CyberPower OL6000ERT3U, OL8000ERT3U, OL10000ERT3U User Manual

Page 1
User’s Manual
OL6000ERT3U
OL8000ERT3U
OL10000ERT3U
CyberPower Systems Inc. www.cpsww.com
K01-0000194-00
Page 2
Copyright © 2011 CyberPower Systems, Inc.
IMPORTANT SAFETY INSTRUCTIONS
1
This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate the UPS.
CAUTION! The UPS must be connected to a grounded AC power
outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit.
CAUTION! The battery can power hazardous components inside the
unit, even when the AC input power is disconnected.
CAUTION! The UPS should be placed near the connected equipment
and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric shock, do
not remove cover. No user serviceable parts inside. Refer servicing to qualified service personnel.
CAUTION! (Non-Isolated Battery Supply): Risk of electric shock,
battery circuit is not isolated from AC power source; hazardous voltage may exist between battery terminals and ground. Test before touching.
CAUTION! To reduce the risk of fire, connect the UPS to a branch
circuit with 40 amperes (OL6000) / 50 amperes (OL8000) / 60 amperes (OL10000) maximum over-current protection in accordance to CE requirement.
CAUTION! The AC outlet where the UPS is connected should be close
to the unit and easily accessible.
CAUTION! Please use only VDE-tested, CE-marked mains cable, (e.g.
the mains cable of your equipment), to connect the UPS to the AC outlet.
CAUTION! Please use only VDE-tested, CE-marked power cables to
connect any equipment to the UPS.
CAUTION! When installing the equipment, ensure that the sum of the
leakage current of the UPS and the connected equipment does not exceed 3.5mA.
CAUTION! The OL6000 / OL8000 / OL10000 models are
permanently-connected equipment and only qualified maintenance personnel may carry out installations.
CAUTION! Do not unplug the unit from AC Power during operation, as
this will invalidate the protective ground insulation.
CAUTION! To avoid electric shock, turn off and unplug the unit before
installing the input/output power cord with a ground wire. Connect the ground wire prior to connecting the line wires!
CAUTION! Do not use an improper size power cord as it may cause
damage to your equipment and cause fire hazards.
CAUTION! Wiring must be done by qualified personnel.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT
EQUIPMENT! Under no circumstances this unit should be used for
medical applications involving life support equipment and/or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce
the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
CAUTION! Do not dispose of batteries in fire as the battery may
explode.
CAUTION! Do not open or mutilate the battery, released electrolyte is
harmful to the skin and eyes.
CAUTION! A battery can present a risk of electric shock and high short
circuit current. The following precaution should be observed when working on batteries
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handles.
CAUTION! The unit has a dangerous amount of voltage. When the
UPS indicators is on, the units may continue to supply power thus the units outlets may have a dangerous amount of voltage even when its not plugged in to the wall outlet.
CAUTION! Make sure everything is turned off and disconnected
completely before conducting any maintenance, repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety conductor before
any other cables are connected.
WARNING! (Fuses): To reduce the risk of fire, replace only with the
same type and rating of fuse.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS OUTPUT SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED PERSONNEL AWAY FROM BATTERIES!
Page 3
Copyright © 2011 CyberPower Systems, Inc.
UNPACKING
2
Power module
Input / Output terminal block cover
User’s manual Register card
Rackmount left rail * 2 sets Rackmount right rail * 2 sets
Phone line
USB communication cable
Serial Interface Cable (RS-232)
Battery module
Rackmount ears (Stands) (2) * 2 sets
Tie plate (1) * 2 sets
Flat head screws: M5X8L (8) * 2 sets
Pan head screws: M5X12L (12) * 2 sets
Plastic washers (8) * 2 sets
Screw hole dust covers (12) * 2 sets
Power cords
PowerPanel® Business Edition software CD
Page 4
Copyright © 2011 CyberPower Systems, Inc.
HARDWARE INSTALLATION
3
HARDWARE INSTALLATION
These versatile UPS systems can be mounted in a rackmount or vertical /tower orientation. This versatility is especially important to growing organizations with changing needs that value having the option to position a UPS on a floor or in a rackmount system. Please follow the
instructions below for the respective mounting methods.
SAFETY PRECAUTIONS
CAUTION! To prevent the risk of fire or electric shock, only use the
supplied hardware to attach the mounting brackets.
