OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY
PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS.
KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
FOR PERMANENTLY CONNECTED EQUIPMENT, A READILY ACCESSIBLE
DISCONNECT DEVICE SHALL BE INCORPORATED IN THE BUILDING
INSTALLATION WIRING.
A battery can present a risk of electric shock and high short circuit current. The
following precaution should be observed when working on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
The UPS must be connected to a grounded AC power outlet with fuse or circuit
breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If
you need to power-drain this equipment, turn off and unplug the unit.
(No User Serviceable Parts): Risk of electric shock, do not remove cover. No user
serviceable parts inside. Refer servicing to qualified service personnel.
To prevent the risk of fire or electric shock, install in a temperature and humidity
controlled indoor area, free of conductive contaminants. (Please see specifications
for acceptable temperature and humidity range).
To avoid electric shock, turn off and unplug the unit before installing the input/
output power cord with a ground wire. Connect the ground wire prior to
connecting the line wires!
Connect the Protection Earth (PE) safety conductor before any other cables are
connected.
(Fuses): To reduce the risk of fire, replace only with the same type and rating of
fuse.
The battery can power hazardous components inside the unit, even when the AC
input power is disconnected.
The UPS should be placed near the connected equipment and easily accessible.
(Non-Isolated Battery Supply): Risk of electric shock, battery circuit is not isolated
from AC power source; hazardous voltage may exist between battery terminals
and ground. Test before touching.
All UPS models covered in this document are permanently-connected equipment
and only qualified maintenance personnel may carry out installations.
Wiring must be done by qualified personnel.
BATTE RY
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no
circumstances should this unit be used for medical applications involving life
support equipment and/ or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use
with or near aquariums. Condensation from the aquarium can come in contact with
metal electrical contacts and cause equipment to short out.
The unit has a dangerous amount of voltage. When the UPS indicators is on, the
units may continue to supply power thus the unit’s outlets may have a dangerous
amount of voltage even when it’s not plugged in to the wall outlet.
Do not dispose of batteries in fire as the battery may explode.
Do not open or mutilate the battery, released electrolyte is harmful to the skin and
eyes.
SAFETY INSTRUCTIONS .............................................................................................................................. II
Special Symbols ..................................................................................................................................................................... II
Personal Safety ...................................................................................................................................................................... III
Whats In The Box ................................................................................................................................................................... 3
Power Module .......................................................................................................................................................................... 4
INSTALLING YOUR UPS SYSTEM ................................................................................................................ 6
System Block Diagram ......................................................................................................................................................... 6
LCD Menu Tree ......................................................................................................................................................................21
CyberPower Smart App Online rack/tower UPS systems, with double-conversion topology,
provide sine wave output to mission-critical applications and equipment requiring seamless power
correction. These units offer generator compatibility and deliver clean AC power with zero transfer time.
They offer Smart Battery Management (SBM), which helps extend overall battery life, and Fast
Charge Technology, which helps keep charge times to less than four hours, regardless of the
number of Extended Battery Modules (EBMs). Features include energy-saving GreenPower UPS™
ECO Mode technology, and PowerPanel® Business Edition software for monitoring and managing
the UPS. Smart App Online 5-6kVA UPS systems come with a three-year warranty and a $300,000
Connected Equipment Guarantee.
UPS EXTENDED BATTERY MODULES
Extended Battery Modules (EBMs) from CyberPower (BP144VL2U01) increase battery runtimes
during power outages. Each rack/tower convertible EBM uses 2U of rack space, depending upon the
model, and can be installed in a tower form factor to match the UPS installation. The DC plug-andplay power connectors allow to daisy- chain additional EBMs to a UPS system. EBMs compatible
with Smart App Online UPS systems also have a built-in battery charger, providing Fast Charge
Technology to quickly restore the backup power supply.
Every CyberPower EBM has a three-year warranty.
STEP-DOWN TRANSFORMER
CyberPower Step-Down and Isolation Transformers support hardwire installations (OL6KSTF) and
are designed for a variety of CyberPower UPS systems. When connected to the UPS, the step-down
transformer converts voltage from 200-240V down to 100-120V.
The UPS system is very heavy, please handle with care. Wear safety shoes and use a hydraulic
equipment lift if one is available. At least two people are required for all handling operations,
including unpacking, lifting, and installation in a rack system. Do not use the lifting straps to carry
the unit around; they are provided to manually unpack the unit only.
USE LIFTING STRAPS TO REMOVE THE UNIT FROM THE BOX.
Master ON/OFF switch for the UPS. Indicates that the UPS is on and supplying power.
2. UPS Status / Multifunction LCD Readout
Shows UPS status, information, settings and events.
3. Function Buttons
Scroll DOWN scroll UP, ENTER, and ESCAPE.
