CyberPower BPSE240V47A, BPSE240V47AOA User Manual

Page 1
1
BPSE240V47A
BPSE240V47AOA
Users Manual
This manual contains important instructions. Please read and follow all
instructions carefully during installation and operation of the unit. Read
this manual thoroughly before attempting to unpack, install, or operate
the Battery modules.
CAUTION! The UPS unit must be connected to a grounded AC
SAFETY
Page 2
2
power outlet with fuse or circuit breaker protection. The Battery
modules grounded are through the UPS.
CAUTION! The battery can power hazardous components
inside the unit, even when the AC input power is disconnected.
CAUTION! To prevent the risk of fire or electric shock, install in
a temperature and humidity controlled indoor area, free of
conductive contaminants. (Please see specifications for
acceptable temperature and humidity range).
CAUTION! (No User Serviceable Parts): Risk of electric shock,
do not remove cover. No user serviceable parts inside. Refer
servicing to qualified service personnel.
CAUTION! (Non-Isolated Battery Supply): Risk of electric
shock, battery circuit is not isolated from AC power source;
hazardous voltage may exist between battery terminals and
ground. Test before touching.
CAUTION! Wiring must be done by qualified personnel.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS!
To reduce the risk of fire, do not use with or near aquariums.
Condensation from the aquarium can come in contact with
metal electrical contacts and cause the machine to short out.
CAUTION! Do not dispose of batteries in fire as the battery
may explode.
CAUTION! Do not open or mutilate the battery, released
electrolyte is harmful to the skin and eyes.
CAUTION! A battery can present a risk of electric shock and
high short circuit current. The following precaution should be
observed when working on batteries
1. Remove watches, rings or other metal objects.
2. Use tools with insulated handles.
CAUTION! Make sure everything is turned off and
Page 3
3
disconnected completely before conducting any maintenance,
repairs or shipment.
CAUTION! Connect the Protection Earth (PE) safety conductor
before any other cables are connected.
DO NOT INSTALL THE UNIT WHERE IT WOULD BE EXPOSED
TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE!
SERVICING OF BATTERIES SHOULD BE PERFORMED OR
SUPERVISED BY PERSONNEL KNOWLEDGE OF BATTERIES
AND THE REQUIRED PRECAUTIONS. KEEP UNAUTHORIZED
PERSONNEL AWAY FROM BATTERIES!
The box should contain the following:
Battery Module
Battery Cable
Users manual
UNPACKING
Page 4
4
SCHEMATIC
FRONT/REAR PANEL DESCRIPTION
.Output Connector: Use this output connector to connect the
Battery module and the Power module.
.On-board Replaceable Fuse Cover: Replaceable fuse is accessible
from the rear panel. It must be done by qualified personnel.
.Battery input Terminal Block: Use this input Terminal Block to
daisy chain the next Battery module.
.Self- locking Frame
Fuse
Battery String 1
Battery String 2
BATT.OUTPUT+
BATT.INPUT+
BATT.INPUT-
BATT.OUTPUT-
BASIC OPERATION
Page 5
5
CONNECTION#1: POWER MODULE(UPS) WITH ONE BATTERY MODULE
Step 1: Connect the Battery Cable to the Power module and ensure
the polarity is right.
Step 2: Loosen the screws to remove the battery cable retention
bracket of the Battery module.
Step 3: Connect the Battery Cable to the Battery module.
Page 6
6
Step 4: Rotate the battery cable retention bracket and tighten the
screws to fix battery cable.
CONNECTION#2: POWER MODULE(UPS) WITH MULTIPLE BATTERY MODULES
Step 1: Loosen the screws to remove the input Terminal Block Cover
of the #1 battery module.
Step 2: Connect the Battery Cable to the battery input Terminal Block
and ensure the polarity is right, then retighten the Block Cover.
Step 3: Loosen the screws to remove the battery cable retention
Page 7
7
bracket of the #2 battery module.
Step 4: Connect the #1 Battery module to the #2 Battery module.
#1
#2
Step 5: Rotate the battery cable retention bracket and tighten the
screws to fix battery cable.
Step 6: Connect the #1 Battery module to the Power module. (Refer
to above steps of connection#1)
Page 8
8
UPS #1
#2
Model
BPSE240V47A
BPSE240V47AOA
Battery
Sealed Maintenance Free Lead Acid Battery
12V / 7Ah x20pcs
x2sets
12V / 9Ah x20pcs
x2sets
Rated Battery Voltage
240Vdc
Overload Protection
Fuse
Physical
Maximum Dimensions (HxWxD) (mm)
718x260x550
Weight (kg)
105
116
Environment
Operating Temperature
0C to 40C
Relative Humidity
0 to 90%(Non-condensing)
For more information, visit www.cpsww.com
All rights reserved. Reproduction without permission is prohibited.
TECHNICAL SPECIFICATION