CyberPower 6K On-Line series, 8K On-Line series, 6KXL On-Line series, 10K On-Line series, 8KXL On-Line series User Manual

...
Users Manual
CONTENT:
1. Safety and EMC Instructions .............................................................. 1
1.1 Installation........................................................................................ 1
1.2 Operation ........................................................................................ 2
1.4 Transport ......................................................................................... 3
1.5 Storage ...................................................................................... ...... 3
1.6 Standards ........................................................................................ 4
2. Description of Commonly Used Symbols ......................................... 5
3. Introduction .......................................................................................... 6
3.1 Feature ............................................................................................ 6
3.2 Electrical Specifications................................................................... 7
3.3 Operating Environment ................................................................... 8
3.4 Typical Backup Time (Typical Values at 25°C In Minutes) .............. 9
3.5 Dimensions and Weights........................................................ ......... 9
4. Installation .......................................................................................... 11
4.1 Moving to The Installation Site ...................................................... 11
4.2 Unpacking and Inspection ............................................................. 11
4.3 Input and Output Power Wires and Protective Earth Ground
Installation............................................................................................ 12
4.4 Operating Procedure for Connecting With The External Battery .. 16
4.5 EPO Connection............................................................................ 17
5. Operation........................................................................... .................. 18
5.1 Display Panel................................................................................. 18
5.2 Turning On and Turning Off UPS .................................................. 21
5.3 LCD Operation............................................................................... 22
6. Special Function................................................................................. 28
6.1 ECO Function ................................................................................... 28
6.2 Converter Function ........................................................................ 29
6.3 Parallel Function............................................................................ 29
7. Trouble Shooting................................................................................ 35
7.1 Trouble Shooting According to Warning Indication ....................... 35
7.2 Trouble Shooting According To Fault Indication ............................ 37
7.3 Trouble Shooting In Else Cases .................................................... 38
8. Battery Maintenance .......................................................................... 39
9. Communication Port .......................................................................... 40
9.1 USB Interface ................................................................................ 40
9.2 Dry contact Interface(optional)....................................................... 40
9.3 RS-232 Interface ……….............................................................. 40
9.4 Intelligent slot................................................................................. 40
1. Safety and EMC Instructions
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1.1 Installation
This is permanently connected equipment, and it must be installed by qualified maintenance personnel.
Condensation may occur if the UPS is moved directly from a cold to a warm environment. The UPS must be absolutely dry
before being installed. Please allow an acclimatization time of at
least two hours.
Do not install the UPS near water or in damp environment.
Do not install the UPS where it would be exposed to direct
sunlight or near heat.
Do not connect appliances or items of equipment which would
overload the UPS (e.g. laser printers, etc.) to the UPS output.
Place cables in such a way that no one can step on or trip over
them.
Connect UPS with the earth reliably before connecting to the
building wiring terminal, and external battery source must also
be earthed.
An integral single emergency switching device which prevents
further supply to the load by the UPS in any mode of operation
should be provided in the building wiring installation.
An appropriate disconnect device as short-circuit backup
protection should be provided in the building wiring installation.
The equipment is powered by two sources: the mains source,
the internal battery or the external battery source.
1
With the installation of the equipment, the sum of the leakage current of the UPS and the connected load does not exceed 5%
of rated value of input current.
Do not block ventilation openings in the UPS’s housing. Ensure
allow at least 50cm of space on front and rear of the UPS.
1.2 Operation
Do not disconnect the mains cable on the UPS or the building wiring terminals during operation since this would remove the
protective earth from the UPS and all connected loads.
The UPS output terminal block may still be electrically lived
even if the UPS is not connected to the building wiring terminal,
for there is internal current source (batteries).
In order to fully disconnect the UPS, first turn the input breaker
in the “OFF” position, then disconnect the mains lead.
Indiscriminate operation of switches may cause output loss or
damage to equipment. Refer to instruction before conducting
any control.
While the UPSs work as a parallel system, the external parallel
cable should be reinforced insulation.
Ensure that no liquid or other foreign objects can enter the UPS.
1.3 Maintenance, Servicing and Faults
Do not remove the enclosure since the UPS operates with hazardous voltages. It is to be serviced only by qualified
maintenance personnel.
Caution - risk of electric shock. Even after the unit is
disconnected from the mains power supply (building wiring
terminal), components inside the UPS are still connected to the
battery which are potentially dangerous.
2
Before carrying out any kind of service and/or maintenance, isolate UPS and disconnect the batteries. Verify that no current
is present and no hazardous voltage exists in the capacitor or
BUS capacitor.
Batteries must be replaced only by qualified personnel.
Batteries have a high short-circuit current and pose a risk of
shock. Take all precautionary measures specified below and
any other necessary measures when working with batteries:
remove all jewellery, wristwatches, rings and other metal
objects
use only tools with insulated grips and handles.
When changing batteries, replace with the same quantity and
the same type of batteries.
Do not attempt to dispose of batteries by burning them. It could
cause explosion.
The UPS may be connected to external battery module (EBM).
Proper disposal of batteries is required. Refer to your local
codes for disposal requirements.
Do not open or destroy batteries. Effluent electrolyte can cause
injury to the skin and eyes. It may be toxic.