476811
CRITICAL
LOAD
4
BATTERY INPUT : 144V
NONCRITICAL
3
L6-30
BM / ENV
LOAD
2 1
OUTPUT BREAKER
20A/250V~
L6-20L6-20L6-30
RS232
USBEPO
591210
Back: OL5KRTHD / OL6KRTHD
4. Battery Backup & Surge Protected Outlets
Provides battery backup and surge protection. They ensure power is provided to connected
equipment over a period of time during a power failure.
Critical / Noncritical Load
Allows the creation of load priorities to ensure that battery power reserves are transferred to
specified outlets during a power outage. The unit can be programmed to provide additional runtime
for equipment connected to the “CRITICAL” outlets, while stopping the power supply to equipment
connected to “NONCRITICAL” outlets after a designated period of time.
5. Extended Runtime Battery Module Connector
Connection for additional CyberPower External Battery modules.
The port supports External Battery Modules detection.
7. Output Circuit Breaker
Provides output current overload and fault protection.
8. Serial Port
Serial port provides RS-232 communication between the UPS and a computer. The UPS can trigger
a computer with PowerPanel® Business Edition software installed to shut down during a power
outage through the connection while the computer can monitor the UPS and change its various
programmable settings.
9. EPO (Emergency Power Off) Connector
Enables an emergency UPS power-off from a remote location.
10. USB Port
USB port provides communication between the UPS and a computer. The UPS can trigger a
computer with PowerPanel® Business Edition software installed to shut down during a power
outage through the connection while the computer can monitor the UPS and change its various
programmable settings.
11. Expansion Slot
A network remote management card is pre-installed in the expansion slot.
1. Battery charge loss may occur during shipping and storage. Before using the UPS, it’s strongly
recommended to charge batteries for four hours to ensure the batteries’ maximum charge capacity.
To recharge the batteries, simply connect the UPS to its designated AC electrical service.
2. When using PowerPanel® Business Edition software, connect either the serial or the USB cable
between the computer and the corresponding port on the UPS. Note: If the USB port is used,
the serial port will be disabled. They cannot be used simultaneously. After connecting to either
the USB port or the serial port on the UPS, a computer with PowerPanel® Business Edition Agent
software installed can control the operating schedule, battery test, outlets, as well as obtain UPS
status information. However, other computers with PowerPanel® Business Edition Client software
can only obtain UPS status information via LAN connection.
3. Connect your computer, monitor, and any externally-powered data storage device (Hard drive,
Tape drive, etc.) into the outlets only when the UPS is off and unplugged. DO NOT plug a laser
printer, copier, space heater, vacuum, paper shredder or other large electrical device into the
UPS. The power demands of these devices will overload and possibly damage the unit.
4. Press the ON/OFF switch to turn the UPS on. The Power-On indicator LED will turn on when
activated. If an overload is detected, an audible alarm will sound and the UPS will continuously
emit two beeps per second. For resetting the unit, unplug some equipment from the outlets.
Make sure your equipment carries a load current within the unit’s safe range, (refer to the
technical specifications).
5. This UPS is equipped with an auto-charge feature. When the UPS is connected to AC electrical
service the battery will automatically charge, even when the unit is switched off.
6. To maintain an optimal battery charge, leave the UPS connected to AC electrical service at all times.
7. Before storing the UPS for an extended period of time, turn the unit OFF. Then cover it and
store it with the batteries fully charged. Recharge the batteries every three months to ensure
good battery capacity and long battery life. Maintaining a good battery charge will help prevent
possible damage to the unit from battery leakage.
8. The UPS has one USB port (default) and one serial port that allows connection and
communication between the UPS and any attached computer running PowerPanel® Business
Edition Agent software. The UPS can control the computer’s shutdown during a power outage
through the connection while the computer can monitor the UPS and alter various programmable
parameters. Note: Only one communication port can be used at a time. The port not in use will
automatically become disabled or the serial port will be disabled if both ports are attached.
9. EPO (Emergency Power Off) Port: EPO ports allow administrators the capability to connect the
UPS unit to customer-supplied EPO switches. These installations give operators a single access
point to immediately power-off all equipment connected to the UPS during an emergency.
10. To avoid electric shock, turn the unit OFF and disconnect the unit from utility power before
hardwiring the UPS (in/out power cord). The in/out power cord MUST be grounded.
11. Please note the internal UPS temperature will increase when fans are not in operation or
ventilation is obstructed. When the high temperature sensor activates protection, the UPS
generates an alarm and shuts down to avoid unexpected equipment damage. When the over
temperature occurs, please check the Troubleshooting section. If the condition persists, please
contact CyberPower for technical support.
