Cyber Power OL5KRTHD, OL6KRTHD Installation Manual

SMART APP ONLINE UPS SYSTEM
INSTALLATION AND OPERATION MANUAL
OL5KRTHD/OL6KRTHD
SAVE THESE INSTRUCTIONS
Please read this manual and follow the instructions for installation and operation.
©2020 Cyber Power Systems, Inc. All rights reserved. K01-0000759- 02
SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
The Smart App Online 5-6kVA UPS models that are covered in this manual are intended for installation in an environment within 32°F to 104°F (0°C to 40°C), free of conductive contaminants.
SPECIAL SYMBOLS
Warning: High voltage – Risk of Electric Shock
Caution - Important Instructions: Must always be followed.
Do Not Discard: The UPS or UPS batteries in trash. The batteries
contain lead acid. For more information, contact your local recycling or hazardous waste facility.
Information, advice, help
See applicable user manual
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
SAFETY INSTRUCTIONS CONT.
PERSONAL SAFETY
CAUTION
To reduce the risk of fire, connect the UPS to a branch circuit with 50 amperes (5,000/6,000 VA) maximum over-current protection in accordance with the National Electric Code, ANSI/NFPA 70.
The AC electrical service where the UPS is connected should be close to the unit and easily accessible.
Please use only UL-marked mains cable, (e.g. the mains cable of your equipment), to connect the UPS to the AC outlet.
Please use only UL-marked power cables to connect any equipment to the UPS.
When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected equipment does not exceed 3.5mA.
Do not unplug the unit from AC power during operation, as this will disconnect the protective ground insulation.
Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards.
Make sure everything is turned off and disconnected completely before conducting any maintenance, repairs or shipment.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
FOR PERMANENTLY CONNECTED EQUIPMENT, A READILY ACCESSIBLE DISCONNECT DEVICE SHALL BE INCORPORATED IN THE BUILDING INSTALLATION WIRING.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
III
SAFETY INSTRUCTIONS
PERSONAL SAFETY CONT.
RISK OF ELECTRIC SHOCK
A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit.
(No User Serviceable Parts): Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
To avoid electric shock, turn off and unplug the unit before installing the input/ output power cord with a ground wire. Connect the ground wire prior to connecting the line wires!
Connect the Protection Earth (PE) safety conductor before any other cables are connected.
(Fuses): To reduce the risk of fire, replace only with the same type and rating of fuse.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
IV
SAFETY INSTRUCTIONS CONT.
PRODUCT SAFETY
RISK OF ELECTRIC SHOCK
The battery can power hazardous components inside the unit, even when the AC input power is disconnected.
The UPS should be placed near the connected equipment and easily accessible.
(Non-Isolated Battery Supply): Risk of electric shock, battery circuit is not isolated from AC power source; hazardous voltage may exist between battery terminals and ground. Test before touching.
All UPS models covered in this document are permanently-connected equipment and only qualified maintenance personnel may carry out installations.
Wiring must be done by qualified personnel.
BATTE RY
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances should this unit be used for medical applications involving life support equipment and/ or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause equipment to short out.
The unit has a dangerous amount of voltage. When the UPS indicators is on, the units may continue to supply power thus the unit’s outlets may have a dangerous amount of voltage even when it’s not plugged in to the wall outlet.
Do not dispose of batteries in fire as the battery may explode.
Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
V
TABLE OF CONTENTS
SAFETY INSTRUCTIONS .............................................................................................................................. II
Special Symbols ..................................................................................................................................................................... II
Personal Safety ...................................................................................................................................................................... III
Product Safety ........................................................................................................................................................................V
INTRODUCTION ..............................................................................................................................................1
Smart App Online UPS Systems .......................................................................................................................................1
UPS Extended Battery Modules .......................................................................................................................................1
Step-Down Transformer .......................................................................................................................................................1
Unpacking Procedures ........................................................................................................................................................ 2
Whats In The Box ................................................................................................................................................................... 3
OVERVIEW ..................................................................................................................................................... 4
Power Module .......................................................................................................................................................................... 4
INSTALLING YOUR UPS SYSTEM ................................................................................................................ 6
System Block Diagram ......................................................................................................................................................... 6
Hardware Installation Guide .............................................................................................................................................. 6
HARDWARE INSTALLATION ....................................................................................................................... 8
Rackmount Installation For 4-Post Rack ..................................................................................................................... 8
Rackmount Installation For 2-Post Rack .................................................................................................................... 1 0
Vertical/Tower Installation ...............................................................................................................................................1 1
ELECTRICAL INSTALLATION ....................................................................................................................12
Connecting Internal Battery ............................................................................................................................................12
Input/Output Configuration ............................................................................................................................................ 13
UPS SYSTEM STARTUP ............................................................................................................................... 16
USING THE UPS SYSTEM ............................................................................................................................ 17
LCD Module. .......................................................................................................................................................................... 17
LCD Menu Tree ......................................................................................................................................................................21
MAINTENANCE ............................................................................................................................................ 39
Battery Replacement .........................................................................................................................................................39
TECHNICAL SPECIFICATIONS. ................................................................................................................ 42
TROUBLESHOOTING ..................................................................................................................................44
PRODUCT REGISTRATION .........................................................................................................................45
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE ................................................46
CONFORMANCE APPROVAL ..................................................................................................................... 50
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
VI
INTRODUCTION
CyberPower Smart App Online rack/tower UPS systems, with double-conversion topology, provide sine wave output to mission-critical applications and equipment requiring seamless power correction. These units offer generator compatibility and deliver clean AC power with zero transfer time.
