Cyber Power OL6000ERT3UP, OL8000ERT3UP, OL8000ERT3UM, OL10000ERT3UM, OL10000ERT3UP User Manual

...
Page 1
User’s Manual
Cyber Power Systems, Inc.
OL6000ERT3UP
OL8000ERT3UP
OL10000ERT3UP
OL6000ERT3UM
OL8000ERT3UM
OL10000ERT3UM
www.cy
berpower.com
Page 2
IMPORTANT SAFETY INSTRUCTIONS
1
This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit.
CAUTION! The battery can power hazardous components inside the unit, even when the AC input power is disconnected.
CAUTION! The UPS should be placed near the connected equipment and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric shock, do not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
CAUTION! (Non-Isolated Battery Supply): Risk of electric shock, battery circuit is not isolated from AC power source; hazardous voltage may exist between battery terminals and ground. Test before touching.
CAUTION! To reduce the risk of fire, connect the UPS to a branch circuit with 40 amperes (OL6000) / 50 amperes (OL8000) / 70 amperes (OL10000) maximum over-current protection in accordance to CE requirement.
CAUTION! The AC outlet where the UPS is connected should be close to the unit and easily accessible.
CAUTION! Please use only VDE-tested, CE-marked mains cable, (e.g. the mains cable of your equipment), to connect the UPS to the AC outlet.
CAUTION! Please use only VDE-tested, CE-marked power cables to connect any equipment to the UPS.
CAUTION! When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected equipment does not exceed 3.5mA.
medical applications involving life support equipment and/or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
CAUTION! Do not dispose of batteries in fire as the battery may explode.
CAUTION! Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes.
CAUTION! A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when working on batteries
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handles.
CAUTION! The unit has a dangerous amount of voltage. When the UPS indicators is on, the units may continue to supply power thus the units outlets may have a dangerous amount of voltage even when its not plugged in to the wall outlet.
CAUTION! Make sure everything is turned off and disconnected completely before conducting any maintenance, repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety conductor before any other cables are connected.
CAUTION! The UPS is a professional equipment with a total rated power larger than 1kW. The equipment complies with IEC61000-3-12 provided that the short-circuit ratio is larger than or equal to 66 at the
interface point between the user’s power supply and the power grid. It is
the responsibility of the installer or user of the equipment to ensure, by consultation with the power supply department if necessary, that the UPS is connected only to a power supply with a short-circuit ratio Rsce larger than or equal to 66.
WARNING! (Fuses): To reduce the risk of fire, replace only with the same type and rating of fuse.
CAUTION! The OL6000 / OL8000 / OL10000 models are permanently-connected equipment and only qualified maintenance personnel may carry out installations.
CAUTION! Do not unplug the unit from AC Power during operation, as this will invalidate the protective ground insulation.
CAUTION! To avoid electric shock, turn off and unplug the unit before installing the input/output power cord with a ground wire. Connect the ground wire prior to connecting the line wires!
CAUTION! Do not use an improper size power cord as it may cause damage to your equipment and cause fire hazards.
CAUTION! Wiring must be done by qualified personnel.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances this unit should be used for
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
Copyright © 2017 Cyber Power Systems, Inc.
Page 3
UNPACKING
2
Power module
Battery module
Rackmount ears (Stands) (2) * 2 sets
PDU or HW PDU with Manual Bypass
User’s manual Register card
Rackmount left rail * 2 sets Rackmount right rail * 2 sets
Left hanging bracket * 2 sets Right hanging bracket * 2 sets
Tie plate (1) * 1 set
Flat head screws: M5X7L (8) * 2 sets
Pan head screws: M5X12L (4) * 2 sets
Pan head screws: M5X6L (14) * 2 sets
Guide screws: M5X10L (2)*2 sets
Plastic washers (8) * 2 sets
Phone line
USB communication cable
Serial Interface Cable (RS-232)
Copyright © 2017 Cyber Power Systems, Inc.
Screw hole dust covers (14) * 2 sets
Power cord
* PowerPanel® Business Edition software is available
on our website. Please visit www.cpsww.com and go to the Software Section for FREE download.
Page 4
HARDWARE INSTALLATION
3
HARDWARE INSTALLATION
These versatile UPS systems can be mounted in a rackmount or vertical tower orientation. This versatility is especially important to growing organizations with changing needs that value having the option to position a UPS on a floor or in a rackmount system. Please follow the
instructions below for the respective mounting methods.
SAFETY PRECAUTIONS
CAUTION! To prevent the risk of fire or electric shock, only use the
supplied hardware to attach the mounting brackets.
RACKMOUNT INSTALLATION
Step 1: Remove the dust covers
Remove the dust covers *10pcs from the screw holes.
Step 3: Rackmount rail Installation
The rails adjust to mount in 48-cm (19-inch) racks from 52 to 91.5cm (20.5 to 36 inches) deep. Select the proper holes in the rack for positioning the UPS in the rack. The UPS takes up 3 rack units, rack holes positions 1 through 9.
Position the guide screws on the rails into the rear rack square holes to temporarily support the rails in place. Tighten the front rail screws on the rack.
Step 2: Rackmount ears & hanging brackets installation
Attach two rackmount ears to the UPS using the provided M5X7L*8pcs screws and tighten two hanging brackets with the M5X6L*6pcs screws.
Copyright © 2017 Cyber Power Systems, Inc.
