CWC DIGICHEM-XP2 Instruction Manual

Page 1
Instruction Manual
Cooling Water Treatment Controller
Model: DIGICHEM-XP2
Biocide A
Power Bleed
Biocide B Inhibitor Alarm
Time & Date
UP
Main Menu
DOWN
Reset
ENTER
Water Treatment Controller
Comms
Supplied by:
Convergent Water Controls Pty Ltd
2/4 Huntley Street, PO Box 7058 Alexandria NSW 2015
t: (02) 9698 3131 w: cwc.com.au f: (02) 9698 3210 e: support@cwc.com.au
M1 ver 1.5
Fill in serial number here
Ö
Refer to back page
Page 2
Manufacturer:
Convergent Water Controls Pty Ltd, Sydney Australia.
Note:
On-going product development at Convergent Water Controls may lead
to changes in the specifications of this product.
Warranty:
This product is guaranteed for a period of 12 months from installation
date or 18 months from Invoice date (whichever occurs first). The warranty applies to manufacturing or component defects which may cause the unit to malfunction under specified conditions. The guarantee does not cover damage due to abuse, tampering or improper installation.
Disclaimer:
Convergent Water Controls will not be held liable for any consequential
damage or loss arising resulting from product malfunction.
Page 3
TTaabbllee ooff CCoonntteennttss
1.
Introduction...........................................................................................................................7
2. Installation ............................................................................................................................7
2.1 Electrical Wiring...........................................................................................................................7
2.2 Conductivity Probe Installation & Maintenance...............................................................................8
3. Controller Functionality.........................................................................................................9
3.1 Menu Logic..................................................................................................................................9
3.2 Pushbuttons .............................................................................................................................. 10
3.3 LED Indication........................................................................................................................... 11
3.4 Comms Port............................................................................................................................... 12
4. Commissioning.....................................................................................................................13
4.1 Start-Up .................................................................................................................................... 13
4.2 Setting Time & Date................................................................................................................... 14
4.3 Calibration................................................................................................................................. 15
4.4 Testing Relay Outputs................................................................................................................ 18
4.5 Manual Dose.............................................................................................................................. 19
4.6 View Settings............................................................................................................................. 20
4.7 Factory Settings......................................................................................................................... 20
5. Programming Setup Menu...................................................................................................21
5.1 Set Units ................................................................................................................................... 23
5.2 Set Bleed Setpoint ..................................................................................................................... 23
5.3 Set Hysteresis............................................................................................................................ 24
5.4 Set Bleed Cycle..........................................................................................................................25
5.5 Alarm Parameters ...................................................................................................................... 26
5.5.1 High Conductivity Alarm....................................................................................................................27
5.5.2 Low Conductivity Alarm.....................................................................................................................27
5.5.3 No Flow Alarm..................................................................................................................................28
5.5.4 Delay On Alarm................................................................................................................................28
5.5.5 Bld Timer Alarm................................................................................................................................29
5.6 Inhibitor Setup........................................................................................................................... 29
5.7 Biocide Setup............................................................................................................................. 33
5.8 Pre-Bleed Setpoint ..................................................................................................................... 36
5.9 Bleed Lock-out Setpoint.............................................................................................................. 36
5.10 Auxiliary Output On Timer ........................................................................................................ 37
5.11 Flow Switch ............................................................................................................................. 39
5.12 Data Logging........................................................................................................................... 40
6. Factory Settings...................................................................................................................41
7. Specifications.......................................................................................................................42
8. Service & Technical Support................................................................................................43
Page 4
1. Introduction
Designed for cooling tower water treatment, the DIGICHEM-XP2 electronic controller incorporates the following key features:
Conductivity bleed control
Inhibitor pump dosing control
Dual Biocide pump contro l (via 10 independent 28-day timer programs)
Data logging
Tower circulating/condenser pump override facility with delay-off timer
High and Low Conductivity alarms with programmable delay-of f timer
2. Installation
Mount the DIGICHEM-XP2 on a flat vertical surface away from extreme heat, humidity or areas where temperature variations are extreme, ideally at eye­level to allow good visibility of the LCD display. Also ensure that a 240VAC mains power point is located nearby.
2.1 Electrical Wiring
CAUTION: If opening the controller, pull the lid away from the base slowly to
ensure you do not impose any strain on the interconnecting cable, which easily unplugs from the motherboard.
Page 5
Page 5 of 43
The diagrams below shows the connections to the DIGICHEM-XP2 controller circuitry (release 1 & release 2).
