FUNCTION TREE .............................................................................................................................................. 1 5
MAIN MENU: FUNCTION SELECT ............................................................................................................... 1
EVENT CODE LIST ............................................................................................................................................ 24
LCD WORD INDEX ............................................................................................................................................ 26
APPENDIX - LCD WORD COMPARISON TABLE ............................................................................34
Page 4
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions. Please read and follow all instructions
carefully during installation and operation of the unit. Read this manual thoroughly before
attempting to unpack, install, or operate the UPS.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit
breaker protection. DO NOT plug the UPS into an outlet that is not grounded. If you need to
power-drain this equipment, turn off and unplug the unit.
CAUTION! The battery can power hazardous components inside the unit, even when the AC
input power is disconnected.
CAUTION! The UPS should be placed near the connected equipment and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity
controlled indoor area, free of conductive contaminants. (Please see specifications for
acceptable temperature and humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric shock, do not remove cover. No user
serviceable parts inside. Refer servicing to qualified service personnel.
CAUTION! (Non-Isolated Battery Supply): Risk of electric shock, battery circuit is not
isolated from AC power source; hazardous voltage may exist between battery terminals and
ground. Test before touching.
CAUTION! To reduce the risk of fire, connect the UPS to a branch circuit with 10 amperes (1000
/ 1500 / 2000) / 16 amperes (3000) maximum over-current protection in accordance to CE
requirement.
CAUTION! The AC outlet where the UPS is connected should be close to the unit and easily
accessible.
CAUTION! Please use only VDE-tested, CE-marked mains cable, (e.g. the mains cable of your
equipment), to connect the UPS to the AC outlet.
CAUTION! Please use only VDE-tested, CE-marked power cables to connect any equipment
to the UPS.
CAUTION! When installing the equipment, ensure that the sum of the leakage current of the
UPS and the connected equipment does not exceed 3.5mA.
CAUTION! The 1000 / 1500 / 2000 / 3000 / Battery module models are only qualified
maintenance personnel may carry out installations.
CAUTION! Do not unplug the unit from AC Power during operation, as this will invalidate the
protective ground insulation.
CAUTION! To avoid electric shock, turn off and unplug the unit before installing the input/
output power cord with a ground wire. Connect the ground wire prior to connecting the line
wires!
CAUTION! Do not use an improper size power cord as it may cause damage to your
equipment and cause fire hazards.
CAUTION! Wiring must be performed by qualified personnel.
1
Page 5
IMPORTANT SAFETY INSTRUCTIONS
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no
circumstances this unit should be used for medical applications involving life support
equipment and/or patient care.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use
with or near aquariums. Condensation from the aquarium can come in contact with metal
electrical contacts and cause the machine to short out.
CAUTION! Do not dispose of batteries in fire as the battery may explode.
CAUTION! Do not open or mutilate the battery, released electrolyte is harmful to the skin and
eyes.
CAUTION! A battery can present a risk of electric shock and high short circuit current. The
following precaution should be observed when working on batteries
• Remove watches, rings or other metal objects.
• Use tools with insulated handles.
CAUTION! The unit has a dangerous amount of voltage. When the UPS indicators is on, the
units may continue to supply power thus the unit’s outlets may have a dangerous amount of
voltage even when it’s not plugged in to the wall outlet.
CAUTION! Make sure everything is turned off and disconnected completely before
conducting any maintenance, repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety conductor before any other cables are
connected.
WARNING! (Fuses): To reduce the risk of fire, replace only with the same type and rating of
fuse.
DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR
NEAR A STRONG HEAT SOURCE!
DO NOT BLOCK OFF VENTILATION OPENINGS AROUND THE HOUSING!
DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS OUTPUT
SOCKETS!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR SUPERVISED BY PERSONNEL
KNOWLEDGE OF BATTERIES AND THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED
PERSONNEL AWAY FROM BATTERIES!
2
Page 6
UNPACKING
UPS
User’s manual
Phone cable
M5 nut (8)Machine screw with
Input power cordOutput power cord(s)USB communication cable
Flat head screws:
M4X8L (8)
round washer:
M4X8L (6)
Pan head screws:
M5X12L (12)
Rackmount ears
(Stands) (2)
Rackmount rails (2)
Plastic washers (12)
Screw hole dust
covers (8)
PowerPanel® Business software is available on our website.
Please visit www.cyberpower.com and go to the Software Section for free download.
3
Page 7
HARDWARE INSTALLATION
3U
2U
1U
position 9
position 8
position 7
position 6
position 5
position 4
position 3
position 2
position 1
position 3
position 1
HARDWARE INSTALLATION
These versatile UPS systems can be mounted in a rackmount or vertical tower orientation. This
versatility is especially important to growing organizations with changing needs that value
having the option to position a UPS on a floor or in a rackmount system. Please follow the
instructions below for the respective mounting methods.
CAUTION! To prevent the risk of fire or electric shock, only use the supplied hardware to
attach the mounting brackets
RACKMOUNT INSTALLATION
Step 1: Rackmount ears installation
Attach the two rackmount ears to the UPS using the provided screws M4X8L*8pcs.