Page 5
HARDWARE INSTALLATION
4
Step 4: Adjust rackmount rails to fit your rack
Adjust the rail depth to match your rack depth. Attach the rackmount rail to your rack with two screws and two plastic washers at the front of the rack. (Located in position 4 & position 8) Tighten the M5X6L screws on the front bracket. Secure the rail to the rear of the rack with two M5X6L screws and two plastic washers.
How to slide the UPS out from the rack
The UPS will be secured by a safety locking mechanism midway of pulling it out of the rack. Use both hands to hold the UPS and press the safety locking tab to pull the UPS out.
Step 5: Place and secure the UPS on the rails
Slide the hanging brackets on the UPS into the rails mounted in the rack with the front of the unit facing toward you. Secure the UPS to your rack with four M5X12L*4pcs screws at the front of the rack. (Located in position 5 & position 7)
Copyright © 2017 Cyber Power Systems, Inc.
Page 6
HARDWARE INSTALLATION
5
VERTICAL/TOWER INSTALLATION
Step 1: Adhere the rubber feet on the bottom side of base stands Adhere the protective rubber feet on the bottom side of UPS.
Step 3: Rotate the Multifunction LCD Module
Unscrew the upper panel of the UPS. Separate the upper panel from the UPS. Gently lift the LCD module out. Rotate it to the tower orientation. Reinstall it for a tower configuration.
Step 2: Attach the base stands and attach the dust covers
Secure the tie bracket with the screws (M5X7*4pcs). Insert dust covers into the screw holes that are not being used.
ELECTRICAL INSTALLATION
After completing the hardware installation of the UPS, you are now ready to plug in the UPS and connect your equipment.
Copyright © 2017 Cyber Power Systems, Inc.
Page 7
HARDWARE INSTALLATION
6
PDU or HW PDU INSTALLATION
Step 1: Remove the cover from the PDUs Loosen the two screws and remove the cover from the PDUs to expose the connectors.
Step 2: Attach the PDUs to the Power module
Align the connectors of the PDUs with the connectors of the Power module to attach the device and tighten the two screws to fix the cover on the PDU or HW PDU.
Step 3: Screw the PDUs
Secure the PDUs to the Power module with four screws.
Copyright © 2017 Cyber Power Systems, Inc.
ELECTRICAL INSTALLATION
After completing the hardware installation of the UPS, you are now ready to plug in the UPS and connect your equipment.
SAFETY PRECAUTIONS
CAUTION! Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants. Do not install this UPS where excessive moisture or heat is present (Please see specifications for acceptable temperature and humidity range).
CAUTION! Never install a UPS, or associated wiring or equipment, during a lightning storm.
CAUTION! Do not work alone under hazardous conditions.
CAUTION! In case of the risk of electric shock, do not remove the top
cover.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
Page 8
INSTALLING YOUR UPS SYSTEM
7
SYSTEM BLOCK DIAGRAM
Output
Input Filter
PFC
AC/DC
BUS
Inverter
DC/AC
STS
Charger
AC/DC
Internal Bypass
Battery
Output
Filter
Input
Line Mode Battery Mode Bypass Mode
Control
&
Monitoring
LCD Module
USB & DB9
SNMP Slot
Bypass
Switch
Maintenance
Bypass
Maintenance Bypass
HARDWARE INSTALLATION GUIDE
1. Battery charge loss may occur during shipping and storage. Before
using the UPS, it’s strongly recommended to charge batteries for four hours to ensure the batteries maximum charge capacity. To recharge the batteries, simply plug the UPS into an AC outlet.
2. When using the included software, connect either the serial or the
USB cable between the computer and the corresponding port on the UPS. Note: If the USB port is used, the serial port will be disabled. They cannot be used simultaneously. After connecting to either the USB port or the Serial port on the UPS, a computer with the PowerPanel® Business Edition Agent software installed can control the operating schedule, battery test, outlets, as well as obtain UPS status information. However, other computers with PowerPanel® Business Edition Client software can only obtain UPS status information via LAN connection.
3. Connect your computer, monitor, and any externally-powered data
storage device (Hard drive, Tape drive, etc.) into the outlets only when the UPS is off and unplugged. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage the unit.
6. This UPS is equipped with an auto-charge feature. When the UPS is
plugged into an AC outlet, the battery will automatically charge, even when the unit is switched off.
7. To maintain an optimal battery charge, leave the UPS plugged into an
AC outlet at all times.
8. Before storing the UPS for an extended period of time, turn the unit
OFF. Then cover it and store it with the batteries fully charged. Recharge the batteries every three months to ensure good battery capacity and long battery life. Maintaining a good battery charge will help prevent possible damage to the unit from battery leakage.
9. The UPS has one USB port (default) and one Serial port that allows
connection and communication between the UPS and any attached computer running the PowerPanel® Business Edition Agent software. The
UPS can control the computer’s shutdown during a power outage
through the connection while the computer can monitor the UPS and alter various programmable parameters. Note: Only one communication port can be used at a time. The port not in use will automatically become disabled or the serial port will be disabled if both ports are attached.
4. To protect a fax machine, telephone, modem line or network cable,
connect the telephone or network cable from the wall jack outlet to the jack marked “IN” on the UPS and connect a telephone cable or network cable from the jack marked “OUT” on the UPS to the modem, computer, telephone, fax machine, or network device.
