Package Contents
CyberPower
Reliability. Quality. Value.
User's
Manual
R
RECON SERIES
ENVIROSENSOR
User Manual
ENVIROSENSOR
Flat Head Screw (M3x20)
with Plastic Nylon Anchor
Hook and Loop Tape
CAT5 RJ45 Ethernet Cable
(10 feet/3.05 m)
User Manual
Technical Specifications
ENVIROSENSOR
Input Voltage 7V - 28V
Power Dissipation Normal mode 110 mW
Measurement Range and Accuracy
Temperature
Humidity 10-90 RH with accuracy ± 2%
Communication
Connection Port RJ45 Port
Input Dry Contact 4
Physical
Dimensions (L x W x H)
Weight 1.46 oz /41.5 g
Safety Approvals FCC Class B, CE, EAC
Warranty 3 Year Limited
Halt mode 72 mW/
(Default 12V input)
32-158℉ with accuracy ± 1.8℉/
0-70℃ with accuracy ± 1℃
2.32 x 1.77 x 1.14 inches/
59 x 45 x 29 mm
Overview
The CyberPower environmental sensor (ENVIROSENSOR) along
with selected Remote Management Cards (RMCARDXXX) or
most Switched and Monitored PDUs enables users to monitor
the temperature and humidity of a server closet and/or data
center remotely. With CyberPower's PowerPanel® Business
Edition software, users can establish thresholds that will
automatically notify users when an event has occurred via
email, SMS and SNMP traps. Additionally, the ENVIROSENSOR
provides 4 input dry contacts that enable users to monitor the
status of connected devices, such as door switch sensors.
Features include:
• Real time environment monitoring
• Remote management and configuration of the sensor via Web
Browsers or NMS
• Automatic events notification via email, SMS and SNMP traps
• 4 input dry contacts application interface provided
• Displays the name and location of the sensor and
connected devices
Product Features
A. LED
B. Input Dry Contact 1-4
C. Common Connection
D. RJ45 Port
(connect to RMCARD/PDU)
A
STATUS
1
Installation Guide
Method 1: Hook and Loop Tape
Mounting
Step 1. Clean the surface of the area
where the sensor will be installed.
Apply one side of the hook and
loop tape to the bottom of the
sensor and the other side to the
sensor location.
Step 2. Attach the sensor on the surface
and hold for about 5 seconds to
ensure cohesion.
NOTE: Once the sensor is installed, you
will want to leave it in place to
ensure the the hook and loop
tape maintains its adhesiveness.
Step 3. To connect the sensor with
RMCARD/PDU, use the attached
RJ45 Ethernet Cable. Plug one
end into the RJ45 Port and the
other end into the
RMCARD/PDU.
NOTE: If the distance of RMCARD/PDU
and the sensor is longer than 10
feet/3.05 m, use a standard RJ45
Ethernet Cable as needed (max
50 feet/15 m).
NOTE: Please refer to Appendix
for Input Dry Contact
Application.
Copyright © 2018 Cyber Power Systems (USA), Inc. All rights reserved.
D
DATA
C
B
COM
41 2 3
32
Universal RX/TXLink
RMCARD205

Method 2: Fixed Mounting
Step 1. Drill a hole that is
compatible with the
anchor and insert the
included anchor.
Step 2. Insert and tighten the
screw into the anchor.
Leave enough of the
screw exposed for the
sensor to be mounted to.
Step 3. Hang the sensor
horizontally or vertically.
Step 4. To connect the sensor
with RMCARD/PDU, use the
attached RJ45 Ethernet Cable.
Plug one end into the RJ45
Port and the other end into the
RMCARD/PDU.
For further configuration
information, please refer to the
RMCARD/PDU user’s manual.
HoleØ6mm(0.24in)
Universal RX/TXLink
RMCARD205
Conformance Approvals
FCC Warning
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the
FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful
interference to radio communications. However, there is no
guarantee that interference will not occur in a particular
installation. If this equipment does not cause harmful
interference to radio or television reception, which can be
determined by turning the equipment o and on, the user is
encouraged to try to correct the interference by one or more
of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit dierent
from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician
for help.
This device compiles with Part 15 of the FCC Rules. Operation
is subject to the following two conditions: (1) this device may
not cause harmful interference, and (2) this device must
accept any interference received, including interference that
may cause undesired operation.
NOTE: THE MANUFACTURER IS NOT RESPONSIBLE FOR ANY
RADIO OR TV INTERFERENCE CAUSED BY UNAUTHORIZED
TO THIS EQUIPMENT. SUCH MODIFICATIONS COULD VOID
THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.
Troubleshooting
Problem Solution
The RMCARD/PDU is
not able to acquire
environment sensor's
information.
The Input Dry
Contact does not
function correctly.
Check the LED.
When the connection is ok, the LED
should always be on; otherwise,
ensure the RJ45 Ethernet cable is
correctly connected to the
RMCARD/PDU and sensor.
Note: Do not use a crossover cable
which is for Tx/Rx.
Ensure the Input Dry Contact wires
are correctly connected and make
sure the open/short circuit setting of
the connected devices is the same
as the setting on the Web Interface.
Appendix
Input Dry Contact Application
Do not input signals that carry
voltage into the input dry
contacts. The input dry contacts
only allow for open/short circuit.
4 5
Dry Contact
1 2 3 4
COM
External Sensor 1/2/3/4
Cyber Power Systems, Inc.
www.cyberpower.com
WARNING: This product can expose you to chemicals including Styrene,
which is known to the State of California to cause cancer, and Bisphenol-A,
which is known to the State of California to cause birth defects or other
reproductive harm.
For more information go to www.P65Warnings.ca.gov.
6
For USA and Canada:
4241 12th Ave East, Suite 400
Shakopee, MN 55379
Toll-free: (877) 297-6937
For all other regions:
Please visit our website for local contact information.
K01-0000207-02