RACKMOUNT INSTALLATION
Step 1: Remove the internal battery trays from the Battery module (See page 17)
Step 2: Rackmount ears installation
Attach the two rackmount ears to the Battery module using the provided screws M5X8L*8pcs.
Step 3: Rackmount rail Installation
The rails adjust to mount in 48-cm (19-inch) panel racks from 52 to
91.5cm (20.5 to 36 inches) deep. Select the proper holes in the rack for positioning the Battery module in the rack. The Power module or the
Battery module takes up position 1 through position 9.
Step 4: Adjust rackmount rails to fit your rack
Attach the rackmount rail to your rack with two M5X12L screws and two plastic washers at the front of the rack. (Located in position 1 & position 6) Do not tighten the screws. Adjust the rail size on the rail assembly of your rack. Secure the rail to the rear of the rack with two M5X12L screws and two plastic washers. Tighten all screws at the front and rear of the rail. Once completed, perform the same steps for assembling the other rackmount rail.
Place the Battery module on a flat stable surface with the front of the unit facing toward you. Secure the Battery module to your rack with four M5X12L screws at the front of the rack. (Located in position 2 & position
8)
Step 5: Place the internal battery trays back into the Battery module (See page 17)
Once completed, perform the same steps for the Power module.
CAUTION! The Battery module must be installed below the Power
module.
Page 5
Copyright © 2011 CyberPower Systems, Inc.
HARDWARE INSTALLATION
4
VERTICAL/TOWER INSTALLATION
Step 1: Rotate the Multifunction LCD Module
Unscrew the right panel of the Power module. Separate the right panel from the UPS. Gently lift the LCD module out. Rotate it to the tower
orientation. Reinstall it for a tower configuration.
Step 2: Attach the base stands
Secure the tie bracket with the screws (M5X8*4pcs). Tighten the screws (M5X12*4pcs) of the base stands (rackmount ears) onto the bottom of the power module and the battery module.
Step 3: Attach dust covers
Insert dust covers into the rackmount ear screw holes that are not being used.
ELECTRICAL INSTALLATION
After completing the hardware installation of the UPS, you are now ready to plug in the UPS and connect your equipment.
SAFETY PRECAUTIONS
CAUTION! Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants. Do not install this UPS
where excessive moisture or heat is present (Please see specifications for acceptable temperature and humidity range).
CAUTION! Never install a UPS, or associated wiring or equipment, during a lightning storm. CAUTION! Do not work alone under hazardous conditions. CAUTION! In case of the risk of electric shock, do not remove the top cover.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
Page 6
Copyright © 2011 CyberPower Systems, Inc.
INSTALLING YOUR UPS SYSTEM
5
SYSTEM BLOCK DIAGRAM
Output
Input Filter
PFC
AC/DC
BUS
Inverter
DC/AC
STS
Charger
AC/DC
Bypass
Battery
Output
Filter
Input
Line Mode Battery Mode Bypass Mode
Control
&
Monitoring
LCD Module
USB & DB9
SNMP Slot
HARDWARE INSTALLATION GUIDE
1. Battery charge loss may occur during shipping and storage. Before
using the UPS, its strongly recommended to charge batteries for four hours to ensure the batteries’ maximum charge capacity. To recharge the batteries, simply plug the UPS into an AC outlet.
2. When using the included software, connect either the serial or the
USB cable between the computer and the corresponding port on the UPS. Note: If the USB port is used, the serial port will be disabled. They cannot be used simultaneously. After connecting to either the USB port or the
Serial port on the UPS, a computer with the PowerPanel® Business Edition Agent software installed can control the operating schedule, battery test, outlets, as well as obtain UPS status information. However,
other computers with PowerPanel® Business Edition Client software can only obtain UPS status information via LAN connection.
3. Connect your computer, monitor, and any externally-powered data
storage device (Hard drive, Tape drive, etc.) into the outlets only when the UPS is off and unplugged. DO NOT plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage the unit.
4. To protect a fax machine, telephone, modem line or network cable,
connect the telephone or network cable from the wall jack outlet to the jack marked “IN” on the UPS and connect a telephone cable or network cable from the jack marked “OUT” on the UPS to the modem, computer, telephone, fax machine, or network device.
5. Press the ON/OFF switch to turn the UPS on. The Power-On indicator
light will display when activated. If an overload is detected, an audible alarm will sound and the UPS will continuously emit two beeps per second. For resetting the unit, unplug some equipment from the outlets. Make sure your equipment carries a load current within the units safe range, (refer to the technical specifications).