5. Press the ON/OFF switch to turn the UPS on. The Power-On indicator
light will display when activated. If an overload is detected, an audible alarm will sound and the UPS will continuously emit two beeps per second. For resetting the unit, unplug some equipment from the outlets. Make sure your equipment carries a load current within the units safe range, (refer to the technical specifications).
10. EPO (Emergency Power Off) Port:
EPO ports allow administrators the capability to connect the UPS unit to customer-supplied EPO switches. These installations give operators a single access point to immediately power-off all equipment connected to the UPS during an emergency.
11. To avoid electric shock, turn the unit OFF and disconnect the unit
from utility power before hardwiring the UPS (in/out power cord). The in/out power cord MUST be grounded.
Copyright © 2017 Cyber Power Systems, Inc.
Page 9
HARDWIRING THE INPUT/ OUTPUT TERMINALS
8
CHECK CIRCUIT BREAKER/WIRING
UPS Capacity
Branch Circuit Breaker
Wiring AWG
Wiring mm
2
6KVA
40A
10 AWG
5.5 mm
2
8KVA
50A
8 AWG
8.0 mm
2
10KVA
70A
6 AWG
14.0 mm
2
PDU/HW
UPS
PFC
AC/DC
Inverter
DC/AC
STS
L N PE
Input
Circuit Breaker
Wiring
AWG
L N PE
External
EPO
Output
Mains
Battery
N
L
PE
N
L
PE
Manual Bypass
Check branch circuit breaker rating and wiring dimensions with the following table.
INPUT/ OUTPUT CONFIGURATION
Hardwire the input/output terminals as shown in the following diagram.
SAFETY PRECAUTIONS
CAUTION! Input and Output circuit breakers must be “OFF” during the building installation. CAUTION! An additional two pole disconnect device is necessary during the building installation. CAUTION! Disconnected EPO will immediately shut down the logic circuit output of the UPS. Wiring the EPO signal is optional.
CAUTION! Local safety rules may require a separate, external EPO to turn off output circuit breakers. Refer to local wiring rules, the EPO should use
approved components.
Step 1: Remove the inspection window cover
Loosen the four screws to remove the inspection window cover.
Step 2: Remove the terminal block cover Loosen the four screws to remove the terminal block cover.
Copyright © 2017 Cyber Power Systems, Inc.
Page 10
HARDWIRING THE INPUT/ OUTPUT TERMINALS
9
Step 3: Input configuration
Insert the input cable through the appropriate cable gland (not included) and connect the three wires to the input terminal block.
Step 5: Fix the terminal block cover on the PDUs
Tighten the four screws to fix the terminal block cover on the PDUs.
Step 6: Fix the inspection window cover on the PDUs
Tighten the four screws to fix the inspection window cover on the PDUs.
Step 4: Output configuration
Insert the output cable through the appropriate cable gland (not included) and connect the three wires to the output terminal block.
Copyright © 2017 Cyber Power Systems, Inc.
Page 11
BACKFEED PROTECTION
10
BACKFEED PROTECTION OPERATION
UPS
L
N
PSDR
AC-L AC-N
IP-L
IP-N
Backfeed
1 2
4 5
3
L
N
I/P
EMI
L N
L N PE
Mains
PE
Jumper2
Jumper1
UPS
L
N
PSDR
AC-L AC-N
IP-L IP-N
Backfeed
1 2 3 4 5
MC
L N
L N
A1
A2
I/P
EMI
L
N
L N
L N PE
Mains
PE
2A Fuse
(Slow Blow)
1. If the Bypass circuit is shorted and the UPS is running in Line Mode or Battery Mode, backfeed protection will be active and the external isolation device (Magnetic Contactor) will open.
2. Save your data and perform a controlled shutdown.
3. Contact CyberPower for repair.
WITHOUT BACKFEED PROTECTION CONFIGURATION
1. Hardwire the input terminals as shown in the following diagram.
2. Do not remove the interconnection wires (Jumper1 / Jumper2) on Backfeed Protection Connector.
WITH BACKFEED PROTECTION CONFIGURATION
1. Customers should provide an external isolation device (Magnetic Contactor) which is upstream and outside the UPS and capable of supporting the UPS
2. Remove the interconnection wires (Jumper1 / Jumper2) on Backfeed Protection Connector.
3. Hardwire the input terminals and Backfeed Protection Connector as shown in the following diagram.
4. The external isolation device must be installed in the Mains path.
input current.
Copyright © 2017 Cyber Power Systems, Inc.
Page 12
BASIC OPERATION
11
POWER MODULE FRONT/REAR PANEL DESCRIPTION
OL6KERT3UPDUPM / OL8KERT3UPDUPM / OL10KERT3UPDUPM
1. Power Button / Power on Indicator
Master ON/OFF for the UPS. Indicates that the UPS is on and supplying power.
2. UPS Status / Fault / Replace Battery LED Indicator
Indicates the status of the UPS whether is operating in Line, Battery or Bypass Mode, or the UPS has an internal fault and the battery need to be replaced.
3. Multifunction LCD Readout
Shows UPS status, information, settings and events.
4. Function Buttons
Scroll up, scroll down, select and cancel LCD menu.
5. USB port
This is a connectivity port which allows communication and control between the UPS and the connected computer. It is recommended to install the PowerPanel® Business Edition Agent software on the PC/Server connected with the USB cord.
6. Serial Port
Serial port provides communication between the UPS and the computer. The UPS can control the computer’s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters.
7. Surge Protected Communication Ports RJ-45/RJ-11 These ports are used to protect standard RJ-45/RJ-11 based products (ADSL, LAN, Phone/ Modem-Lines) and cabling systems from surges.