Step 2: Rackmount rails installation
(1) The rails adjust to mount in 48-cm (19-inch) panel racks from 46.4 to 73.8cm (18.3 to 29
inches) deep. Select the proper holes in the rack for positioning the UPS in the rack. The rails
take up position 1 through position 3.
(2) Attach the rackmount rail to your rack with two M5X12L screws, two plastic washers, and
two M5 nuts at the front of the rack. (Located in position 1 & position 3; It can also be located
in position 1 & position 2 or position 2 & position 3 alternatively). Do not tighten the screws.
Adjust the rail length on the rail assembly of your rack. Secure the rail to the rear of the rack
with two M5X12L screws, two plastic washers, and two M5 nuts. Tighten all screws at the
front and rear of the rail. Once completed, perform the same steps for assembling the other
rackmount rail.
(1) (2)
4
Page 8
HARDWARE INSTALLATION
Step 3: Install the UPS on the rack
Place the UPS onto the rackmount rails with the front of the unit facing you. Secure the UPS to
your rack with four M5X12L screws at the front of the rack. (Located in position 2 & position 5).
position 5
position 2
position 3
position 1
VERTICAL/TOWER INSTALLATION
Step 1: Rotate the multifunction LCD module
(1) Unscrew the right panel of the UPS. Separate the right panel from the UPS.
(2) Unscrew the LCD plate; gently lift the LCD module out. Rotate it to the tower orientation.
Reinstall it for a tower configuration. Attach the LCD plate and LCD module to the right panel
using the provided screws.
(1)
Step 2: Attach the base stands
Tighten the screws (M5X12*4pcs) of the base stands (rackmount ears) onto the bottom of the UPS
Step 3: Attach dust covers
Insert dust covers into the rackmount ear screw holes that are not being used.
23
(2)
1
2
3
4
5
Page 9
HARDWARE INSTALLATION
SAFETY PRECAUTIONS
CAUTION! Installation environment should be in a temperature and humidity controlled
indoor area free of conductive contaminants. Do not install this UPS where excessive moisture
or heat is present (Please see specifications for acceptable temperature and humidity range).
CAUTION! Never install a UPS, or associated wiring or equipment, during a lightning storm.
CAUTION! Do not work alone under hazardous conditions.
CAUTION! In case of the risk of electric shock, do not remove the top cover.
CAUTION! The battery can energize hazardous live parts inside even when the AC input
power is disconnected.
6
Page 10
INSTALLING YOUR UPS SYSTEM
SYSTEM BLOCK DIAGRAM
BYPA SS
InputOutput
Line Mode
Battery Mode
Bypass Mode
Control Signal
Input
Filter
Charger
AC/DC
PFC
AC/DC
Battery
BUS
DC/DC
Inverter
DC /AC
Control
&
Monitoring
INV
RLY
LCD
Module
USB&DB9
SNMP
Slot
Output
Filter
HARDWARE INSTALLATION GUIDE
1. Battery charge loss may occur during shipping and storage. Before using the UPS, it’s
strongly recommended to charge batteries for five hours to ensure the batteries’ maximum
charge capacity. To recharge the batteries, simply plug the UPS into an AC outlet.
2. When using the included software, connect either the serial or the USB cable between the
computer and the corresponding port on the UPS. Note: If the USB port is used, the serial
port will be disabled. They cannot be used simultaneously.
3. Connect your computer, monitor, and any externally-powered data storage device (Hard
drive, Tape drive, etc.) into the outlets only when the UPS is off and unplugged. DO NOT
plug a laser printer, copier, space heater, vacuum, paper shredder or other large electrical
device into the UPS. The power demands of these devices will overload and possibly
damage the unit.
4. To protect a fax machine, telephone, modem line or network cable, connect the telephone
or network cable from the wall jack outlet to the jack marked “IN” on the UPS and connect
a telephone cable or network cable from the jack marked “OUT” on the UPS to the modem,
computer, telephone, fax machine, or network device.
5. Press the ON/OFF switch to turn the UPS on. If an overload is detected, an audible alarm
will sound and the UPS will continuously emit one beep per second. For resetting the unit,
unplug some equipment from the outlets. Make sure your equipment carries a load current
within the unit’s safe range, (refer to the technical specifications).
6. This UPS is equipped with an auto-charge feature. When the UPS is connected to an AC
outlet, the battery will automatically charge, even when the unit is switched off.
7
Page 11
INSTALLING YOUR UPS SYSTEM
7. To maintain an optimal battery charge, leave the UPS connected to AC electrical service at
all times.
8. Before storing the UPS for an extended period of time, turn the unit OFF. Then cover it
and store it with the batteries fully charged. Recharge the batteries every three months to
ensure good battery capacity and long battery life. Maintaining a good battery charge will
help prevent possible damage to the unit from battery leakage.