6. This UPS is equipped with an auto-charge feature. When the UPS is
plugged into an AC outlet, the battery will automatically charge, even when the unit is switched off.
7. To maintain an optimal battery charge, leave the UPS plugged into an
AC outlet at all times.
8. Before storing the UPS for an extended period of time, turn the unit
OFF. Then cover it and store it with the batteries fully charged. Recharge the batteries every three months to ensure good battery capacity and long battery life. Maintaining a good battery charge will help prevent possible damage to the unit from battery leakage.
9. The UPS has one USB port (default) and one Serial port that allows
connection and communication between the UPS and any attached computer running the PowerPanel® Business Edition Agent software. The
UPS can control the computer’s shutdown during a power outage
through the connection while the computer can monitor the UPS and alter various programmable parameters. Note: Only one communication port can be used at a time. The port not in use will automatically become disabled or the serial port will be disabled if both ports are attached.
10. EPO (Emergency Power Off) Port:
EPO ports allow administrators the capability to connect the UPS unit to customer-supplied EPO switches. These installations give operators a single access point to immediately power-off all equipment connected to the UPS during an emergency.
11. To avoid electric shock, turn the unit OFF and disconnect the unit
from utility power before hardwiring the UPS (in/out power cord). The in/out power cord MUST be grounded.
Page 7
Copyright © 2011 CyberPower Systems, Inc.
HARDWIRING THE INPUT/ OUTPUT TERMINALS
6
CHECK CIRCUIT BREAKER/WIRING
Check branch circuit breaker rating and wiring dimensions at following table.
UPS Capacity
Branch Circuit Breaker
Wiring AWG
Wiring mm2
6KVA
40A
10 AWG
5.5 mm2
8KVA
50A
8 AWG
8.0 mm2
10KVA
60A
6 AWG
14.0 mm2
INPUT/ OUTPUT CONFIGURATION
Hardwire the input/output terminals as shown in the following diagram.
UPS
PFC
AC/DC
Inverter
DC/AC
STS
L N PE
Input
Circuit Breaker
Wiring
AWG
Wiring
AWG
L N PE
External
EPO
OutputMains
Battery
N
L
PE
N
L
PE
Mains2
SAFETY PRECAUTIONS
CAUTION! Input and Output circuit breakers must be “OFF” during the building installation. CAUTION! An additional two pole disconnect device is necessary during the building installation. CAUTION! Disconnected EPO will immediately shut down the logic circuit output of the UPS. Wiring the EPO signal is optional.
CAUTION! Local safety rules may require a separate, external EPO to turn off output circuit breakers. Refer to local wiring rules, the EPO should use
approved components.
Step 1: Separate the top and bottom covers
Loosen the four screws to separate the top and bottom covers.
Step 2: Fix the bottom cover on the terminal block
Tighten the two screws to fix the bottom cover on the terminal block.
Page 8
Copyright © 2011 CyberPower Systems, Inc.
HARDWIRING THE INPUT/ OUTPUT TERMINALS
7
Step 3: Input configuration
Insert the input cable through the appropriate cable gland (not included).
Connect the three wires to the input terminal block.
Step 4: Output configuration
Insert the output cable through the appropriate cable gland (not included)
Connect the three wires to the output terminal block.
Step 5: Fix the top cover on the bottom cover
Tighten the six screws to fix the top cover on the bottom cover.
Page 9
Copyright © 2011 CyberPower Systems, Inc.
BACKFEED PROTECTION
8
BACKFEED PROTECTION OPERATION
1. If the Bypass circuit is shorted and the UPS is running in Line Mode or Battery Mode, backfeed protection will be active and the external isolation device
(Magnetic Contactor) will open.
2. Save your data and perform a controlled shutdown.
3. Contact CyberPower for repair.
WITHOUT BACKFEED PROTECTION CONFIGURATION
1. Hardwire the input terminals as shown in the following diagram.
2. Do not remove the interconnection wires (Jumper1 / Jumper2) on Backfeed Protection Connector”.
UPS
L N
PSDR
AC-L AC-N
IP-L IP-N
Backfeed
1 2
4 5
3
L
N
I/P
EMI
L N
L N PE
Mains
PE
Jumper2
Jumper1
WITH BACKFEED PROTECTION CONFIGURATION
1. Customers should provide an external isolation device (Magnetic Contactor) which is upstream and outside the UPS and capable of supporting the UPS
input current.
