CyberPower 6K On-Line series, 8K On-Line series, 6KXL On-Line series, 10K On-Line series, 8KXL On-Line series User Manual

...
Page 1
Users Manual
Page 2
CONTENT:
1. Safety and EMC Instructions .............................................................. 1
1.1 Installation........................................................................................ 1
1.2 Operation ........................................................................................ 2
1.4 Transport ......................................................................................... 3
1.5 Storage ...................................................................................... ...... 3
1.6 Standards ........................................................................................ 4
2. Description of Commonly Used Symbols ......................................... 5
3. Introduction .......................................................................................... 6
3.1 Feature ............................................................................................ 6
3.2 Electrical Specifications................................................................... 7
3.3 Operating Environment ................................................................... 8
3.4 Typical Backup Time (Typical Values at 25°C In Minutes) .............. 9
3.5 Dimensions and Weights........................................................ ......... 9
4. Installation .......................................................................................... 11
4.1 Moving to The Installation Site ...................................................... 11
4.2 Unpacking and Inspection ............................................................. 11
4.3 Input and Output Power Wires and Protective Earth Ground
Installation............................................................................................ 12
4.4 Operating Procedure for Connecting With The External Battery .. 16
4.5 EPO Connection............................................................................ 17
5. Operation........................................................................... .................. 18
5.1 Display Panel................................................................................. 18
5.2 Turning On and Turning Off UPS .................................................. 21
5.3 LCD Operation............................................................................... 22
6. Special Function................................................................................. 28
6.1 ECO Function ................................................................................... 28
6.2 Converter Function ........................................................................ 29
6.3 Parallel Function............................................................................ 29
7. Trouble Shooting................................................................................ 35
7.1 Trouble Shooting According to Warning Indication ....................... 35
7.2 Trouble Shooting According To Fault Indication ............................ 37
Page 3
7.3 Trouble Shooting In Else Cases .................................................... 38
8. Battery Maintenance .......................................................................... 39
9. Communication Port .......................................................................... 40
9.1 USB Interface ................................................................................ 40
9.2 Dry contact Interface(optional)....................................................... 40
9.3 RS-232 Interface ……….............................................................. 40
9.4 Intelligent slot................................................................................. 40
Page 4
1. Safety and EMC Instructions
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
1.1 Installation
This is permanently connected equipment, and it must be installed by qualified maintenance personnel.
Condensation may occur if the UPS is moved directly from a cold to a warm environment. The UPS must be absolutely dry
before being installed. Please allow an acclimatization time of at
least two hours.
Do not install the UPS near water or in damp environment.
Do not install the UPS where it would be exposed to direct
sunlight or near heat.
Do not connect appliances or items of equipment which would
overload the UPS (e.g. laser printers, etc.) to the UPS output.
Place cables in such a way that no one can step on or trip over
them.
Connect UPS with the earth reliably before connecting to the
building wiring terminal, and external battery source must also
be earthed.
An integral single emergency switching device which prevents
further supply to the load by the UPS in any mode of operation
should be provided in the building wiring installation.
An appropriate disconnect device as short-circuit backup
protection should be provided in the building wiring installation.
The equipment is powered by two sources: the mains source,
the internal battery or the external battery source.
1
Page 5
With the installation of the equipment, the sum of the leakage current of the UPS and the connected load does not exceed 5%
of rated value of input current.
Do not block ventilation openings in the UPS’s housing. Ensure
allow at least 50cm of space on front and rear of the UPS.
1.2 Operation
Do not disconnect the mains cable on the UPS or the building wiring terminals during operation since this would remove the
protective earth from the UPS and all connected loads.
The UPS output terminal block may still be electrically lived
even if the UPS is not connected to the building wiring terminal,
for there is internal current source (batteries).
In order to fully disconnect the UPS, first turn the input breaker
in the “OFF” position, then disconnect the mains lead.
Indiscriminate operation of switches may cause output loss or
damage to equipment. Refer to instruction before conducting
any control.
While the UPSs work as a parallel system, the external parallel
cable should be reinforced insulation.
Ensure that no liquid or other foreign objects can enter the UPS.
1.3 Maintenance, Servicing and Faults
Do not remove the enclosure since the UPS operates with hazardous voltages. It is to be serviced only by qualified
maintenance personnel.
Caution - risk of electric shock. Even after the unit is
disconnected from the mains power supply (building wiring
terminal), components inside the UPS are still connected to the
battery which are potentially dangerous.
2
Page 6
Before carrying out any kind of service and/or maintenance, isolate UPS and disconnect the batteries. Verify that no current
is present and no hazardous voltage exists in the capacitor or
BUS capacitor.
Batteries must be replaced only by qualified personnel.
Batteries have a high short-circuit current and pose a risk of
shock. Take all precautionary measures specified below and
any other necessary measures when working with batteries:
remove all jewellery, wristwatches, rings and other metal
objects
use only tools with insulated grips and handles.
When changing batteries, replace with the same quantity and
the same type of batteries.
Do not attempt to dispose of batteries by burning them. It could
cause explosion.
