CyberPower OL1-10KVA UPS, OL1000TEXL, OL1000EXL-M, OL2000TEXL, OL2000EXL-M User Manual

...
PARAGON SERIES
USER MANUAL
OL1-10KVA UPS
Contents
1. Safety and EMC Instructions.........................................................................................1
1.1 Installation....................................................................................................................1
1.2 Operation......................................................................................................................2
1.3 Maintenance, Servicing and Faults.............................................................................2
1.4 Transport......................................................................................................................2
1.5 Storage..........................................................................................................................3
1.6 Standars........................................................................................................................4
2. Description of Commonly Used Notations..................................................................5
3. Introduction -OL1000TEXL/OL1000EXL-M/OL2000TEXL/OL2000EXL-M/
OL3000TEXL/OL3000EXL-M......................................................................................6
4. System Description........................................................................................................7
5. Connection and Operation for OL1000TEXL/OL1000EXL-M/OL2000TEXL
/OL2000EXL-M/ OL3000TEXL/OL3000EXL-M...........................................................9
6. Trouble Shooting..........................................................................................................13
7. Maintenance.................................................................................................................14
7.1 Operation....................................................................................................................14
7.2 Storage........................................................................................................................14
8. Technical data..............................................................................................................15
8.1 Electrical Specifications............................................................................................15
8.2 Operating Environment.............................................................................................15
8.3 Typical Battery Back-up Time...................................................................................15
8.4 Dimensions and Weights...........................................................................................16
9. Product Specification and Performance-
OL6000TEXL/OL6000EXL-M/OL10000TEXL/OL10000EXL-M................................17
9.1 Gerenal Specification.................................................................................................17
9.2 Electrical Performance..............................................................................................17
9.2 Operating Environment.............................................................................................18
10. Installation..................................................................................................................19
10.1 Unpacking and Inspection.......................................................................................19
10.2 Input and Output Power Cords and Protective Earth Ground Installation..........19
10.3 Operating Procedure for Connecting the Extended Backup Time Model UPS
with the External Battery.........................................................................................21
10.4 Parallel Operation.....................................................................................................23
11. Operation and Maintenance......................................................................................29
12. Battery Maintenance..................................................................................................29
13. Notes for Battery Disposal and Battery Replacement ...........................................30
14. Trouble Shooting........................................................................................................31
15. Operating Mode for all Models..................................................................................33
16. Communication Port..................................................................................................36
17. Software for All Models.............................................................................................37
Appendix 1Display Panelfor OL6000TEXL/OL6000EXL-M/
OL10000TEXL/OL10000EXL-M............................................................................38
Appendix 2The Corresponding Form of The LED Display for OL6000TEXL/
OL6000EXL-M/OL10000TEXL/OL10000EXL-M.......................................................39
Appendix 3Back Panel.................................................................................................41
-1-
1. Safety and EMC instructions
1.1 Installation
Condensation may occur if the UPS is moved directly from a cold to a
warm environment. The UPS must be absolutely dry before being installed. Please allow an acclimatization time of at least two hours.
Do not install the UPS near water or in damp environment. Do not install the UPS where it would be exposed to direct sunlight or
near heat.
Do not block ventilation openings in the UPSs housing. Do not connect appliances or items of equipment which would
overload the UPS (e.g. laser printers, etc) to the UPS outlet sockets.
Place cables in such a way that no one can step on or trip over them.
1.1.1 Installation for OL1000TEXL/OL1000EXL-M/OL2000TEXL/ OL2000EXL-M/OL3000TEXL/OL3000EXL-M
Socket-outlets and socket of batteries are earthed by the input
power cord, please insert the power cord into mains socket before using of UPS.
Connect the UPS only to an earthed shockproof socket outlet. The building wiring socket outlet (shockproof socket outlet) must be
easily accessible to close to the UPS.
This is operator installable.
1.1.2 Installation for OL6000TEXL/OL6000EXL-M/OL10000TEXL/
OL10000EXL-M
UPS has provided earthed terminal, in the final installed system
configuration, equipotential earth bonding to the external UPS battery cabinets.
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
-2-
An integral single emergency switching device which prevents
further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation.
An appropriate disconnect device as short-circuit backup protection
should be provided in the building wiring installation.
For three-phase equipment connection to an IT power system, a
four-pole device which disconnect all phase conductors and the neutral conductor should be provided in the building wiring installation.
This is permanently connected equipment , it must be installed by
qualified maintenance personnel.
Earth connection essential before connecting to the building wiring
terminal.
1.2 Operation
Do not disconnect the mains cable on the UPS or the building wiring
socket (grounded shockproof socket) during operation as this would remove the ground to the UPS and of all connected loads.
The UPS output socket or output terminal block may be electrically
lived even if the UPS system is not connected to the building wiring terminal.
In order to fully disconnect the UPS, first press the Standby button, then
disconnect the mains lead.
Ensure that no liquid or other foreign objects can enter the UPS. The UPS can be operated by any individuals with no previous
experience.
1.3 Maintenance, servicing and faults
The UPS operates with hazardous voltages. Repairs may be carried
out only by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from
the mains power supply (building wiring socket), components inside
-3-
the UPS are still connected to the battery which are potentially dangerous.