L14
L13
L12
L11
L10
R4
R15
R14
R13
R5 R6
R3
R2
R1
FUSE
2A/250VAC
R20
R19
L9
L8
L7
L6
R10 R11 R12
R9
R8
R7
R18
R17
R16
Release 1
L6: Conductivity Probe PR+ (Brown or Red) L7: Conductivity Probe PR- (Yellow) L8: Conductivity Probe CM+ (Blue) L9: Water Meter In L10: Flow Switch In L11: Flow Switch Common / Water Meter Common / Probe
Cable Screen (Grey) L12 + L14: Alarm Relay N/O volt-free (10A/250VAC res) L13 + L14: Alarm Relay N/C volt-free (10A/250VAC res)
R1: Mains Active 240VAC (power supply) R2: Mains Neutral R3: Auxiliary Continuous Active 240VAC (2A fused) R4: Auxiliary Neutral R5: Solenoid Valve Active 240VAC (2A fused) R6: Solenoid Valve Neutral R7: Inhibitor Pump Active 240VAC (2A fused) R8: Inhibitor Pump Neutral R9: Biocide ‘A’ Active 240VAC (2A fused) R10: Biocide ‘A’ Neutral
Page 6
Page 6 of 43
R11: Biocide ‘B’ Active 240VAC (2A fused) R12: Biocide ‘B’ Neutral R13 - R18: Common Earth R19: Condenser Pump Relay common R20: Condenser Pump Relay N/O volt-free (10A/250VAC res)
Fuse: 2A/250VAC (M205, 20mm x 5mm diameter)
Notes on Alarm Relay Contacts :
1. Alarm relay is energised (ie. L14 connected to L12) during normal operation of the unit.
2. Alarm relay de-energises (ie. L14 connected to L13) when an alarm condition is confirmed or when the unit loses power.
Notes on Flow Switch:
A flow switch with N/O or N/C volt-free contacts are required to be connected to terminals L10 & L11 (not polarity sensitive). The flow switch logic is programmable via the menu.
Page 7
Page 7 of 43
L4
L13
L12
L11
L10
R4
R15
R14
R13
R5 R6
R3
R2
R1
FUSE
2A/250VAC
R20
R19
L9
L8
L7
L6
R10 R11 R12
R9
R8
R7
R18
R17
R16
L5
Release 2
L4: Conductivity Probe Cable Screen (Grey) L5: Conductivity Probe PR+ (Brown or Red) L6: Conductivity Probe PR- (Yellow) L7: Conductivity Probe CM+ (Blue) L8: Water Meter In L9: Flow Switch In L10: Flow Switch Common / Water Meter Common / Probe
Cable Screen (Grey) L11 + L13: Alarm Relay N/O volt-free (10A/250VAC res) L12 + L13: Alarm Relay N/C volt-free (10A/250VAC res)
R1: Mains Active 240VAC (power supply) R2: Mains Neutral R3: Auxiliary Continuous Active 240VAC (2A fused) R4: Auxiliary Neutral R5: Solenoid Valve Active 240VAC (2A fused) R6: Solenoid Valve Neutral R7: Inhibitor Pump Active 240VAC (2A fused) R8: Inhibitor Pump Neutral R9: Biocide ‘A’ Active 240VAC (2A fused) R10: Biocide ‘A’ Neutral R11: Biocide ‘B’ Active 240VAC (2A fused)
Page 8
Page 8 of 43
R12: Biocide ‘B’ Neutral R13 - R18: Common Earth R19: Condenser Pump Relay common R20: Condenser Pump Relay N/O volt-free (10A/250VAC res)
Fuse: 2A/250VAC (M205, 20mm x 5mm diameter)
Notes on Alarm Relay Contacts :
1. Alarm relay is energised (ie. L13 connected to L11) during normal operation of the unit.
2. Alarm relay de-energises (ie. L13 connected to L12) when an alarm condition is confirmed or when the unit loses power.
Notes on Flow Switch:
A flow switch with N/O or N/C volt-free contacts are required to be connected to terminals L9 & L10 (not polarity sensitive). The flow switch logic is programmable via the menu.
2.2 Conductivity Probe Installation & Maintenance
The probe is supplied screwed into a PVC Tee piece such that the electrode tips are submerged in the water flowing through the manifold in which the tee is usually fitted. The probe should be positioned with the black markers on the probe aligned with the black markers on the manifold Tee. This ensures that the 2 electrodes of the probe are positioned symmetrically with respect to the direction of water flow. See the photograph and diagrams below:
DIRECTION
OF FLOW
Page 9
Page 9 of 43
The probe’s electrodes should periodically be cleaned to maintain accurate TDS measurements. The frequency of cleaning required will vary from one application to another. In a new installation, it is recommended that the probe be cleaned after 2 weeks of service.
To clean the probe, first unplug the probe lead and unscrew the probe from the manifold. The probe can normally be cleaned using a cloth or paper towel. Occasionally the probe’s carbon electrodes may be coated with substances which requires more vigorous cleaning (this coating may not always be visible). To clean a coated electrode, use a fine grit abrasive, such as emery paper.
After cleaning, apply more Teflon
®
tape to the probe thread and screw back into the manifold. The controller should always be calibrated after probe cleaning.
3. Controller Functionality
3.1 Menu Logic
The DIGICHEM-XP2 has an advanced but very user-friendly menu system:
The menu structure is circular
The relevant menu item, or programmed value flashes
Up & Down arrow pushbuttons allow you to scroll through the menu items
and to increase/decrease programmed settings
The MAIN MENU expands to several levels of SUB MENUS when pressing ENTER on various menu items
The LCD is backlit
The MAIN MENU of the controller is illustrated as follows (see next page):
Page 10
Page 10 of 43
MANUAL DOSE
EXIT
SETUP MENU
FACTORY SETTINGS
TEST OUTPUTS
CALIBRATE
TIME & DATE
VIEW SETTINGS
995 TDS [1000]
Hold
To access menu item press
3.2 Pushbuttons
The DIGICHEM-XP2 has 3 pushbuttons which each have dual functions:
1. Scroll UP (Time & Date)
2. Scroll DOWN (Main Menu)
3. ENTER (Reset)
The Scroll UP and DOWN pushbuttons allows you to scroll in both directions in the circular menus. Once a menu item has been selected and there is a value to program, the Scroll pushbuttons allow you to increase or decrease the number programmed.