The UPS may be connected to external battery module (EBM).
Proper disposal of batteries is required. Refer to your local
codes for disposal requirements.
Do not open or destroy batteries. Effluent electrolyte can cause
injury to the skin and eyes. It may be toxic.
Replace the fuse only by a fuse of the same type and of the
same spec in order to avoid fire hazards.
1.4 Transport
Please transport the UPS only in the original packaging to protect against shock and impact.
1.5 Storage
The UPS must be stockpiled in the room where it is ventilated and dry.
3
Page 7
* Safety
IEC/EN 62040-1
* EMI
Conducted Emission..........................:IEC/EN 62040-2
Category C3
Radiated Emission.............................:IEC/EN 62040-2
Category C3
* EMS
Level 3
Level 3
Level 4
Level 4
CS……………………………………...:IEC/EN 61000-4-6
Level 3
MS……………………………………..: IEC/EN 61000-4-8
Level 3
Voltage Dips……………………….....: IEC/EN 61000-4-11
Low Frequency Signals.....................:IEC/EN 61000-2-2
Warning: This is a product for commercial and industrial application in the
needed to prevent disturbances.
1.6 Standards
4
Page 8
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself with them and understand their
meaning:
5
Symbol and Explanation
Symbol
Explanation
Symbol
Explanation
Alert you to pay
special
attention
Caution of high
voltage
Alternating
current
source(AC)
Direct current
source(DC)
Turn on or turn
off the UPS
Protective
ground
Recycle
Do not dispose
with ordinary
trash
Page 9
Model No.
Type
Model No.
Type
6K
Standard
6KXL
Exended
backup time
8K
8KXL
10K
10KXL
3. Introduction
This On-Line series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically
for computer equipments, communication servers, and data centers.
The double-converter principle eliminates all mains power
disturbances. A rectifier converts the alternating current from the mains
power to direct current. On the basis of this DC voltage, the inverter
generates an AC sinusoidal voltage, which constantly supplies the
loads. In the event of power failure, the maintenance-free batteries
power the inverter.
This manual covers the UPS listed as follows. Please confirm whether
it is the model you intend to purchase by performing a visual inspection
of the Model No. on the rear panel of the UPS.
“XL” Model: Extended backup time
3.1 Feature
This series UPS is a new generation of UPS, which provides the outstanding reliability, and most cost-performance ratio in the industrial.
Following benefit the product has:
True online double-conversion technology with high power
density, frequency independence, and generator compatibility.
Output power factor is 0.9, perfect output sine waveform,
suitable almost all critical equipment.
High input power factor 0.99,overall high efficiency 0.92,
save power and wiring expense for user. Low input current
distortion, avoid power pollution.
6
Page 10
INPUT
Model No.
6K(XL)
8K(XL)
10K(XL)
Phase
Single
Voltage
176~276VAC
Frequency
(45~55)/(54~66) Hz
Current(A)
31(36)
40(45.5)
50(55)
THDI
< 5% @ full load
Power Factor
0.99 @ full load
OUTPUT
Model No.
6K(XL)
8K(XL)
10K(XL)
Power rating
6kVA/5.4kW
8kVA/7.2kW
10kVA/9kW
Voltage
208*/220/230/240×(1±1%) VAC
Frequency
50/60× (1±0.05) Hz (Battery mode)
Outstanding adaptability to the worst mains input condition.
Extra wide input voltage, frequency range and waveform, avoid
excessive dissipating limited battery energy.
Internal charger could be up to 4Amps to decrease recharging
time of battery. Optional external large charging current charger
which is up to 12Amps could be supplied.
N+X parallel redundancy to increase the reliability and flexibility.
Number of parallel operating UPS is up to 4.
ECO mode with high efficiency 0.96, save power expense for
user.
Start-able without battery.
3.2 Electrical specifications
7
Page 11
Wave form
sine
Load type
PF 0.5~1, lagging
THDV
< 2% @ full linear load
<5% @ full nonlinear load
Overload
In Line mode**:
10 min 105~125% 1 min 125~150%
10 S >150%
100 mS >170%
In Battery mode:
2 min 105~125% 30 S 125~150%
100 mS >150%
Operating Temperature 0 C to 45 C
Operating humidity < 95%
Altitude < 1000m*
Storage temperature -15 C to 50 C
BATTERIES
Model No.
6K8K10K
Internal BAT
number and type
20×12V 28W
20×12V 28W
20×12V 34W
BAT pack
28A 37.4A 47A
*The load capacity would be derated to 90% automatically when the output
voltage is adjusted to 208VAC.
**The overload capacity would be derated automatically in Line mode while the
circumstance temperature is larger than 35 degree.
3.3 Operating Environment
*The load capacity should be derated 1% every 100m heightened on the basis of 1000m.
8
Page 12
Model No.