They offer Smart Battery Management (SBM), which helps extend overall battery life, and Fast Charge Technology, which helps keep charge times to less than four hours, regardless of the number of Extended Battery Modules (EBMs). Features include energy-saving GreenPower UPS™ ECO Mode technology, and PowerPanel® Business Edition software for monitoring and managing the UPS. Smart App Online 5-6kVA UPS systems come with a three-year warranty and a $300,000 Connected Equipment Guarantee.
UPS EXTENDED BATTERY MODULES
Extended Battery Modules (EBMs) from CyberPower (BP144VL2U01) increase battery runtimes during power outages. Each rack/tower convertible EBM uses 2U of rack space, depending upon the model, and can be installed in a tower form factor to match the UPS installation. The DC plug-and­play power connectors allow to daisy- chain additional EBMs to a UPS system. EBMs compatible with Smart App Online UPS systems also have a built-in battery charger, providing Fast Charge Technology to quickly restore the backup power supply. Every CyberPower EBM has a three-year warranty.
STEP-DOWN TRANSFORMER
CyberPower Step-Down and Isolation Transformers support hardwire installations (OL6KSTF) and are designed for a variety of CyberPower UPS systems. When connected to the UPS, the step-down transformer converts voltage from 200-240V down to 100-120V.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
1
INTRODUCTION CONT.
UNPACKING PROCEDURES
Information, advice, help
The UPS system is very heavy, please handle with care. Wear safety shoes and use a hydraulic equipment lift if one is available. At least two people are required for all handling operations, including unpacking, lifting, and installation in a rack system. Do not use the lifting straps to carry the unit around; they are provided to manually unpack the unit only.
USE LIFTING STRAPS TO REMOVE THE UNIT FROM THE BOX.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
2
INTRODUCTION CONT.
WHATS IN THE BOX
1 2 3 4 5
7 8 9
14 1715 1816 19
ITEM CONTENT QTY
1 UPS
Input terminal block cover & NEMA
2
L6-30P power cord
3 Rackmount left rail
10 11 12
ITEM CONTENT QTY
1
1
1
20
PowerPanel Management Software
12
Download Card
13 Rackmount ears
14 Flat head screws M5X7L
6
13
21 22
1
2
8
4 Rackmount right rail
5 Left hanging bracket
6 Right hanging bracket
7 Serial Interface Cable (RS-232)
8 USB communication cable
9 Quick Start Guide
10 Installation and Operation Manual
11 Registration warranty card
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
1
1
1
1
1
1
1
1
15 Pan head screws M5X12L
16 Pan head screws M5X6L
17 Plastic washers
18 Screw hole dust covers
19 Rubber pads
20 Stand
21 Input bottom cover
22 Screwdriver
12
6
8
18
12
2
1
1
3
OVERVIEW
POWER MODULE
2
ENTER ESC
1
3
Front: OL5KRTHD / OL6KRTHD
1. Power Button / Power on Indicator
Master ON/OFF switch for the UPS. Indicates that the UPS is on and supplying power.
2. UPS Status / Multifunction LCD Readout
Shows UPS status, information, settings and events.
3. Function Buttons
Scroll DOWN scroll UP, ENTER, and ESCAPE.