8. Relay Output Connector Convert UPS signals into real potential-free Dry Contacts for industrial control.
9. SNMP/HTTP Network slot Slot to install the optional SNMP card for remote network control and monitoring.
10. Backfeed Protection Connector Prevents power feedback from the inverter to utility power in case of power failure and a fault in the bypass circuit.
11. EPO (Emergency Power Off) Connector Enables an emergency UPS Power-Off from a remote location.
12. Extended Runtime Battery Module Connector Connection for additional CyberPower XL Battery modules.
13. Input / Output Connectors Use these connectors to attach the PDU or HW PDU to the Power module.
Copyright © 2017 Cyber Power Systems, Inc.
Page 13
BASIC OPERATION
12
PDU / HW PDU FRONT/REAR PANEL DESCRIPTION
OL6KE6UPDU OL8K10KE6UPDU
OL6KE3UPDUHW OL8K10KE3UPDUHW
1. Input Circuit Breaker
Provides input overload and fault protection.
2. Manual Bypass Switch
Provide UPS output to connected equipment when turned to Normal. Provide utility power to connected equipment when turned to Bypass.
3. Input / Output Terminal Block
Connect to utility power / your equipment.
4. Interlock Bracket
Avoid turning the Manual Bypass Switchunder normal operation.
5. Inspection Window
Visual check the wiring condition and secure the terminal.
6. Input / Output Connectors
Use these connectors to attach the PDU or HW PDU to the Power module.
7. Connectors Cover Provides safety protection when removing the PDU or HW PDU.
8. Output Circuit Breaker Provides output overload and fault protection.
9. Battery Backup & Surge Protected Outlets Provides battery backup and surge protection. They ensure power is provided to connected equipment over a period of time during a power failure.
Critical / Noncritical Load Allows the creation of load priorities to ensure that battery power reserves are transferred to specified outlets during a power outage. The unit can be programmed to provide additional runtime for equipment connected to the CRITICAL outlets, while stopping the power supply to equipment connected to NONCRITICAL outlets after a designated period of time.
Copyright © 2017 Cyber Power Systems, Inc.
Page 14
BASIC OPERATION
13
BATTERY MODULE FRONT/REAR PANEL DESCRIPTION
1. On-board Replaceable Fuse Cover
Replaceable fuse is accessible from the rear panel. It must be done by qualified personnel.
2. AC Circuit Breaker
Provides overload and fault protection.
3. AC Output Outlet
Use this outlet to connect to the AC Input Inlet of a downstream Battery module.
4. AC Input Inlet (Charge Only)
AC power connectivity to wall receptacle.
5. Input Connector
Use this input connector to daisy chain the next Battery module. Remove the connector cover for access.
6. Output Cable
Use this output cable to connect the Battery module to the Power module or to the next Battery module.
BPE240V30ART3U / BPE240V50ART3U
CONNECTION #1 : POWER MODULE WITH ONE BATTERY MODULE
Step 1: Loosen the two screws to remove the battery cable
retention bracket of the power module.
Step 2: Use the output cable of the Battery module to connect
the Battery module to the Power module.
Step 3: Rotate the battery cable retention bracket and tighten
the two screws to fix battery cable.
Step 4: Use a power cord to plug AC input inlet of the battery
module into a wall receptacle.
Copyright © 2017 Cyber Power Systems, Inc.
Page 15
BASIC OPERATION
14
CONNECTION #2 : POWER MODULE WITH MULTIPLE BATTERY MODULES
Step 1: Connect the 1st Battery module to the Power module
using the instructions above.
Step 2: Loosen the two screws to remove the battery cable
retention bracket of the 1st battery module.
Step 3: Use the output cable of the 2nd Battery module to
connect the 2nd Battery module to the 1st Battery module.
Step 4: Rotate the battery cable retention bracket and tighten
the two screws to fix battery cable.
Step 5: Use a power cord to plug AC input inlet of the 2nd battery
module into AC output outlet of the 1
st
Battery module.
Copyright © 2017 Cyber Power Systems, Inc.
Page 16
OPERATION INSTRUCTIONS FOR LCD MODULE
15
LED INDICATORS – UPS STATUS
LED Indicators
Color
UPS Status Description
ON/OFF
White
UPS power is on.
ON-LINE
Green
UPS is operating in Line Mode.
BATTERY ON
Yellow
UPS is operating in Battery Mode.
BYPASS
Yellow
UPS is operating in Bypass Mode, Manual Bypass or ECO (Economy) Mode.
FAULT
Red
UPS has an internal fault. See “Trouble Shooting” for additional information.
REPLACE BATTERY
Red
Battery will soon need to be replaced due to insufficient runtime.
LCD Screen
UPS Status Description
Line Mode
UPS is operating in Line Mode.
Battery Mode
UPS is operating in Battery Mode.
Bypass Mode
UPS is operating in Bypass Mode.
Manual Bypass
UPS is operating in Manual Bypass.
ECO Mode
UPS is operating in ECO (Economy) Mode.
Button
Operation Description
ON/OFF
Press this button to turn on or turn off UPS.
Press this button to scroll up in the LCD menu.
Press this button to scroll down in the LCD menu.
ENTER
Press this button to select an option.
ESC
Press this button to cancel or return to previous LCD menu.
LCD SCREEN – UPS STATUS
BUTTON OPERATION
Copyright © 2017 Cyber Power Systems, Inc.