Before carrying out any kind of service and/or maintenance,
disconnect the batteries. Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals.
Batteries must be replaced only by qualified personnel. Caution - risk of electric shock. The battery circuit is not isolated from
the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Verify that no voltage is present before servicing!
Batteries have a high short-circuit current and pose a risk of shock
Take all precautionary measures specified below and any other measures necessary when working with batteries:
remove all jewellery, wristwatches, rings and other metal objects use only tools with insulated grips and handles.
When changing batteries, replace with the same quantity and the same
type of batteries.
Do not attempt to dispose of batteries by burning them. It could cause
explosion.
Do not open or destroy batteries. effluent electrolyte can cause injury
to the skin and eyes. It may be toxic.
Please replace the fuse only by a fuse of the same type and of the
same amperage in order to avoid fire hazards.
Do not dismantle the UPS, except the qualified maintenance
personnel.
1.4 Transport
Please transport the UPS only in the original packaging (to protect
against shock and impact).
1.5 Storage
The UPS must be stockpiled in the room where it is ventilated and dry.
-4-
1.6 Standards
For OL1000TEXL/OL1000EXL-M/OL2000TEXL/OL2000EXL-M/ OL3000TEXL/OL3000EXL-M
* Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission...........................:IEC/EN 62040-2 Category C1
Radiated Emission..............................:IEC/EN 62040-2 Category C1
Harmonic Current................................:IEC/EN 61000-3-2
Voltage Fluctuation and Flicker............:IEC/EN 61000-3-3
*EMS
ESD.................................................:IEC/EN 61000-4-2 Level 4
RS...................................................:IEC/EN 61000-4-3 Level 3
EFT..................................................:IEC/EN 61000-4-4 Level 4
SURGE............................................:IEC/EN 61000-4-5 Level 4
Low Frequency Signals...................:IEC/EN 61000-2-2
For OL6000TEXL/OL6000EXL-M/OL10000TEXL/OL10000EXL-M * Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission...........................:IEC/EN 62040-2 Category C3
Radiated Emission..............................:IEC/EN 62040-2 Category C3
*EMS
ESD.................................................:IEC/EN 61000-4-2 Level 4
RS...................................................:IEC/EN 61000-4-3 Level 3
EFT..................................................:IEC/EN 61000-4-4 Level 4
SURGE............................................:IEC/EN 61000-4-5 Level 4
Low Frequency Signals....................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the second environment-installation restrictions or additional measures may be needed to prevent disturbances.
-5-
2. Description of commonly used notations
Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself with them and understand their meaning.
Symbol and Explanation
Symbol Explanation
Alert! Pay special attention Caution! high voltage
I
Turn on the UPS Turn off the UPS Idle or shut down the UPS Altermating current source(AC) Direct current source(DC) Protective ground Alarm silence Overload indication Battery Recycle Do not dispose with ordinary trash
-6-
3. Introduction – OL1000TEXL/OL1000EXL-M/ OL2000TEXL/OL2000EXL-M/ OL3000TEXL/OL3000EXL-M
The On-Line-Series is an uninterruptible power supply incorporating double convertion technology. It provides failsafe power to the connected equipment.
The double convertion design eliminates all power disturbances. A rectifier converts the alternating current from the socket to direct current. This direct current charges the batteries and powers the inverter. The inverter generates a sinusoidal AC voltage to power the loads.
In the event of power failure, the maintenance-free batteries power the inverter.
This manual covers the UPS units listed below.
Model No. Type Model No. Type
OL1000TEXL OL1000EXL-M OL2000TEXL OL2000EXL-M OL3000TEXL
Standard
OL3000EXL-M
Extended
backup time
-7-
4. System Description
Figure 1: Display Panel
Switch Function
ON - Switch
Turn on UPS system: By pressing the ON-Switch I the UPS system is turned on.
Deactivate audible: By pressing this switch an acoustic alarm can be deactivated.
OFF-Switch
Utility power is normal, the UPS system switches to Standby mode by pressing OFF-Switch “ “. It is then switched to Bypass and the inverter is off. At this time, the output sockets are supplied with voltage via the bypass if the utility power is available.
Display Function
1: FAULT LED
The red fault LED lights up and an acoustic warning signal is issued continuously when the UPS system is in fault condition. Press the Standby switch in order to turn off the warning tone.
12: BYPASS LED
The orange-coloured BYPASS LED lights up when the UPS system is supplying voltage provided by the utility power via the bypass.
-8-
13: BATTERY LED
The green-coloured BATTERY-LED lights up when the utility power has failed and the inverter is being powered by the batteries.
14: UPS ON LED
The green-coloured UPS ON LED lights up if the UPS system is supplying voltage provided by the utility power via the inverter.
15: AC INPUT LED
The green AC INPUT LED lights up if utility voltage is applied to the UPS input.
AC INPUT LED blinks when the phase and neutral conductor have been reversed at the input of the UPS system.
If AC INPUT LED and BATTERY-LED light up, the utility power supply is out of tolerance.
