CyberPower BPE240V30AS, BPE240V50AS User Manual

Page 1
User’s Manual
BATTERY PACK
BPE240V30AS BPE240V50AS
K01-0000425-00
Page 2
Copyright © 2014 CyberPower Systems, Inc.
OVERVIEW
1
The CyberPower Battery modules (BPE240V30AS / BPE240V50AS) support 30A/50A polarized plugs, and are designed for variety of CyberPower UPS systems. When combining with the UPS, the Battery module provides extended runtime with a 240VDC external connection. Additional parallel-connected Battery modules provide the UPS for a longer extended runtime operation.
Battery Pack
User’s manual Register card
SAFETY PRECAUTIONS
CAUTION! Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants. Do not install this Battery module where excessive moisture or heat is present (Please see specifications for acceptable temperature and humidity range).
CAUTION! Never install a Battery module, or associated wiring or equipment, during a lightning storm.
CAUTION! Do not work alone under hazardous conditions. CAUTION! In case of the risk of electric shock, do not remove the top cover.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
Page 3
Copyright © 2014 CyberPower Systems, Inc.
2
BASIC OPERATION
BATTERY MODULE FRONT/REAR PANEL DESCRIPTION
1. On-board Replaceable Fuse Cover Replaceable fuse is accessible from the rear panel. It must be done by qualified personnel.
2. Input Connector Use this input connector to daisy chain the next Battery module. Remove the connector cover for access.
3. Output Cable Use this output cable to connect the Battery module to the Power module or to the next Battery module.
BPE240V30AS / BPE240V50AS
Page 4
Copyright © 2014 CyberPower Systems, Inc.
BASIC OPERATION
3
CONNECTION #1 : POWER MODULE WITH ONE BATTERY MODULE
Step 1: Loosen the two screws to remove the battery cable
retention bracket of the power module.
Step 2: Use the output cable of the Battery module to connect the Battery module to the Power module.
Step 3: Rotate the battery cable retention bracket and tighten the two screws to fix battery cable.
CONNECTION #2 : POWER MODULE WITH MULTIPLE BATTERY MODULES
Step 1: Connect the 1st Battery module to the Power module using the instructions above.
Step 2: Loosen the two screws to remove the battery cable
retention bracket of the 1st battery module.
Step 3: Use the output cable of the 2nd Battery module to connect the
2nd Battery module to the 1st Battery module.
Step 4: Rotate the battery cable retention bracket and tighten the two
screws to fix battery cable.
Page 5
Copyright © 2014 CyberPower Systems, Inc.
BASIC OPERATION
4
EXTERNAL BATTERY PACKS CONFIGURATION
The UPS can be configured to reflect the correct estimated run-times for the number of battery packs installed by using the LCD Control Panel to select the number of battery packs installed.
1. Press the “ENTER” button to activate the “MAIN MENU”.
2. Press the and buttons to scroll to the Configure option.
3. Press the “ENTER” button to select the “Configure submenu.
4. Press the and buttons to scroll to the EBP Number option.
5. Press the “ENTER” button to select the EBP Number submenu.
The first configuration number will be displayed on the second column of LCD display.
6. Press the “ and buttons to scroll through the number of attached Battery packs.
7. Press the “ENTER” button to select the number of Battery packs installed. You may be prompted to save the selection, if so press the “ENTER” button to save the setting.
8. Press the “ESC” button to cancel or return to the previous LCD menu.
Configure Submenu
Available Settings
Default Settings
EBM Number
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
0
Storage
To store your Extended Battery Packs for a long period of time, cover it and store with the batteries fully charged.
Battery Replacement
Please read and follow the Safety Instructions before servicing the battery. Battery replacement should be performed by trained personnel who are familiar with the procedures and safety precautions. Make a note of the replacement Battery pack number.
Safety Precautions
CAUTION! Only use replacement batteries which are certified by CyberPower Systems. Use of incorrect battery type is an electrical
hazard that could lead to explosion, fire, electric shock, or short circuit.
CAUTION! Batteries contain an electrical charge that can cause severe burns. Before servicing batteries, please remove any conductive materials such as jewelry, chains, wrist watches, and rings.
CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is
harmful to the skin/eyes and may be toxic.
CAUTION! To avoid electric shock, turn off and unplug the Battery pack from the wall receptacle before servicing the battery. CAUTION! Only use tools with insulated handles. Do not lay tools or metal parts on top of the UPS or battery terminals.
Replacement Batteries
Please refer to the front side of the Battery pack for the model number of the correct replacement batteries. For battery procurement, log onto www.CPSww.com, or contact your local dealer.
Battery Disposal
Batteries are considered hazardous waste and must be disposed of properly. Contact your local government for more information about proper disposal and recycling of batteries. Do not dispose of batteries in fire.
Page 6
Copyright © 2014 CyberPower Systems, Inc.
TECHNICAL SPECIFICATIONS
5
CyberPower Systems Inc.
www.cpsww.com Entire contents copyright© 2014 CyberPower Systems Inc., All rights reserved. Reproduction in whole or in part without permission is prohibited. PowerPanel® Business Edition and PowerPanel® Personal Edition are trademarks of CyberPower Systems Inc.
Model
BPE240V30AS
BPE240V50AS
Configuration
DC Output Voltage
240Vdc
Amperage
30A
50A
Physical
Dimensions
L x W x H = 26 x 10.4 x 23.6in. (660 x 265 x 600mm)
Net Weight
277lbs(126Kg)
286lbs(130Kg)
Battery
Specifications
(20) 12V/7.2AH
(20) 12V/9.0AH
Recharge Time (Typically)
4 hours
5 hours
Interface
PP45
Sealed, Maintenance Free
Yes
Environment
Operating Temperature
32℉ to 104℉ ( 0℃ to 40℃)
Operating Relative Humidity
0 to 90% Non-Condensing
Safety
Conformance Approvals
CE
RoHS
RoHS Compliant
Warranty
Product Warranty
3-year limited warranty, Free Tech Support
Problem
Possible Cause
Solution
Warning
BAT Disconnected
Missing battery power.
Check battery connector and battery breaker.
Battery Failure
UPS has failed in Battery Test.
1. Check battery connector and battery breaker.
2. Contact technical support to replace the battery.
Replace Battery
Battery will soon need to be replaced due to insufficient runtime.
Contact technical support to replace the battery.
Fault
Over Charge
Battery is overcharged.
1. Remove battery connector and check charger voltage.
2. Contact CyberPower for repair.
Charger Failure
Charger has failed.
TROUBLE SHOOTING