9. The UPS has one USB port (default) and one Serial port that allow connection and
communication between the UPS and any attached computer running the PowerPanel®
Business Edition Agent software. The UPS can control the computer’s shutdown during a
power outage through the connection while the computer can monitor the UPS and alter
various programmable parameters. Note: Only one communication port can be used at
a time. The port not in use will automatically become disabled or the serial port will be
disabled if both ports are attached.
10. EPO (Emergency Power Off) / ROO (Remote on/off) Port: EPO/ROO ports allow
administrators the capability to connect the UPS unit to customer-supplied EPO/ROO
switches. If EPO is enabled, these installations give operators a single access point to
immediately power-off all equipment connected to the UPS during an emergency. If ROO is
enabled, these installations give operators an access point to turn on/off UPS remotely.
11. To avoid electric shock, turn the unit OFF and disconnect the unit from utility power before
hardwiring the UPS (in/out power cord). The in/out power cord MUST be grounded.
1. Power On/Off Button
Master ON/OFF switch for the UPS.
2. Function Buttons
Scroll DOWN, scroll UP, and ENTER.
3. UPS Status / Multifunction LCD Readout
Shows UPS status, information, settings and events.
4. Battery Backup & Surge Protected Outlets
Provide battery backup and surge protection. They ensure power is provided to connected
equipment over a period of time during a power failure.
5. AC Input Inlet
Connect the AC Power cord to a properly wired and grounded outlet.
6. Input Circuit Breaker
Provide input current overload and fault protection.
7. Serial Port
Serial port provides RS-232 communication between the UPS and the computer. The UPS
can control the computer’s shutdown during a power outage through the connection while
the computer can monitor the UPS and change its various programmable settings.
8. USB Port
This is a connectivity port which allows communication and control between the UPS and
the connected computer. It is recommended to install the PowerPanel® Business Agent
software on the PC/Server connected with the USB cord.
9
Page 13
OVERVIEW
9. EPO (Emergency Power Off) Connector
Enables an emergency UPS power-off from a remote location.
10. Surge Protected Communication Ports RJ-45/RJ-11
These ports are used to protect standard RJ-45/RJ-11 based products (ADSL, LAN, Phone/
Modem-Lines) and cabling systems from surges.
11. EBM Detection Connector
Provide External Battery Module detection function.
12. Relay Output Connector
Convert UPS signals into real potential-free Dry Contacts for industrial control.
13. SNMP/HTTP Network Slot
Slot to install the optional SNMP card for remote network control and monitoring.
14. Extended Runtime Battery Module Connector
Connection for additional CyberPower Battery modules.
10
Page 14
OVERVIEW
BATTERY MODULE FRONT/REAR PANEL DESCRIPTION
1243
BPSE24V40ART2U/BPSE48V40ART2U/BPSE72V40ART2U
1. Input Connector
Use this input Connector to connect the Battery module to the Power module or to the next
Battery module.
2. On-board Replaceable Fuse Cover
Replaceable fuse is accessible from the rear panel. It must be done by qualified personnel.
3. Output Connector
Use this output connector to daisy chain the next Battery module. Remove the connector
cover for access.
4. Automatic Detection of Extended Battery Module Connector
Connect to UPS for automatic detection of battery modules.
CONNECTION 1:
POWER MODULE WITH ONE BATTERY MODULE
Use the battery cable of the Battery module to connect the Battery module to the Power module.
CONNECTION 2:
POWER MODULE WITH MULTIPLE BATTERY MODULES
Step 1: Connect the first Battery module to the Power module via battery cable.
Step 2: Use the battery cable to connect the second Battery module to the first Battery module.
11
Page 15
UPS SYSTEM STARTUP
After completing the hardware installation of the UPS, you are now ready to connect the UPS
and connect your equipment.
To start the UPS:
1. Verify that the UPS input cable or terminal blocks are connected to AC source.
2. The UPS LCD shows “Standby Mode” and fans turn on.
3. Press the ON/OFF button on the UPS front panel for at least 3 seconds to turn on the UPS.
4. UPS will perform a brief self-test lasting about 15 seconds. The LCD will be lighted up during
this time.
5. The UPS is operating in Battery Mode first then transfer to Line Mode if Input power is
qualification and powering the output.
23 4
12
Page 16
USING THE UPS SYSTEM
LCD PANEL
ITEM BUTTONFUNCTION DESCRIPTION
1ON/OFF
2DOWN Press this button to scroll down in the LCD menu.
3UPPress this button to scroll up in the LCD menu.
4ENTER Press this button to select an option.
Silencing the alarm:
Press any button to silence the alarm. If the alarm status changes,
4213
LCD Display introduction:
There are 4 display Zones: ICON, CONTENT, EVENT CODE/INDEX and TOPOLOGY.
ICON ZONE
CONTENT ZONE
the alarm will override the previous alarm silencing and will beep again.
Press this button for at least 3 seconds to turn
on or turn off UPS.
EVENT CODE/
INDEX ZONE
TOPOLOGY ZONE
ICON ZONE:
In the top area, there are 6 ICONS for displaying the UPS working status, Fault (Warning) and Mute.
CONTENT ZONE:
The Content area is on the middle screen.