2. Remove the interconnection wires (Jumper1 / Jumper2) on Backfeed Protection Connector”.
3. Hardwire the input terminals and Backfeed Protection Connector” as shown in the following diagram.
4. The external isolation device must be installed in the Mains path.
UPS
L
N
PSDR
AC-L AC-N
IP-L IP-N
Backfeed
1 2 3 4 5
MC
L N
L N
A1
A2
I/P
EMI
L N
L N
L N PE
Mains
PE
2A Fuse
(Slow Blow)
Page 10
Copyright © 2011 CyberPower Systems, Inc.
BASIC OPERATION
9
POWER MODULE FRONT/REAR PANEL DESCRIPTION
1. Power Button / Power on Indicator
Master ON/OFF for the UPS. Indicates that the UPS is on and supplying power.
2. UPS Status / Fault / Replace Battery LED Indicator
Indicates the status of the UPS whether is operating in Line, Battery or Bypass Mode, or the UPS has an internal fault and the battery need to be replaced.
3. Multifunction LCD Readout
Shows UPS status, information, settings and events.
4. Function Buttons
Scroll up, scroll down, select and cancel LCD menu.
5. Input Circuit Breaker
Provides input overload and fault protection.
6. Input / Output Terminal Block
Connect to utility power / your equipment.
7. Output Circuit Breaker
Provides output overload and fault protection.
8. Battery Backup & Surge Protected Outlets
Provides battery backup and surge protection. They ensure power is provided to connected equipment over a period of time during a power failure.
Critical / Noncritical Load
Allows the creation of load priorities to ensure that battery power reserves are transferred to specified outlets during a power outage. The unit can be programmed to provide additional runtime for equipment connected to the CRITICAL outlets, while stopping the power supply to equipment connected to “NONCRITICAL outlets after a designated period of time.
9. Serial Port
Serial port provides communication between the UPS and the computer. The UPS can control the computer’s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters.
10. USB port
This is a connectivity port which allows communication and control between the UPS and the connected computer. It is recommended to install the PowerPanel® Business Edition Agent software on the PC/Server connected with the USB cord.
11. Remote Control Port
Connects to remote LCD module to the UPS.
12. Surge Protected Communication Ports RJ-45/RJ-11
These ports are used to protect standard RJ-45/RJ-11 based products (ADSL, LAN, Phone/ Modem-Lines) and cabling systems from surges.
OL6000ERT3U / OL8000ERT3U / OL10000ERT3U
OL6KRT3UPM
OL8KRT3UPM / OL10KRT3UPM
13. Relay Output Connector
Convert UPS signals into real potential-free Dry Contacts for industrial control.
14. SNMP/HTTP Network slot
Slot to install the optional SNMP card for remote network control and monitoring.
15. Extended Runtime Battery Module Connector
Connection for additional CyberPower XL Battery modules.
16. EPO (Emergency Power Off) Connector
Enables an emergency UPS Power-Off from a remote location.
17. Backfeed Protection Connector
Prevents power feedback from the inverter to utility power in case of power failure and a fault in the bypass circuit.
Page 11
Copyright © 2011 CyberPower Systems, Inc.
BASIC OPERATION
10
BATTERY MODULE FRONT/REAR PANEL DESCRIPTION
1. On-board Replaceable Fuse Cover
Replaceable fuse is accessible from the rear panel. It must be done by qualified personnel.
2. AC Circuit Breaker
Provides overload and fault protection.
3. AC Output Outlet
Use this outlet to connect to the AC Input Inlet of a downstream Battery module.
4. AC Input Inlet (Charge Only)
AC power connectivity to wall receptacle.
5. Input Connector
Use this input connector to daisy chain the next Battery module. Remove the connector cover for access.
6. Output Cable
Use this output cable to connect the Battery module to the Power module or to the next Battery module.
BPE240V30ART3U / BPE240V50ART3U
CONNECTION #1 : POWER MODULE WITH ONE BATTERY MODULE
Step 1: Loosen the two screws to remove the battery cable
retention bracket of the power module.
Step 2: Use the output cable of the Battery module to connect the Battery module to the Power module.
Step 3: Rotate the battery cable retention bracket and tighten
the two screws to fix battery cable.
Step 4: Use a power cord to plug AC input inlet of the battery module into a wall receptacle.
Page 12
Copyright © 2011 CyberPower Systems, Inc.