Page 17
OPERATION INSTRUCTIONS FOR LCD MODULE
16
MULTI-FUNCTION LCD MAIN MENU
MAIN MENU submenu
Function Description
Information
Displays the UPS information.
Configure
Displays the UPS settings that can be configured by the user.
Event Log
Displays the 5 most recent events, by event count, time (day/hour/minute), and event description.
Information Submenu
Description
O/P Volt
= XXX.XV
Displays the Output Voltage
O/P Freq
= XX.XHz
Displays the Output Frequency
I/P Volt
= XXX.XV
Displays the Input Voltage
I/P Freq
= XX.XHz
Displays the Input Frequency
O/P Load
= XXX%
Displays the Output Load as a Percentage of Maximum load
O/P Amp
= X.XA
Displays the Output Current
O/P Watt
= XXXXXW
Displays the Output Wattage
O/P VA
= XXXXXVA
Displays the Output VA
Load Energy
XXXX.XKWh
Display UPS Load Energy Consumption
BAT Volt
= XXX.XV
Displays the Battery Voltage
BAT Cap
= XXX%
Displays the Estimated Percentage of Battery Capacity
BAT Runtime
= XXXM
Displays the Estimated Battery Runtime in Minutes
EBM Number
= X
Displays the Extended Battery Module Number
TEMP
= XX°C / XXX°F
Displays the Approximate inside Temperature in both °C (Celsius) and °F (Fahrenheit) for the UPS
SBM
= XXXXX XH(M)
Displays the stage of Smart Battery Management with Operation Time
Rating
= XXK VA
Displays the UPS Rating
MCU Ver
= XXXX
Displays the MCU Firmware Version
Press “Enter” button to activate “MAIN MENU”.
LCD INFORMATION READOUT
There are 23 types of UPS information available for display.
1. Press the “ENTER” button to activate the “MAIN MENU”.
2. Press the and buttons to scroll to the “Information” option.
3. Press the “ENTER” button to select the “Information” submenu.
4. Press the “ and buttons to scroll through the “Information” submenu in the following table.
5. Press the “ESC” button to return to UPS Status.
Copyright © 2017 Cyber Power Systems, Inc.
Page 18
OPERATION INSTRUCTIONS FOR LCD MODULE
17
Model Name
Displays the UPS Model Name
Date & Time
- - - - / - - / - - - -:- -
Displays the present Date & Time
Next BATT Change
XXX / XXXX
Displays the next Battery Change Date & Time
IP
XXXXXX XXX.XXX.XXX.XXX
Display the device IP address
Subnet Mask
XXX.XXX.XXX.XXX
Display the device Subnet Mask
Gateway
XXX.XXX.XXX.XXX
Display the device Gateway
MAC
XX-XX-XX-XX-XX-XX
Display the device MAC
LCD EVENT LOG
Event Log Submenu
Description
(X)
XXDXXHXXM (without PowerPanel® Business or RMCARD)
- - / - - - -:- - (with PowerPanel® Business or RMCARD)
Event Content
5 Event Logs of UPS can be recorded.
1. Press the “ENTER” button to activate the “MAIN MENU”.
2. Press the “ and buttons to scroll to the “Event Log” option.
3. Press the “ENTER” button to select the “Event Log” submenu.
4. Press the “ and buttons to scroll through the “Event Log” submenu in the following table.
5. Press the “ESC” button to return to UPS Status.
MULTI-LANGUAGE INTERFACE
Users can configure 1 of the 4 available languages for display. ([English], [Español-Spanish], [Français-French], [Deutsch-German])
1. Press the “ENTER” button to activate the “MAIN MENU”.
2. Press the and buttons to scroll to the “Configure” option.
3. Press the “ENTER” button to select the “Configure” submenu.
4. Press the “ and buttons to scroll through the “Language” options.
5. Press the “ENTER” button to select the “Language” submenu.
6. Press the and buttons to scroll to the language that you want to select.
You may be prompted to save the selection, if so press the “ENTER” button to save the setting.
7. Press the “ESC” button to cancel or return to previous LCD menu.
LCD SETTINGS CONFIGURATION
There are 27 UPS settings that can be configured by the user.
1. Press the “ENTER” button to activate the “MAIN MENU”.
2. Press the and buttons to scroll to the “Configure” option.
3. Press the “ENTER” button to select the “Configure” submenu.
4. Press the and buttons to scroll to the “Configure” submenu in the following table.
Copyright © 2017 Cyber Power Systems, Inc.
Page 19
OPERATION INSTRUCTIONS FOR LCD MODULE
18
5. Press the “ENTER” button to select the setting you want to configure.
Configure Submenu
Available Settings
Default Setting
Output Voltage
= [200V] [208V] [220V] [230V] [240V]
230V*
Sync Freq Window
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
+/- 5%
Bypass V Window
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
+10%/-15%
Bypass Condition
[Check Freq/Volt] [Check Volt Only] [No Bypass]
Check Freq/Volt
ECO Mode
1
[Disable] [Enable]
Disable
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
V Range= +/-10%
Manual Bypass
[Disable] [Enable]
Disable
UPS Diagnostic
[Battery Test] [Alarm Test] [Indicator Test] [Fan Test]
[Battery Test]
[Activate?]