The top of Content area is for displaying UPS Menu.
The bottom area is the UPS status which depends on different UPS status to provide different
information included Input / Output / Battery / Load parameters. Please find LCD WORD
COMPARISON TABLE on page 34 for reference.
EVENT CODE/INDEX ZONE:
In the upper right corner of the Content area, there are two seven-segment displays to show
the event code when UPS fault. Besides, this area will show the index of setup, event and
information menu.
TOPOLOGY ZONE:
The Content area is on the bottom screen.
In this area, there are 6 TOPOLOGYS for displaying the UPS working status. The topology will
be lighted up when the area is working.
UPS is operating in Line Mode.
The UPS is operating and protecting
the equipment normally.
Battery Mode
UPS is operating in Battery Mode.A
utility power failure has occurred.
The UPS is using battery power to
work and protect the equipment.
Bypass Mode
UPS is operating in Bypass Mode.A
Warning or Fault has been detected
and the UPS transfers output to
utility power.
ECO ModeUPS is operating in ECO (Economy)
UPS STATUSSTATUS DESCRIPTION
Fault (Warning)
Mute
Mode. If Bypass quality is within the
ECO mode setting specifications,
the UPS will operate in Bypass until
input power is disqualified per set
specifications. At that time the UPS
will automatically switch to Line
Mode.
A Warning or Fault has been detected and the UPS transfers output to
utility power.
The audible alarm is disabled.
14
Page 18
FUNCTION TREE
USING THE UPS SYSTEM
Menu
Status
Output Voltage
Output Frequency
Input Voltage
Input Frequency
Output Load
Output Ampere
Output Watt
Output VA
Load Energy
Battery Voltage
Battery Capacity
Battery Runtime
Setup
Output Voltage
Sync Frequency Window
Bypass V Window
Bypass Condition
ECO Mode
Manual Bypass
Audible Alarm
EBM Number
Generator Mode
Communication
Converter Mode
Screen Saver
Clear Event Log
Signal Input
Dry Relay Function
Reset Replace Battery
IP Address
Reset Load Energy
Battery Test
Alarm Test
Indicator Test
Fan Test
Date & Time
Automatic Restore
Mandatory Power Cycle
Recharged Delay Time
Recharged Capacity
Startup Delay
Period Battery Test
Low Battery Threshold
Low Runtime Threshold
Outlet Group
ESC
Event Logs
Log Item 1
Log Item 2
Log Item 3
Log Item 4
Log Item 5
Log Item 6
Log Item 7
Log Item 8
Log Item 9
Log Item 10
Log Item 11
Log Item 12
ESC
Information
EBM Number
UPS Rating
MCU Version
Model Name
Date & Time
Next Battery Change
IP Address
Subnet Mask
Gateway
MAC
ESC
15
Page 19
USING THE UPS SYSTEM
MAIN MENU: FUNCTION SELECT
1. Press the "ENTER" button in the Status function or select the "ESC" selection in the Setup/
Event/Info function to enter the Main Menu.
2. The function block will blink when enter the Main Menu.
3. Press the "UP" and "DOWN" buttons to select the function.
4. Press the "ENTER" button to enter the selected function.
The Main Menu has 4 icons of different function listed in the table below.
FUNCTION SELECT MENUICONDESCRIPTION
UPS STATUSDisplays the UPS status.
SET UP
EVENT LOGS
INFORMATIONDisplays the UPS information.
(1) STATUS
There are 12 types of UPS status Readout available for display.
1. Select “UPS Status” Icons
2. Press the “ENTER” button to enter the “UPS Status”.
3. Press the “UP” and “DOWN” buttons to scroll through the “UPS Status” items shown in the
table below.
4. Press the “ENTER” button to return to the Main Menu.
UPS STATUS ITEMSDATA DISPLAYEDDESCRIPTION
OUTPUT VOLTAGE= XXX.XVDisplays the Output Voltage
OUTPUT
FREQUENCY
INPUT VOLTAGE= XXX.XVDisplays the Input Voltage
INPUT FREQUENCY= XX.XHzDisplays the Input Frequency
OUTPUT LOAD= XXX%
OUTPUT CURRENT= X.XADisplays the Output Current
OUTPUT WATT= XXXXWDisplays the Output Wattage
= [XX.XHz] /
[CXX.XHz] /
[nXX.XHz]
Displays the UPS Set Up items that can
be configured by the user.
Displays the 12 most recent events, by
event count, time (Year/Month/Day
Hour: Minute), and event description.
Displays the Output Load as a Percentage
of Maximum Load
16
Page 20
USING THE UPS SYSTEM
UPS STATUS ITEMSDATA DISPLAYEDDESCRIPTION
OUTPUT VA= XXXXVADisplays the Output VA
LOAD ENERGY
BATTERY VOLTAGE= XXX.XVDisplays the Battery Voltage
BATTERY CAPACITY = XXX%
BATTERY RUNTIME= XXXM
Example : Output Voltage 230.0V
=[XXXWh]/
[XXXXKWh]/
[XXXXKKWh]
Display UPS Load Energy Consumption.