CyberPower UPS systems can be installed in a rackmount or vertical/tower orientation. This
versatility is especially important to growing organizations with changing needs that value having
the option to position a UPS on the floor or in a rackmount system. Note that the included rack
mounting hardware is only compatible with square hole racks. Please follow the instructions below
for the respective mounting methods.
RACKMOUNT INSTALLATION FOR 4-POST RACK
Caution: Important Instructions
To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting
brackets.
Step 1: Remove the dust covers
Remove ten dust covers from the screw holes as shown below.
Attach two rackmount ears to the UPS using eight black M5X7L flat head screws and tighten two
hanging brackets using six silver M5X6L pan head screws.
12
Step 3: Rackmount rail Installation
The mounting depth of the included rackmount rails can adjust from 20.5 in to 36 in (52 cm to 91.5 cm).
Select the proper holes in the rack for positioning the UPS in the rack. The UPS takes up 2 rack
units: rack hole positions 1 through 6.
Position the guide screws on the back of the rackmount rails into the rear rack square holes to
temporarily support the rails in place.
Step 4: Adjust rackmount rails to fit your rack
Adjust the rail depth to match your rack depth. Attach each rackmount rail to your rack with two
black M5X12L pan head screws and two plastic washers at the front of the rack (square holes 1 and
4 as shown below). Secure each rail to the rear of the rack with two black M5X12L pan head screws
and two plastic washers.
Slide the hanging brackets on the UPS on to the rails mounted in the rack with the front of the unit
facing toward you. Secure the UPS to your rack with four black M5X12L pan head screws at the
front of the rack (square holes 2 and 5 as shown above).
NOTE: To slide the UPS out from the rack
The UPS will be secured by a safety locking mechanism midway of pulling it out of the rack. Use
both hands to hold the UPS and press the safety locking tab to pull the UPS out.
CAUTION! Due to the weight of this unit, it is strongly recommended to install it at the
bottom of the rack.
CAUTION! Prior to installing the unit, remove internal batteries to reduce the weight of the
unit. Refer to the battery replacement section in this user manual for instructions.
CAUTION! It is strongly recommend having 2-3 people assist during the installation process.
CAUTION! It is strongly recommended that the 2 post rack be bolted to the floor prior to
the installation of the UPS
.
Step 1: Remove side dust covers
Remove seven dust covers from screw holes as shown below.
Step 2: Rackmount ears installation
Attach the included rackmount ears to the center holes on the sides of the UPS using eight black
M5X7L screws as shown below.
Step 3: Secure the UPS to the rack
Secure the UPS to your rack with four black M5X12L screws at the front of the rack (square holes 2
and 5 as shown below).
Adhere twelve circular rubber pads to the stands and to the left hand side of the UPS as shown below.
This will become the bottom of the UPS. Insert the dust covers into the open screw holes on bottom.
Step 2: Attach the base stands and attach the dust covers
Stand the UPS system on its side and attach the tower stands using four silver M5X6L pan head screws
onto the bottom of the UPS as shown below. Insert the dust covers into the open screw holes on top.
Verify branch circuit breaker rating and wiring dimensions with the following table for hardwired
input UPS models.
UPS CAPACITY
5KVA
6KVA
Hardwire the input/output terminals for OL6KRTHD UPS models as shown in the following diagram.
BRANCH CIRCUIT
BREAKER
50A8 AWG8.0 mm
Wiring
AWG
WIRING AWGWIRING mm
2
SCREW TORQUE
2
lbf-in
18 lbf-in
UPS
Mains
L1 L2 PE
Input
Circuit Breaker
L1
L2L2
PE
PFC
AC/DC
Inverter
DC/AC
Battery
RLY
External
EPO
L1
L2
PE
Outlet
L1
PE
Caution: Important Instructions
Input and Output circuit breakers must be “OFF” during the installation process.
An additional two pole disconnect device is necessary during the installation process.
Disconnected EPO will immediately shut down the logic circuit output of the UPS. Wiring the EPO
port is optional.
Local safety rules may require a separate, external EPO to turn off output circuit breakers. Refer to
local wiring rules, the EPO should use approved components.
OL5KRTHD and OL6KRTHD ELECTRICAL CONNECTION : Please see the instructions as shown
below.
1. Fix the input bottom cover on the rear panel by tightening the two screws.
2. Insert the input cable through the appropriate cable gland (not included). Connect the three
wires to the input terminal block.
3. Separate the top cover from the unused input power cord by loosening the two screws.
4. Fix the top cover on the bottom cover by tightening two screws.
12
L1L2
43
IMPORTANT! Make sure the utility circuit breaker feeding the UPS input is in the OFF position.
IMPORTANT! Verify the input branch circuit breaker and wiring meet the recommended sizing.
There are 2 display Zones: Icon Zone and Content Zone.