Replace the fuse only by a fuse of the same type and of the
same spec in order to avoid fire hazards.
1.4 Transport
Please transport the UPS only in the original packaging to protect against shock and impact.
1.5 Storage
The UPS must be stockpiled in the room where it is ventilated and dry.
3
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission..........................:IEC/EN 62040-2
Category C3
Radiated Emission.............................:IEC/EN 62040-2
Category C3
* EMS
Level 3
Level 3
Level 4
Level 4
CS……………………………………...:IEC/EN 61000-4-6
Level 3
MS……………………………………..: IEC/EN 61000-4-8
Level 3
Voltage Dips……………………….....: IEC/EN 61000-4-11
Low Frequency Signals.....................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the
needed to prevent disturbances.
1.6 Standards
4
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself with them and understand their
meaning:
5
Symbol and Explanation
Symbol
Explanation
Symbol
Explanation
Alert you to pay
special
attention
Caution of high
voltage
Alternating
current
source(AC)
Direct current
source(DC)
Turn on or turn
off the UPS
Protective
ground
Recycle
Do not dispose
with ordinary
trash
Model No.
Type
Model No.
Type
6K
Standard
6KXL
Exended
backup time
8K
8KXL
10K
10KXL
3. Introduction
This On-Line series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically
for computer equipments, communication servers, and data centers.
The double-converter principle eliminates all mains power
disturbances. A rectifier converts the alternating current from the mains
power to direct current. On the basis of this DC voltage, the inverter
generates an AC sinusoidal voltage, which constantly supplies the
loads. In the event of power failure, the maintenance-free batteries
power the inverter.
This manual covers the UPS listed as follows. Please confirm whether
it is the model you intend to purchase by performing a visual inspection
of the Model No. on the rear panel of the UPS.
“XL” Model: Extended backup time
3.1 Feature
This series UPS is a new generation of UPS, which provides the outstanding reliability, and most cost-performance ratio in the industrial.
Following benefit the product has:
True online double-conversion technology with high power
density, frequency independence, and generator compatibility.
Output power factor is 0.9, perfect output sine waveform,
suitable almost all critical equipment.
High input power factor 0.99,overall high efficiency 0.92,
save power and wiring expense for user. Low input current
distortion, avoid power pollution.
6
INPUT
Model No.
6K(XL)
8K(XL)
10K(XL)
Phase
Single
Voltage
176~276VAC
Frequency
(45~55)/(54~66) Hz
Current(A)
31(36)
40(45.5)
50(55)
THDI
< 5% @ full load
Power Factor
0.99 @ full load
OUTPUT
Model No.
6K(XL)
8K(XL)
10K(XL)
Power rating
6kVA/5.4kW
8kVA/7.2kW
10kVA/9kW
Voltage
208*/220/230/240×(1±1%) VAC
Frequency
50/60× (1±0.05) Hz (Battery mode)
Outstanding adaptability to the worst mains input condition.
Extra wide input voltage, frequency range and waveform, avoid
excessive dissipating limited battery energy.
Internal charger could be up to 4Amps to decrease recharging
time of battery. Optional external large charging current charger
which is up to 12Amps could be supplied.
N+X parallel redundancy to increase the reliability and flexibility.
Number of parallel operating UPS is up to 4.
ECO mode with high efficiency 0.96, save power expense for
user.
Start-able without battery.
3.2 Electrical specifications
7
Wave form
sine
Load type
PF 0.5~1, lagging
THDV
< 2% @ full linear load
<5% @ full nonlinear load
Overload
In Line mode**:
10 min 105~125% 1 min 125~150%
10 S >150%
100 mS >170%
In Battery mode:
2 min 105~125% 30 S 125~150%
100 mS >150%
Operating Temperature 0 C to 45 C
Operating humidity < 95%
Altitude < 1000m*
Storage temperature -15 C to 50 C
BATTERIES
Model No.
6K8K10K
Internal BAT
number and type
20×12V 28W
20×12V 28W
20×12V 34W
BAT pack
28A 37.4A 47A
*The load capacity would be derated to 90% automatically when the output
voltage is adjusted to 208VAC.
**The overload capacity would be derated automatically in Line mode while the
circumstance temperature is larger than 35 degree.
3.3 Operating Environment
*The load capacity should be derated 1% every 100m heightened on the basis of 1000m.
8
Model No.
Dimensions W×H×D
(mm)
Net Weight
(kg)
6K 260 x 708 x 550 70
6KXL 260 x 708 x 550 25
8K 260 x 708 x 550 86
8KXL 260 x 708 x 550 28
10K 260 x 708 x 550 86
10KXL 260 x 708 x 550 28
Model No. 100 % Load
6K
5
8K
5
10K 4
3.4 Typical Backup Time (Typical values at 25°C in minutes)
3.5 Dimensions and Weights
9
USB Port
RS 232
EPO Port
Dry contact (optional)
Intelligent Slot
Fan
Parallel Port
Maintenance Switch
Input Breaker
Terminal Block
6K(XL)
10K(XL)
Fig. 3-1 Back View of 6K(XL)/10K(XL)
*The back view of 8K(XL) models are same as 10K(XL) models.
10