Dimensions W×H×D
(mm)
Net Weight
(kg)
6K 260 x 708 x 550 70
6KXL 260 x 708 x 550 25
8K 260 x 708 x 550 86
8KXL 260 x 708 x 550 28
10K 260 x 708 x 550 86
10KXL 260 x 708 x 550 28
Model No. 100 % Load
6K
5
8K
5
10K 4
3.4 Typical Backup Time (Typical values at 25°C in minutes)
3.5 Dimensions and Weights
9
Page 13
USB Port
RS 232
EPO Port
Dry contact (optional)
Intelligent Slot
Fan
Parallel Port
Maintenance Switch
Input Breaker
Terminal Block
6K(XL)
10K(XL)
Fig. 3-1 Back View of 6K(XL)/10K(XL)
*The back view of 8K(XL) models are same as 10K(XL) models.
10
Page 14
4. Installation
The system may be installed and wired only by qualified electricians in accordance with applicable safety regulations!
When installing the electrical wiring, please note the nominal amperage of your incoming feeder.
4.1 Moving to The Installation Site
The series UPS has wheels making it easy to move the UPS to the installation site after it has been unpacked. However, if the receiving
area is far from the installation site, it is recommended to move the
UPS by using a pallet jack or a truck before unpacking the UPS.
4.2Unpacking and Inspection
1. At the installation site, the utmost care shall be taken when removing the packaging in order to avoid damaging the equipment.
Cut the plastic poly-straps around the shipping container and
remove the corrugated carton and the PS foam on the top of the
UPS. With one or two people on each side of the UPS, lift the UPS
out of the pallet.
Warning: the plastic poly-straps around the shipping container are under tension. While cutting, don’t face to them, they will
spring back and may cause eye injury.
The shipping materials are recyclable. After unpacking, save them for later use or dispose of them appropriately.
11
Page 15
2. Check all packaging materials to ensure that no items are missing. The shipping package contains:
A UPS
A user’s manual
A USB cable
A RS232 cable (optional)
A parallel cable
A parallel port cover plate
Terminal splices 12pcs (using for the wire connection on
input terminal)
EPO connector
PowerPanel® Business Edition software CD
3. Inspect the appearance of the UPS to see if there is any damage during transportation. Do not turn on the unit and notify the carrier
and dealer immediately if there is any damage or lacking of some
parts.
4.3 Input and Output Power Wires and Protective Earth Ground Installation
4.3.1 Notes for installation
1) The UPS must be installed in a location with good ventilation, far away from water, inflammable gas and corrosive agents.
2) Ensure the air vents on the front and rear of the UPS are not
blocked. Allow at least 0.5m of space on each side.
3) Condensation to water drops may occur if the UPS is unpacked
in a very low temperature environment. In this case it is
necessary to wait until the UPS is fully dried inside out before
proceeding installation and use. Otherwise there are hazards of
electric shock.
12
Page 16
Model
6k
8/10k
Protective earthing conductor Min cross section
6mm2(8AWG)
10 mm2(6AWG)
Input L, N, G Min conductor cross section
6mm2(8AWG)
10 mm2(6AWG)
Input breaker
40A/250VAC
63A/250VAC
Output L,N, Min conductor cross section
6mm2(8AWG)
10 mm2(6AWG)
External Battery Cabinet
Positive Pole(+), Negative pole(-), Neutral Pole
Min conductor cross section
6mm2(8AWG)
10 mm2(6AWG)
External Battery Cabinet Fuse in Positive Pole(+), Negative pole(-), Neutral Pole
30A/240VDC
60A/240VDC
External Battery Cabinet Breaker in Positive Pole(+), Negative pole(-), Neutral Pole
32A/240VDC
50A/240VDC
Torque for fixing above terminals
3.95~4.97Nm (35~44 1b in)
4.3.2 Installation
For safety, please cut off the mains power switch before installation!
Use cable cross section and protective device specification
1)
It is suggested to install an external isolating device against
current backfeed between Mains input and UPS (see Fig.4-6).
After the device is installed, it must add a warning label with the
following wording or the equivalent on the external AC contactor:
RISK OF VOLTAGE BACKFEED. Isolate the UPS before
operating on this circuit, then check for hazardous voltage
between all terminals.
13
Page 17
Fig.4-6 Typical external isolating device installation
2) No matter the UPS is connected to the mains power or not, the output of the UPS may be electrically live. The parts inside the
unit may still have hazardous voltage after turning off the UPS.
To make the UPS have no output, power off the UPS, and then
cut off the mains power supply, wait the UPS shut down
completely.
3) Open the terminal block cover located on the rear panel of UPS, please refer to the appearance diagram.
4) For 6KVA UPS, it is recommended to select the UL1015 8AWG/6mm2or other insulated wire which complies with AWG
Standard for the UPS input and output wirings.
5) For 8/10KVA UPS, it is recommended to select the UL1015 6AWG/10mm2or other insulated wire which complies with AWG
Standard for the UPS input and output wirings.
6) Ensure the capacity of mains power supply. Do not use the wall receptacle as the input power source for the UPS, as its rated
current is less than the UPS’s maximum input current.
Otherwise the receptacle may be burned and destroyed.