None
Audible Alarms
[Disable] [Enable]
Enable
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
0
Wiring Fault
[Disable] [Enable]
Disable
NCL Control
[Outlet On] [Outlet Off]
Outlet On
Language
[English] [Español-Spanish] [Français-French] [Deutsch-German]
English
Generator Mode
2
[Disable] [Enable]
Disable
Communication
[Disable] [Enable]
Enable
Dry Relay Set
[I/P Power Fail] [Battery Low] [Summary Alarm] [UPS On Bypass] [UPS Fail]
I/P Power Fail
Converter Mode
3
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Converter OFF
Screen Saver
[Disable] [1 Minutes] [5 Minutes]
5 minutes
Clear Event Log
[Activate?]
None
Button OFF LOCK
[Disable] [Enable]
Disable
Charger Function
[SBM] [Constant]
SBM
Signal Inputs
[Disable] [EPO][ROO]
Disable
Charger Check
[Disable] [Enable]
Disable
The first configuration parameter will be displayed on the second column of LCD screen.
6. Press the “ and buttons to scroll through the different parameters.
7. Press the “ENTER” button to select the parameter you want to change.
You may be prompted to save the selection, if so press the “ENTER” button to save the setting. Some options are saved and started automatically. (See the following table for additional details.)
8. Press the “ESC” button to cancel or return to the previous LCD menu.
Copyright © 2017 Cyber Power Systems, Inc.
Page 20
OPERATION INSTRUCTIONS FOR LCD MODULE
19
With Transformer
[Disable] [Enable]
Disable
Backfeed Check
[Disable] [Enable]
Disable
Reset ReplaceBAT
[Activate?]
None
IP Address
[Mode:DHCP] [Mode:Manual]
Mode:DHCP
Reset Load Energy
[Activate?]
None
1
Discharging Capacity
The LCD screen displays the remaining battery
capacity with a graphical icon while on Battery Mode.
Charging Capacity
The LCD screen displays the battery capacity during
charging with a graphical icon while on Line Mode.
LOAD and BAT Capacity
The LCD screen displays the Load and Battery capacity
with a graphical icon.
This function can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
2
UPS has no bypass when Generator Mode is enabled.
3
UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
SILENCING AUDIBLE ALARMS
1. Press any of four function buttons on the LCD module; Note: the alarm can not be turned off for a Battery Low condition. This condition will still result in an audible alarm.
2. Configure Audible Alarms” as Disable” on the LCD module and it will stop warning of any malfunction audibly.
MANUAL BATTERY TEST
Configure Battery Test” as “Active” on the LCD module; and it will perform the “Manual Battery Test
Graphical Load/Battery Capacity Display
1. Press the “ESC” button to return to UPS Status.
2. Press the “▲” and “▼” buttons to scroll to the “LOAD” and “BAT” Capacity.
3. Press the “▲” and “▼” buttons to scroll to the “Charging” or “Discharging” Capacity.
Copyright © 2017 Cyber Power Systems, Inc.
Page 21
LCD MODULE REMOTE CONTROL and WALL-MOUNTING INSTRUCTIONS
20
REMOTE CONTROL
Step 1: Remove the Multifunction LCD Module
Unscrew the right panel of the Power module. Separate the right panel
from the UPS. Gently lift the LCD module out. Reinstall the right panel.
WALL-MOUNTING INSTRUCTIONS
Step 1: Remove the Multifunction LCD Module
Unscrew the right panel of the Power module. Separate the right panel
from the UPS. Gently lift the LCD module out. Reinstall the right panel.
Step 2: Connect the DB26 Cable
Connect a DB26 cable (not included) from LCD module to the “Remote Control Port on the front panel as shown in the following figure.
Step 2: Rotate the DB26 Connector of LCD Module
Step 3: Connect the DB26 Cable
Connect a DB26 cable (not included) from LCD module to the “Remote Control Port on the front panel as shown in the following figure.
Step 4: Mount LCD Module on the Wall
SAFETY PRECAUTIONS
CAUTION! It must be done by qualified personnel. CAUTION! To avoid electric shock, turn off and unplug the unit before installing REMOTE CONTROL or WALL-MOUNTING INSTRUCTIONS.
Copyright © 2017 Cyber Power Systems, Inc.
Page 22
MAINTENANCE
21
Storage
To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to ensure
battery life.
Battery Replacement
Please read and follow the Safety Instructions before servicing the battery. Battery replacement should be performed by trained personnel who are familiar with the procedures and safety precautions. Make a note of the replacement Battery module number.
CAUTION! To avoid electric shock, turn off and unplug the UPS from the wall receptacle before servicing the battery.
CAUTION! Only use tools with insulated handles. Do not lay tools or metal parts on top of the UPS or battery terminals.
Replacement Batteries
Please refer to the front side of the Battery module for the model number of the correct replacement batteries. For battery procurement, log onto www.CPSww.com, or contact your local dealer.
Safety Precautions
CAUTION! Only use replacement batteries which are certified by Cyber Power Systems. Use of incorrect battery type is an electrical
hazard that could lead to explosion, fire, electric shock, or short circuit.
CAUTION! Batteries contain an electrical charge that can cause severe burns. Before servicing batteries, please remove any conductive materials such as jewelry, chains, wrist watches, and rings.
CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is harmful to the skin/eyes and may be toxic.
Battery Replacement
Battery Disposal
Batteries are considered hazardous waste and must be disposed of properly. Contact your local government for more information about proper disposal and recycling of batteries. Do not dispose of batteries in fire.
