Cyber Power Mini Central CPSPV40000ETL Series, Mini Central CPSPV30000ETL Series, Mini Central CPSPV33000ETL Series User Manual

Page 1
User’s Manual
CPSPV30000ETL/ CPSPV33000ETL/ CPSPV40000ETL
CyberPower Systems Inc.
Page 2
Index
1 Information on this Manual ...................................................................................................... 3
1.1 Validity ........................................................................................................................................................... 3
1.2 Target Group .................................................................................................................................................. 3
1.3 Symbols Used ................................................................................................................................................. 3
2 Safety ....................................................................................................................................... 4
2.1 Intended Use .................................................................................................................................................. 4
2.2 Safety Precautions ......................................................................................................................................... 5
2.3 Assembly Warnings ........................................................................................................................................ 5
2.4 Electrical Connection Warnings ..................................................................................................................... 6
2.5 Operation Warnings ....................................................................................................................................... 7
2.6 Symbols on the inverter ................................................................................................................................. 8
3 Product Description .................................................................................................................. 9
3.1 CPS Mini Central series overview ................................................................................................................... 9
3.2 Type label ..................................................................................................................................................... 10
3.3 Size and weight ............................................................................................................................................ 11
3.4 Transportation.............................................................................................................................................. 12
3.5 Storage of Inverter ....................................................................................................................................... 12
3.6 The advantage of the CPS Mini Central inverters ........................................................................................ 12
4 Unpacking .............................................................................................................................. 13
5 Installation ............................................................................................................................. 14
5.1 Safety instruction ......................................................................................................................................... 14
5.2 Selecting the Installation Location ............................................................................................................... 15
5.3 Installation guide ......................................................................................................................................... 16
5.3.1 Mounting the Bracket ....................................................................................................................... 16
5.3.2 Mounting Inverter ............................................................................................................................. 18
5.3.3 Installation layout ............................................................................................................................. 19
5.4 Electrical Connections .................................................................................................................................. 20
5.4.1 Safety ................................................................................................................................................ 20
5.4.2 Wiring AC Output ............................................................................................................................ 200
5.4.3 Wiring DC Input ................................................................................................................................. 23
5.4.4 Grounding ................................................................................................................................................. 24
5.5 Grid Type ...................................................................................................................................................... 26
5.5.1 Common grid type ............................................................................................................................ 26
5.5.2 Compatibility Table ........................................................................................................................... 27
6 Commissioning ....................................................................................................................... 28
6.1 Commission the Inverter.............................................................................................................................. 28
6.2 Operation Modes ......................................................................................................................................... 28
6.3 Initial Settings and LCD Display .................................................................................................................... 29
6.3.1 Initial Settings ................................................................................................................................... 29
6.3.2 Power on Display .............................................................................................................................. 31
6.3.3 Operate by knock .............................................................................................................................. 33
6.3.4 Data checking and parameters setting ............................................................................................. 34
User Manual 1 / 54 CPS Mini Central series
Page 3
6.4 Double MPPT of the CPS Mini Central ......................................................................................................... 40
6.5 Communication ............................................................................................................................................ 41
6.5.1 Using ‘Solar Power Setup’ to set the information of the inverter or update firmware .................... 41
6.5.2 Monitor the inverters ........................................................................................................................ 41
6.5.3 RS485 cable connection .................................................................................................................... 42
7 Start-Up and shut down the inverter ....................................................................................... 45
7.1 Start-Up the inverter .................................................................................................................................... 45
7.2 Shut down the Inverter ................................................................................................................................ 45
8 Maintenance and Cleaning ..................................................................................................... 46
8.1 Cleaning Fans and Grills ............................................................................................................................... 46
8.2 Exchange Fan ............................................................................................................................................... 47
9 Trouble shooting..................................................................................................................... 48
9.1 Error Messages displayed on LCD ................................................................................................................ 48
9.1.1 System fault ...................................................................................................................................... 49
9.1.2 Inverter warning ............................................................................................................................... 49
9.1.3 Inverter fault ............................................................................................................................................. 50
10 Decommissioning ................................................................................................................. 51
10.1 Dismantling the Inverter ............................................................................................................................ 51
10.2 Packing the Inverter ................................................................................................................................... 51
10.3 Disposing of the Inverter ........................................................................................................................... 51
11 Specification ......................................................................................................................... 52
11.1 Specification of CyberPower Mini Central Series ....................................................................................... 52
11.2 Torque Values ............................................................................................................................................. 53
12 Certificates ........................................................................................................................... 53
13 Contact ................................................................................................................................. 53
User Manual 2 / 54 CPS Mini Central series
Page 4
Symbol
description
Read the manual
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.
NOTICE indicates a situation which, if not avoided, could result in
property damage.
Information that you must read and know to ensure optimal operation of
the system.
1 Information on this Manual
1.1 Validity
This installation guide contains installation, commissioning, communication, trouble shooting. Information of CPS
Mini Central series:
CPSPV30000ETL CPSPV33000ETL CPSPV40000ETL
With this installation guide, users are able to install and operate the inverters easily. This manual does not cover
any details concerning equipment connected to the CPS Mini Central series. Store this manual where accessible at
all times.
1.2 Target Group
This manual is for qualified persons such as PV system installers or electricians.
Notes: For possible changes in this manual, CyberPower Systems, Inc. accepts no responsibilities to inform the
users
1.3 Symbols Used
The following types of safety instructions and general information appear in this document as described below:
User Manual 3 / 54 CPS Mini Central series
Page 5
2 Safety
2.1 Intended Use
CPS Mini Central series inverters are to be used solely to feed solar energy converted photovoltaically into the
public grid. CPS Mini Central series inverters are multi-string inverters with multi-MPP trackers, which mean they
are able to connect to different PV module arrays. The equipment may only be operated in compliance with its
intended use.
Grid-tied PV system Overview:
Fig 1.1
The inverter may only be operated with a permanent connection to the public power grid. The inverter is not
intended for mobile use. Any other or additional use is not considered as intended use. The manufacturer is not
responsible for any damages resulting from unintended use. Damage caused by such unintended use is at the
sole risk of the operator.
As drawings shown above, a complete Grid-tied PV system consists of PV modules, PV inverters, public grid and
other components. Moreover, PV inverters always act as key components.
PV modules Capacitive Discharge Currents
PV modules with large capacities relative to earth, such as thin-film PV modules with cells on a metallic substrate,
may only be used if their coupling capacity does not exceed 470nF. During feed-in operation, a leakage current
flows from the cells to earth, the size of which depends on the manner in which the PV modules are installed (e.g.
foil on metal roof) and on the weather (rain, snow). This "normal" leakage current may not exceed 50mA due to
the fact that the inverter would otherwise automatically disconnect from the electricity grid as a protective
measure.
User Manual 4 / 54 CPS Mini Central series
Page 6
If PV modules of the PV system require POSITIVE or NEGATIVE to connect
to GROUND, or the capacitance relative to ground of the modules is
large, please contact CyberPower Systems, Inc. for technical support
before installation.
Prior to installation, inspect the unit to ensure absence of any
transport or handling damage, which could affect insulation integrity
or safety clearances; failure to do so could result in safety hazards.
Unauthorized removal of necessary protections, improper use,
incorrect installation and operation may lead to serious safety, shock
hazards or equipment damage.
In order to minimize the potential of a shock hazard due to hazardous
voltages, cover the entire solar array with dark material prior to
connecting the array to any equipment.
Grounding the PV modules: Comply with the local requirements for
grounding the PV modules and the PV generator.
CyberPower recommends connecting the generator frame and
other electrically conductive surfaces in a manner which ensures
continuous conduction and ground these in order to have optimal
protection of the system and personnel.
2.2 Safety Precautions
The CPS Mini Central series is designed and tested according to international safety requirements; however, certain
safety precautions must be observed when installing and operating this inverter. Read and follow all instructions,
cautions and warnings in this installation manual.