The ENTER pushbutton allows you to ente r a part of the program that you have selected. It also accepts any numbers programmed with the Scroll pushbuttons.
Page 11
Page 11 of 43
If the Scroll UP (Time & Date) pushbutton is pressed momentarily in NORMAL MODE (explained in section 4.1), the time and date is displayed. To revert back to NORMAL MODE, press the pushbutton momentarily again.
The time and date is displayed as follows:
NOTE: The Time & Date is programmable, but the Week No is automatically set. Hence, if you have multiple controllers in the field, the Week No will be the same on all (assuming the Time & Date are programmed correctly).
To get into the me nus of the DIGICHEM-XP2, hold down the Scroll DOWN (Main Menu) pushbutton. The display will count down until you access the menus.
If you wish to cancel an alarm or any timers activated, press and hold the ENTER (Reset) pushbutton until the display says:
3.3 LED Indication
There are 6 LEDs on the front face of the DIGICHEM-XP2:
Power (green): illuminates continuously when power is applied to the
controller
Bleed (amber): illuminates continuously when power is applied to the
solenoid output of the controller. If the solenoid output is suspended due to a pause in the bleed cycle, the LED will flash on and off.
Biocide A (amber): illuminates continuously when power is applied to the
Biocide A output of the controller.
Biocide B (amber): illuminates continuously when power is applied to the
Biocide B output of the controller.
Inhibitor (amber): illuminates continuously when power is applied to the
Inhibitor output of the controller. If the Inhibitor output is suspended due to no flow, the LED will flash on and off during the ON cycle.
Page 12
Page 12 of 43
Alarm (red): illuminates when the alarm relay switches. If the alarm
delay is timing before the alarm condition is confirmed, the LED will flash on and off.
3.4 Comms Port
There is a Comms port on the front panel of the controller next to the LCD. This is used to download data from the controller, and can also used to upload new software versions should they be required.
The data is downloaded via the Comms port on the front panel of the controller. An optional cable is required, P/N SP-XP2-COMCABLE-1, to perform a direct download to a pc or laptop.
Page 13
Page 13 of 43
4. Commissioning
CAUTION: Refer to previous section before reading this section
4.1 Start-Up
Power up the controller after installation. After a start-up sequence, the controller automatically goes into NORMAL MODE. The display should read the measured conductivity as well as the conductivity Setpoint within square brackets (which alternates with the temperature as measured by the conductivity probe), as follows:
NOTE: An asterisk ‘*’ flashes on the screen when the controller receives a pulse from an optional water meter (Software version 2.0 and above). The asterisk '*' may appear on the LHS of the display or within the square brackets just before the Conductivity Setpoint or Temperature.
Other information that you may see on the display, which alternates with the display above:
When an alarm is reported, the actual alarm message will be periodically
displayed, e.g.
When a flow switch is connected to the controller, each output is
suspended when there is no flow past the flow switch, if the output is selected via the Flow Switch Menu.
Page 14
Page 14 of 43
4.2 Setting Time & Date
Main Menu > TIME & DATE
TIME: 10:30
TIME: 11:00
TIME: 10:00
DATE: 1 Jan 2006
DATE: 2 Jan 2006
DATE: 2 Nov 2006
TIME & DATE
Press or to change day
then
Press or to change month
Press or to change year
Example: Setting time & date to 10:30 on 2 Nov 2006
NOTE: The Week No will be automatically set
Page 15
Page 15 of 43
4.3 Calibration
IMPORTANT: Select the display in either µS or TDS before proceeding.
(Refer section 5.1)
Calibrating the SLOPE
Main Menu > CALIBRATE
Take a sample of water from the sample valve on the manifold and measure the conductivity with a hand-held conductivity meter. Alternatively, insert the Conductivity probe in a buffer solution of known conductivity. Should the conductivity readout on the display differ from the sample taken, calibrate the controller as follows:
Adjust the current reading via the Calibration Menu to the desired reading.
Page 16
Page 16 of 43
Calibrating the ZERO
The zero is factory set so should not require calibration. However, if the display reads above zero with the conductivity probe disconnected, recalibrate the zero as follows:
1. Remove the probe from the manifold.
2. Dry the electrodes of the probe, so that there is zero (or minimal) conductivity between the electrodes.
3. Wait until the reading on the LCD is stable. If the reading does not settle to exactly 0, wait until it does not drop any further.
4. Go into the Calibrate Menu and set the Zero Calibration (see below).
5. Screw the probe back into the manifold.
6. Perform the SLOPE calibration again.
Page 17
Page 17 of 43
Resetting the CALIBRATION
If you inadvertently calibrate the zero and/or slope to the incorrect values, and you cannot recover by repeating the normal calibration procedure, then you can reset the calibration and start again.