7) The protective earth ground wire should be installed first according to the following diagram. It is better to use green wire
or green wire with yellow ribbon wire.
14
Page 18
8) Connect other input and output wires to the corresponding input and output terminals according to the following diagram.
9) It is requested to use the accessorial terminal splices which can be compacted on the wires tightly, to ensure the connection
between the wires and the terminal block is reliable.
Fig. 4-7 Input and output Terminal Block wiring diagram
Notes: 1) If the UPS is used in single mode, J1 and J2 must be
connected. If the UPS is used in parallel mode, the Jumper
between J1 and J2 must be removed.
2) Battery+/- connection is only for “XL” model.
10) Install an output breaker between the output terminal of UPS
and the load, and the breaker should with leakage current
protective function if necessary.
11) Turn off all the loads first before connecting the load with the
UPS, then perform the connection and finally turn on the loads
one by one.
12) After completing the installation, check all the wires is
connected correctly and tightly.
13) Suggest charging the batteries for 8 hours before use. After
installation, turn on the mains power switch and turn the input
breaker in the “ON” position, the UPS will charge the batteries
automatically. It can also use the UPS immediately without
charging the batteries, but the backup time may be less than the
standard value.
15
Page 19
14) If it is necessary to connect the inductance load such as a
monitor or a laser printer to the UPS, the start-up power should
be used for calculating the capacity of the UPS, as its start-up
power consumption is too big to make the UPS which capacity
is small fail easily.
4.4 Operating Procedure For Connecting with The External Battery (Only for “XL” model)
1.
2.
3.
4.
5.
The nominal DC voltage of external battery pack is 240VDC. Each battery pack consists of 20 pieces of 12V maintenance free
batteries in series. To achieve longer backup time, it is possible to
connect multi-battery packs, but the principle of “same voltage,
same type” should be strictly followed.
For 6KVA, select the UL1015 8AWG/6mm2respectively or other
insulated wire which complies with AWG Standard for the UPS
battery wirings.
For 8/10KVA, select the UL1015 6AWG/10mm2respectively or other
insulated wire which complies with AWG Standard for the UPS
battery wirings.
The external battery pack must be independent for each UPS. It is forbidden that two UPSs use same external battery pack.
The procedure of installing battery pack should be complied with strictly. Otherwise it may encounter the hazardous of electric
shock.
1)2)Ensure the UPS is not powered on and the mains input breaker is set in the “OFF” position.
A DC breaker must be installed between the external battery pack and the UPS. The capacity of breaker must be not less
than the data specified in the general specification.
16
Page 20
3)
4)
5)
6)
Set the external battery pack breaker in “OFF” position and connect the 20 pieces of batteries in series.
Connect the external battery pack to the battery terminals. Check the polarity of connection is correct.
Set the breaker of the battery pack in the “ON” position.
Set the mains input breaker in the “ON” position, the UPS would power on and start to charge the battery pack.
4.5 EPO Connection
4.5.1 Introduction
Emergency power off function which the UPS supplies is, when the emergency occurs, such as the failure of load, the UPS can cut off
the output at once by operating the EPO port manually.
4.5.2 The connection
Normally the EPO connector is closed with a wire on the rear panel, which is supplied in the accessory. Once the connector is open, the
UPS would stop the output and enter EPO status.
Enable the EPO status Disable the EPO status
Fig. 4-8 Default EPO status
To recover to normal status, first EPO connector should be closed, and enter LCD menu (illustrated in the chapter of 5.3.3) to clear
EPO status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.
17
Page 21
The Button
Function
Illustration
Power on
When the unit is no power and has connected
power on.
Turn on
When the unit is powered on and is in Bypass
mode, press this button more than 1S to turn on.
Turn off
When the unit has been turned on, press this
button more than 3S to turn off.
5. Operation
5.1 Display Panel
The UPS has a five-button, dot matrix LCD with white text and a blue background. Besides the LCD, the UPS has four colorized LEDs to
provide more convenient information.
Fig. 5-1 Control Panel
Table 5-1 Control Button Functions
18
Page 22
Enter
Press this button more than 200mS to confirm
current selection or enter the current selection.
ESC
Exit Press this button more than 200mS to cancel
current selection and return to previous menu.
Up
Press this button more than 200mS to move the
focus to the up menu
Down
Press this button for more than 200mS to move
the focus to the down menu.
UPS state
Normal LED (Green)
Battery LED (Yellow)
Bypass LED (Yellow)
Fault LED (Red)
Bypass mode with no output
Bypass mode with output
Line mode
Battery mode
ECO mode
Fault mode
Warning mode
Table 5-2 LED definition
19
Page 23
UPS condition
Buzzer status
Fault active
Continuous
Warning active
Beep every second
Battery output
Beep every 4 seconds, if battery low, buzzer Beep every second
Bypass output
Beep every 2 minutes
Overload
Beep twice every second
Note
: Lightened constantly
: #1-#4 Lightened circularly
: Flashing
: Depended on the fault/warning status or other status
Table 5-3 Alarm definition
The UPS provides useful information about UPS itself, load status, battery, events, identification, and settings through the front panel display.