[XXXWh] represents the load energy < 1kWh.
[XXXXKWh] represents the load energy
>999Wh and < 1kKWh.
Displays the Estimated Percentage of Battery
Capacity
Displays the Estimated Battery Runtime in
Minutes
17
Page 21
USING THE UPS SYSTEM
(2) SET UP
There are 32 UPS items that can be Set Up by the user.
1. Press the “UP” and “DOWN” buttons to select the “SETUP” ICON.
2. Press the “ENTER” button to enter the “SETUP” function.
3. Press the “UP” and “DOWN” buttons to scroll to the “SETUP” option.
4. When selecting the submenu item, the code number will be exhibited.
5. Press the “ENTER” button to select the “SETUP” submenu items shown in the table below.
6. Press the “UP” and “DOWN” buttons to scroll through the different parameters.
7. Press the “ENTER” button to select the parameter you want to set up.
8. You may be prompted “Save” to save the selection, if so press the “ENTER” button to save
the setting. Some options are saved and started automatically. (See the following table and
screen for additional details.)
9. Press the “ESC” to cancel or return to the previous SET UP menu.
INDEXSET UP ITEMSAVAILABLE SETTINGS
01Output Voltage
Sync Freq
02
Window
Bypass V
03
Window
Bypass
04
Condition
=[208V] [220V] [230V] [240V]
Sets UPS output voltage
Range= [+/- 1%] [+/- 2%] [+/-3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%]
Sets output synchronization frequency range
If input line frequency is outside this range, the UPS
will lock in at the nominal frequency.
Range= [+10%][+15%] / [-10%][-15%][-20%]
Sets Bypass Voltage range
[Check Freq/Volt] [Check Volt Only] [No Bypass]
Bypass Condition:
The default setting [Check Freq/Volt] means the UPS
will check the following specifications (1) and (2) when
UPS has fault and needs transfer to Bypass.
The setting [Check Volt Only] means the UPS will check
the following specification (1) when UPS has fault and
needs transfer to Bypass.
(1) Bypass voltage is inside the range of "Bypass V
Window".
(2) Bypass frequency is inside the range of "Sync
Freq Range".
The setting [No Bypass] means the UPS is forbidden to
transfer to Bypass when UPS has fault.
DEFAULT
SETTING
230V
+/- 5%
+10%/-15%
Check
Freq/Volt
18
Page 22
USING THE UPS SYSTEM
INDEXSET UP ITEMSAVAILABLE SETTINGS
[Disable] [Voltage= +/-15%] [Voltage = +/-10%]
When ECO mode is enabled the UPS will check the
05ECO Mode
06Manual Bypass
07Audible Alarms
08EBM Number
09Generator Mode
10Communication
Converter
11
Mode
12Screen Saver
13Clear Event Log
14Signal Inputs
following specifications of Bypass quality
(1) Bypass voltage is inside the [V Range= +/-10%]
(default setting) or [V Range= +/-15%].
(2) Bypass frequency is inside the +/-3Hz range of
output nominal frequency.
[Disable] [Enable]
When performing UPS maintenance, the user can
manually transfer the connected load to Bypass without
interrupting the output to the connected equipment.
[Disable] [Enable] [Only Bat Low]
User can [Disable] or [Enable] the buzzer sound.
[0] [1] [2] [3] [Auto]
Sets the actual EBM (extended battery modules)
number to get the correct estimated runtime.
[Disable] [Enable]
When the UPS input power source is a generator set
the UPS will operate normally without transferring
to Battery Mode when this is [Enable].
[Disable] [Enable]
All communication ports on the UPS are [Disable]
or [Enable]
[Disable][Output Freq = 50Hz] [Output Freq = 60Hz]
Sets [Output Freq = 50Hz] [Output Freq = 60Hz]
to convert the input frequency to required output
frequency.
[Disable] [1 Minute] [5 Minutes]
Sets the amount of time the LCD screen stays on
after no user input. The [Disable] option keeps the
LCD screen on at all times.
[Activate?]
Clears all the events stored in the LCD Control Panel
Event Log.
[Disable] [EPO] [ROO]
Sets [EPO] (Emergency Power Off) to shutdown
the UPS remotely when the contact is open.
Sets [ROO] (Remote On/Off) to turn On the UPS
remotely when the contact is close and turn Off the
UPS remotely when the contact is open. The On/Off
power button on front panel will be disabled when
set to [ROO].
DEFAULT
SETTING
Disable
Disable
Enable
Auto
Disable
Enable
Disable
5 Minutes
None
Disable
19
Page 23
USING THE UPS SYSTEM
INDEXSET UP ITEMSAVAILABLE SETTINGS
Dry Relay
15
Function
Reset Replace
16
Battery
17IP Address
Reset Load
18
Energy
19Battery Test
20Alarm Test
21Indicator Test
22Fan Test
23Date & Time
Automatic
24
Restore
Mandatory
25
Power Cycle
Recharged
26
Delay Time*
Recharged
27
Capacity*
[I/P Power Fail] [Battery Low] [Summary Alarm]
[UPS On Bypass] [UPS Fail]
Sets the Dry Relay Function output.