Page 18
Page 18 of 43
4.4 Testing Relay Outputs
Main Menu > TEST OUTPUTS
Bleed O/P[OFF]
TEST OUTPUTS
BIO ‘A’ O/P [OFF]
Press or to turn ON
AUX. O/P [OFF]
ALARM O/P [OFF]
BIO ‘B’ O/P [OFF]
INHIBTR O/P [OFF]
Press or to turn ON
Press or to turn ON
Press or to turn ON
Press or to turn ON
Press or to turn ON
When any of the Outputs is activated, the respective Output LED illuminates and the Output relay switches, putting 240VAC power onto the output terminal, which activates the pump or solenoid valve wired to it.
When the Alarm Output is activated, the red Alarm LED illuminates and the relay de-energises, switching the Common from the Normally Open Contact to the Normally Closed contact of the Alarm relay.
NOTES:
1. If any output is activated manually without reverting back to the de­activated state, the controller will automatically turn the output off 2 minutes after no pushbutton activity.
2. If you wish to drive an output for longer than 2 minutes, activate the MANUAL DOSE function within the MAIN MENU
3. The outputs should all switch on when tested, regardless of the flow condition.
4. Do not switch the Aux O/P On relay rapidly ON and OFF, if powering the condenser pump of the cooling tower.
Page 19
Page 19 of 43
4.5 Manual Dose
Main Menu > MANUAL DOSE
To perform an unattended slug dose of chemical, simply program the dose time (up to 99 minutes, in 1 minute increments) as follows:
Note: The pump will not dose if there is no flow
To cancel a manual dose, press and hold the ENTER (Reset) pushbutton
Page 20
Page 20 of 43
4.6 View Settings
Main Menu > VIEW SETTINGS
To view all the settings you have programmed into the controller without going into the menus themselves, you can simply scroll up and down to view them all:
HYSTERESIS 10%
Display: [TDS]
SETPOINT: 1000
ID: 0620-65535
10 P00h00 L00h00
VIEW SETTINGS
Press at any point to escape
4.7 Factory Settings
Main Menu > FACTORY SETTINGS
CAUTION:
Enter this part of the prog r a m ONLY if you wish to erase your program settings.
The default settings (listed in Section 6 of this manual) most likely will not suit your application, so it will be necessary to reprogram the controller with your desired settings.
This menu gives the option of resetting the calibration as well.
Page 21
Page 21 of 43
CONFIRM? [NO ]
RESET? [NO ]
RESET? [YES]
CONFIRM? [YES]
RESET CAL? [NO ]
RESET CAL? [YES]
FACTORY SETTINGS
Press to escape
Press to escape
Press to reset unit to Factory Settings (most recent Calibration NOT reset)
Press to reset unit to Factory Settings and to reset Calibration to Factory default
5. Programming Setup Menu
Main Menu > SETUP MENU
IMPORTANT:
Once settings are changed, it is necessary to exit the SETUP MENU in order to save your settings.
Setup Menu Structure illustrated as follows:
Page 22
Page 22 of 43
HYSTERESIS
PRE-BLD SETPOINT
UNITS
BIOCIDE SETUP
BLEED SETPOINT
BLEED CYCLE
ALARM PARAMETERS
INHIBITOR SETUP
FLOW SWITCH
LOCKOUT SETPOINT
AUX O/P ON TIMER
SETUP MENU
You will be prompted to save any changed settings
To access menu item press
Setup Menu
DATA LOGGING
EXIT SETUP
Page 23
Page 23 of 43
5.1 Set Units
Main Menu > SETUP MENU > UNITS
Conductivity can be displayed in either:
TDS (Total Diss olved Solids), or
• μS (Microsiemens)
Note: The displayed units should be selected before performing any
calibration or programming of the unit.
5.2 Set Bleed Setpoint
Main Menu > SETUP MENU > BLEED SETPOINT
SETPOINT: 0950
BLEED SETPOINT
SETPOINT: 1050
SETPOINT: 1050
SETPOINT: 1000
Example: Increasing setpoint from 950 TDS to 1000 TDS
The Bleed Setpoint is the desired conductivity value of the process (displayed in TDS or μS). When a solenoid valve is connected to the bleed output, the
Page 24
Page 24 of 43
valve opens when the conductivity rises above the setpoint. When this occurs, the tower water is flushed to drain and fresh make-up water dilutes the system, thus lowering the conductivity of the tower water. The valve shuts when the conductivity drops to the hysteresis value (explained in the next section). The cycle repeats.
5.3 Set Hysteresis
Main Menu > SETUP MENU > HYSTERESIS
HYSTERESIS 01%
HYSTERESIS
HYSTERESIS 04%
Example: Increasing Hysteresis from 1% to 4%
Hysteresis is the deadband between the two conductivity points at which the solenoid valve opens and closes. The solenoid valve opens when the conductivity rises above the programmed setpoint and shuts when it drops to a level below the setpoint. This level is called Hysteresis and is a % of the setpoint.
Page 25
Page 25 of 43
5.4 Set Bleed Cycle
Main Menu > SETUP MENU > BLEED CYCLE
When the controller calls for bleed, the solenoid valve can be programmed to bleed continuously or on a cycle until it reaches the Conductivity Setpoint. To leave the Bleed Cycle in its disabled state, proceed to the next section. If you wish to program a bleed cycle, then proceed as follows:
The menu asks for a Bleed Time and a Wait Time to be programmed. The Wait Time follows the Bleed Time, and the cycle is repeated until the Setpoint minus hysteresis is reached.