During powering on, the LCD would display the CyberPower logo for
several seconds and then enter to the default page which shows the
UPS status summary.
On the UPS status screen it provides the following information:
Status summary, including mode, load, battery and utility
Alarm status, if any is present.
Fault status, if any is present.
Output parameter, including output voltage, current and frequency.
Input parameter, including input voltage and frequency.
Bypass parameter, including bypass voltage and frequency.
Power parameter, including output VA and watt.
Battery parameter, including battery capacity, voltage and remain time.
20
Page 24
5.2 Turning On and Turning Off UPS
Attention: The UPS could only be turning on while connecting with the
mains at the first time.
Attention: Please switch off the connected loads first before turning
on the UPS, and switch on the loads one by one after the UPS is turned on. Switch off all of the connected loads before turning off the UPS.
5.2.1 Turning on UPS with mains
1)
2)
Check all the connection is correct. Check the breaker of
external battery pack is in “ON” position.
Set input breaker in “ON” position. At this time the fan begins to
rotate, LCD will show “CyberPower”. Then LCD will show the
default UPS status summary screen after UPS finishing
self-test.
3) By pressing button continuously for more than 1 second,
the buzzer will beep for 1s, UPS starts to turn on.
4) A few seconds later, the UPS turns into Line mode. If the mains
power is abnormal, the UPS will transfer to Battery mode
without output interruption of the UPS.
5.2.2 Turning on UPS without mains
1) Check all the connection is correct. Check the breaker of external battery pack is in “ON” position.
2) By pressing button continuously for more than 200mS, the
UPS would be powered on. At this time the fan begins to rotate,
LCD will show “CyberPower”. Then LCD will show the default
UPS status summary screen after UPS finishing self-test.
3) By pressing button continuously for more than 1s, the
buzzer will beep for 1s, UPS starts to turn on.
4) A few seconds later, the UPS turns into Battery mode. If the
mains power comes back, the UPS will transfer to Line mode
without output interruption of the UPS.
21
Page 25
5.2.3 Turning off UPS with mains
1) To turn off the inverter of UPS by pressing button
continuously for more than 3s and the buzzer will beep for 3s.
The UPS will turn into Bypass mode at once.
2) When completing the above action, UPS output voltage is still
present. In order to cut off the UPS output, simply cut off the
mains power supply. A few seconds later, LCD display shuts
down and no output voltage is available from the UPS output
terminal.
5.2.4 Turning off UPS without mains
1) To power off the UPS by pressin
button continuously for
more than 3s, and the buzzer will beep 3s. The UPS will cut off
the output at once.
2) A few seconds later, LCD shuts down and no voltage is
available from the UPS output.
5.3 LCD Operation
Except the default UPS status summary screen, the user could get more useful information about UPS current status, old events which
ever occurred, UPS own identification, and could change the settings
to fit the user own requirements, optimize the function of UPS.
5.3.1 The status screen
In the UPS status screen, when pressing or >200 mS the detailed information about UPS information that include alarm, fault,
output, input, bypass, load and battery parameter would be shown.
when pressing > 200 mS the main menu would be shown.
In fault or alarm screen, when press > 200mS, the other alarm or fault
would be shown by press or >200mS, and press >200mS
the display would return to status screen.
The main menu includes four branches: UPS control menu, setting menu,
event menu and identification menu.
22
Page 26
Fig. 5-2 status menu
23
Page 27
5.3.2 The UPS main menu
Fig. 5-3 main menu
24
Buzzer mute
EPO
Bat test
Single UPS off
Buzzer mute
Yes
No
Bat test
yes
no
Bat test
Yes
No
EPO
Yes
No
Bat test
yes
no
Single UPS off
Yes
No
Control
Setting Events
ID
Events&alarms
Fault
Clear all events
Clear all faults
Event
0001:12:00:00
Utility abnormal
1/10
Alarm
0002:12:00:00
Overload
1/10
Fault
0003:12:00:00
Over tempearture
1/5
Clear all events
Yes
No
Clear all faults
Yes
No
Type/model
Serial number
Rating
Firmware version
Type/model
OLS 6000VA
Standard model
Serial number
************
Rating IP:230Vac/60Hz OP:230Vac/60Hz
Power:6kVA/5.4kW
Please input
password ...
Firmware version
Ver:0.0.1
Sub settings ....
Page 28
5.3.3 The control menu
By pressing on the menu of “Control”, the display would enter the next control menu screen.
1)
2)
3)
4)
Single UPS turn off: is one command to turn off one UPS which
is operated currently in a parallel system, and other UPSs
continue working to supply the load in the parallel system.
UPS battery test: is one command to control all UPS in
a parallel system to do the battery test at the same time.
Clear EPO status: once EPO status is enabled, the UPS output
would be cut off. To recover to normal status, first EPO
connector should be closed, and enter this menu to clear EPO
status, then UPS would stop alarm and recover to Bypass
model. And UPS needs be turned on by manual operation.