1
A
ICON ZONE
2
3
B
CONTENT ZONE
1.UPS working information
2.UPS status overview
3.Main menu & Quick link
A ICON ZONE:
In the Left area , There are 3 ICONS for displaying the UPS working status / Load % / Battery
Capacity and depend on UPS status changing the ICONS will display Warning and Fault with
Yellow or RED color.
B CONTENT ZONE:
The Content area is on the middle and right screen.
1 The Top of Content area is for displaying UPS working information: Working Normally (Line
Mode) / V+Hz out of range (Battery Mode) / …..Etc.
2 The central area is the UPS status which depends on different UPS status to provide different
information included Input / Output / Battery / Load parameters.
3 The bottom area of content zone is the function select index included Main Menu and quick
link selection which depends on different UPS status to provide relevant functional link.
Push Enter Button to Main Menu When UPS display the summary page.
STAN DBYA utility power has been connected but UPS is Off.
UPS is operating in Line Mode.
Working Normally
V+Hz out of range
V out of range
The UPS is operating and protecting the equipment
normally.
UPS is operating in Battery Mode.
A utility power failure (V+Hz/V/Hz out of range) has occurred.
The UPS is using battery power to work and protect the
equipment.
UPS MODES DESCRIPTION
Bypass Mode
Manual Bypass
Mode
ECO Mode
Hz out of range
Warning or Fault
Information
Manual Bypass
ECO Mode
UPS is operating in Bypass Mode.
A Warning or fault has been detected and the UPS
transfers output to utility power.
UPS is operating in Manual Bypass.
The UPS has been manually transferred to bypass for
maintenance purposes.
UPS is operating in ECO (Economy) Mode.
If Bypass quality is within the ECO mode setting
specifications, the UPS will operate in Bypass until input
power is disqualified per set specifications. At that time the
UPS will automatically switch to Line Mode.
LCD will use RED or Yellow color to indicate the Fault or warning status and also connect the color
frame with ICON which has the same color and locates on the left zone of the screen.
The UPS status in the UPS Summary page will provide the related information by different working
function..
The Function Select Menu in the UPS Summary page will provide the quick link to related function.
Battery Mode
Output OverLoad
Press the “UP” and “DOWN” buttons to select the quick link function.
Push “Enter” Button to select function page.
There are 7 UPS items that can be controlled by the user.
1. Press the “UP” and “DOWN” buttons to select the “CONTROLS” ICON.
2. Press the “ENTER” button to enter the “CONTROLS” function.
3. Press the “UP” and “DOWN” buttons to scroll to the “CONTROLS” option.
4. Press the “ENTER” button to select the “CONTROLS” submenu items shown in the table below.
5. Press the “ENTER” button to select the setting you want to set up.
6. The present SET UP parameter will be displayed by Blue Color with a select mark in the front of
setting parameters.
7. Press the “UP” and “DOWN” buttons to scroll through the different control functions.
8. Press the “ENTER” button to select the parameter you want to set.
9. You may be prompted “Activate?” to act the selection, if so press the “ENTER” button to act the
control function. Some options are started automatically. (See the following table and screen for
additional details.)
10. Press the “ESC” button to cancel or return to the previous SET UP menu.
When performing UPS maintenance, the user can manually
transfer the connected load to Bypass without interrupting the
output to the connected equipment.
When ECO mode is enabled the UPS will check the following
specifications of Bypass quality
(1)Bypass voltage is inside the [V Range= +/-10%] (default setting)
or [V Range= +/-15%].
(2)Bypass frequency is inside the +/-3Hz range of output nominal
frequency.
[Disable] [Enable]
When the UPS input power source is a generator set the UPS will
operate normally without transferring to Battery Mode when this is
[Enable].
DEFAULT
SETTING
Disable
V Range=
+/-1 0 %
Disable
[Disable] [Enable]
Converter
Mode***
Outlet Group
Reset Load
Energy
Reset
ReplaceBAT
*This function can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
**UPS has no bypass when Generator Mode is enabled.
***UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
There are 28 UPS items that can be Set Up by the user.
1. Press the “UP” and “DOWN” buttons to select the “SET UP” ICON.
2. Press the “ENTER” button to enter the “SET UP” function.
3. Press the “UP” and “DOWN” buttons to scroll to the “SET UP” option.
4. Press the “ENTER” button to select the “SET UP” submenu items shown in the table below.
5. Press the “ENTER” button to select the setting you want to set up.
6. The present SET UP parameter will be displayed by Blue Color with a select mark in the front of
setting parameters.
7. Press the “UP” and “DOWN” buttons to scroll through the different parameters.
8. Press the “ENTER” button to select the parameter you want to set.
9. You may be prompted “Save Change?” to save the selection, if so press the “ENTER” button to
save the setting. Some options are saved and started automatically. (See the following table and
screen for additional details.)