A bleed cycle can prevent excessive tower drainage in a very small system and allows the make-up to efficiently mix with the cooling tower water.
The ability to cycle is also useful because it prevents flooding by slowing down the bleed flow rate into a blocked drain.
The following diagram illustrates a bleed cycle programmed for a 10 second bleed off followed by 40 second wait:
In the example above, the solenoid bleeds 10 seconds during every 50 second cycle (ie 10+40), which equates to a 20% bleed cycle.
If you wish to have the control output continuously active during bleed (rather than cycling ON and OFF), simply set the Bleed/Wait times to 00/00s
Note: If the conductivity is greater than 25% above the programmed
setpoint, then the controller automatically adjusts the ON/OFF bleed cycle to bring it to setpoint more quickly.
Page 26
Page 26 of 43
5.5 Alarm Parameters
Main Menu > SETUP MENU > ALARM PARAMETERS
NO FLOW ALARM
HIGH ALARM
LOW ALARM
DELAY ON ALARM
BLD TIMER ALARM
EXIT
ALARM PARAMETERS
To access alarm menu item press
The controller has 5 programmable alarm functions as outlined above. If any of the alarms are activated and confirmed, the common alarm contact switches, the red Alarm LED illuminates, and the Alarm message is displayed on the LCD.
Page 27
Page 27 of 43
5.5.1 High Conductivity Alarm
The High Conductivity Alarm is activated if the Conductivity rises above the programmed setting, and automatically resets if the Conductivity drops below the programmed setting again.
Main Menu > SETUP MENU > ALARM PARAMETERS > HIGH ALARM
HIGH ALARM
HIGH ALARM: 1400
HIGH ALARM: 0000
Example: Setting a High Alarm of 1450 TDS
HIGH ALARM: 1450
then
Note: A setting of 0000 means the High Alarm is disabled.
5.5.2 Low Conductivity Alarm
The Low Conductivity Alarm is activated if the Conductivity drops below the programmed setting, and automatically resets if the Conductivity rises above the programmed setting again.
Main Menu > SETUP MENU > ALARM PARAMETERS > LOW ALARM
Note: A setting of 0000 means the Low Alarm is disabled.
Page 28
Page 28 of 43
5.5.3 No Flow Alarm
Main Menu > SETUP MENU > ALARM PARAMETERS > NO FLOW ALARM
If the No Flow Alarm is enabled, the Alarm will activate when there is no flow detected by the optional flow switch. If the No Flow Alarm is left disabled, then the Alarm is unaffected by a no-flow condition.
5.5.4 Delay On Alarm
Main Menu > SETUP MENU > ALARM PARAMETERS > DELAY ON ALARM
DELAY ON ALARM
TRIP DELAY: 0030s
TRIP DELAY: 0008s
then
Example: Setting alarm delay of 30 seconds
When an alarm condition is detected, eg High Conductivity Alarm, the relay only trips immediately if the Trip Delay is set to 0 seconds. However, if alarms do not become immediately critical, it is better to program a delay on the alarm to prevent “nuisance trips”.
If a Trip Delay, eg. 120s, is programmed, the alarm relay will only trip if the High Conductivity condition exists continuously for 120 seconds. However, if the Conductivity drops to below the High Conductivity Alarm level before the 120 seconds times out, the Alarm condition will reset.
Whilst the Trip Delay is timing, the red Alarm LED will flash. If the alarm condition still exists after the time delay, the LED will illuminate continuously until the alarm cancels, at which point, the LED goes off.
Page 29
Page 29 of 43
5.5.5 Bld Timer Alarm
Main Menu > SETUP MENU > ALARM PARAMETERS > BLD TIMER ALARM
The Bld (Bleed) Timer Alarm is the maximum acceptable bleed time for the system to reach the Setpoint. This alarm is designed to protect the system from excessive bleeding in the event of a false reading from a faulty Conductivity probe, or if the controller itself is faulty.
To leave the alarm in its disabled state, the programmed setting is 000m. If the system Conductivity reaches the Setpoint within the programmed
time, the timer resets. However, if the timer times out before the Conductivity reaches the Setpoint, the bleed solenoid switches off and remains disabled until the unit is manually reset by holding down the Reset pushbutton.
5.6 Inhibitor Setup
Main Menu > SETUP MENU > INHIBITOR SETUP There are 4 Possible Inhibitor Feed Pump Modes to select from:
Continuous on Bleed
% of Time on Blee d
% of Time on Flow (24 hrs/day) – [Note: Optional Flow Switch required]
Water M e ter Pulse
Page 30
Page 30 of 43
Inhib: [On Bleed]
INHIBITOR SETUP
Inhib: [24hr/day]
Inhib: [ Pulses]
*
*
*
* Press to access settings
Continuous on bleed:
Pump doses continuously when measured Conductivity > Setpoint, regardless of any bleed cycle programmed.
% of Time on Bleed:
Pump doses on a duty cycle when measured Conductivity > Setpoint, independent from any bleed cycle programmed. Duty cycle is repeating ON and OFF times, eg ON=30sec, followed by OFF=30sec & repeating (ie. 50% duty cycle).