2.3 Assembly Warnings
User Manual 5 / 54 CPS Mini Central series
Page 7
Some components in the inverter are live. Touching live components can
result in serious injury or death.
Danger to life due to high voltages in the inverter
All work on the inverter may be carried out by qualified personnel only. The appliance is not to be used by children or persons with reduced
physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction.
Children are forbidden to play around the CPS Mini Central series.
Make all electrical connections (e.g. conductor termination, fuses, PE
connection, etc.) in accordance with prevailing regulations. When working
with the inverter powered on, adhere to all prevailing safety regulations to
minimize risk of accidents.
The CPS Mini Central series may only be operated with PV generators
(modules and cabling) with protective insulation. Do not connect any source
of energy other than PV modules to the CPS Mini Central series.
Systems with inverters typically require additional control (e.g., switches,
disconnects) or protective devices (e.g., fusing circuit breakers) depending
upon the prevailing safety rules.
Please read this manual carefully, the manufacturer or supplier is not
responsible for damage caused by incorrect operation, installation, wiring,
transport, etc.
The CPS Mini Central series is to be used solely to feed solar energy
converted photovoltaic into the public grid. The inverter is suitable for
mounting indoors and outdoors.
You can use the AC current generated as follows:
House
grid:
Energy flows into the house grid. The consumers connected,
for example, household devices or lighting, consume the
energy. The energy left over is fed into the public grid. When
the CPS Mini Central series do not generate any energy, e.g., at
night, the consumers which are connected are supplied by the
public grid. The energy displayed on the LCD of inverter is for
reference only. When energy is fed into the public grid, the
energy meter spins backwards.
Public grid:
Energy is fed directly into the public grid. The CPS Mini Central
series need install a separate energy meter. The energy
produced is compensated at a rate depending on the electric
power company.
2.4 Electrical Connection Warnings
User Manual 6 / 54 CPS Mini Central series
Page 8
2.5 Operation Warnings
Ensure all covers and doors are closed and secure during operation. Although designed to meet all safety requirements, some parts and
surfaces of Inverter are still hot during operation. To reduce the risk of
injury, do not touch the heat sink at the back of the PV-Inverter or nearby
surfaces while Inverter is operating.
Incorrect sizing of the PV plant may result in voltages being present which
could destroy the inverter. The inverter display will read the error
message “ PV Voltage High
Turn the rotary switch of the DC Disconnect to the Off position
immediately.
Contact installer.
All operations regarding transport, installation and start-up, including
maintenance must be operated by qualified, trained personnel and in
compliance with all prevailing codes and regulations.
Anytime the inverter has been disconnected from the power network,
use extreme caution as some components can retain charge sufficient to
create a shock hazard; to minimize occurrence of such conditions, comply
with all corresponding safety symbols and markings present on the unit
and in this manual.
In special cases, there may still be interference for the specified
application area despite maintaining standardized emission limit values
(e.g. when sensitive equipment is located at the setup location or when
the setup location is near radio or television receivers).In this case, the
operator is obliged to take proper action to rectify the situation.
Possible damage to health as a result of the effects of radiation!
Do not stay closer than 20 cm to the inverter for any length of time.
User Manual 7 / 54 CPS Mini Central series
Page 9
Symbol
Explanation
Refer to operation instruction
Caution, risk of electrical shock
Caution, hot surface
Earth (ground) terminal
Caution, risk of electrical shock. Energy stored discharge time.
Direct Current (DC)
Alternating Current (AC)
CE mark. The inverter complies with the requirements of the applicable EC guidelines.
2.6 Symbols on the inverter
User Manual 8 / 54 CPS Mini Central series
Page 10
Position
Description
A
LCD B LED C DC Switch
D
PV input terminals
E
AC output
F
RS232 lid
G
RS485
H
Serial Number
I
Warning Label
J
Type label
3 Product Description
3.1 CPS Mini Central series overview
C D E F G B I J A H
User Manual 9 / 54 CPS Mini Central series
Page 11
Symbol on the inverter
Symbol
Description
Explanation
Tap symbol
Indicates display operation (see Section 6).
Inverter state symbol
Green/constant
Operation
Red/constant
1Fault-- contact installer 2Standby module
Red/flashing
1Fans Fault-- contact installer 2Software update
3.2 Type label
The type labels provide a unique identification of the inverter (The type of product, Device-specific
characteristics, Certificates and approvals). The type labels are on the right-hand side of the enclosure.
More detail about the type label as the chart below:
User Manual 10 / 54 CPS Mini Central series
Page 12
Model Name
CPSPV30000ETL
CPSPV33000ETL
CPSPV40000ETL
Max DC voltage
1000V
1000V
1000V
Max input current
35A / 35A
38A / 38A
38A / 38A
MPP voltage range
460V-1000V
460V-1000V
550V-1000V
AC Nominal voltage
3/N/ PE
230V/400V
3/N/ PE
230V/400V
3/ PE
277V/480V
AC grid frequency;
Range
50/60Hz
-6Hz/+5Hz
50/60Hz
-6Hz/+5Hz
50/60Hz
-6Hz/+5Hz
Max. AC output power
30kW/30kVA
33kW/33kVA
40kW/40kVA
Nominal output current
43.5A
47.8A
48.1A
Max. output current
45.5A
50A
50A
Protection Degree
IP65
IP65
IP65
Operation temperature
range
-25°C ~ +60°C
-25°C ~ +60°C
-25°C ~ +60°C
A(mm)
B(mm)
C(mm)
D(mm)
Weight(kg)
CPSPV30000ETL
CPSPV33000ETL
CPSPV40000ETL
740
550
276
778
61.6
3.3 Size and weight
User Manual 11 / 54 CPS Mini Central series
Page 13
After long term storage, the Real Time Clock of the inverter maybe
not correct, it will cause the Energy produced today (E_day) error,
you need to set the time and date, refer to Fig 6.3.15 or 6.4.3 text
line.
3.4 Transportation
The inverter is thoroughly tested and inspected strictly before delivery. Our inverters leave our factory in
proper electrical and mechanical condition. Special packaging ensures safe and careful transportation.
However, transport damage may still occur. The shipping company is responsible in such cases. Thoroughly
inspect the inverter upon delivery. Immediately notify the responsible shipping company if you discover any
damage to the packaging which indicates that the inverter may have been damaged or if you discover any
visible damage to the inverter. We will be glad to assist you, if required. When transporting the inverter, the
original or equivalent packaging should to be used, and the maximum layers for original carton is four, as this
ensures safe transport.
3.5 Storage of Inverter
If you want to storage the inverter in your warehouse, you should choose an appropriate location to store the inverter.
The unit must be stored in original package and desiccant must be left in the package. The storage temperature should be always between -25and +70. And the storage relative
humidity should be always between 0 and 95%.
If there are lots of inverters need to be stored, the maximum layers for original carton is four. After long term storage, local installer or service department of CyberPower should perform a
comprehensive test before installation
3.6 The advantage of the CPS Mini Central inverters
The features of CPS Mini Central series inverter are below:
Dual independent MPP trackers Integrated DC disconnect switch Wide PV voltage range300V~1000V The maximum efficiency is 98.2% The Europe efficiency is 97.8% IP65 environmental protection Easy to install
User Manual 12 / 54 CPS Mini Central series
Page 14
Item
quantity
Description
A
1 pcs
CPS Mini Central inverter
B
1 pcs
Waterproof cover for AC power cable
C
1 pcs
Wall-Mount bracket
D
1 set
Cable gland for AC connection
E
4 pcs
M4 cross recessed countersunk head screws for
Waterproof cover
F
3 set
M6 socket head cap screws for fix inverter on wall mount bracket
G
6 set
Hex head cap screw and nuts for wall mount bracket
H
2 set
RS485 waterproof plug assembly
I
4 set
Field Wiring DC connectors
J
6 set
Plugs for unused PV terminals
K
5 pcs
Ring Terminals
--
1 pcs
Warranty(not show in the picture)
--
1 pcs
User manual (not show in the picture)
Though the packaging box of CPS Mini Central inverter is durable, please
treat the packing box gently and avoid dispose the packing box.