Reset fault status: when fault occurs, UPS would keep in Fault
mode and alarm. To recover to normal status, enter this menu
to reset error status, then UPS would stop alarm and recover to
Bypass mode. And the reason of fault should be checked and
deleted before UPS is turned on again by manual operation.
25
Page 29
5.3.4 The setting menu
Please contact your local distributor for further information before using the settings. Some settings would change the specification,
and some settings would enable or disable some functions. The
unsuitable option set by user may result in potential failures or
protecting function loss, even directly damage the load, battery or
UPS.
The most of settings could only be done while UPS is in Bypass
mode.
26
Page 30
Submenu item
Optional Values
Default value
User password
enabled/disabled
disabled
Audio alarm
enabled/disabled
enabled
Site wiring fault alarm
enabled/disabled
enabled
Ambient temperature warning
enabled/disabled enabled
DC start
enabled/disabled
enabled
Auto Restart
enabled/disabled
enabled
Automatic overload restart
enabled/disabled
enabled
AutoBypass
enabled/disabled
enabled
Short circuit clearance
enabled/disabled
disabled
Power strategy**
normal
Rated output voltage
208/220/230/240V
230V
Output frequency
autosensing/50/60Hz
autosensing
Bypass voltage low range
10%,15%,20%
15%
Bypass voltage high range
10%,15%
10%
Bypass frequency range
10%
10%
ECO voltage range
10%,15%
10%
ECO frequency range
1%~10%
5%
Automatic battery tests
period
0-45days 7days
Set running time
Day:hour:minute:second
0000:0000:00~9999:23:59:59
Running time
Restore default setting
Table 5-4
*Password is AAAA when enabled.
**Read the chapter of 6.1 and 6.2, before using ECO or converter function.
27
Page 31
6. Special Function
The series UPS has some special functions, which could satisfy some special application of user. And the functions have own features, please contact your local distributor for further information before using the function.
6.1 ECO Function
6.1.1 Brief introduction of ECO function
If ECO function is set to enable, after the UPS is turned on, the power used by the load is directly supplied from the mains power via
internal filter while the utility power is in normal range, so the
economy mode could be gained in ECO mode. Once the mains power
is loss or abnormal, the UPS would transfer to Line mode or Battery
mode and the load is supplied continuously. The great virtue is overall high efficiency 0.96 of UPS, to save
power for user.
But the disadvantage is 1) the load can not be protected as well as
in Line mode, for the load is directly supplied from the mains; 2) the
transfer time of UPS output from ECO mode to Battery mode is about
10ms.
So the function is not suitable to some sensitive loads, and the
region where the mains power is unstable.
6.1.2 Set the function
The function could be enabled through the LCD setting in Bypass mode.
Enter the power strategy setting menu by following chapter of 5.3.4
28
Page 32
6.2 Converter Function
6.2.1 Brief introduction of Converter function
In converter mode, the UPS would free run with fixed output frequency (50Hz or 60Hz). Once the mains power is loss or
abnormal, the UPS would transfer to Battery mode and the load is
supplied continuously.
The great virtue is the output frequency is fixed, which is required by
some very sensitive loads. But the disadvantage is the load capacity of UPS
should be derated to 60% in converter mode.
6.2.2 Set the function
The function could be enabled through the LCD setting in Bypass mode.
Enter the power strategy setting menu by following chapter of 5.3.4.
6.3 Parallel Function
6.3.1 Brief introduction of the redundancy
N+X is currently the most reliable power supply structure. N represents the minimum UPS number that the total load needs, X
represents the redundant UPS number, i.e. the fault UPS number
that the system can handle simultaneously. When the X is larger, the
reliability of the power system is higher. For occasions where
reliability is highly depended on, N+X is the optimal mode.
As long as the UPS is equipped with parallel cables, up to 4 UPSs can be connected in parallel to realize output power sharing and
power redundancy.
29
Page 33
6.3.2 Parallel installation and operation
How to install a new parallel UPS system:
1)
2)
3)
4)
5)
6)
7)
8)
9)
Before installing a new parallel UPS system, user need to
prepare the input and output wires, the output breaker, and the
parallel cable.
Users need to use a standard 25-pin communication cable,
which should have 25 cores, corresponding stitches and shield,
as the UPS parallel cable. The length of the parallel cable is
appropriate to be less than 3m. And there is one standard
parallel cable in the accessories of every UPS.
Remove the cover plate of the parallel port on the UPS,
connect each UPS one by one with the parallel cable, and
re-screw the Parallel port cover which is supplied in the
accessories.
Strictly follow the chapter of 4, the wiring requirement of single
UPS to perform the wiring of each UPS.
Connect the output wires of each UPS to an output breaker
panel.
Disconnect the Jumper on J1 and J2 of the terminal block
first, and connect each output breaker to a main output breaker
and then to the loads.
Each UPS need an independent battery pack.
Please refer to the wiring diagram in the following diagram.
The distance between the UPSs in parallel and the breaker
panel is required to be less than 20 meters. The difference
between the wires of input and output of the UPSs is required to
be less than 20%.