10. Press the “ESC” button to cancel or return to the previous SET UP menu.
The default setting [Check Freq/Volt] means the
UPS will check the the following specifications (1)
and (2) when UPS has fault and needs transfer to
Bypass.
DEFAULT
SETTING
208V
+/- 5%
+10%/-15%
Bypass
Condition
Audible Alarms
CommunicationIP Address
The setting [Check Volt Only] means the UPS will
check the the following specification (1) when
UPS has fault and needs transfer to Bypass.
(1)Bypass voltage is inside the range of "Bypass
V Window ".
(2)Bypass frequency is inside the range of "Sync
Freq Range".
The setting [No Bypass] means the UPS is
forbidden to transfer to Bypass when UPS has
fault.
Sets [EPO] (Emergency Power Off) to shutdown the
UPS remotely when the contact is open.
Sets [ROO] (Remote On/Off) to turn On the UPS
remotely when the contact is close and turn Off the
UPS remotely when the contact is open. The On/Off
power button on front panel will be disabled when
set to [ROO].
Sets [Manual Bypass] if MBP(option) is installed with
UPS. Please refer to the MBP User Manual.
[Disable] [Enable]
All communication ports on the UPS are [Disable] or
[Enable].
If UPS has EQM function, the UPS will Auto detect
the external batt number.
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
Sets the actual EBM (extended battery modules)
number to get the correct estimated runtime.
DEFAULT
SETTING
Disable
Enable
None
0
Charger Function
Charger Check
Wiring Fault
Button OFF LOCK
[SBM] [Constant]
Sets [SBM] to activate the Smart Battery
Management to charge the batteries.
Sets [Constant] to use trickle charge method to
charge the batteries.
[Disable] [Enable]
Sets [Disable] or [Enable] to constantly monitor the
charger function.
[Disable] [Enable]
Sets [Disable] or [Enable] the auto checking of Input
wiring fault.
[Disable] [Enable]
When [Enable] is set the Power ON/OFF Button is
locked and will not function to prevent accidental
UPS power ON/OFF operation.
*When connected with power cord (OPTIONAL L6-30P), the UPS will be derated.
**Enhanced feature or functionality added. Earlier production models may not have this.
[30min] [60min] [120min]
When the utility power is restored, the UPS will
restore the output of this NCL outlet bank after the
delay time is met.
The UPS will record the 12 most recent system events in the Event Log.
1. Select “EVENT LOGS” Icons
2. Press the “ENTER” button to enter the “Event Logs”.
EVENT DISPLAYEDDESCRIPTION
xx) - - - - / - - / - - - - : - -
Event Content
EVENT ITEMAVAILABLE SET TI N G S
Clear Event Log
3. Press the “UP” and “DOWN” buttons to scroll through the “Event Logs”. The UPS will record
events listed in the table below. (See the reference screen with No Event.)
4. If you want to clear the present Event logs data, press the “UP” and “DOWN” buttons to scroll to
the “Clear Event Logs” Option then press the “Enter” button.
5. You may be prompted “Activate?” to act the selection, if so press the “ENTER” button to act the
Clear Event Logs function.
6. Press the “ESC” button to return to the Main Menu.
Event date and time followed by event description.
[Ac tivate?]
Clears all the events stored in the LCD Control Panel Event Log.
There are 4 UPS Diagnostic items that can be tested by the user.
1. Select “DIAGNOSTICS” Icons
2. Press the “ENTER” button to enter the “DIAGNOSTICS”.
3. Press the “UP” and “DOWN” buttons to scroll through the “DIAGNOSTICS” items shown in the
table below.
4. You may be prompted “Activate?” to act the selection, if so press the “ENTER” button to act the
test function and the test will start automatically.
5. Press the “ESC” button to return to the Main Menu.
ITEMSAVAI LABLE SETTINGSDESCRIPTION
Bat ter y Tes t *
Ala r m Tes tStarts a manual Alarm test, buzzer will sound for 5 seconds.
DIAGNOSTIC
Indicator Test
Fa n Tes t
*The Battery Test may not perform if the UPS condition did not match the testing condition.
Starts a manual battery test, UPS will operate 10 seconds
on Battery mode to check battery condition.
Starts a manual Indicator test, UPS will change LCD color
display to Yellow/Blue/Green and initialize the screen to
WELCOM page then back to Main Menu.
Starts a manual Fan test, UPS will operate fan with full
speed 5 seconds.
35
Page 42
TROUBLESHOOTING
LCD will use RED or Yellow color to indicate the Fault or warning status and also connect the color
frame with ICON which has the same color and locates on the left zone of the screen.
WAR NING ICONPOSSIBLE CAUSESOLUTION
Battery ModeUPS is operating on battery power.
Your equipment requires more
Load Over
XXX%
power than the setting in the
Power Management Software
(Power Panel® Business) will allow.