4 Unpacking
Before opening the packing box of CPS Mini Central inverters, please note that whether there are any visible
external damages.
Once open the packing box, please check the delivery for completeness and for any visible external damages of the
inverter. If there are anything damaged or missing, please contact your dealer. Complete delivery should contain as
follows.
Fig 4.1
User Manual 13 / 54 CPS Mini Central series
Page 15
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires. Do not install the inverter on easily flammable materials and where
flammable materials are stored.
Risk of burns due to hot enclosure parts
Mount the inverter in such a way that it cannot be touched inadvertently.
5 Installation
5.1 Safety instruction
All electrical installations shall be done in accordance with the local and national electrical codes.
Do not remove the casing. Inverter contains no user serviceable parts. Refer servicing to qualified service personnel. All wiring and electrical installation should be conducted by a qualified service personnel.
Carefully remove the unit from its packaging and inspect for external damage. If you find any
imperfections, please contact your local dealer.
Be sure that the inverters connect to the ground in order to protect property and personal
safety.
The inverter must only be operated with PV generator. Do not connect any other source of
energy to it.
Both AC and DC voltage sources are terminated inside the PV Inverter. Please disconnect these
circuits before servicing.
This unit is designed to feed power to the public power grid (utility) only. Do not connect this
unit to an AC source or generator. Connecting Inverter to external devices could result in serious damage to your equipment.
When a photovoltaic panel is exposed to light, it generates a DC voltage. When connected to this
equipment, a photovoltaic panel will charge the DC link capacitors.
Energy stored in this equipment’s DC link capacitors presents a risk of electric shock. Even after
the unit is disconnected from the grid and photovoltaic panels, high voltages may still exist inside the PV-Inverter. Do not remove the casing until at least 5 minutes after disconnecting all power sources.
Although designed to meet all safety requirements, some parts and surfaces of Inverter are still
hot during operation. To reduce the risk of injury, do not touch the heat sink at the back of the PV-Inverter or nearby surfaces while Inverter is operating.
User Manual 14 / 54 CPS Mini Central series
Page 16
5.2 Selecting the Installation Location
This is guidance for installer to choose a suitable installation location, to avoid potential damages to device and
operators.
1) The wall selected to install the inverter must be strong and firm enough to support and bear the weight
of the inverter for a long period time. (Refer to Chapter 11 Specifications)
2) The location selected must be suitable for inverters’ dimension. (Refer to 3.3 Dimensions and Fig.5.2
Required Clearances)
3) Do not install the inverter on structures constructed of flammable or thermo labile materials.
4) Never install the inverter in environment of little or no air flow, nor dust environment.
5) The Ingress Protection rate is IP65 which means the inverter can be installed outdoors and indoors.
6) Do not expose the inverter to direct sunlight, in order to avoid the power and efficiency derating caused
by excessive heating.
7) The humidity of the installation location should be 0~95% without condensation.
8) The ambient temperature of the inverter should be -25~+60.
9) The installation location must be freely and safely to get at all times.
10) Vertically installation and make sure the connection of inverter must be downwards. Never install
horizontal and avoids forward and sideways tilt.( Refer to drawings below)
Fig 5.1
11) Notice the minimum clearances of the inverter. (Refer to 3.3 Dimensions and Fig.5.2 Required
Clearances).
User Manual 15 / 54 CPS Mini Central series
Page 17
In order to avoid electrical shock or other injury, inspect existing electronic or plumbing installations before drilling holes.
Fig 5.2
12) Do not install the inverter near television antenna or any other antennas and antenna cables.
13) Do not install the inverter in living area, the noise caused by the machine may affect daily life.
14) For security reasons, dont install the inverter in place where the children can reach.
5.3 Installation guide
5.3.1 Mounting the Bracket
To mount the inverter on the wall, we should mount the bracket to the wall firmly first of all.
User Manual 16 / 54 CPS Mini Central series
Page 18
Dimension of Bracket (units :mm)
Fig 5.3
Steps:
Drill 6 holes for screws while use the mounting frame as template. Fix the mounting frame on the wall as the figures shown below, combine as the screws as the Items Fig
4.1 shows (items D)
Fig 5.4
User Manual 17 / 54 CPS Mini Central series
Page 19
Falling equipment can cause serious or even fatal injury, never mount the inverter on the bracket unless you are sure that the mounting frame is really firmly mounted on the wall after carefully checking.
5.3.2 Mounting Inverter
After the bracket is firmly mounted on the wall, then mount the inverter on the bracket.
Rise up the CPS Mini Central a little higher than the bracket. Considering the weight of CPS Mini Central, you
need to hang on the inverter. During the process please maintain the balance of the CPS Mini Central.
Hang the inverter on the bracket through the match hooks on bracket and the back of the inverter. Please
reference in Fig5.5
Installed one M6*10 screw at each side of inverter to reliable fixed it on the wall. Please reference in Fig 5.6. Connection of a second protective earthing conductor. Please reference in Fig5.7. Recommend awning installation, the purpose is to extend the inverter service life and reduce the power
derating of the inverter. The dimension of the awning refer to Fig5.8.
Fig 5.5 Fig 5.6
Fig. 5.7
User Manual 18 / 54 CPS Mini Central series
Page 20
5.3.3 Installation layout
Avoid exposing inverter to direct sunlight, rain or snow to extend the inverter service life despite the IP65
protection degree. Exposure to the sunlight may cause additional internal heating which will cause power derating.
Fig. 5.8
More than one inverter need to be installed, the dimensions below should be considered.
User Manual 19 / 54 CPS Mini Central series
Page 21
Danger to life due to hazards voltages!
High voltages which may cause electric shocks are present in the
conductive parts of the inverter. Prior to performing any work on the
inverter, disconnect the inverter on the AC and DC sides
Danger of damage to electronic components due to electrostatic
discharge.
Take appropriate ESD precautions when replacing and installing the
inverter.
Fig. 5.9
5.4 Electrical Connections
5.4.1 Safety
5.4.2 Wiring AC Output
Conditions for the AC Connection
You must comply with the connection requirements of your utility operator.
User Manual 20 / 54 CPS Mini Central series
Page 22
Model
Cable outer Diameter
(mm)
Cross-section Conductor Area
(mm²)
Available wire gauge
(AWG)
CPSPV30000ETL
3.67~4.62
10~16
7~5
CPSPV33000ETL
3.67~4.62
10~16
7~5
CPSPV40000ETL
3.67~4.62
10~16
7~5
Conductor
Cross section
Max. cable length(m)
CPSPV30000ETL
CPSPV33000ETL
CPSPV40000ETL
10.0 mm²
30
25
25
14.0 mm²
42
38
38
16.0 mm²
50
45
45
All usages must comply with the regulations.
Residual-current protective device
The inverter is equipped with an integrated universal residual-current monitoring unit.
If the network operator stipulates a residual-current protective device, you must use a
residual-current protective device that triggers in the event of a residual-current of 100 mA or more.
Connection of a second protective conductor
In some installation countries, a second protective conductor is required to prevent a touch current in
the event of a malfunction in the original protective earthing conductor.
For installation countries falling within the scope of validity of the IEC standard 62109, you must install
the protective conductor on the AC terminal with a conductor cross-section of at least 10 mm²Cu.
Or install a second protective conductor on the earth terminal with the same cross-section as the original
protective earthing conductor on the AC terminal
Load disconnection unit
You must install a separate three-phase miniature circuit-breaker or other load disconnection unit for each inverter
in order to ensure that the inverter can be safely disconnected under load.