30
Page 34
Fig. 6-1 Input and output Terminal Block wiring diagram
31
Page 35
Fig. 6-2 Parallel System Installation Diagram
10) Do not switch on the output breaker of each UPS, switch on the input breaker of the each UPS, the UPS should work in bypass
with output, observe their display to check if there are any
warning or fault information, measure the output voltage of
each UPS separately to check if the voltage difference between
them is less than 1V. If the difference is more than 1V, check
the wiring.
11) Press the button of one UPS, each UPS would start to turn
on, all the UPSs would transfer to the INV mode together.
Measure the output voltage of each UPS separately to check if
the voltage difference between them is less than 0.5V. If the
difference is more than 0.5V, the UPSs need to be regulated.
12) Press the button of one UPS, each UPS would start to turn
off and transfer to the Bypass mode, switch on the output
breaker of each UPS to parallel all the output of UPSs together.
32
Page 36
13) Press the button of one UPS, each UPS would start to turn on, after turning on, the UPSs should work parallel in the Line
mode.
How to join a new UPS to a parallel system:
1)
2)
3)
4)
5)
6)
First the parallel system must be installed one main
maintenance mechanical switch or static switch.
Regulate the output voltage of the new UPS separately: check
if the output voltage difference between the new UPS and the
parallel system is less than 0.5V.
Ensure the bypass of the parallel system is normal and the
bypass setting is “enable”, remove the cover plate of
maintenance switch on the rear panel of each UPS, the UPS
system would transfer to bypass automatically, set the own
maintenance switch of each UPS from “UPS” to “BPS”.
Set the main maintenance switch or static switch from “UPS” to
“BPS”, switch off the main output breaker and the main input
breaker, the UPSs would shut down.
Ensure the UPSs shut down totally, add the new UPS and
reinstall the new UPS parallel system by following step 1) to 9)
of last chapter - “install a new parallel UPS system”.
Switch on the main input breaker and the main output breaker,
and set the main maintenance switch or static switch from
“BPS” to “UPS”, then set the UPS own maintenance switch
from “BPS” to “UPS” and screw the maintenance cover plate
back again. Press the button of one UPS, each UPS would
start to turn on, after turning on, the UPSs should work parallel
in the Line mode.
How to remove a single UPS from a parallel system:
1) First the parallel system must be installed one main
maintenance mechanical switch or static switch.
33
Page 37
2)
3)
4)
5)
6)
Ensure the bypass is normal and the bypass setting is “enable”,
remove the cover plate of maintenance switch on the rear panel
of each UPS, the UPS system would transfer to bypass
automatically, set the own maintenance switch of each UPS
from “UPS” to “BPS”.
Set the main maintenance switch or static switch from “UPS” to
“BPS”, switch off the main output breaker and the main input
breaker, and the UPSs would shut down.
Ensure the UPSs shut down totally, remove the wanted UPS
and reinstall the new UPS parallel system by following step 1)
to 9) of last chapter - “install a new parallel UPS system”.
If the removed UPS or the remained UPS will be used in a
stand-alone mode, then J1 and J2 on the terminal block
should be connected with a short connection wire.
Switch on the main input breaker and the main output breaker,
and set the main maintenance switch or static switch from
“BPS” to “UPS”, then set the UPS own maintenance switch
from “BPS” to “UPS” and screw the maintenance cover plate
back again. Press the button of one UPS, each UPS would
start to turn on, after turning on, the UPSs should work parallel
in the Line mode.
34
Page 38
Problem Displayed
Possible cause
Remedy
Read EEPROM Error
UPS internal fault
Consult dealer.
EPO Active
EPO connector is open
Check the EPO connector status
On Maintain Bypass
Maintain bypass switch is open
Check the maintain bypass switch status
IP softstart failed
UPS internal fault
Consult dealer
Site Wiring Fault
Phase and neutral conductor at input of
UPS system are
reversed
Reverse mains power wiring.
Battery Disconnect
Battery pack is not
connected correctly
Do the battery test to confirm.
Check the battery bank is connected to the UPS. Check the battery breaker is
turn on.
Battery low
Battery voltage is low
When audible alarm sounding
empty.
Output Overload
Overload
Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Fan Failure
Fan abnormal
Check if the fan is running normally.
Charger Fail
The charge fails
Consult dealer.
Battery Over Voltage
Battery voltage is
higher than normal
value
Check if the battery quantity is
right.
7. Trouble Shooting
If the UPS system does not operate correctly, first check the operating information on the LCD display. Please attempt to solve the problem using the table below. If the problem still persists, consult your dealer.
7.1 Trouble Shooting According To Warning Indication
35
Page 39
Over Charge
Battery is over
charged
The UPS will turn off the
is normal
Model Pin Error
UPS internal fault
Consult dealer.
Ambient Over
Temperature
The ambient
temperature is too
high
Check the environment
ventilation.
Heatsink Over Temperature
Inside temperature of UPS is too high
Check the ventilation of UPS and the ambient temperature.
Ambient NTC abnormal
UPS internal fault
Consult dealer.