Line and neutral wires are reversed. Exchange line and neutral wires.
Wiring Fault*
*Only applicable
in areas where
200-240 V
electrical service
is provisioned
with a Neutral
line.
Missing ground wire.Connect ground wire.
No ground wire.
Save your data and perform a
controlled- shutdown.
Shut off the non-essential
equipment or increase the
level in the Power Management
Software.
Check whether voltage or
frequency of utility power is out
of range.
Remove battery connector and
check charger voltage.
If batteries have been recently
replaced, then reset the Battery
Replacement Date using
PowerPanel® Business
Edition-Agent software,
RMCARD interface or through
the LCD control panel on
the UPS (See LCD Setting
Configuration).
36
Page 43
TROUBLESHOOTING CONT.
WAR NING ICONPOSSIBLE CAUSESOLUTION
Your equipment requires more
power than the UPS can provide.
Output Overload
Battery Low
BAT DisconnectedMissing battery power.
Battery FailureUPS has failed in Battery Test.
Output ShortOutput short circuit.
If the UPS is in Line Mode then it
will transfer to Bypass Mode; if
the UPS is in Battery Mode it will
shutdown.
UPS is operating on battery power
and will be shutting down soon
due to extremely low battery
voltage.
Shut off non-essential
equipment. If this solves
the overload problem, the
UPS will transfer to normal
operation.
UPS will restart
automatically when
acceptable utility power
returns.
Check battery connector
and battery breaker.
Check battery connector
and battery breaker.
Contact technical support
to replace the battery.
Your attached equipment
may have problems, please
remove them and check
again.
Over Temperature
Bypass Forbidden
EPO OFF
Cold start Lock
Auto restart Lock
N/A
High temperature sensor activates
protection.
Manual Bypass Forbidden when
the LCD screen shows “Generator
On” or “Converter On”.
Missing the EPO connection.Check the EPO connection.
UPS is locked to prevent
consuming battery power during
shipping.
“Automatic Restore” is disabled
in Power Management Software
(PowerPanel® Business)
Check the fan for operation
and if the ventilation hole
has been covered.
Slide the Interlock Bracket
to the right. (For the
Maintenance Bypass
Module only)
Connect UPS to utility
power for first-time
operation.
Press “ON/OFF” button
to turn on UPS or let the
UPS auto restart by setting
“Automatic Restore”
to Enable via Power
Management Software
(PowerPanel® Business). Or
RMCARD.
To store your UPS for an extended period of time, cover and store it with the battery fully charged.
Recharge the battery every three months to ensure battery life.
Battery Replacement
Please read and follow the Safety Instructions before servicing the battery. Battery replacement
should be performed by trained personnel who are familiar with the procedures and safety
precautions. Make a note of the Replacement Battery part number.
Safety Precautions
Warning: High voltage – Risk of Electric Shock
Only use replacement batteries that are certified by Cyber Power Systems. Use of incorrect battery
type is an electrical hazard that could lead to explosion, fire, electric shock, or short circuit.
Batteries contain an electrical charge that can cause severe burns. Before servicing batteries, please
remove any conductive materials such as jewelry, chains, wrist watches, and rings.
Do not open or mutilate the batteries. Electrolyte fluid is harmful to the skin/eyes and may be toxic.
To avoid electric shock, turn off and unplug the UPS from the wall receptacle before servicing the
battery.
Only use tools with insulated handles. Do not lay tools or metal parts on top of the UPS or battery
terminals.
Replacement Batteries
Please refer to the front side of the EBM for the model number of the correct replacement batteries.
For battery procurement, go to www.CyberPowerSystems.com, or contact your local dealer.
When the Replace Battery the LCD displays Service Battery, use PowerPanel® Business Edition
Agent software or log on to the RMCARD to perform a runtime calibration to verify battery
capacity is sufficient and acceptable.
Battery Disposal
Do Not Discard
Batteries are considered hazardous waste and must be disposed of properly. Contact your local
government for more information about proper disposal and recycling of batteries. Do not dispose
of batteries in fire.
Step 5: Pull the battery trays out slowly and then put the new battery trays into the compartment.
Step 6 : Assemble the battery retention bracket and tighten the thumbscrew.
Step 7: Connect the internal battery connector and battery management module connector. Ensure
that they are seated properly (connector will click into place).
Step 8: Tighten the screw on the battery access door and install the front panel.
Step 9: Execute a battery test via the LCD control panel. To do this go to the Main Menu and select
the Diagnostics Icon, then select Battery Test and Activate. After Battery test, go back to the Main
Menu then select the Set UP icon, then select Batt Install Date to set the battery installation date.
This operation can also be done via PowerPanel® Business Edition Agent or the RMCARD web
interface. Please see their respective User Manuals for detailed instructions.
