IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual
thoroughly before attempting to unpack, install, or operate the Maintenance Bypass PDU (MBP).
CAUTION! The MBP must be connected to a grounded AC power
outlet with a fuse or circuit breaker protection. DO NOT plug the MBP into
an outlet that is not grounded.
CAUTION! The MBP should be placed near the connected equipment
and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a
temperature and humidity controlled indoor area, free of conductive
contaminants. (Please see specifications for acceptable temperature and
humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric shock, do
not remove the cover. There are no user serviceable parts inside. Seek
service from qualified service personnel.
CAUTION! To reduce the risk of fire, connect the MBP to a branch
circuit with 15 amperes (MBP15A6) / 20 amperes (MBP20A6) / 30
amperes (MBP30A5) maximum over-current protection in accordance
with the National Electric Code, ANSI/NFPA 70.
CAUTION! The AC outlet, where the MBP is connected, should be
close to the unit and easily accessible.
CAUTION! Only use UL-marked power cords, (e.g. the power cords on
you equipment), to connect the MBP to an AC outlet.
CAUTION! Only use UL-marked power cords to connect any
equipment to the MBP.
CAUTION! Only qualified maintenance personnel should install a MBP.
CAUTION! Do not unplug the unit from AC Power during operation, as
this will remove the ground connection.
CAUTION! To avoid electric shock, turn off and unplug the unit before
installing the input/output power cord with a ground wire. Connect the
ground wire prior to connecting the line wires!
CAUTION! Do not use an improper sized power cord as it may cause
damage to your equipment and cause fire hazards.
CAUTION! Wiring must be done by qualified personnel.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT
EQUIPMENT! Under no circumstances should this unit should be used
for medical applications involving life support equipment and/or patient
care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce
the risk of fire, do not use with or near aquariums. Condensation from the
aquarium can come in contact with metal electrical contacts and cause
the equipment to short out.
CAUTION! The unit has a dangerous amount of voltage. When the
MBP indicators is on, the units may continue to supply power thus the
unit’s outlets may have a dangerous amount of voltage even when it’s not
plugged in to the wall outlet.
CAUTION! Make sure everything is turned off and disconnected
completely before conducting any maintenance, repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety conductor before
any other cables are connected.
CAUTION! Never install a MBP, or associated wiring or equipment,
during a lightning storm.
CAUTION! Do not work alone under hazardous conditions.
DO NOT INSTALL THE MBP WHERE IT WOULD BE EXPOSED TO
DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR
DRYERS TO MBP OUTPUT SOCKETS!
Copyright © 2014 CyberPower Systems, Inc.
User’s manual Registration card
Rackmount brackets (2)
15A / 20A or 30A MBP
(Maintenance Bypass PDU)
Flat head screws: M4X8L (4)
Pan head screws: M5X12L (4)
Copyright © 2014 CyberPower Systems, Inc.
HARDWARE INSTALLATION
The MBP can be mounted in a rackmount or vertical tower orientation. Please follow the instructions below for the respective mounting methods.
Step 1: Brackets installation
Attach the two brackets to the MBP using the provided screws M4X8L*4pcs.
Step 2: MBP Installation
Secure the MBP to the rack, CyberPower rack mounted UPS, or a wall with the provided screws M5X12L*2pcs
MBP mounted horizontally in a rackmount
MBP mounted with a CyberPower UPS in rackmount mode
Copyright © 2014 CyberPower Systems, Inc.
MBP mounted vertically in a rackmount
MBP mounted with a CyberPower UPS in tower mode
Copyright © 2014 CyberPower Systems, Inc.
Wall-mounted