Main Menu > SETUP MENU > INHIBITOR SETUP
ON Period: 0000s
Inhib: [On Bleed]
OFF Period: 0000s
ON Period: 0010s
OFF Period: 0040s
Example: Setting a 10s on period followed by a 40s off period
then
then
Page 31
Page 31 of 43
% of Time on Flow (24 hours/day):
Pump doses on a continuous duty cycle. Duty cycle is repeating ON and OFF times, eg ON=20sec, followed by OFF=60sec & repeating (ie. 25% duty cycle). If there is not continuous flow through the manifold at all times, flow switch option AF04 should be fitted.
Main Menu > SETUP MENU > INHIBITOR SETUP
ON Period: 0000s
Inhib: [24hr/day]
OFF Period: 3600s
ON Period: 0060s
OFF Period: 3600s
Example: Setting a 60s on period followed by a 3600s (i.e. 1 hr) off period
then
then
For any of the % of Time modes above, you can use the following table as a guide to set your Inhibitor pump duty cycle:
Dosing Pump Turn-down required ON Period OFF Period
10% of maximum dose rate 0010s 0090s 20% of maximum dose rate 0020s 0080s 30% of maximum dose rate 0030s 0070s 40% of maximum dose rate 0040s 0060s 50% of maximum dose rate 0050s 0050s 60% of maximum dose rate 0060s 0040s 70% of maximum dose rate 0070s 0030s 80% of maximum dose rate 0080s 0020s 90% of maximum dose rate 0090s 0010s 100% of maximum dose rate 0000s 0000s
Page 32
Page 32 of 43
Water Meter Pulse:
Pump doses proportional to pulses received from a water meter fitted in the make-up line. The DIGICHEM-XP2 activates the pump for a set time once a pre-determined number of pulses is counted, explained further in the following example:
Water meter pulse rate = 1 pulse / litre Desired concentration = 100 p.p.m.
[100 p.p.m. = 10ml chemical / 100 litres flow = 10ml chemical / 100 pulses]
Hence, we require the pump to dose 10ml every 100 pulses counted.
How long does the pump need to dose to deliver 10ml?
Pump dose rate = 1300ml/hr = 0.36ml/sec Dose time = 10ml / 0.36ml/sec = 27.8 seconds (i.e. approx. 30 sec)
Set PULSE COUNT = 100 Set DOSE PERIOD = 30 seconds
In the example above, the pump doses for 30 seconds (i.e. programmed dose time) every 100 litres of make-up water (i.e. programmed pulse count of 100).
Main Menu > SETUP MENU > INHIBITOR SETUP
Pulse Count 0100p
Inhib: [ Pulses]
Dose Period 0000s
Pulse Count 0100p
Dose Period 0030s
Example: Setting Inhibitor to dose for 30s every 100 pulses
from water meter
then
then
Notes: (v2.0 or later) An ‘*’ will be displayed on the LCD screen momentarily for each water meter pulse received.
Page 33
Page 33 of 43
5.7 Biocide Setup
Main Menu > SETUP MENU > BIOCIDE SETUP
Biocide is dosed according to 28 day timer programs set up by the user. There are 10 independent programs which can be programmed to operate daily, once per week, or on any number of days per week, fortnightly or once a month. A typical biocide program, which will operate at the same time on the specified days of the week, consists of 3 consecutive time durations:
1. Pre-bleed
2. Biocide Dosing
3. Bleed Lock-out
1. Pre-bleed
This reduces the system conductivity to a lower temporary setpoint (eg. 85% of setpoint) prior to biocide dosing in order to allow for a longer Bleed Lock-out duration without the risk of entering scaling conditions. Pre-bleed duration is programmable from 1 minute up to 23 hours. (Note: The Pre-Bleed Setpoint of 85%, ie. Setpoint -15% is fully programmable, and is explained further in section 5.8).
2. Biocide dosing
The biocide pump (Pump A or Pump B) doses chemical, typically into a manifold. Dose duration is programmable from 1 minute up to 23 hours and commences immediately after Pre-Bleed. Bleed-off is disabled (ie. locked out) during dosing provided the Bleed Lock-out setpoint is not exceeded.
3. Bleed Lock-out
After biocide dosing, bleed-off continues to be disabled for the lock-out duration, programmable from 1 minute up to 23 hours, provided the Bleed Lock-out setpoint is not exceeded. (Note: The default Bleed Lock­out Setpoint of Setpoint +20% is fully programmable, and is explained further in section 5.9).
By preventing bleed-off during and after biocide dosing, the system is ensured of receiving maximum benefit from the dosed biocide, as no biocide will be lost during this time via bleed-off. Furthermore, because the conductivity is reduced during Pre-Bleed, the system has a longer retention period. As a result, a highly effective “kill” is achieved without resulting in high scaling conditions.
Each of the 10 Biocide Dosing programs can be set up to operate Biocide pump A or Biocide pump B. In other words, the programs can be allocated in any combination to either of the two biocide outputs, A and B.
Page 34
Page 34 of 43
For instance, if pump A is set up in 6 programs, pump B can only have up to 4 programs controlling it. Not all of the programs need to be allocated. If only two of the programs are required, then the other 8 will remain disabled. Pump A and Pump B work totally independently and each program has its own START TIME, followed by its own consecutive PRE-BLEED, BIOCIDE DOSING and BLEED LOCK-OUT durations. However, biocide programs should not
overlap.