[Clear] [Setup]
Manually reset the Battery Replacement date.
[DHCP] [Manual]
Select [Mode:Manual] to set IP Address,Subnet
Mask and Gateway to network interface (RMCARD)
or select DHCP to set automatically.
[Activate]
Reset Load Energy Consumption (KWH) value.
[Activate]
Starts a manual battery test, UPS will operate 10
seconds on Battery mode to check battery condition.
[Activate]
Starts a manual Alarm test, buzzer will sound for 5
seconds.
[Activate]
Starts a manual Indicator test.
[Activate]
Starts a manual Fan test, UPS will operate fan with full
speed 5 seconds.
[----] [--.--] [--:--]
set Year/Month/Day Hour: Minute: Second to UPS
or get Date & Time from PPBE (Agent) or RMCARD
automatically.
[Disable] [Enable]
User can [Disable] or [Enable] the auto restart function.
[Disable] [Enable]
User can [Disable] or [Enable] the Mandatory power
cycle function.
When the utility power restores, the UPS will delay
the restoration of output power.
29
30
31
Period Battery
Te s t
Low Battery
Threshold**
Low Runtime
Threshold**
[Disable][1 Week][2 Weeks] [3 Weeks] [4 Weeks]
Sets the battery test period.
[20%][25%] [30%][35%][40%][45%][50%][55%]
[60%][65%]
Sets the capacity to alarm battery low.
[0 Minute][1 Minute][2 Minutes][3 Minutes]......
[29 Minutes][30 Minutes]
Sets the Runtime to alarm battery low.
Disable
20%
5 Minutes
[On] [Off]
32Outlet Group
Sets Non-Critical Load (NCL) [On] or [Off] directly. When
the user sets NCL [Off], the NCL output power will turn
On
off directly.
* UPS will restore output when reaches the setting of “26. Recharged Delay Time” and “27. Recharged Capacity” at
the same time.
** The battery low alarm triggers when “30. Low Battery Threshold” or “31. Low Runtime Threshold” is reached.
Example: Index 01, SETUP: Output Voltage to 220V then press enter to save the setting.
21
Page 25
USING THE UPS SYSTEM
(3) EVENT LOGS
The UPS will record the 12 most recent system events in the Event Log.
1. Select “EVENT” Icons.
2. Press the “ENTER” button to enter the “Event Logs”.
3. Press the “UP” and “DOWN” buttons to scroll through the “Event Logs”. The UPS will record
events listed in the table below.
INDEXEVENT DISPLAYEDDESCRIPTION
XX Event ContentEvent description [Please check the Event Code List.]
4. When selecting the submenu item, the index which represents the sequence will be exhibited.
5. Press the “ENTER” button to see the event code and event date/time.
INDEXEVENT DISPLAYEDDESCRIPTION
Event Code Number :
[C-XX]
[C-XX]
XX
(XXD)(XXH)(XXM) /
[- - - -] [--.--] [--:--]
Event date and time :
(XXD)(XXH)(XXM) (without PowerPanel® Business or
RMCARD)
[- - - -] [--.--] [--:--] [Year][Month. Day][Hour: Minute]
(with PowerPanel® Business or RMCARD)
6. Press the “ESC” to return to the Main Menu.
Example: Event 1: Battery Failure / 21min ago
22
Page 26
USING THE UPS SYSTEM
(4) INFORMATION
There are 10 UPS Information items that can be tested by the user.
1. Select “INFO” Icons.
2. Press the “ENTER” button to enter the “INFO”.
3. Press the “UP” and “DOWN” buttons to scroll through the “INFO” items shown in the table
below.
4. Press the “ESC” to return to the Main Menu.
INDEX
Example: Index 1, EBM Number=0
INFORMATION
ITEMS
01EBM NumberX
02UPS RatingXXXXVA/XXXXWDisplays the UPS Rating
03MCU Version[XXXX]
04Model Name[OLSX] [000E] [RT2U] [A ]Displays the UPS Model Name
05Date and Time
Next BATT
06
Change
07IP
08Subnet Mask
09Gateway
10MAC[XX.XX] [XX.XX] [XX.XX]
DATA DISPLAYEDDESCRIPTION
Displays the EBM (extended
battery modules) number.
Displays the UPS MCU Firmware
Version
[- - - - ]
[- -. - - ]
[- - : - -]
[- - - - ]
[- -. - - ]
[1.XXX] [2.XXX]
[3.XXX] [4.XXX]
[1.XXX] [2.XXX]
[3.XXX] [4.XXX]
[1.XXX] [2.XXX]
[3.XXX] [4.XXX]
Displays the present Date & Time
Displays the next Battery
Change Date.
Display the network IP address
Display the network Subnet
Mask
Display the network Gateway
Display the network card MAC
address
23
Page 27
EVENT CODE LIST
USING THE UPS SYSTEM
EVENT
CODE
01Over Charge
02
04Battery LowThe Battery has been discharged to low level.