Cyber Power Systems encourages environmentally sound methods for disposal and recycling of its UPS products. Please dispose and/or recycle your UPS and batteries in accordance with local regulations.
Step 1: Remove the front panels Step 2: Remove the retaining screws from
the cable protection cover and then remove
the cover itself
Step 4: Insert the battery connectors and tighten the screws of battery retaining cover
Step 5: Install the front panels, then to execute battery test via the LCD control panel, go to the Configuration Menu, then scroll to the UPS Diagnostic then select battery test and Activate, then scroll to Reset ReplaceBAT to reset the battery replacement date. This operation can also be done via PowerPanel® Business Edition Agent or RMCARD web interface if it is installed. Please see their respective User Manuals for detailed instructions.
Step 3: Pull the battery trays out slowly and then put the new battery trays back into the compartment
Copyright © 2017 Cyber Power Systems, Inc.
Page 23
22
MAINTENANCE
MANUAL BYPASS SWITCH OPERATION
This operation allows qualified personnel to remove the detachable PDU or HW PDU from the Power module for routine maintenance or replacement without disrupting power to connected equipment.
REMOVE PDU or HW PDU
Step 1: Slide the Interlock Bracket to the left
Remove the one screw that fix the Interlock Bracket in the right.
Slide the Interlock Bracket to the left.
Step 2: Check the Power module auto transfer to Manual Bypass
After Sliding the Interlock Bracket to the left, the Power module will auto transfer to Manual Bypass. Check that the LCD screen shows Manual
Bypass before turning the Manual Bypass Switch to Bypass“.
Step 5: Pull the PDU or HW PDU away from the Power module
Loosen the four screws that hold the PDU or HW PDU to the Power module.
Pull the PDU or HW PDU away from the Power module and loosen the two screws that hold the cover.
Step 6: Fix the cover on the PDU or HW PDU
Tighten the two screws and fix the cover on the PDU or HW PDU to hide the connectors.
Step 3: Turn the Manual Bypass Switch“ to “Bypass“
Step 4: Press ON/OFF button to turn off UPS
Copyright © 2017 Cyber Power Systems, Inc.
The Power module shutdown safely and it can perform routine maintenance or replacement now.
SAFETY PRECAUTIONS
CAUTION! It must be done by qualified personnel to prevent from the risk of fire or electric shock. CAUTION! Hazardous voltage may exist between the connectors of the PDU or HW PDU. Do not let the connectors touch any surface. CAUTION! Do not slide the Interlock Bracket when the LCD screen shows
Generator On or Converter On. CAUTION! Do not turn the Manual Bypass Switch when hearing a warning
beep from the Power module.
Page 24
23
MAINTENANCE
REATTACH PDU or HW PDU
Step 1: Remove the cover from the PDU or HW PDU
Loosen the two screws and remove the cover from the PDU or HW PDU to expose the connectors.
Step 2: Reattach the PDU or HW PDU to the Power module
Reattach the PDU or HW PDU to the Power module and tighten the two screws to fix the cover on the PDU or HW PDU.
Step 4: Turn the Manual Bypass Switch“ to Normal
Step 5: Slide the Interlock Bracket to the right
Slide the Interlock Bracket to the right.
Tighten the one screw that fix the Interlock Bracket in the right.
Tighten the four screws that hold the PDU or HW PDU to the Power module.
Step 3: Press ON/OFF button to turn on UPS in Manual Bypass
Step 6: Check the Power module auto transfer to Line Mode
After Sliding the Interlock Bracket to the right, the Power module will auto transfer to Line Mode. Check the LCD screen shows Line Mode.
SAFETY PRECAUTIONS
CAUTION! It must be done by qualified personnel to prevent from the risk of fire or electric shock. CAUTION! Hazardous voltage may exist between the connectors of the PDU or HW PDU. Do not let the connectors touch any surface. CAUTION! Do not slide the Interlock Bracket when the LCD screen shows
Generator On or Converter On. CAUTION! Do not turn the Manual Bypass Switch when hearing a warning
beep from the Power module.
Copyright © 2017 Cyber Power Systems, Inc.
Page 25
Copyright © 2017 Cyber Power Systems, Inc.