Measure the public grid voltage and frequency
Note,
Nominal 3-Phase line to line voltage is 400Vac for model CPSPV30000ETL/CPSPV33000ETL
and 480Vac for model CPSPV40000ETL
Open the DC Switch between the PV inverter and utility;
Specification of AC breaker: CPSPV30000ETL: 63A/400V
CPSPV33000ETL: 80A/400V
CPSPV40000ETL: 80A/480V
AC Power Cable requirements:
User Manual 21 / 54 CPS Mini Central series
Page 23
Please do not use single-core wire cable.
There are two types of AC connector for CPS Mini Central series inverters. Please follow the instructions
corresponding to the parts we offer.
AC terminal :
1) The AC side terminals of the inverter are like the following figure, it is clear to confirm that ‘L1, L2, L3’
represents three live line output, ‘N’ represents neutral line and is grounding line. Note that,
CSPV40000ETL have no N terminal. See Fig 5.10.
Following diagram illustrate the step of installation for AC connection with CSPV30000ETL and CSPV33000ETL.
The similar step can be applied CSPV40000ETL, except the cable no is 4 instead of 5 because there is no N
required.
2) Connect standard cables into relevant terminals.
The cables should be put through the protection shell, then to press the ring terminal onto the AC cable.
Following with tighten the ring terminal to AC terminal block shown as figure below. See Fig 5.11
3) Fasten the protection shell onto the bottom of the inverter, make sure the four screws are tightened, the
completed appearance is like the below figure. See Fig 5.12
AC Terminal of CSPV30000ETL/CSPV33000ETL
Fig 5.10
Fig 5.11 Fig 5.12
User Manual 22 / 54 CPS Mini Central series
Page 24
5.4.3 Wiring DC Input
Danger to life due to hazards voltages!
Before connecting the PV array, ensure that the DC switch and AC breaker are disconnect from the inverter. NEVER connect or disconnect the DC connectors under load.
Improper operation during the wiring process can cause fatal injury to operator or unrecoverable damage to the inverter. Only qualified personnel can perform the wiring work.
Risk of damage to the inverter. If the voltage of the PV modules exceeds the maximum input voltage of the inverter, it can be destroyed by the overvoltage. This will void all warranty claims. Do not connect strings to the inverter that have an open-circuit voltage greater than the maximum input voltage of the inverter.
To reduce the risk of electric shock, avoid touching the live components and treat the
terminals carefully.
The PV modules should have an IEC61730 Class A rating*.
Please use the same brand male and female PV connectors.
Under any conditions the total circuit current should never exceed the Max. Current.
Excessive DC voltages can destroy the measuring device Only use measuring devices with a DC input voltage range up to at least 1,000 Vdc.
*Relate only to transformerless installation.
1 Check the connection cables of the PV modules for correct polarity and make sure that the maximum
open circuit voltage of each string should never exceed 1000V.
2 The diagram drawing of DC side is shown as below, Fig 5.13, notice that the connectors are in paired
User Manual 23 / 54 CPS Mini Central series
Page 25
Type
Max. current
CPSPV30000ETL
35A/35A
CPSPV33000ETL
38A/38A
CPSPV40000ETL
38A/38A
Model
Diameter(mm)
Area(mm²)
AWG
CPSPV30000ETL
CPSPV33000ETL
CPSPV40000ETL
2.05-2.59
3.332-5.26
12-10
(male and female connectors). The vendor of DC connectors for both PV arrays and inverters should be
H4 (Amphenol).
Fig.5.13
3 Check the assembled DC connectors for correct polarity and connect them to the inverter. 4 The maximum MPPT currents are varying from different inverter types.
5 In order to seal the inverter, all unused DC inputs must be closed with sealing plugs:
Cable requirements:
5.4.4 Grounding
AC Grounding
The CPS Mini Central inverter must be connected to the AC grounding conductor of the power distribution grid via
the ground terminal (PE).
PV Grounding
The grounding conductor in the framework of the PV array must be connected to the PV grounding conductor and
the DC grounding conductor. The cross-section of the grounding conductor corresponds to the cross-section of the
largest conductor in the DC system.
DC Grounding Conductor
A DC grounding conductor may be required by the Authority Having Jurisdiction (AHJ). Use the terminal block for
the PV grounding conductor and DC grounding conductor.
Ground kit
User Manual 24 / 54 CPS Mini Central series
Page 26
If PV modules of the PV system require POSITIVE or NEGATIVE to connect to GROUND, the output of inverter
should connect to grid with an isolating transformer. The connection method is below:
N of transformer should not be connected to PE under such application.
User Manual 25 / 54 CPS Mini Central series
Page 27
If the output of inverter was connected to grid with an isolation transformer, and the inverter display PV Isolation Low error during when you start-up the inverter, please set the parameter Enable Neutral via CyberPower software Solar Power Setup, or connect the Neutral of inverter output to PE.
5.5 Grid Type
5.5.1 Common grid type
Based on the local GRID standards, it may select different connection types. In the following you will find an
overview of the most common type of grid structure.
User Manual 26 / 54 CPS Mini Central series
Page 28
5.5.2 Compatibility Table
Grid type
Inverter
TN-C grid
TN-S grid
TN-C-S grid
TT grid
IT grid
CPSPV30000ETL
Yes
(N and PE of inverter
both should connect to
PEN of grid.)
Yes
Yes
Yes,
if U
N-PE
< 30V
No
CPSPV33000ETL
Yes
(N and PE of inverter
both should connect to
PEN of grid.)
Yes
Yes
Yes,
if U
N-PE
< 30V
No
CPSPV40000ETL
Yes
(There is no N
connected required .PE
of inverter should
connect to PEN of grid.)
Yes
(Left N unconnected. Because there
is no terminal reserved for N point)
Yes,
if U
N-PE
< 30V
(Left N unconnected.
Because there is no
terminal reserved for
N point)
Yes
User Manual 27 / 54 CPS Mini Central series
Page 29
6 Commissioning
6.1 Commission the Inverter
1) Remove all covers from the PV array.
2) Check the PV and AC voltage.
3) Plug in the PV input.
4) Turn the DC Disconnect to position "ON"
5) If the inverter is connected with PV panel arrays and the input voltage is higher than 300Vdc, while the
AC grid is not connected yet, LCD will display messages in order as below:
Company info Basic info State info The LCD will display AC V outrange at State info and the LED turns red. Please check all information on the LCD, operate by knocks you will see the different parameters. Single knock to Light the backlight State info (single knock) Input info (single knock) Output
info
6) Turn on the AC breaker between inverter and grid, the system will operate automatically.
7) Under normal operating conditions, the LCD displays ‘Power: xx.xx KWat State info, this is the power
feed into grid. The LED turns green.
8) Check the time and date of inverter as follow:
Single knock to Light the backlight State info (Thrice knock) Inverter info (single knock) System Time(double knock), if they are not correct, please set them, refer to Fig 6.3.15 or 6.4.3 text
line.
9) Finish commissioning.
6.2 Operation Modes
Normal Mode
In this mode, the inverter works normally and LED turns green.
Whenever the DC voltage is higher than 300Vdc, inverter converts power to grid as generated by the PV
panels;
Whenever the DC voltage is lower than 250Vdc, the inverter will work in waiting state and attempt to
connect the grid. In waiting state the inverter consumes just enough power generated by the PV panel to
monitor the internal system.
Notes: The inverter starts up automatically when DC power from the PV panel is sufficient.
Fault Mode
The internal intelligent controller can continuously monitor and adjust the system state. If inverter finds any
unexpected conditions such as system fault and inverter fault, the fault information will be displayed on the LCD. In
fault mode the LED turns red.
Notes: a) Detailed fault information refers to Chapter 9.1 ERROR messages displayed on LCD.
b) When PV Isolation error occurred in SAA safety standard, the buzzer will give an alarm every fifteen seconds.
User Manual 28 / 54 CPS Mini Central series
Page 30
Please set Cert: VFR2014
Please set Cert: VDE0126_1_1/A1
1
VDE0126-1-1
2
VDE0126-1-1/A1
3
VDE0126 Taiwan
4
PEA Thailand
5
VFR 2014
6
IEC61727+62116
Shutdown Mode
Inverters automatically stop running during periods of little or no sunlight. In shutdown mode the inverters take no
power from the grid and panel, and the LCD and LED turns off.