If batteries have been recently
replaced, then reset the Battery
Replacement Date using
PowerPanel® Business Edition Agent
software, RMCARD web interface
or through the LCD control panel
on the UPS (See LCD Configuration
Settings).
Disable Wiring Fault alarm on LCD
control panel.
44
Page 51
TROUBLESHOOTING CONT.
PROBLEMPOSSIBLE CAUSESOLUTION
WAR NING
Line Abnormal
Output ShortOutput short circuit.
Over Temperature
Cold start Lock
Auto restart Lock
Bypass Forbidden
FAULT
Over ChargeBattery is overcharged.
Charger FailureCharger has failed.
Utility power is out of range for the
UPS to auto-restart.
High temperature sensor activated
protection.
UPS is locked to prevent consuming
battery power during shipping.
“Automatic Restore” is disabled
in Power Management Software
(PowerPanel® Business Edition)
Manual Bypass Forbidden when the
LCD screen shows “Generator On”
or “Converter On”.
Check whether voltage or frequency of
input power is out of range.
The connected equipment may have
problems, please remove them and
check again.
Check the fan for operation and verify
that ventilation is not obstructed.
Connect UPS to utility power for firsttime operation.
Press “ON/OFF“ button to turn UPS on.
Slide the Interlock Bracket to the
right. (Only for UPS models with a
Maintenance Bypass Module)
Remove battery connector and check
charger voltage.
Contact CyberPower for assistance.
High O/P VOutput voltage is too high.
Shut down UPS and turn off input
Low O/P VOutput voltage is too low.
Bus Fault
Internal DC bus voltage is too high
or too low.
breaker.
Contact CyberPower for assistance.
PRODUCT REGISTRATION
CyberPower requests that you complete and return the Warranty Registration Card enclosed with
the Product or register the Product at its website (www.cyberpowersystems.com/registration) to
establish that you are the Initial Customer of the Product, and therefore entitled coverage under
the Limited Warranty and the Connected Equipment Guarantee. (Registration is not required for
coverage, but note: if you do not register your purchase, you will be required to provide proof of
purchase.)
LIMITED WARRANTY AND CONNECTED
EQUIPMENT GUARANTEE
Read the following terms and conditions carefully before using the CyberPower OL5KRTHD /
OL6KRTHD. By using the Product you consent to be bound by and become a party to the terms
and conditions of this Limited Warranty and Connected Equipment Guarantee (together referred
to as this “Warranty”). If you do not agree to the terms and conditions of this Warranty, you should
return the Product for a full refund prior to using it.
Who is Providing this Warranty?
CyberPower Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
What Does This Warranty Cover?
This warranty covers defects in materials and workmanship in the Product under normal use and
conditions. It also covers equipment that was connected to the Product and damaged because of
the failure of the Product.
What is the Period of Coverage?
This warranty covers the Product for three years and connected equipment for as long as you own
the Product.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the
Product.
How Do You Get Warranty Service?
1. Before contacting CyberPower, identify Your Product model number, the Purchase Date, and
each item of Connected Equipment.
2. Email us at tech@cpsww.com or Call us at (877) 297-6937.
3. If your product requires warranty service you must provide a copy of your dated purchase
receipt or invoice.
LIMITED WARRANTY AND CONNECTED
EQUIPMENT GUARANTEE CONT.
How Do You Open A Connected Equipment Claim?
1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave.
E., STE 400, Shakopee, MN 55379, or send us an e-mail message to claims@cpsww.com for
instructions, within 10 days of the occurrence.
2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of
Connected Equipment. Have information on all applicable insurance or other resources of
recovery/payment that are available to the Initial Customer and Request a Claim Number.
3. You must provide a dated purchase receipt (or other proof of the original purchase) for the Cyber
Power unit and connected equipment. You also need to provide a description of the damage to
your connected equipment.
4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment,
a repair cost estimate for the damage to the Connected Equipment, and all claim forms that
CyberPower provides to you. Show the Claim Number on the shipping label or include it with the
product. You must prepay all shipping costs, you are responsible for packaging and shipment,
and you must pay the cost of the repair estimate.
How Long Do I Have To Make A Claim?
All claims must be made within ten days of the occurrence.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product.
If the Product is defective in material or workmanship, CyberPower will repair or replace it at
CyberPower's expense, or, if CyberPower is unable to or decides not to repair or replace the Product
(if defective) within a reasonable time, CyberPower will refund to you the full purchase price you
paid for the Product (purchase receipt showing price paid is required).
If it appears that our Product failed to protect any equipment plugged into it, we will also send you
forms for making your claim for the connected equipment. We will repair or replace the equipment
that was damaged because of the failure of our Product or pay you the fair market value (NOT
REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue
Book, or another a third- party valuation guide, or eBay, craigslist, or other source to establish that
amount. Our maximum liability is limited to $300,000 for OL5KRTHD / OL6KRTHD.