Main Menu > SETUP MENU > BIOCIDE SETUP
PROGRAM [01]
BIOCIDE SETUP
EXIT
PROGRAM [02]
PROGRAM [10]
* Press to access program settings
*
*
*
Main Menu > SETUP MENU > BIOCIDE SETUP > PROGRAM [02]
(see next page)
Page 35
Page 35 of 43
Example: Setting a Biocide Dosing Program (i.e. 2) to take place in Week 2 and Week 4, on a
Monday beginning at 14:15. Biocide will be dosed for 30 minutes after a pre-bleed time of 45 minutes, after which bleed lockout will occur for 4 hours.
Page 36
Page 36 of 43
5.8 Pre-Bleed Setpoint
Main Menu > SETUP MENU > PRE-BLD SETPOINT
PreBLD: Setp – 15%
PRE-BLD SETPOINT
PreBLD: Setp – 10%
Example: Decreasing Pre-bleed Setpoint from Setpoint - 15% to Setpoint - 10%
In the example above, the Pre-Bleed setpoint is set as the Normal Conductivity Setpoint less 10%. Hence, during the Pre-bleed time (ie. Immediately before biocide dosing), the normal conductivity setpoint is reduced by 10%, and the controller will try to maintain this reduced setpoint until biocide dosing commences. The objective of pre-bleed is to allow for a longer Bleed Lock-out duration without the risk of entering scaling conditions.
5.9 Bleed Lock-out Setpoint
Main Menu > SETUP MENU > LOCKOUT SETPOINT
Lock/O: Setp + 20%
LOCKOUT SETPOINT
Lock/O: Setp + 50%
Example: Increasing Lockout Setpoint from Setpoint + 20% to Setpoint + 50%
In the example above, the Lockout setpoint is set as the Normal Conductivity Setpoint plus 50%. Hence, during Biocide Dosing and during the Lockout time (ie. Immediately after biocide dosing), the normal conductivity setpoint is increased by 50%, and the controller will try to maintain this increased setpoint until the Lockout Period expires. By preventing bleed-off during and after biocide dosing, the system is ensured of receiving maximum benefit from the dosed biocide, as no biocide will be lost during this time via bleed-off. Furthermore, because the conductivity is reduced during Pre-Bleed, the system has a longer retention period. As a result, a highly effective “kill” is achieved without resulting in high scaling conditions.
Page 37
Page 37 of 43
5.10 Auxiliary Output On Timer
Main Menu > SETUP MENU > AUX O/P ON TIMER
Biocid dose + 000m
AUX O/P ON TIMER
Biocid dose + 015m
Example: Setting Auxiliary Output Timer to 15 minutes
Often when biocides are dosed into the manifold of the DIGICHEM-XP2 systems, the circulating/ condenser pump of the cooling tower is not running. This can cause problems of clogging and corrosion in the manifold, as well as biocide not being dosed into the cooling tower water.
The DIGICHEM-XP2 controller has an on-board relay contact (N/O) which can be wired into the condenser pump contactor (see wiring diagram in section
2.1). The contact provided is a dry contact so can be connected in series with the condenser pump contactor circuit, or any other circuit as required. Alternatively, the relay contact can power the contactor by looping 240VAC active to the common of the relay contact and connecting the N/O contact to the coil of the contactor. Note: In this instance, the contactor must have a 240VAC coil and must be normally powered from the same 240VAC mains circuit as the DIGICHEM-XP2.
When either biocide pump starts dosing, the N/O contact closes, powering the contactor which in turn starts the condenser pump. The condenser pump will continue to run while the biocide is dosing, as well as for a period of time after biocide dosing. This ensures continuous water circulation and effective mixing of the biocide chemical.
This time that the pump runs AFTER a biocide dose, is programmed here as the Auxilliary Output ON Time.
IMPORTANT: If this feature is used, it is not recommended to switch the
condenser pump on and off rapidly using the output test feature, explained in section 4.4
Page 38
Page 38 of 43
The following is another example of a biocide program set to dose on a weekly cycle:
Start time: 07:00 Pre-Bleed: 00h60m (ie. 07h00 to 08h00) Dose for: 00h60m (ie. 08h00 to 09h00) Bleed L/O: 04h00m (ie. 09h00 to 13h00)
Other Program Settings
Setpoint = 1000 TDS Pre Bleed Setpoint = Setpoint – 13% (ie. 870 TDS) Bleed Lock-out Setpoint = Setpoint + 50% (ie. 1500 TDS) Program = 01 Pump = A Auxiliary Output On Timer = 30m (i.e. delay off time after A dose)
Page 39
Page 39 of 43
5.11 Flow Switch
Main Menu > SETUP MENU > FLOW SWITCH
If an optional flow switch (eg. AF04) is connected to the controller, any or all of the outputs can be disabled when there is no flow. An output, when selected via this menu for flow detection, will stop immediately if no flow is detected. For example, when bleeding, the solenoid valve will close immediately if no flow is detected.