BASIC OPERATION
11
CONNECTION #2 : POWER MODULE WITH MULTIPLE BATTERY MODULES
Step 1: Connect the 1st Battery module to the Power module using the instructions above.
Step 2: Loosen the two screws to remove the battery cable
retention bracket of the 1st battery module.
Step 3: Use the output cable of the 2nd Battery module to
connect the 2nd Battery module to the 1st Battery module.
Step 4: Rotate the battery cable retention bracket and tighten
the two screws to fix battery cable.
Step 5: Use a power cord to plug AC input inlet of the 2nd battery module into AC output outlet of the 1
st
Battery module.
Page 13
Copyright © 2011 CyberPower Systems, Inc.
OPERATION INSTRUCTIONS FOR LCD MODULE
12
LED INDICATORS – UPS STATUS
LED Indicators
Color
UPS Status Description
ON/OFF
Blue
UPS power is on.
ON-LINE
Green
UPS is operating in Line Mode.
BATTERY ON
Yellow
UPS is operating in Battery Mode.
BYPASS
Yellow
UPS is operating in Bypass Mode, Manual Bypass or ECO (Economy) Mode.
FAULT
Red
UPS has an internal fault. See “Trouble Shooting” for additional information.
REPLACE BATTERY
Red
Battery will soon need to be replaced due to insufficient runtime.
LCD SCREEN – UPS STATUS
LCD Screen
UPS Status Description
Line Mode
UPS is operating in Line Mode.
Battery Mode
UPS is operating in Battery Mode.
Bypass Mode
UPS is operating in Bypass Mode.
Manual Bypass
UPS is operating in Manual Bypass.
ECO Mode
UPS is operating in ECO (Economy) Mode.
BUTTON OPERATION
Button
Operation Description
ON/OFF
Press this button to turn on or turn off UPS.
Press this button to scroll up in the LCD menu.
Press this button to scroll down in the LCD menu.
ENTER
Press this button to select an option.
ESC
Press this button to cancel or return to previous LCD menu.
Page 14
Copyright © 2011 CyberPower Systems, Inc.
LCD SETUP FUNCTIONS
13
MULTI-FUNCTION LCD MAIN MENU
Press “Enter” button to activate “MAIN MENU”.
MAIN MENU submenu
Function Description
Information
Displays the UPS information.
Configure
Displays the UPS settings that can be configured by the user.
Event Log
Displays the 3 most recent events, by event count, time (day/hour/minute), and event description.
LCD INFORMATION READOUT
There are 19 types of UPS information available for display.
1. Press the ENTER” button to activate the MAIN MENU”.
2. Press the and buttons to scroll to the Information option.
3. Press the ENTER” button to select the Information submenu.
4. Press the and buttons to scroll through the Information submenu in the following table.
5. Press the ESC” button to return to UPS Status.
Information Submenu
Description
O/P Volt = XXX.XV
Displays the Output Voltage
O/P Freq = XX.XHz
Displays the Output Frequency
I/P Volt = XXX.XV
Displays the Input Voltage
I/P Freq = XX.XHz
Displays the Input Frequency
O/P Load = XXX%
Displays the Output Load Percentage of Maximum load
O/P Amp = X.XA
Displays the Output Current
O/P Watt =XXXXXW
Displays the Output Wattage
O/P VA =XXXXXVA
Displays the Output VA
BAT Volt = XXX.XV
Displays the Battery Voltage
BAT Cap = XXX%
Displays the Estimated Percentage of Battery Capacity
BAT Runtime =XXXM
Displays the Estimated Battery Runtime in Minutes
EBM Number = X
Displays the External Battery Module Number
TEMP =XX°C / XXX°F
Displays the Approximate inside Temperature in both (Celsius) and (Fahrenheit) for the UPS
SBM = XXXXX
Displays the Stage of Smart Battery Management
Rating = XXK VA
Displays the UPS Rating
MCU Ver = XXXX
Displays the MCU Firmware Version
Model Name
Displays the UPS Model Name
Date & Time
- - - - / - - / - - - -:- -
Displays the present Date & Time
Next BAT Change
XXX / XXXX
Displays the next Battery Change Date & Time
Page 15
Copyright © 2011 CyberPower Systems, Inc.