Para Cable Male Loss
The parallel cable is disconnected
Check the parallel cable.
Para Cable Female Loss
The parallel cable is disconnected
Check the parallel cable.
Para Bat Differ
The battery packs of
some UPSs are
disconnected
Check if all the battery pack is
connected.
Para Line Differ
The mains input of
some UPSs is disconnected
Check the building wiring and
input cable. Check if the input breaker is closed. Ensure the UPSs are connected to same input
source.
Para Work Mode Differ
There are different power strategy setting
in parallel system
The UPSs with different power
strategy setting (Ex. one Line
are forbidden to parallel.
Para Rate Power Differ
There are different
UPSs in parallel system
The UPSs with different
capacity (Ex. one 6KVA and one 10KVA) are forbidden to
parallel.
ECO In Para
ECO function is
enabled in parallel
system
ECO function is forbidden in
parallel system.
IP Fuse Open
Input fuse break
Check the input fuse status
36
Page 40
Problem Displayed
Possible cause
Remedy
Inv Overload Fault Overload Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Byp Overload Fault Overload Check the loads and remove
some non-critical loads.
Check if some loads are failed.
Output Short Circuit Output short circuit
Remove all the loads. Turn off
the UPS.
Check if UPS output and loads
is short circuit.
Ensure short circuit is removed
before turning on again.
Heatsink Over
Temperature Fault
Inside temperature of
UPS is too high
Check the ventilation of UPS
and the ambient temperature.
Bus Over Voltage
UPS internal fault
Consult dealer.
Bus Under Voltage
UPS internal fault
Consult dealer.
Bus Unbalance
UPS internal fault
Consult dealer.
Bus short
UPS internal fault
Consult dealer.
Bus Softstart Fail
UPS internal fault
Consult dealer.
Inv Over Voltage
UPS internal fault
Consult dealer.
Inv Under Voltage
UPS internal fault
Consult dealer.
Inv Softstart Fail
UPS internal fault
Consult dealer.
Negative Power Fault
The load is pure inductive
and capacitive
Remove some non-critical loads.
Bypass supplies the load first,
ensure there is no overload,
then turn on UPS.
Cable male and female Loss fault
The parallel cable is
disconnected
Check the parallel cable.
Fan lock fault
Fan blocked or disconnected over time
Check the fan status
Back Feed
Output voltage is returned to input
Consult dealer
7.2 Trouble Shooting According To Fault Indication
37
Page 41
Problem
Possible cause
Remedy
No indication, no warning tone even though system is connected to mains
power supply
No input voltage Check the building wiring and
input cable.
Check if the input breaker is
closed.
BYPASS LED light up
even though the power supply is available
Inverter not switched
on
Press On-Switch “I” to turn on
UPS.
BATTERY LED lights
up, and audible alarm
sounding every 1 beep
in every 4 seconds
Input voltage and/or
frequency are out of
tolerance
Check input power source.
Check the building wiring and
input cable.
Check if the input breaker is
closed.
Emergency supply period shorter than
nominal value
Batteries not fully charged / batteries
defect
12 hours and then check
capacity.
7.3 Trouble Shooting In Else Cases
Please have the following information at hand before calling the
After-Sales Service Department:
1. Model number, serial number
2. Date on which the problem occurred
3. LCD/LED display information, Buzzer alarm status
4. Mains power condition, load type and capacity, environment temperature,
ventilation condition
5. The information (battery capacity, quantity) of external battery pack if the
UPS is “XL” model
6. Other information for complete description of the problem
38
Page 42
8. Battery Maintenance
Battery replacement should be performed by qualified personnel.
This series UPS only requires minimal maintenance. The
battery used for standard models are value regulated sealed lead-acid maintenance free battery. These models require minimal repairs. The only requirement is to charge the UPS regularly in order to maximize the expected life of the battery. When being connected to the mains power, whether the UPS is turned on or not, the UPS keeps charging the batteries and also offers the protective function of overcharging and over-discharging.
The UPS should be charged once every 4 to 6 months if it has
not been used for a long time.
In the regions of hot climates, the battery should be charged
and discharged every 2 months. The standard charging time should be at least 12 hours.
Under normal conditions, the battery life lasts 3 to 5 years. In
case if the battery is found not in good condition, earlier replacement should be made.
Replace batteries with the same number and same type of
batteries.
Do not replace the battery individually. All the batteries should
be replaced at the same time following the instructions of the battery supplier.
If the battery service life (3~5 years at 25°C ambient
temperature) has been exceeded, the batteries must be replaced.
39
Page 43
9. Communication Port
9.1 USB Interface
The USB port is compliance with USB 1.1 protocol for its communication software.
9.2 Dry contact Interface(optional)
This series UPS has independent dry contact interface. Please contact your local distributor for details.
9.3 RS-232 Interface
The RS-232 port is available for UPS monitoring, control, and firmware updates.
9.4 Intelligent slot
This series is equipped with an intelligent slot for other optional card to achieve remote management of the UPS through internet / intranet. Please contact your local distributor for further information.
40
Loading...