4 768 11
CRITICAL
LOAD
4
BATTERY INPUT : 144V
NONCRITICAL
3
L6-30
BM / ENV
LOAD
2 1
OUTPUT BREAKER
20A/250V~
L6-20L6-20L6-30
RS232
USBEPO
5 9 1210
Back: OL5KRTHD / OL6KRTHD
4. Battery Backup & Surge Protected Outlets
Provides battery backup and surge protection. They ensure power is provided to connected equipment over a period of time during a power failure.
Critical / Noncritical Load Allows the creation of load priorities to ensure that battery power reserves are transferred to specified outlets during a power outage. The unit can be programmed to provide additional runtime for equipment connected to the “CRITICAL” outlets, while stopping the power supply to equipment connected to “NONCRITICAL” outlets after a designated period of time.
5. Extended Runtime Battery Module Connector
Connection for additional CyberPower External Battery modules.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
4
OVERVIEW CONT.
POWER MODULE CONT.
6. BM/ENV Port
The port supports External Battery Modules detection.
7. Output Circuit Breaker
Provides output current overload and fault protection.
8. Serial Port
Serial port provides RS-232 communication between the UPS and a computer. The UPS can trigger a computer with PowerPanel® Business Edition software installed to shut down during a power outage through the connection while the computer can monitor the UPS and change its various programmable settings.
9. EPO (Emergency Power Off) Connector
Enables an emergency UPS power-off from a remote location.
10. USB Port
USB port provides communication between the UPS and a computer. The UPS can trigger a computer with PowerPanel® Business Edition software installed to shut down during a power outage through the connection while the computer can monitor the UPS and change its various programmable settings.
11. Expansion Slot
A network remote management card is pre-installed in the expansion slot.
12. Input Terminal Block
Connect to utility power.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
5
INSTALLING YOUR UPS SYSTEM
SYSTEM BLOCK DIAGRAM
Bypass
Input Output
Line Mode Battery Mode Bypass Mode Control Signal
Input Filter
Charger
AC/DC
PFC
AC/DC
Battery
BUS
Inverter
DC/AC
Control
&
Monitoring
INV RLY
LCD
Module
USB&DB9
SNMP
Slot
Output
Filter
HARDWARE INSTALLATION GUIDE
1. Battery charge loss may occur during shipping and storage. Before using the UPS, it’s strongly recommended to charge batteries for four hours to ensure the batteries’ maximum charge capacity. To recharge the batteries, simply connect the UPS to its designated AC electrical service.
2. When using PowerPanel® Business Edition software, connect either the serial or the USB cable between the computer and the corresponding port on the UPS. Note: If the USB port is used, the serial port will be disabled. They cannot be used simultaneously. After connecting to either the USB port or the serial port on the UPS, a computer with PowerPanel® Business Edition Agent software installed can control the operating schedule, battery test, outlets, as well as obtain UPS status information. However, other computers with PowerPanel® Business Edition Client software can only obtain UPS status information via LAN connection.
3. Connect your computer, monitor, and any externally-powered data storage device (Hard drive, Tape drive, etc.) into the outlets only when the UPS is off and unplugged. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage the unit.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
6
INSTALLING YOUR UPS SYSTEM CONT.
HARDWARE INSTALLATION GUIDE CONT.
4. Press the ON/OFF switch to turn the UPS on. The Power-On indicator LED will turn on when activated. If an overload is detected, an audible alarm will sound and the UPS will continuously emit two beeps per second. For resetting the unit, unplug some equipment from the outlets. Make sure your equipment carries a load current within the unit’s safe range, (refer to the technical specifications).
5. This UPS is equipped with an auto-charge feature. When the UPS is connected to AC electrical service the battery will automatically charge, even when the unit is switched off.
6. To maintain an optimal battery charge, leave the UPS connected to AC electrical service at all times.
7. Before storing the UPS for an extended period of time, turn the unit OFF. Then cover it and store it with the batteries fully charged. Recharge the batteries every three months to ensure good battery capacity and long battery life. Maintaining a good battery charge will help prevent possible damage to the unit from battery leakage.
8. The UPS has one USB port (default) and one serial port that allows connection and communication between the UPS and any attached computer running PowerPanel® Business Edition Agent software. The UPS can control the computer’s shutdown during a power outage through the connection while the computer can monitor the UPS and alter various programmable parameters. Note: Only one communication port can be used at a time. The port not in use will automatically become disabled or the serial port will be disabled if both ports are attached.
9. EPO (Emergency Power Off) Port: EPO ports allow administrators the capability to connect the UPS unit to customer-supplied EPO switches. These installations give operators a single access point to immediately power-off all equipment connected to the UPS during an emergency.