05Battery FailureThe UPS has detected battery failure.
06
07
12
21Output shortThe UPS has detected output short.
22
25EPO OFFThe UPS has been turned off by EPO.
27ROO OFFThe UPS has been turned off by ROO.
EVENT
CONTENT
Charger
Failure
BAT
Disconnected
Service
Battery
Load Over
Set%
Output
Overload
LCD DISPLAYDESCRIPTION
The Battery has been charged too High
voltage.
The Battery Charger has malfunctioned.
The UPS has not detected batteries.
The Battery Replacement Date has reached
the maintenance period.
The UPS has detected Output Watt or VA has
exceeded user set parameter.
The UPS has detected Output Watt or VA are
too High.
30Inverter FaultThe inverter has malfunctioned.
High Output
31
Voltage
Low Output
32
Voltage
Over
33
Temperature
34Fan ErrorThe UPS has detected a fan malfunction.
35Rear Fan ErrorThe UPS has detected a rear fan malfunction.
Middle Fan
36
Error
Front Fan
37
Error
The UPS has detected Inverter voltage too
High.
The UPS has detected Inverter voltage too
Low.
The UPS has detected internal temperature
too High.
The UPS has detected a middle fan
malfunction.
The UPS has detected a front fan malfunction.
24
Page 28
EVENT CODE LIST
USING THE UPS SYSTEM
EVENT
CODE
40Bus FaultThe UPS has detected DC Bus too High or Low.
41
42
43
44
50
51
52
53
54Line Abnormal
N/AReady ONThe UPS has been turned on.
EVENT
CONTENT
Bus Fault
+High
Bus Fault
+Low
Bus Fault
-High
Bus Fault
-Low
Input Power
Fail
Input V+Hz
out of range
Input V out of
range
Input Hz out
of range
LCD DISPLAYDESCRIPTION
The UPS has detected +DC Bus too High.
The UPS has detected +DC Bus too Low.
The UPS has detected -DC Bus too High.
The UPS has detected -DC Bus too Low.
The UPS has detected input voltage or
frequency out of range.
The UPS has detected input voltage and
frequency out of range.
The UPS has detected input voltage out of range.
The UPS has detected input frequency out of range.
The UPS has detected the utility is out of
range when the UPS is running auto-restart
process.
N/AShutdownThe UPS has been shutdown.
N/ASleep ModeThe UPS has been entered sleep mode.
N/ABattery TestThe Batteries have been tested.
25
Page 29
USING THE UPS SYSTEM
LCD WORD INDEX
WORDLCD DISPLAYDESCRIPTION
NONO Bypass/NO IP Address
ENAEnable
DISDisable
ACTActivate
SAVESave
ESCEscape
VOFEBypass condition: Check Voltage and Frequency
OLVOBypass condition: Check only Voltage
OLBLBuzzer enable only battery Low
IPPFDry relay function output: Input power fail
BATLDry relay function output: Bat Low
SUMLDry relay function output: Summary alarm
BYPADry relay function output: Bypass
UPSFDry relay function output: UPS fail
CLERClear
SETUSetup
EPOEmergency power off
ROORemote On/Off
DHCPIP address: DHCP
26
Page 30
USING THE UPS SYSTEM
LCD WORD INDEX
WORDLCD DISPLAYDESCRIPTION
MANUIP address: Manual
BATEBattery test
ALTEAlarm test
INTEIndicator test
FATEFan test
NULLNULL
27
Page 31
TROUBLESHOOTING
LCD will use FAULT ICON with RED to indicate the Fault or Warning status.
EVENT
CODE
N/ABattery Mode
01Over Charge
04Battery Low
05
06
07
12
WARNINGICONPOSSIBLE CAUSESOLUTION
Battery
Failure
BAT
Disconnected
Service
Battery
Load Over
XXX%
(Yellow)
(Red)
UPS is operating
on battery power.
Battery is
overcharged.
UPS is operating
on battery power
and the alarm
triggers when the
set percentage of
battery capacity
or remaining backup time is reached.
UPS will be
shutting down
soon due to
extremely low
battery voltage.
UPS has failed in
Battery Test.
Missing battery
power.
The Battery
Replacement Date
has reached the
recommended 3
year maintenance
period.
Your equipment
requires more
power than
the setting
in the Power
Management
Software (Power
Panel® Business)
will allow.
28
Save your data and perform
a controlled- shutdown.
Remove battery connector
and check charger voltage.
UPS will restart automatically
when acceptable utility
power returns.
Check battery connector
and battery fuse.
Contact technical support
to replace the battery.
Check battery connector
and battery fuse.
If batteries have been
recently replaced, then reset
the Battery Replacement
Date using PowerPanel®
Business Edition-Agent
software, RMCARD interface
or through the LCD control
panel on the UPS (See LCD
Setting Configuration).
Shut off the non-essential
equipment or increase
the level in the Power
Management Software.