Notes: If the PV string DC voltage is too low, the inverter will also turn to Shutdown Mode.
Derating mode
When AC frequency is higher than 50.3Hz(settable), the inverter will derate its output power according to the rule.
When user set the output power limit command to the inverter, the inverter will also limit the output according to
the setting.
In this derating mode, the LCD will show “DERATING”.
6.3 Initial Settings and LCD Display
In the lower right corner of inverter there is the LCD display. We can check inverter running state, historical
generation data, etc, on the LCD screen. Items displayed can be changed by knock; you can also change some
inverter parameters by knock.
6.3.1 Initial Settings
If it is the first time the inverter starts up after installation, LCD will quickly switch to and stay at the grid code
setting interface that is the first setting interface of initial settings. Only the inverter is completed all initial settings,
it will work and display normally. Otherwise, LCD will always stay at the ’Please select’ interface.
Grid code (Country) setting
Please finish the grid code setting according to the following steps:
1) When at the first interface ‘Please Set Cert:’ the option is ‘VFR2014’ in default. By single knock, grid
codes will vary from one to another, for example, ‘VDE0126-1-1/A1’, as Fig 6.3.1 and Fig 6.3.2
Fig 6.3.1 Fig 6.3.2
Note: If you have ordered the inverter with specific grid code settings, the parameters have been preset
in factory and you don't need to operate this step any more.
2) There are five grid codes to select:
3) When it comes to the grid code you want, double knock to enter, as Fig 6.3.3.
User Manual 29 / 54 CPS Mini Central series
Note: if you can’t find the grid code you want, please contact CyberPower Systems, Inc.
Page 31
Set Cert OK
Set Language English
Regler Langue Francaise
1
English
2
French
3
Chinese
Set OK! Current Language English
Set Time Time:2014-12-08 12:21:23
Set Time Time:2015-12-08 12:21:40
Single knock
Fig 6.3.3
Language setting
The second setting interface is language setting. Please finish the language setting according to the following steps:
1) When at the language interface ‘Set Language:’ the option is ‘English’ in default. By single knock,
languages will vary from one to another, for example, ‘Francaise’, as Fig 6.3.4 and Fig 6.3.5
Fig 6.3.4 Fig 6.3.5
2) There are 3 languages to select:
3) When it comes to the language you want, double knock to enter, as Fig 6.3.6.
Fig 6.3.6
System time setting
The last setting interface is system time setting. Please finish the system time setting according to the following
steps:
1) When at the system time interface, the time setting will start from the following sequence: Year ->
Month -> Date -> Hour -> Minute. By single knock, the setting will increase 1 unit, for example, increasing
1 year, as Fig 6.3.7 and Fig 6.3.8
2) By double knock, the setting will decrease 1 unit, for example, decreasing 1 year, as Fig 6.3.9 and Fig
User Manual 30 / 54 CPS Mini Central series
Fig 6.3.7 Fig 6.3.8
Note: System time will be set to current time in factory. Maybe you only need to adjust the Hour due to
different time zone in your country.
6.3.10.
Page 32
Set Time Time:2015-12-08 12:21:40
Set Time Time:2014-12-08 12:21:52
Set Time Time:2015-12-08 12:22:32
Set Time Time:2015-12-08 12:22:35
Set Time Time:2015-12-08 12:23:35
Set Time Time:2015-12-08 12:23:39 Set Time OK
Set Time Time:2015-12-08 12:21:23 Set Finished
CyberPower
CPSPV30000ETL
Double knock
Thrice knock
Thrice knock
Fig 6.3.9 Fig 6.3.10
3) When finish the current sequence, thrice knock to enter and then go to next sequence, as Fig 6.3.11 and
Fig 6.3.12.
Fig 6.3.11 Fig 6.3.12
4) When finish the Minute sequence, thrice knock to enter, as Fig 6.3.13 and Fig 6.3.14.
Fig 6.3.13 Fig 6.3.14
5) Then, thrice knock again to finish settings, as Fig 6.3.15. Few seconds later, system will restart and the
initial settings are completed.
Fig 6.3.15
6.3.2 Power on Display
Power on display
After power on for several seconds, LCD screen will display the figure of inverter, company name, inverter’s power
rating, etc.
Fig 6.3.5 inverter’s power rating
After 3 seconds, it will switch to the next interface. See Fig6.3.6 for reference.
User Manual 31 / 54 CPS Mini Central series
Page 33
VNNES20103 CPSPV30000ETL Main Ver:XXXXXX Comm Ver:XXXXXX
State:Fault AC V outrange E_today: 000kWh E_all: 00.0kWh
Input Info V-pv: 620/ 622 V I-pv:15.8/16.3 A P-pv: 9796/10139
Fig6.3.6 Serial number, model name and version
Here is explanation of items on Fig6.3.6:
First line: Serial number of this inverter. Second line: model name of this inverter. Main Ver: firmware version of control board. Comm Ver: firmware version of communication board.
After displaying information of the third interface for 3 seconds, the background light will turn off.
LCD Display when backlight off
After the power on information is displayed automatically and the backlight turns off, the LCD display will switch to
the following Interface 1. There are 4 interfaces, which can be displayed in turn by single knock.
Interface 1: Running state.
The first line displays inverter’s state description, for example, in faulty state it will display Fault and followed
with faulty codes, which is convenient to compare with error code list in manual.
The second line displays inverter’s states name. The third line displays energy generated today The fourth line displays the total energy generated since installation.
Fig6.3.7 Interface 1: Running state Fig6.3.8 Interface 2: Input information
Interface 2: Input information.
This interface displays parameters of PV input, including input voltage, current, and power of each MPP tracker.
V-pv: input voltage of MPPT1 and MPPT2 I-pv: input current of MPPT1 and MPPT2 P-pv: input power of MPPT1 and MPPT2 ,unit is W
Interface 3: Output information. See Fig6.3.9 for reference.
This interface displays output information of inverter, including output voltage of each phase, output current of
each phase, and output power of each phase.
V: output voltage of each phase I: output current of each phase
User Manual 32 / 54 CPS Mini Central series
Page 34
P: output power of each phase
Output Info V: 232/ 233/ 232 I:27.6/27.5/27.6 P:6.17/6.41/6.40
Power chart
Max: 26 kWh
State:Waiting Connect in 007S E_today: 000kWh E_all: 4532.2kWh
State:Normal Power: 0.97KW E_today: 000kWh LOCK
Knock type
Definition
Single knock
Down
Double knock
Enter
Thrice knock
Esc
Knock four times
Unlock LCD
Fig6.3.9 Interface 3: Output information Fig6.3.10 Interface 4: 24 hour’s generation curve
Interface 4: 24 hour’s generation curve. See Fig6.3.10 for reference.
This interface shows the generated power of every hour this day.
Max: maximum power of today Power curve: today’s power curve
6.3.2.3 Connecting messages
When inverter started to connect to grid, the following message will appear on LCD screen. See Fig6.3.11 for reference.
Fig6.3.11 Connect to gird interface
6.3.2.4 LCD Lock and unlock
LCD display will be locked while there is no any operation in two minutes. You need knock four times to unlock LCD. See Fig6.3.12 for reference.
Fig6.3.12 Lock LCD display
6.3.3 Operate by knock
Knock type and definition
The inverter can support four kinds of knock: single knock, double knock, thrice knock, Knock four times. Each kind
of knock has different function. Refer to specified definition in Table 6.1.