10. To avoid electric shock, turn the unit OFF and disconnect the unit from utility power before hardwiring the UPS (in/out power cord). The in/out power cord MUST be grounded.
11. Please note the internal UPS temperature will increase when fans are not in operation or ventilation is obstructed. When the high temperature sensor activates protection, the UPS generates an alarm and shuts down to avoid unexpected equipment damage. When the over temperature occurs, please check the Troubleshooting section. If the condition persists, please contact CyberPower for technical support.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
7
HARDWARE INSTALLATION
CyberPower UPS systems can be installed in a rackmount or vertical/tower orientation. This versatility is especially important to growing organizations with changing needs that value having the option to position a UPS on the floor or in a rackmount system. Note that the included rack mounting hardware is only compatible with square hole racks. Please follow the instructions below for the respective mounting methods.
RACKMOUNT INSTALLATION FOR 4-POST RACK
Caution: Important Instructions
To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting brackets.
Step 1: Remove the dust covers
Remove ten dust covers from the screw holes as shown below.
Step 2: Rackmount ear & hanging bracket installation
Attach two rackmount ears to the UPS using eight black M5X7L flat head screws and tighten two hanging brackets using six silver M5X6L pan head screws.
1 2
Step 3: Rackmount rail Installation
The mounting depth of the included rackmount rails can adjust from 20.5 in to 36 in (52 cm to 91.5 cm). Select the proper holes in the rack for positioning the UPS in the rack. The UPS takes up 2 rack units: rack hole positions 1 through 6.
Position the guide screws on the back of the rackmount rails into the rear rack square holes to temporarily support the rails in place.
Step 4: Adjust rackmount rails to fit your rack
Adjust the rail depth to match your rack depth. Attach each rackmount rail to your rack with two black M5X12L pan head screws and two plastic washers at the front of the rack (square holes 1 and 4 as shown below). Secure each rail to the rear of the rack with two black M5X12L pan head screws and two plastic washers.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
8
HARDWARE INSTALLATION CONT.
position 2
position 5
RACKMOUNT INSTALLATION FOR 4-POST RACK CONT.
Rack mount ear
Rack mount rail
43
��
6
��
5 4
3
��
2 1
position 4
position 1
5
position 4
position 1
Step 5: Place and secure the UPS on the rails
Slide the hanging brackets on the UPS on to the rails mounted in the rack with the front of the unit facing toward you. Secure the UPS to your rack with four black M5X12L pan head screws at the front of the rack (square holes 2 and 5 as shown above).
NOTE: To slide the UPS out from the rack
The UPS will be secured by a safety locking mechanism midway of pulling it out of the rack. Use both hands to hold the UPS and press the safety locking tab to pull the UPS out.
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
9
HARDWARE INSTALLATION CONT.
position 5
position 2
RACKMOUNT INSTALLATION FOR 2-POST RACK
CAUTION! Due to the weight of this unit, it is strongly recommended to install it at the bottom of the rack.
CAUTION! Prior to installing the unit, remove internal batteries to reduce the weight of the unit. Refer to the battery replacement section in this user manual for instructions.
CAUTION! It is strongly recommend having 2-3 people assist during the installation process.
CAUTION! It is strongly recommended that the 2 post rack be bolted to the floor prior to
the installation of the UPS
.
Step 1: Remove side dust covers
Remove seven dust covers from screw holes as shown below.
Step 2: Rackmount ears installation Attach the included rackmount ears to the center holes on the sides of the UPS using eight black M5X7L screws as shown below.
Step 3: Secure the UPS to the rack
Secure the UPS to your rack with four black M5X12L screws at the front of the rack (square holes 2 and 5 as shown below).
321
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
10
HARDWARE INSTALLATION CONT.
VERTICAL/TOWER INSTALLATION
Step 1: Adhere rubber pads
Adhere twelve circular rubber pads to the stands and to the left hand side of the UPS as shown below. This will become the bottom of the UPS. Insert the dust covers into the open screw holes on bottom.
Step 2: Attach the base stands and attach the dust covers
Stand the UPS system on its side and attach the tower stands using four silver M5X6L pan head screws onto the bottom of the UPS as shown below. Insert the dust covers into the open screw holes on top.
1 2
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
11
ELECTRICAL INSTALLATION
CONNECTING INTERNAL BATTERY
1. Unscrew and open the battery access door. This screw is designed to be fixed on the door, do not remove it from the metal cover.
2. Connect the internal battery connector. Ensure it is seated properly (connector will click into place).
3. Tighten the screw on the battery access door and install the front panel.
1
2 3
©2020 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
12