Page 32
TROUBLESHOOTING
EVENT
CODE
21Output Short
22
25EPO OFF
27ROO OFF
33
54
EVENT
CODE
02
31High Output V
32Low Output V
40Bus Fault
34Fan Error
WARNINGICONPOSSIBLE CAUSESOLUTION
Output
Overload
Over
Temperature
Line
Abnormal
FAULTICONPOSSIBLE CAUSESOLUTION
Charger
Failure
(Red)
(Red)
Output short circuit.
Your equipment
requires more
power than the
UPS can provide.
If the UPS is in
Line Mode then
it will transfer to
Bypass Mode;
if the UPS is in
Battery Mode it
will shutdown.
Missing the EPO
connection.
Missing the ROO
connection.
High temperature
sensor activates
protection.
Utility power is
out of range for
the UPS to autorestart.
Charger has
failed.
Output voltage is
too high.
Output voltage is
too low.
Internal DC bus
voltage is too
high or too low.
Internal Fan has
failed.
Your attached equipment may
have problems, please remove
them and check again.
Shut off non-essential
equipment. If this solves
the overload problem, the
UPS will transfer to normal
operation.
Check the EPO connection.
Check the ROO connection.
Check the fan for operation
and if the ventilation hole
has been covered.
Check whether voltage or
frequency of utility power
is out of range.
Contact CyberPower for
assistance.
Shut down UPS and turn
off input breaker.Contact
CyberPower for assistance.
Perform a Fan Test and
check the Alarm. If the
Alarm continues, Shut
down UPS and turn off
input breaker.Contact
CyberPower for assistance.
29
Page 33
MAINTENANCE
Storage
To store your UPS for an extended period, cover it and store with the battery fully charged.
Recharge the battery every three months to ensure battery life.
Warning: High voltage – Risk of Electric Shock
CAUTION! Only use replacement batteries that are certified by Cyber Power Systems. Use of
incorrect battery type is an electrical hazard that could lead to explosion, fire, electric shock,
or short circuit.
CAUTION! Batteries contain an electrical charge that can cause severe burns. Before
servicing batteries, please remove any conductive materials such as jewelry, chains, wrist
watches, and rings.
CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is harmful to the skin/eyes
and may be toxic.
CAUTION! To avoid electric shock, turn off and unplug the UPS from the wall receptacle
before servicing the battery.
CAUTION! Only use tools with insulated handles. Do not lay tools or metal parts on top of the
UPS or battery terminals.
Replacement Batteries
Please refer to the front side of the UPS for the model number of the correct replacement
batteries. For battery procurement, log onto www.cyberpower.com, or contact your local
dealer.
When the Replace Battery the LCD displays Service Battery, use PowerPanel® Business Edition
Agent software or log on to the RMCARD to perform a runtime calibration to verify battery
capacity is sufficient and acceptable.
CAUTION! Batteries replacement must be performed by qualified personnel.
Battery Disposal
Do Not Discard
Batteries are considered hazardous waste and must be disposed of properly. Contact your
local government for more information about proper disposal and recycling of batteries. Do
not dispose of batteries in fire.
30
Page 34
MAINTENANCE
Battery Installation and Replacement
Step 1:
(1) Remove the right front panel.
(2) Remove the battery connector from the battery compartment cover and disconnect.
(3) Loosen the three screws to remove the plastic sheet and the battery compartment cover.
Step 2:
Pull the battery trays out slowly and then put the new battery trays into the compartment.
Step 3:
Re-install the battery compartment cover and the plastic sheet by tightening the screws.
Connect the battery connector and secure onto the battery compartment cover.
Please make sure the connection is properly seated.
Step 4:
Re-install the right front panel and tighten with two screws.
Connectivity Ports(1) Serial Port (RS232), (1) USB Port
SNMP/HTTP Capable(1) Expansion Port (With optional RMCARD 205)
Software
Power Management
Software
Physical
Dimension
(WxHxD)mm
Net Weight (kg)10.413.817.227. 6
Battery Mode, Battery Test Fail, Battery Low,Overload,
UPS Fault, Over Charged, Fan Failure
32°F to 104°F ( 0°C to 40°C)
20 to 90% Non-Condensing
438 x 88 x 430438 x 88 x 430438 x 88 x 430438 x 88 x 610
4 Hours
Yes
PowerPanel® Business
* Within 50/60HZ ±5% by default, the output frequency is synchronization with input mains. User can adjust
the acceptable range for output frequency (±1, 2, 3, 4, 5, 6, 7, 8%). When UPS work on Converter Mode, the
output frequency is regulated at 50/60Hz
0.5% with load derating by 40%.
±
33
Page 37
APPENDIX - LCD WORD COMPARISON TABLE
WORD
0ALV
1BMW
2CNX
3DOY
4EP
5FQ
LCD
DISPLAY
WORD
LCD
DISPLAY
WORD
LCD
DISPLAY
WORD
LCD
DISPLAY
6GR
7HS
8IT
9JU
34
Page 38
Page 39
Page 40
Cyber Power Systems, Inc.
11F., No.26, Jinzhuang Rd., Neihu Dist., Taipei City 114, Taiwan