LCD SETUP FUNCTIONS
14
LCD EVENT LOG
3 Event Logs of UPS can be recorded.
1. Press the ENTER” button to activate the MAIN MENU”.
2. Press the and buttons to scroll to the Event Log option.
3. Press the ENTER” button to select the Event Log submenu.
4. Press the and buttons to scroll through the Event Log submenu in the following table.
5. Press the ESC” button to return to UPS Status.
Event Log Submenu
Description
(X)
XXDXXHXXM (without PowerPanel® Business or RMCARD302)
- - / - - - -:- - (with PowerPanel® Business or RMCARD302)
Event Content
MULTI-LANGUAGE INTERFACE
Users can configure 1 of the 3 available languages for display.
([English], [Español-Spanish], [Français-French])
1. Press the ENTER” button to activate the MAIN MENU”.
2. Press the and buttons to scroll to the Configure option.
3. Press the ENTER” button to select the Configure submenu.
4. Press the and buttons to scroll through the Language options.
5. Press the ENTER” button to select the Language submenu.
6. Press the and buttons to scroll to the language that you want to select.
You may be prompted to save the selection, if so press the ENTER” button to save the setting.
7. Press the ESC” button to cancel or return to previous LCD menu.
LCD SETTINGS CONFIGURATION
There are 20 UPS settings that can be configured by the user.
1. Press the ENTER” button to activate the MAIN MENU”.
2. Press the and buttons to scroll to the Configure option.
3. Press the ENTER” button to select the Configure submenu.
4. Press the and buttons to scroll to the Configure submenu in the following table.
5. Press the ENTER” button to select the setting you want to configure.
The first configuration parameter will be displayed on the second column of LCD screen.
6. Press the and buttons to scroll through the different parameters.
7. Press the ENTER” button to select the parameter you want to change.
You may be prompted to save the selection, if so press the ENTER” button to save the setting. Some options are saved and started automatically. (See the following table for additional details.)
8. Press the ESC” button to cancel or return to the previous LCD menu.
Page 16
Copyright © 2011 CyberPower Systems, Inc.
LCD SETUP FUNCTIONS
15
Configure Submenu
Available Settings
Default Setting
Output Voltage
= [200V] [208V] [220V] [230V] [240V]
230V*
Sync Freq Window
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
+/- 5%
Bypass V Window
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
+10%/-15%
Bypass Condition
[Check Freq/Volt] [Check Volt Only] [No Bypass]
Check Freq/Volt
ECO Mode**
[Disable] [Enable]
Disable
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
V Range= +/-10%
Manual Bypass
[Disable] [Enable]
Disable
Battery Test
[Activate?]
None
Audible Alarms
[Disable] [Enable]
Enable
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
0
Wiring Fault
[Disable] [Enable]
Enable
NCL Control
[Outlet On] [Outlet Off]
Outlet On
Language
[English] [Deutsch-German] [Français-French]
English
Generator Mode***
[Disable] [Enable]
Disable
Communication
[Disable] [Enable]
Enable
Dry Relay Set
[I/P Power Fail] [Battery Low] [Summary Alarm] [UPS On Bypass] [UPS Fail]
I/P Power Fail
Converter Mode****
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
Converter OFF
Screen Saver
[Disable] [1 Minutes] [5 Minutes]
5 minutes
Clear Event Log
[Activate?]
None
Button OFF LOCK
[Disable] [Enable]
Disable
Charger Function
[SBM] [Constant]
SBM
*) Output voltage default setting depends on different nation or order requested. **) This function can’t be set when Manual Bypass, Generator Mode or Converter Mode is enabled. ***) UPS has no bypass when Generator Mode is enabled. ****) UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
SILENCING AUDIBLE ALARMS
1. Press any of four function buttons on the LCD module; Note: the alarm can not be turned off for a Battery Low
condition. This condition will still result in an audible alarm.
2. Configure Audible Alarms” as Disable” on the LCD module and it will stop warning of any malfunction audibly.
MANUAL BATTERY TEST
Configure Battery Test” as “Active” on the LCD module; and it will perform the “Manual Battery Test
Page 17
Copyright © 2011 CyberPower Systems, Inc.
LCD MODULE REMOTE CONTROL and WALL-MOUNTING INSTRUCTIONS
16
REMOTE CONTROL
Step 1: Remove the Multifunction LCD Module
Unscrew the right panel of the Power module. Separate the right panel
from the UPS. Gently lift the LCD module out. Reinstall the right panel.
Step 2: Connect the DB26 Cable
Connect the DB26 cable from LCD module to the Remote Control
Port” on the front panel or rear panel as shown in the following figure.