TECHNICAL SPECIFICATIONS
24
Model
OL6000ERT3UP OL6000ERT3UM
OL8000ERT3UP OL8000ERT3UM
OL10000ERT3UP
OL10000ERT3UM
Configuration
Capacity (VA)
6000VA
8000VA
10000VA
Capacity (Watts)
6000W
8000W
10000W
Form Factor
Rackmount / Tower
Energy-saving Technology
Yes, ECO Mode Efficiency > 95%
Input
Input Voltage Range
120~139Vac for 0~ 25% Load 140~159Vac for 0~ 50% Load 160~179Vac for 0~ 75% Load 180~280Vac for 0~100% Load
Input Frequency Range
40~70Hz
Input Power Factor
0.99
Cold Start
Yes
Output
Output Waveform
Sine wave
Output Voltage
200, 208, 220, 230, 240Vac (Configurable) ±2%
Output Frequency
50 / 60Hz (Auto-Sensing or Configurable) ±0.25Hz
Transfer Time (Typically)
0ms
Rated Power Factor
1
Harmonic Distortion
THD < 3% at Linear Load, < 5% at Non-linear Load
Crest Factor
3 : 1
ECO Mode Voltage Regulation
±10%, ±15% (Configurable)
Outlets for the PDU unit
(8) IEC C13, (2) IEC C19, (1) Hard Wire 3-wire
Outlets for the HW PDU unit
(1) Hard Wire 3-wire
Protection
Surge Protection
IEC 61000-4-5 Level 3
Phone / Network Protection
RJ11/RJ45 (One In/One Out)
Overload Protection
Line Mode 105~125% Load for 1 min, 126~150% Load for 10 sec Battery Mode 105~130% Load for 10 sec, 131~150% Load for 2 sec
Short Circuit Protection
UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
Battery
Specifications
(20) 12V/7.2AH
(20) 12V/9.0AH
Recharge Time (Typically)
4 hours
5 hours
Sealed, Maintenance Free
Yes
Hot-Swappable
Yes
Status Indicators
LCD Screen
Multi-Function LCD Readout that Supports
Multi-Language Interface, (23) Types of Read Out, (27) Types of Function Setting, (5) Event Logs
LED Indicators
Power On (White), Line Mode (Green), Battery Mode (Yellow), Bypass Mode (Yellow), Fault (Red), Replace Battery (Red)
Audible Alarms
Battery Mode, Battery Low, Overload, UPS Fault
Environment
Operating Temperature
32℉ to 104℉ ( 0℃ to 40℃)
Operating Relative Humidity
0 to 90% Non-Condensing
Management
On-Device Features
Start-up Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
Connectivity Ports
(1) Serial Port (RS232), (1) USB Port, (1) Remote Control Port, (1) Relay Out
SNMP/HTTP Capable
(1) Expansion Slot for optional remote management cards
Software
Power Management Software
PowerPanel® Business Edition
Physical
Dimensions--Power Module
L x W x H = 32.3 x 17 x 5.2in. (82 x 43.3 x 13.2cm)
Dimensions--Battery Module
L x W x H = 32.3 x 17 x 5.2in. (82 x 43.3 x 13.2cm)
Net Weight--Power Module
63lbs(28.5Kg)
Net Weight--Battery Module
167.2lbs(76Kg)
171.6lbs(78Kg)
Safety
Conformance Approvals
CE, RCM
Page 26
25
TROUBLE SHOOTING
Problem
Possible Cause
Solution
Warning
O/P Overload
Your equipment requires more power than the UPS can provide. If the UPS is in Line Mode then it will transfer to Bypass Mode; if the UPS is in Battery Mode it will shutdown.
Shut off non-essential equipment. If this solves the overload problem, the UPS will transfer to normal operation.
Load Over XXX%
Your equipment requires more power than the setting in the Power Management Software (PowerPanel
®
Business) will allow.
Shut off the non-essential equipment or increase the level in the Power Management Software.
Battery Mode
UPS is operating on battery power.
Save your data and perform a controlled­shutdown.
Battery Low
UPS is operating on battery power and will be shutting down soon due to extremely low battery voltage.
UPS will restart automatically when acceptable utility power returns.
BAT Disconnected
Missing battery power.
Check battery connector and battery breaker.
Battery Failure
UPS has failed in Battery Test.
1. Check battery connector and battery breaker.
2. Contact technical support to replace the battery.
Replace Battery
Battery will need to be replaced soon due to insufficient runtime.
Install new batteries, execute battery test, and reset the replace battery date.
Service Battery (Battery Expired)
The Battery Replacement Date has reached the recommended 3 years maintenance period.
Perform a runtime calibration to verify battery capacity is sufficient and acceptable. If batteries have been recently replaced, then reset the Battery Replacement Date using PowerPanel® Business Edition-Agent software, RMCARD interface (if installed) or through the LCD control panel on the UPS (See LCD Setting Configuration).
EPO OFF
Missing the EPO connection.
Check the EPO connection.
Wiring Fault Line and neutral wires are reversed.
Exchange line and neutral wires.
Missing ground wire.
Connect ground wire.
No ground wire.
Disable Wiring Fault alarm on LCD panel.
Line Abnormal
Wrong utility power backed up during UPS auto­restart.
Check whether voltage or frequency of utility power is out of range.
Output Short
Output short circuit.
Your attached equipment may have problems, please remove them and check again.
Over Temperature
High ambient temperature.
Check the fan for operation and if the ventilation hole has been covered.
Coldstart Lock
UPS is locked to prevent consuming battery power during shipping.
Plug into utility power for first-time operation.
Autorestart Lock
Automatic Restore is disabled in Power Management Software (PowerPanel® Business)
Press ON/OFF button to turn on UPS
Bypass Forbidden
Manual Bypass Forbidden when the LCD screen shows “Generator On” or “Converter On”.
Slide the Interlock Bracket to the right. (For the PDU or HW PDU only)
Fault
Over Charge
Battery is overcharged.
1. Remove battery connector and check charger voltage.
2. Contact CyberPower for repair.
Charger Failure
Charger has failed.
High O/P V
Output voltage is too high.
1. Shut down UPS and turn off input breaker.
2. Contact CyberPower for repair.
Low O/P V
Output voltage is too low.
Bus Fault
Internal DC bus voltage is too high or too low.
Copyright © 2017 Cyber Power Systems, Inc.
Page 27
26
TROUBLE SHOOTING
Cyber Power Systems, Inc.
www.cyberpower.com Entire contents copyright© 2017 Cyber Power Systems, Inc., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® Business Edition and PowerPanel® Personal Edition are trademarks of Cyber Power Systems, Inc.
Copyright © 2017 Cyber Power Systems, Inc.
Loading...