Display Function
LOAD and BATTERY CAPACITY LEDs
2-6 LEDs show the load of the UPS system (+/-5%
Tolerance): LED 2: 0-30% LED 3: 31%-50%
LED 4: 51%-70% LED 5: 71%-95% LED 6: 96%-105%
7-11 LEDs show the load of the batteries (+/-5%
Tolerance): LED 7: 0-25 % LED 8: 26%-50%
LED 9: 51%-75% LED 10: 76%-95% LED 11: 96%-100%
-9-
5. Connection and Operation for OL1000TEXL/
OL1000EXL-M/OL2000TEXL/OL2000EXL-M/ OL3000TEXL/OL3000EXL-M
5.1 Inspection:
Inspect the packaging carton and its contents for damage. Please inform the freight carrier immediately if you find signs of damage.
Please keep the packaging in a safe place for future use.
Note: Please ensure that the incoming feeder is isolated and secured to
prevent it from being switched back on again.
5.2 Connection:
5.2.1 UPS Input Connection
If the UPS is connected via the power cord, please use a proper wired and grounded socket. Pay attention to the capacity of the socket: over 10A for OL1000TEXL, OL1000EXL-M & OL2000TEXL, over 16A for OL2000EXL-M& OL3000TEXL/OL3000EXL-M.
5.2.2 UPS Output Connection
The output of OL1000TEXL, OL1000EXL-M and OL2000TEXL are socket-types only. Simply plug the load power cord to the output sockets to complete connection.
The system must be installed
and wired only by licensed electricians in
accordance with applicable electrical regulations!
When installing the electrical wiring, please note the nominal amperage of your incoming feeder.
-10-
Besides output sockets, the OL2000EXL-M and OL3000TEXL/ OL3000EXL-M units have a terminal block available for output as well. The terminal block can be wired using the following procedure:
1. Remove the terminal block cover.
2. Use AWG14 or 2.1mm2 wires for wiring configuration.
3. Upon completion of the terminal block wiring, check to ensure the wires are securely fastened.
4. Replace the terminal block cover.
Figure 2: Terminal Blcok Connectiondiagram of OL2000EXL-M and OL3000TEXL/ OL3000EXL-M
5.2.3 Computer Connection:
Connect your computer to the sockets of the UPS system following the above diagram.
Model No. Output Socket (pcs) Terminal Block
OL1000TEXL 4 Not Available OL1000EXL-M 4 Not Available OL2000TEXL 6 Not Available OL2000EXL-M 4 Available OL3000TEXL 4 Available OL3000EXL-M 4 Available
Caution!
Do not connect equipment which would overload the UPS system (e.g. laser printers)
-11-
5.3 Charge Battery:
Fully charge the batteries of the UPS system by leaving the UPS system connected to the utility power for 1-2 hours. You may use the UPS system directly without charging it but the battery run time may be shorter than the listed run times.
5.4 Power on the UPS:
5.4.1 Utility power present:
Press Power On” button for more than 1 second to turn on the UPS. The UPS will go into self-test status first. The UPS will go into the inverter mode next. At this time, the AC Input, UPS On, Load Capacity, and Battery Capacity LEDs will light up.
5.4.2 Utility power not present:
Even without the utility power connected to the UPS, the UPS still can be turned on by just simply pressing Power On button for more than 1 second. The UPS will go into self-test status first. The UPS will then go into the inverter mode. At this time, Battery, UPS On, Load Capacity, and Battery Capacity LEDs will light up.
5.5 Test Function:
Test the function of the UPS system by either pressing the Power On button or disconnecting the input of the UPS system from the power supply.
5.6 Power off the UPS:
5.6.1 In Inverter Mode:
Press “ “ button continuously for more than 1 second to turn off the UPS. Then the UPS will enter self-test status. After finishing the self-test, the UPS will enter bypass mode and the AC Input LED and Bypass LED will light up. At this time, the UPS might provide output. Disconnect the utility power to turn off the output.
-12-
5.6.2 In Battery Mode:
Press “ “ button for more than 1 second to turn off the UPS. Then the UPS enter into self-test status. After finishing the self-test, the UPS will be turned off completely.
5.7 Audible Alarm Mute Function:
To disable the alarm in battery mode, you may press Power On button for more than 1 second to clear it. However, the alarm will be automatically restored when the battery is low to indicate shutdown is imminent.
5.8 Operation Procedure of External Battery for extended run times (EXL-M Models)
The units with CE markings
(a) Use the battery pack with the following voltages: 36VDC for
OL1000TEXL(3 pcs of 12V batteries), 96VDC for OL2000TEXL / OL3000TEXL (8 pcs of 12V batteries). Do not connect any other quantities or voltages of batteries.
(b) One end of the external battery cord is a plug for connecting the UPS
and the other end has a plug for connecting the battery cabinet
(c) Do not connect a load to the UPS yet. Connect the power cord of the
UPS to the utility supplied power.
(d) Connect the plug of the external battery cord to the external battery
socket on the rear panel of the UPS to complete the connection and the UPS will automatically charge the battery pack.
The Caution!
The output sockets of the UPS system may still be electrically charged even if the power supply system has been disconnected or the Bypass
switch is in
the OFF position.