WALL-MOUNTING INSTRUCTIONS
Step 1: Remove the Multifunction LCD Module
Unscrew the right panel of the Power module. Separate the right panel
from the UPS. Gently lift the LCD module out. Reinstall the right panel.
Step 2: Rotate the DB26 Connector of LCD Module
Step 3: Connect the DB26 Cable
Connect the DB26 cable from LCD module to the Remote Control
Port” on the front panel or rear panel as shown in the following figure.
Step 4: Mount LCD Module on the Wall
SAFETY PRECAUTIONS
CAUTION! It must be done by qualified personnel. CAUTION! To avoid electric shock, turn off and unplug the unit before installing REMOTE CONTROL or WALL-MOUNTING INSTRUCTIONS.
Page 18
Copyright © 2011 CyberPower Systems, Inc.
MAINTENANCE
17
Storage
To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to ensure
battery life.
Battery Replacement
Please read and follow the Safety Instructions before servicing the battery. Battery replacement should be performed by trained personnel who are familiar with the procedures and safety precautions. Make a note of the replacement Battery module number.
Safety Precautions
CAUTION! Only use replacement batteries which are certified by
CyberPower Systems. Use of incorrect battery type is an electrical
hazard that could lead to explosion, fire, electric shock, or short circuit.
CAUTION! Batteries contain an electrical charge that can cause
severe burns. Before servicing batteries, please remove any conductive materials such as jewelry, chains, wrist watches, and rings.
CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is
harmful to the skin/eyes and may be toxic.
CAUTION! To avoid electric shock, turn off and unplug the UPS from
the wall receptacle before servicing the battery.
CAUTION! Only use tools with insulated handles. Do not lay tools or
metal parts on top of the UPS or battery terminals.
Replacement Batteries
Please refer to the front side of the Battery module for the model number of the correct replacement batteries. For battery procurement, log onto www.CPSww.com, or contact your local dealer.
Battery Disposal
Batteries are considered hazardous waste and must be disposed of properly. Contact your local government for more information about proper disposal and recycling of batteries. Do not dispose of batteries in fire.
Battery Installation
Step 1: Remove the front panels
Step 2: Remove the retaining screws from the cable protection cover and then remove
the cover itself
Step 3: Pull the battery trays out slowly and then put the new battery trays back into the compartment
Step 4: Insert the battery connectors and tighten the screws of battery retaining cover
Step 5: Install the front panels
Page 19
Copyright © 2011 CyberPower Systems, Inc.
TECHNICAL SPECIFICATIONS
18
Model
OL6000RT3U
OL8000RT3U
OL10000RT3U
Configuration
Capacity (VA)
6000VA
8000VA
10000VA
Capacity (Watts)
5400W
7200W
9000W
Form Factor
Rackmount / Tower
Energy-saving Technology
Yes, ECO Mode Efficiency > 95%
Input
Input Voltage Range
120~139Vac for 0~ 25% Load 140~159Vac for 0~ 50% Load 160~179Vac for 0~ 75% Load 180~280Vac for 0~100% Load
Input Frequency Range
40~70Hz
Input Power Factor
0.99
Cold Start
Yes
Output
Output Waveform
Sine wave
Output Voltage*
200, 208, 220, 230, 240Vac (Configurable) ±2%
Output Frequency
50 / 60Hz (Auto-Sensing or Configurable) ±0.25Hz
Transfer Time (Typically)
0ms
Rated Power Factor
0.9
Harmonic Distortion
THD < 3% at Linear Load, < 5% at Non-linear Load
Crest Factor
3 : 1
ECO Mode Voltage Regulation
±10%, ±15% (Configurable)
UPS Outlets
(8) IEC C13, (2) IEC C19,
(1) Hard Wire 3-wire
(4) IEC C13, (4) IEC C19,
(1) Hard Wire 3-wire
Protection
Surge Protection
IEC 61000-4-5 Level 3
Phone / Network Protection
RJ11/RJ45 (One In/One Out)
Overload Protection
Line Mode 105~125% Load for 1 min, 126~150% Load for 10 sec Battery Mode 105~130% Load for 10 sec, 131~150% Load for 2 sec
Short Circuit Protection
UPS Output Cut off Immediately or Input Fuse / Circuit Breaker Protection
Battery
Specifications
(20) 12V/7.2AH
(20) 12V/9.0AH
Recharge Time (Typically)
4 hours
5 hours
Sealed, Maintenance Free
Yes