Table 6.1 Knock definition list
Light backlight and single knock to check running information
User Manual 33 / 54 CPS Mini Central series
Page 35
->Working History Property Setting
->Working History Property Setting
->Inverter info System Time
->Error Record E In 7 Days E In This Year E In Each Year
VNNES20103 CPSPV30000ETL Main Ver:XXXXXX Comm Ver:XXXXXX
->Set Time Set Language Set Com Addr Set GroundKit
Enter
Before light the backlight, the four types of knock functions are the same, which is just lighting the backlight. Note
that the background lighting will automatically turn off if there is no knock detected in 10 seconds.
During cloudy days or in the area of low light, it’s inconvenient for users to check inverter running information such
as state, input data, output data, energy generated. In this case user can light the backlight and check those data
by single knock, a single knock will switch LCD screen to a following interface. The interface display on LCD screen
will circle as follow: Fir6.3.7 -> Fir6.3.8 -> Fig6.3.9 -> Fig 6.3.10 -> Fig6.3.11, and then again Fig6.3.7.
6.3.4 Data checking and parameters setting
First level menu
It is a little bit different to enter the first level menu, note that using thrice knock to enter first level menu instead
of double knock. Fig 6.3.13 is the interface of first level menu.
Fig 6.3.13 First level menu
In current interface, a single knock will switch the index to next item, double knock will enter the corresponding
second level menu.
Second level menu
In first level menu, double knock will lead to next level menu.
The followings are second level menu interfaces for each first level menu items, shown in Fig 6.3.14.
In second level menu, a single knock will switch the index to next item; a double knock will enter the corresponding
third level menu. And a thrice knock will back to first level menu.
Fig 6.3.14 Second level menu for each first level menu items
Third level menu and explanation
Working information
User Manual 34 / 54 CPS Mini Central series
Page 36
Input Info V-pv: 620/ 622 V I-pv:15.8/16.3 A P-pv: 9796/10139
Output Info V: 232/ 233/ 232 I:27.6/27.5/27.6 P:6.17/6.41/6.40
State:Normal Power: 0.97KW E_today: 000kWh E_all: 00.0kWh
Power chart
Max: 26 kWh
Power Info P_Factor: 1.00 GridFreq:50.01Hz Q: 0.00 kvar
->Working History Property Setting
->Inverter info System Time
Enter Enter
Down
Down
Down
Down
Enter
System time
Time:2015-12-08 12:29:23
Second level menu
Third level items
Item explanation
Inverter info
State: Normal
Inverter running state
Power: xxx.xx
AC output power
E_today
Energy produced today
E_all
Energy produced since installation
Input info
Inverter input parameters
V_pv: xxx/xxx
PV input voltage for each MPP tracker
I_pv: xx.x/xx.x
PV input current for each MPP tracker
P_pv: xxxxx/xxxxxx
PV input power for each MPP tracker
Output info
Inverter output parameters
V: xxx/xxx/xxx
AC output voltage for each phase
I: xx.x/xx.x/xx.x
AC output current for each phase
P: x.xx/x.xx/x.xx
AC output power for each phase(units:kW)
Second level menu
Third level items
Item explanation
Power chart
Histogram of generation power
The followings are third level menu interfaces for each second level menu items of working information, shown in
The followings are third level menu interfaces for each second level menu items of working information, shown in
Fig6.3.15
Fig 6.3.15 Third level menu interface of working information
Explanations of each item in third level menu interface of working information:
State information:
Table 6.2 Working information sub-items explanation
User Manual 35 / 54 CPS Mini Central series
Page 37
Max
Maximum output power of inverter
Power info
Generation power information of inverter
P_Factor
Power factor
GridFreq
Utility grid frequency
Q
Reactive power
->Working History Property Setting
->Error Record E In 7 Days E In This Year E In Each Year
->Error 1:130 Error 2:129 Error 3:129 MORE
->Error 4:130 Error 5:129
Error 1:130 2015/12/08/12:10 Chk:396/396/395V Set:458.2/318.7V
Chk: 59.94 Hz Set: 50.20/47.50
7 Days
12.08: 128.3kWh
12.07: 109.9kWh
12.06: 95.9kWh
Month 12 : 2340 kWh 11 : 2411 kWh 10 : 3002 kWh
Year 2015: 32.8MWh 2014: 36.1MWh 2013: 12.7MWh
Enter
Enter
7 Days
12 Months
20 Years
MORE
Enter
Down
Second level menu
Third level items
Item explanation
Error Record
Error1: xxx
Five latest error records
Error2: xxx
Error3: xxx
Error4: xxx
Error5: xxx
More
More error record
Second level menu
Third level items
Item explanation
E in 7 Days
7 Days
Title indicates this is latest 7 days running data
Historical information
Fig 6.3.16 is the third level menu interfaces for each second level menu items of historical information.
Fig 6.3.16 Third level menu interface of historical information
Explanation of each item in third level menu interface of working information:
State information:
User Manual 36 / 54 CPS Mini Central series
Table 6.3 Historical information sub-items explanation
Page 38
MM:DD: xxx.x kWh
Format is Month:Date, xxxx.x is energy generated in that day.
E in Each Month
Month
Title indicates this is every month’s running data in this year.
MM: xxxxx kWh
xxxx.x is energy generated in that month.
E in Each Year
Year
Title indicates this is latest 10 years running data.
20XX: xxxx.x Mwh
xxxx.x is energy generated in the corresponding year.
Working History
->Property Setting
VNNES20103 CPSPV30000ETL Main Ver:XXXXXX Comm Ver:XXXXXX
Enter
First level menu
Second level items
Item explanation
Property
VANNES20103
Serial number of this inverter.
CPSPV30000ETL
Model name of this inverter.
Main Ver:xxxxxx
Firmware version of Control Board
Comm Ver:xxxxxx
Firmware version of Communication Board
Property information
Fig 6.3.17 is the second level menu interfaces of property
Fig 6.3.17 Property information
Explanation of each item in third level menu interface of working information:
State information:
User Manual 37 / 54 CPS Mini Central series
Page 39
Working History Property
->Setting
->Set Time Set Language Set Com Addr Set GroundKit
PLEASE INPUT:123 INPUT:0**
Enter
Enter
->Set Year Set Month Set Day MORE
->Year Up Year Down
Year Up 2014-12-08 12:21:23
Enter Enter
MORE
->Set Hour Set Minute
Year Up 2015-12-08 12:21:23
Down
Set Language English
Set OK! Current Language English
Enter
->Current Addr COM Addr Up CoM Addr Down
Current Addr 001
----------------
Enter
Set Com Addr 001
----------------
Set Com Addr 002
----------------
Set Com Addr 001
----------------
Enter
Enter
Down
Enter
->Disable Enable Set success
Enter
Enter
Enter
Enter
Enter
NO
->YES COM Addr: 002
Set Addr OK! Current Addr 001
Enter
Parameters set
Fig 6.3.18 is the setting information in second level menu.
Set inverter’s COM address
When communicating with monitoring software or device, the software or device may regard inverter’s COM
address as communication address (Also may use inverter’s serial number as communication address).The COM
address could be assigned. The second level menu “Set COM Addr” of setting is to set inverter’s COM address.
Setting steps:
Input password->Setting->Set COM addr->Set Manual, Current Addr is the current address of inverter. COM
Addr Up adds address. COM Addr Up decreases address. Single knock to change value of fixed address, double
knock enter next manual. Choose YES to save changes, and LCD screen will display “Set Addr OK! Current Addr
XXX”.
Set language
Fig 6.3.18 setting second level menu and its sub-menus
User Manual 38 / 54 CPS Mini Central series
Page 40
Language
Sequence Number
English
0
French
1
Chinese
2
To change inverter’s displaying language, please select Setting->Set language, then LCD screen will display current
language type, single knock to change current language, double knock will save changes and displays “Set
Language OK! Current Language English” see Fig 6.3.6 for reference.
Please note in order to prevent disoperation, system language won’t be change in second level menu “Set
language”, but it will be only if user saves save the choice by double knock and LCD displays “Set OK!”
The inverter provides three languages: English, French and Chinese. The number on Set language interface is
sequence number of these three languages, the sequence number and its corresponding language are shown in
Table6.5.