Who Pays For Shipping?
We pay when we send items to you; you pay when you send items to us.
LIMITED WARRANTY AND CONNECTED
EQUIPMENT GUARANTEE CONT.
What Are Some Examples Of What This Warranty Does Not Cover?
1. This Warranty does not cover any software that was damaged or needs to be replaced due to
the failure of the Product or any data that is lost as a result of the failure or the restoration of
data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside
environmental limits of the Product or the equipment connected to it, nor for damage while in
transit or in storage, nor if there has been improper operation or maintenance, or use with items
not designed or intended for use with the Product, such as laser printers, appliances, aquariums,
medical or life support devices, etc.
What Other Limitations Apply?
The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.
1. This Warranty does not apply unless the Product and the equipment that was connected to it
were connected to properly wired and grounded outlets (including compliance with electrical
and safety codes of the most current electrical code), without the use of any adapters or other
connectors.
2. The Product must have been plugged directly into the power source and the equipment
connected to the Product must be directly connected to the Product and not “daisy-chained”
together in serial fashion with any extension cords, another Product or device similar to the
Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty.
3. The Product and equipment connected to it must have been used properly in a suitable and
proper environment and in conformance with any license, instruction manual, or warnings
provided with the Product and the equipment connected to it.
4. The Product must have been used at all times within the limitations on the Product’s VA
capacity.
The Product was designed to eliminate disrupting and damaging effects of momentary (less than
1ms) voltage spikes or impulses from lightning or other power transients. If it can be shown that
a voltage spike lasting longer than 1ms has occurred, the occurrence will be deemed outside the
rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or
Undertake Any Liability in Any Event for Any of the Following:
1. Loss of or damage to data, records, or software or the restoration of data or records, or the
LIMITED WARRANTY AND CONNECTED
EQUIPMENT GUARANTEE CONT.
What Other Limitations Apply? Cont.
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly
installed, grounded and code-compliant 120 volt power lines in the United States and Canada;
transients, surges or spikes on standard telephone land lines, PBX telephone equipment lines
or Base 10T Ethernetlines, when properly installed and connected. (This exclusion applies,
for example, to fluctuations in data transmission or reception, by CATV or RF transmission or
fluctuations, or by transients in such transmission.)
3. Damage from any circumstance described as excluded above with respect to the Product.
4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse,
misuse or alteration of either the product or the Connected Equipment.
5. CyberPower excludes any liability for personal injury under the Limited Warranty and
Connected Equipment Guarantee. CyberPower excludes any liability for direct, indirect, special,
incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR
(AND ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty
benefits regarding "Connected Equipment" under this Warranty], loss of profits, business
interruption, or loss of information or data. NOTE: Some States or Provinces do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation may not
apply to you.
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed
or intended for use in hazardous environments requiring fail-safe performance, or for use in any
circumstance in which the failure of the Product could lead directly to death, personal injury,
or severe physical or property damage, or that would affect operation or safety of any medical
or life support device (collectively, "High Risk Activities"). CyberPower expressly disclaims any
express or implied warranty of fitness for High Risk Activities or with aquariums. CyberPower
does not authorize use of any Product in any High Risk Activities or with Aquariums. ANY SUCH
USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT.
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International Sale of Goods is
expressly excluded.
CyberPower is the warrantor under this Limited Warranty.
For further information please feel free to contact CyberPower at
Cyber Power Systems (USA), Inc. | 4241 12th Ave E., STE 400, Shakopee, MN 55379
(877) 297-6937 | claims@cpsww.com
This device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference that may cause undesired operation.
WARNING!! This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense. Shielded signal cables must
be used with this product to ensure compliance with the Class A FCC limits.
The Class A digital apparatus meets all requirements of the Canadian Interference-Causing
Equipment Regulation.
Cet appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel
brouilleur du Canada.
This document is believed to be accurate, but CyberPower reserves the right to change or correct
the contents and does not assume any responsibility for omissions or errors.
Need Additional Help?
See Operation and Installation Manual provided and also available to download at
www.CyberPowerSystems.com Still Need Help? Please contact our Tech Support department with
installation, troubleshooting, or general product questions.
CyberPower Technical Support
Phone: 1-877-297- 6937
Email: tech@cpsww.com
Web: www.CyberPowerSystems.com
Address: 4241 12th Avenue E., Suite 400, Shakopee, MN 55379, USA
Cyber Power Systems, Inc. | www.CyberPowerSystems.com
For USA and Canada | 4241 12th Ave East, Suite 400, Shakopee, MN 55379 | Toll-free: 877.297.6937
For all other regions | Please visit our website for local contact information.