Hot-Swappable
Yes
Status Indicators
LCD Screen
Multi-Function LCD Readout that Supports Multi-Language Interface, (19) Types of Read Out,
(20) Types of Function Setting, (3) Event Logs
LED Indicators
Power On (Blue), Line Mode (Green), Battery Mode (Yellow), Bypass Mode (Yellow), Fault (Red), Replace Battery (Red)
Audible Alarms
Battery Mode, Battery Low, Overload, UPS Fault, Replace Battery
Environment
Operating Temperature
32℉ to 104℉ ( 0℃ to 40℃)
Operating Relative Humidity
0 to 90% Non-Condensing
Management
On-Device Features
Self Test, Auto-Charge, Auto-Restart, Auto-Overload Recovery
Connectivity Ports
(1) Serial Port (RS232), (1) USB Port, (1) Remote Control Port, (1) Relay Out
SNMP/HTTP Capable
(1) Expansion Port (With optional SNMP card or RMCARD 302)
Software
Power Management Software
PowerPanel® Business Edition
Physical
Dimensions--Power Module
L x W x H = 26 x 17 x 5.2in. (66 x 43.3 x 13.2cm)
Dimensions--Battery Module
L x W x H = 26 x 17 x 5.2in. (66 x 43.3 x 13.2cm)
Net Weight--Power Module
53lbs(24Kg)
Net Weight--Battery Module
167.2lbs(76Kg)
171.6lbs(78Kg)
Safety
Conformance Approvals
CE, C-tick
Page 20
Copyright © 2011 CyberPower Systems, Inc.
19
TROUBLE SHOOTING
Problem
Possible Cause
Solution
Warning
O/P Overload
Your equipment requires more power than the UPS can provide. If the UPS is in Line Mode then it will transfer to Bypass Mode; if the UPS is in Battery Mode it will shutdown.
Shut off non-essential equipment. If this solves the overload problem, the UPS will transfer to normal operation.
Load Over XXX%
Your equipment requires more power than the setting in the Power Management Software (PowerPanel
®
Business) will allow.
Shut off the non-essential equipment or increase the level in the Power Management Software.
Battery Mode
UPS is operating on battery power.
Save your data and perform a controlled­shutdown.
Battery Low
UPS is operating on battery power and will be shutting down soon due to extremely low battery voltage.
UPS will restart automatically when acceptable utility power returns.
BAT Disconnected
Missing battery power.
Check battery connector and battery breaker.
Battery Failure
UPS has failed in Battery Test.
1. Check battery connector and battery breaker.
2. Contact technical support to replace the battery.
Replace Battery
Battery will soon need to be replaced due to insufficient runtime.
Contact technical support to replace the battery.
EPO OFF
Missing the EPO connection.
Check the EPO connection.
Wiring Fault Line and neutral wires are reversed.
Exchange line and neutral wires.
Missing ground wire.
Connect ground wire.
No ground wire.
Disable Wiring Fault alarm on LCD panel.
Line Abnormal
Wrong utility power backed up during UPS auto­restart.
Check whether voltage or frequency of utility power is out of range.
Output Short
Output short circuit.
Your attached equipment may have problems, please remove them and check again.
Over Temperature
High ambient temperature.
Check the fan for operation and if the ventilation hole has been covered.
Coldstart Lock
UPS is locked to prevent consuming battery power during shipping.
Plug into utility power for first-time operation.
Autorestart Lock
Automatic Restore is disabled in Power Management Software (PowerPanel® Business)
Press ON/OFF button to turn on UPS
Bypass Forbidden
Manual Bypass Forbidden when the LCD screen shows “Generator On” or “Converter On”.
Slide the Interlock Bracket to the right. (For the PDU or HW PDU only)
Fault
Over Charge
Battery is overcharged.
1. Remove battery connector and check charger voltage.
2. Contact CyberPower for repair.
Charger Failure
Charger has failed.
High O/P V
Output voltage is too high.
1. Shut down UPS and turn off input breaker.
2. Contact CyberPower for repair.
Low O/P V
Output voltage is too low.
Bus Fault
Internal DC bus voltage is too high or too low.
CyberPower Systems Inc.
www.cpsww.com Entire contents copyright© 2011 CyberPower Systems Inc., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® Business Edition and PowerPanel® Personal Edition are trademarks of CyberPower Systems Inc.