Table6.5 sequence number of languages
Set inverter time
Inverter provides a system clock; user must set the system time after installation, as the historical statistic data for
a period were based on the clock. User can set the following time parameters: year, month, day, hour, minute.
Set year: Setting->Set time->Set year->Year up or Year down->knock to change year. Thrice knock to exit and save
changes.
Set month: Setting->Set time->Set month->Month up or Month down->knock to change month. Thrice knock to
exit and save changes.
Set date: Setting->Set time->Set date->Date up or Date down->knock to change date. Thrice knock to exit and save
changes.
Set hour: Setting->Set time->Set hour->Hour up or Hour down->knock to change Hour. Thrice knock to exit and
save changes.
Set minute: Setting->Set time->Set minute->minute up or minute down->knock to change minute. Thrice knock to
exit and save changes.
User Manual 39 / 54 CPS Mini Central series
Page 41
6.4 Double MPPT of the CPS Mini Central
The CPS Mini Central includes dual input section to process eight strings with independent MPPT, high speed and
precise MPPT algorithm for real-time power tracking and energy harvesting, as well as transformerless operation
for high performance, the max conversion efficiency is up to 98.2%. The wide input voltage range makes the
inverter suitable to low power operation as well as the high power operation.
As the weather influence and the location of two MPPT PV arrays different, the power of the MPPT A inputs is
different from the power inputs of the MPPT B at the same time, the CPS Mini Central works at a non-symmetrical
input state. But the MPPT algorithm of the inverter makes it tracking the maximum power point of each MPPT
channel to improve the energy utilization of the PV arrays.
User Manual 40 / 54 CPS Mini Central series
Page 42
If you want to update firmware online, please disconnect AC breaker of the
inverter first.
6.5 Communication
6.5.1 Using Solar Power Setup_3P to Update firmware & monitor inverter
About the software -Solar Power Setup_3P , please download from CyberPower official website. For more detail
information about firmware upgrade, please refer to service manual or contact with CyberPower System, Inc.
The connecting diagram as follow:
6.5.2 Monitor the inverters
The inverter provides RS232/RS485 interface to communicate with remote PC or logger. User can monitor the
inverter state via the following types of communication systems. For more detail information, please contact with
CyberPower Systems, Inc.
Monitor the inverters through RS485 interface with software Solar Power Monitoring.
Monitor the inverters through RS485 interface with CPS Data Logger for cloud application.
User Manual 41 / 54 CPS Mini Central series
Page 43
CPS Mini Central series inverters are compatible with Solar-Log 200/500/1000.
CPS Mini Central series inverters are compatible with Meteocontrol WEBlog series.
6.5.3 RS485 cable connection
1. To find out the assembly parts for water-proof RJ45 in the package of accessory, like the following pic.
2. To stump the rubber seal on the head of plug for waterproof.
User Manual 42 / 54 CPS Mini Central series
Page 44
3. To pull the RS485 cable through the RJ45 components, before crimping connector of CAT-5e or CAT-6 onto the RJ45 crystal connector.
4. The connection between crystal connectors and RS485 cable is one-to-one correspondence, one pin of crystal connector to one specific color wire, as shown in the following table and picture.
Pin Definition of RJ45 for RS485 protocol
User Manual 43 / 54 CPS Mini Central series
Page 45
Before you connect the RJ45 crystal connector to the inverter, we are recommending you use the professional tool to check whether the cable is well fixed and working.
Pull cables outwards to confirm whether the installation firm or not.
5. To crimp cable on RJ45 crystal connector then push the connector into water-proof plug.
6. To seal the cable by tightening the end screw of cable gland.
7. Please open the RJ45 protection cover of the RJ45 socket on inverter and connect the RJ45 crystal connector in the inverter port.
8. To tighten the front screw of RJ45 plug onto the socket for water-proof.
User Manual 44 / 54 CPS Mini Central series
Page 46
7 Start-Up and shut down the inverter
7.1 Start-Up the inverter
1. Turn on the AC grid breaker;
2. Turn on the DC switch of the inverter, and the inverter will start automatically when the input voltage is higher
than 300V.
7.2 Shut down the Inverter
1. Turn off the AC grid breaker;
2. Turn off the DC switch of the inverter.
3. Check the inverter operating state.
4. Until the display of LCD goes out, the inverter is shut down.
User Manual 45 / 54 CPS Mini Central series
Page 47
8 Maintenance and Cleaning
Once the output power is derating because of too high warming, some tips can help you solve such problems:
The air grills or cooling fans are clogged. To clean the air grills and cooling fans please refer to 8.1
Cleaning Fans and Grills.
One or two cooling fans failed. To exchange the cooling fans please refer to 8.2 Exchanging Fans. Ventilation of installation location is poor. Choose appropriate installation location before mounting.
8.1 Cleaning Fans and Grills
Maintain fans and grills every half a year to reduce the power derating caused by excessive heat.
If fans or grills are just covered by soft dust particles, using tools such as vacuum cleaner to clean the fans. And if
user has no such tools or there are obstructions in fans, grills or the cooling area of inverter, you need to clean the
fans and grills after they are took apart from the inverter.
1. Please disconnect the DC and AC connection.
Turn off the DC switch. Disconnect the DC terminal. (You might need some tool to disconnect the male and female
terminals)
Disconnect the AC terminal.
2. Remove the protecting plants at the bottom of inverter.
Remove the inverter from mounting bracket, and place inverter horizontally on clean and dry place.
3. Screw off the screws to open the cover with suitable tool, then fans will be seen, as figures below:
Fig 8.1.5
4. Pull out the white connectors with some tinny tools.
User Manual 46 / 54 CPS Mini Central series
Page 48
Fig 8.1.6
5. Take away the fans from the cover and clean them thoroughly.
Fig 8.1.7
6. When finishing cleaning, put back the fans in reverse order.
8.2 Exchange Fan
Sometimes the heat dissipation error occurred because the cooling fans failed, under such situation, you need to
exchange the cooling fans.
The procedure is similar to 8.1 Cleaning Cooling Fan and Grill (Step 1 ~ 6), step 7 should be exchanging the fans and
assembling the inverter in reverse order.
User Manual 47 / 54 CPS Mini Central series
Page 49
9 Trouble shooting
Our quality control program assures that every inverter is manufactured to accurate specifications and is
thoroughly tested before leaving our factory. If you have difficulty in the operation of your inverter, please read
through the following information to correct the problem.
9.1 Error Messages displayed on LCD
An error message will be displayed on the LCD screen when a fault occurs. The faults consist of system fault and
inverter fault.
You may be advised to contact CyberPower in some situation, please provide the following information.
Information concerning the inverter:
Serial number Model number Error message on LCD Short description of the problem Grid voltage DC input voltage Can you reproduce the failure? If yes, how? Has this problem occurred in the past? What was the ambient condition when the problem occurred?
Information concerning the PV panels:
Manufacturer name and model number of the PV panel Output power of the panel Voc of the panel Vmp of the panel Imp of the panel Number of panels in each string
If it is necessary to replace the unit, please ship it in the original box.
User Manual 48 / 54 CPS Mini Central series
Page 50
Error message
Description
Suggestion
AC V Outrange
Utility grid voltage is out of permissible
range.
1. Check grid voltage.
2. Check AC wiring, especially the ground wire.
3. If the error message still exists despite the grid
voltage being within the tolerable range, contact
CyberPower.
AC F Outrange
Utility grid frequency out of permissible
range.
1. Check AC wiring and grid frequency.
2. If the error message is displayed despite the grid
frequency being within the tolerable range, contact
CyberPower
PV Isolation Low
Insulation problem.
1. Check if panel enclosure ground properly.
2. Check if inverter ground properly.
3. Check if the DC breaker gets wet.
4. Check the impedance of PV (+) & PV (-) between
ground (must be more than 1 M ). If the error
message is displayed despite the above checking
passed, contact CyberPower.