There are 3 possible settings in the menu for the flow switch:
DISABLE: All outputs activate if required, regardless of flow or no flow
NORMAL: Enabled outputs activate if required, only if the flow switch
input is shorted
REVERSE: Enabled outputs activate if required, only if the flow switch input is open circuit
LOGIC: [DISABLE]
LOGIC: [REVERSE]
LOGIC: [NORMAL]
Press to disable
FLOW SWITCH
Press to select which outputs are disabled by flow switch
Press to select which outputs are disabled by flow switch
None, one, two, three or all four of the outputs can be selected to be disabled if there is no flow. Typically, the Bleed output and Inhibitor output are disabled if there is no flow and the Biocides dose during their programs regardless of the flow status. However, either or both of the Biocide outputs can be set to be disabled if there is no flow.
Page 40
Page 40 of 43
Main Menu > SETUP MENU > FLOW SWITCH > LOGIC [NORMAL]
5.12 Data Logging
Main Menu > SETUP MENU > DATA LOGGING
The controller has the facility to log the following items at the pre-programmed intervals:
Date
Time
Conductivity reading (in TDS or μS )
Temperature
Percentage of time the Flow Switch was registering flow
Percentage of time the Bleed Output was active
Percentage of time the Inhibitor Pump was dosing
Percentage of time the Bio cide A Pump was dosing
Percentage of time the Bio cide B Pump was dosing
Percentage of time the Co mmon Alarm was activated
Page 41
Page 41 of 43
The pre-programmed intervals are 5, 10, 15, 30, 60, 120 or 240 minutes. If the controller is set to log every 0 minutes, then logging is disabled.
Each logged entry takes up memory, so the longer the interval, the longer the time can be between downloads. For example, the controller will have enough memory to store data for 9.4 days for a log taken every 5 minutes, 56.8 days for a log taken every 30 minutes, or for 455 days for a log taken every 240 minutes.
Once the memory is full, the data logger loses the oldest information first. The data is downloaded via the Comms port on the front panel of the
controller. An optional cable is required, P/N SP-XP2-COMCABLE-1, to perform a direct download to a pc or laptop.
6. Factory Settings
The default factory settings are outlined below. These are the settings programmed when a manual Factory Reset is initiated via the menu.
Menu Setting/Item Default
Units TDS (ie ppm Total Dissolved Solids) Bleed Setpoint 1000 ppm TDS Hysteresis 3% Bleed Cycle ON/OFF = 00s/00s (ie. Disabled) High Conductivity Alarm 0000 ppm TDS (ie. Disabled) Low Conductivity Alarm 0000 ppm TDS (ie. Disabled) No Flow Alarm Enable? [No] Delay on Alarm Trip Delay: 0008s Bleed Timer Alarm Max Bleed: 000m (ie. Disabled) Inhibitor Mode On bleed Inhibitor Duty Cycle ON/OFF = 0050s/0050s (ie. On Bleed Only) Biocide Programs All programs disabled Pre-Bleed Setpoint Setpoint -15% Bleed Lockout Setpoint Setpoint +20% Aux O/P On Timer Biocide Dose + 000m Flow Switch Logic Disabled (ie no flow switch fitted) Outputs disabled on no flow * Bleed & Inhibitor Data Logging LOG Every: 000m (ie. Logging disabled)
* only if flow switch fitted and flow switch logic enabled
Page 42
Page 42 of 43
7. Specifications
Item Specification
Power Supply 220-240VAC, 50/60Hz Power Consumption 10W max (with no loads on outputs)
Inputs Conductivity Probe (incl.)
Water meter volt-free contact (optional) Flow switch (optional, code AF04)
Auxiliary Mains Output 240VAC continuous (2A fused) Control Output 2A/250VAC (fused) Alarm Relay Output N/O & N/C (10A/250VAC resistive) Condenser Pump (Aux) Relay Output N/O (10A/250VAC resistive)
Optional Outputs 4-20mA (P/N AF09)
4-20mA plus events (P/N AF10) 4mA = 0 µS/TDS, 20mA = 5000 µS/TDS
Measured Conductivity Resolution 1µS / 1 ppm TDS Accuracy 0.5% of measured range Repeatability & drift 1.0% of measured range
Logged Items Controller Model, Software version, No of log
entries, Controller ID No, Date, Time, Conductivity, Temperature, Flow %, Bleed %, Inhibitor %, Biocide A %, Biocide B %, Alarm %
Data retention 100 years Battery backup 1 year (approx) Enclosure rating IP55 Operating Temperature 0 - 50°C
Page 43
Page 43 of 43
8. Service & Technical Support
Important: Please note the serial number and product/system
part number before calling for assistance.
Note:
1. Controllers incorporated in a system, have the same serial numbers as the system itself.
2. The First 6 digits of serial is the date of manufacture (yymmdd)
Company Pty Ltd
Street, Suburb, State Postcode Tel: ( ) Fax: ( ) E-mail
Part No: DIGICHEM-Plus+ Description: Cooling Tower Controller Serial No: 0804070613
220-240 VAC 50/60Hz 10W IP65
warranty void if l a b e l removed
N1665
Company details
Part number & description of controller
Controller unique
Serial Number
Supply voltage & fre
q
uency
Device power consumption
Enclosure rating
C-tick logo & registration number
Example of Controller Info Label
(Adhered to Controller Enclosure)
Loading...