Residual I High
Leakage current too high.
1.Restart invert
2. If error message still exists, contact CyberPower.
Output High DCI
Output current DC offset too high.
1. Restart inverter.
2. If error message still exists, contact CyberPower.
PV Voltage High
The DC input voltage is exceeding the
maximum tolerable value.
1. Disconnect the DC wire immediately.
2. Check the voltage of each PV string with
multi-meter.
3. If the voltage of PV string is lower than 980V,
contact CyberPower.
Auto Test Failed
Auto test didn’t pass.
Restart inverter, repeat Auto Test, if problem still
exist, contact CyberPower.
Over Temperature
NTC OPEN or the temperature of
heatsink is too high.
If the ambient temperature of inverter is lower than
60°C , restart invert, if error message still exists,
contact CyberPower.
Warning code
Meanings
Suggestion
Warning100
Fan 1~4 might be damamged.
1. Check whether there is anything above fans,
clear them;
2. Turn off dc switch, rotate fan blade with
screwdriver, and then restart inverter.
3. If Warning still exist, Contact CyberPower.
9.1.1 System fault
System fault (system faults are mainly caused by system instead of inverter, please check the items as instructed
below before replacing inverter).
9.1.2 Inverter warning
User Manual 49 / 54 CPS Mini Central series
Page 51
Warning104
Firmware version does not match.
1. Restart the inverter.
2. If Warning still exist, Contact CyberPower.
Error code
Meanings
Suggestion
Error: 101
Communication board has not received
data from control board for 10 seconds.
Electromagnetic Interference cause
communication problem.
1. Restart inverter by cutting off DC supply, and
Error message will disappear.
2. If the error 101 is often displayed, the
environment Electromagnetic Interference is too
strong. Contact CyberPower.
Error: 117
Relay fault.
Restart inverter, if problem still exist, Contact
CyberPower.
Error: 119
GFCI module fault.
(Ground Fault Circuit Interrupter)
Restart inverter, if problem still exist, Contact
CyberPower.
Error: 121
Communication fault.
Restart inverter, if problem still exist, Contact
CyberPower.
Error: 122
Bus voltage fault.
Restart inverter, if problem still exist, Contact
CyberPower.
Error: 125
PV ISO fault.
(Low isolation)
1. Refer the suggestion of error PV Isolation Low.
2. If problem still exist, Contact CyberPower.
Error: 126
High GFCI
Restart inverter, if problem still exist, Contact
CyberPower.
Error: 127
High DCI
1. Refer the suggestion of error Output High DCI.
2. If problem still exist, Contact CyberPower.
Error: 128
High PV voltage
1. Refer the suggestion of error PV Voltage High.
2. If problem still exist, Contact CyberPower.
Error: 129
Grid voltage fault.
1. Refer the suggestion of error AC V Outrange.
2. If problem still exist, Contact CyberPower.
Error: 130
Grid frequency fault.
1. Refer the suggestion of error AC F Outrange.
2. If problem still exist, Contact CyberPower.
9.1.3 Inverter fault
User Manual 50 / 54 CPS Mini Central series
Page 52
Danger of burn injuries due to hot enclosure parts!
Wait 20 minutes before disassembling until the housing has cooled down.
10 Decommissioning
10.1 Dismantling the Inverter
1. Disconnect the inverter as described in section 7.
2. Remove all connection cables from the inverter.
3. Screw off all projecting cable glands.
4. Lift the inverter off the bracket and unscrew the bracket screws.
10.2 Packing the Inverter
If possible, always pack the inverter in its original carton and secure it with tension belts. If it is no longer available,
you can also use an equivalent carton. The box must be capable of being closed completely and made to support
both the weight and the size of the inverter.
10.3 Disposing of the Inverter
Do not dispose of faulty inverters or accessories together with household waste. Please
accordance with the disposal regulations for electronic waste which apply at the installation site at
that time. Ensure that the old unit and, where applicable, any accessories are disposed of in a
proper manner.
User Manual 51 / 54 CPS Mini Central series
Page 53
CPSPV30000ETL
CPSPV33000ETL
CPSPV40000ETL
Input (DC)
Max. DC power
34500 W
36300 W
44000 W
Max. input voltage
1000 V
1000 V
1000 V
MPP voltage range / Rated input voltage
460...800 V / 600 V
460...800 V / 600 V
550...800 V / 700 V
Min. input voltage / initial input voltage
250/300 V
250/300 V
250/300 V
Max. input current
35/35 A
38/38 A
38/38 A
Number of MPP input / strings per MPP input
2 / 4
2 / 4
2 / 4
Output (AC)
Rated AC power
30000 W
33000 W
40000 W
Max apparent AC power
30000 VA
33000 VA
40000 VA
Max. output current
45.5 A
50.0 A
50.0 A
Nominal AC voltage
3/N/PE, 220/380 V, 230/400 V, 240/415 V
3/PE, 277/480 V
Rated frequency
50 Hz, 60 Hz
Cos phi
0.9 over-excited … 0.9 under-excited
Feed-in phases
3
Efficiency
Max efficiency
98.2 %
98.2 %
98.2 %
Euro-eta
97.6 %
97.7 %
97.8 %
MPPT efficiency
99.5 %
99.5 %
99.5 %
General Data
Dimensions(W/H/D)
551/740/276 mm
Weight
61.6kg
Operating temperature
–20 °C ... +60 °C
Storage temperature
–20 °C ... +70 °C
Noise emission
≤ 55 dB(A)
Night consumption
<0.5 W
Topology
Transformer-less
Cooling concept
Smart cooling
Protection Class
IP65
11 Specification
11.1 Specification of CyberPower Mini Central Series
User Manual 52 / 54 CPS Mini Central series
Page 54
Relative humidity
0...100 % (non-condensing)
Features
DC connection
H4/MC4(opt)
H4/MC4(opt)
H4/MC4(opt)
AC connection
Screw terminal
Screw terminal
Screw terminal
Display
LCD
LCD
LCD
RS232/RS485
yes/yes
yes/yes
yes/yes
Warranty: 5/10 years
yes /opt
yes /opt
yes /opt
Certificates
VDE 0126-1-1, VDE 0126-1-1/A1, VFR 2014
CE, IEC 62109
EN61000-6-2 / EN61000-6-3 / EN61000-3-11 /
EN61000-3-12
Enclosure lid screws
1.3Nm(10.8 1bf.in)
Shell and RS232 screws
0.7Nm(6.2 1bf.in)
AC terminal
1.8Nm(16.0 1bf.in)
M6 socket head cap screws for securing the enclosure at the bracket
2Nm(18 1bf.in)
Additional ground screws
2Nm(18 1bf.in)
Fans screws
1Nm(9.0 1bf.in)
Model
Certificates
CPSPV30000ETL
IEC 62109, VDE0126-1-1, VDE0126-1-1/A1, VFR 2014, CE
CPSPV33000ETL
IEC 62109, VDE0126-1-1, VDE0126-1-1/A1, VFR 2014, CE
CPSPV40000ETL
IEC 62109, VDE0126-1-1, VDE0126-1-1/A1, VFR 2014, CE
11.2 Torque Values
12 Certificates
CPS Mini Central series inverters are designed to use worldwide, hence the inverters meet different safety
standards of variety countries and regions.
13 Contact
If you have technical problems concerning our products, contact your installer or CyberPower. During inquiring,
please provide below information:
User Manual 53 / 54 CPS Mini Central series
Page 55
1. Inverter type
2. Modules information
3. Communication method
4. Serial number of Inverters
5. Error code of Inverters
6. Display of inverter
CyberPower Systems, Inc.
6F, No.32, Sec.1, Chenggong Rd.,
Nanggang District, Taipei 115, Taiwan (R.O.C.)
Serviceline
TEL: +886-2-2651-8699
FAX: +886-2-2651-6821
E-mail: service@cpsww.com.tw
User Manual 54 / 54 CPS Mini Central series
Loading...