IEC Contactors & Starters
XT IEC Power Control
February 2007
Contents
Description Page
Overload Relays — XTOB, XTOT
Catalog Number
Selection . . . . . . . . . . . . . . . . 34-95
Product Selection . . . . . . . . . . 34-96
Accessories . . . . . . . . . . . . . . . 34-97
Technical Data and
Specifications . . . . . . . . . . . . 34-99
Dimensions . . . . . . . . . . . . . . . 34-101
Reference Data . . . . . . . . . . . . 34-200
Catalog Number Selection
Table 34-124. XT IEC Overload Relays — Catalog Numbering System
Overload Relays — XTOB, XTOT
XTOB Overload Relay XTOT Overload Relay
X T O B P 1 6 B C 1 S
34-95
34
Designation
XT = XT Line of IEC Control
Type
OB =
Bimetallic Overload Relay
OT =
Current Transformer Overload Relay
Frame B
0.1 – 0.16A
P16 =
0.16 – 0.24A
P24 =
0.24 – 0.4A
P40 =
0.4 – 0.6A
P60 =
0.6 – 1A
001 =
1.0 – 1.6A
1P6 =
1.6 – 2.4A
2P4 =
2.4 – 4A
004 =
4 – 6A
006 =
6 – 10A
010 =
9 – 12A
012 =
12 – 16A
016 =
Frame C
0.1 – 0.16A
P16 =
0.16 – 0.24A
P24 =
0.24 – 0.4A
P40 =
0.4 – 0.6A
P60 =
0.6 – 1A
001 =
1.0 – 1.6A
1P6 =
1.6 – 2.4A
2P4 =
2.4 – 4A
004 =
4 – 6A
006 =
6 – 10A
010 =
10 – 16A
016 =
16 – 24A
024 =
24 – 32A
032 =
Frame D
6 – 10A
010 =
10 – 16A
016 =
16 – 24A
024 =
24 – 40A
040 =
40 – 57A
057 =
50 – 65A
065 =
Frame F
035 =
25 – 35A
050 =
35 – 50A
070 =
50 – 70A
100 =
70 – 100A
Overload Release
Frame G
035 =
050 =
070 =
100 =
125 =
150 =
Frame L
070 =
100 =
125 =
160 =
220 =
250 =
Frame M
063 =
090 =
125 =
160 =
240 =
290 =
400 =
540 =
Frame N
063 =
090 =
125 =
160 =
240 =
290 =
400 =
540 =
630 =
25 – 35A
35 – 50A
50 – 70A
70 – 100A
95 – 125A
120 – 150A
50 – 70A
70 – 100A
95 – 125A
120 – 160A
160 – 220A
200 – 250A
42 – 63A
60 – 90A
85 – 125A
110 – 160A
160 – 240A
190 – 290A
270 – 400A
360 – 540A
42 – 63A
60 – 90A
85 – 125A
110 – 160A
160 – 240A
190 – 290A
270 – 400A
360 – 540A
420 – 630A
Mounting
BLANK = Direct to Contactor
S = Separate Mount
Trip Class
C1 = Class 10A
C3 = Class 30
Frame Size
Designation
B = 45 mm
C = 45 mm
D = 55 mm
G = 90 mm
L = 140 mm
BLANK = XTOT Only
CA08102001E For more information visit: www.eaton.com
34-96
34
IEC Contactors & Starters
XT IEC Power Control
Overload Relays — XTOB, XTOT
Product Selection
Table 34-125. Overload Relay
Overload
Releases, I
r
Contact
Sequence
Contact
Configuration
For Use
with
Contactor
Amp Range
Frame B — Direct Mount
0.1 – 0.16
0.16 – 0.24
0.24 – 0.4
0.4 – 0.6
0.6 – 1
1 – 1.6
1.6 – 2.4
2.4 – 4
4 – 6
6 – 10
9 – 12
12 – 16
97 95
2 4 6 98 96A2 14
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
22
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
7 – 15A
7 – 15A
7 – 15A
7 – 15A
7 – 15A
7 – 15A
7 – 15A
7 – 15A
7 – 15A
7 – 15A
9 – 15A
12 – 15A
Frame C — Direct Mount
0.1 – 0.16
0.16 – 0.24
0.24 – 0.4
0.4 – 0.6
0.6 – 1
1 – 1.6
1.6 – 2.4
2.4 – 4
4 – 6
6 – 10
10 – 16
16 – 24
24 – 32
97 95
2 4 6 989614/
22
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
18 – 32A
18 – 32A
18 – 32A
18 – 32A
18 – 32A
18 – 32A
18 – 32A
18 – 32A
18 – 32A
18 – 32A
18 – 32A
18 – 32A
25 – 32A
Frame D — Direct Mount
6 – 10
10 – 16
16 – 24
24 – 40
40 – 57
50 – 65
2 4 6 98 96
97 95
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
40 – 65A
40 – 65A
40 – 65A
40 – 65A
50 – 65A
65A
Frame F – G — Direct Mount
25 – 35
35 – 50
50 – 70
70 – 100
95 – 125
120 – 150
2 4 6 98 96
97 95
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
80 – 150A
80 – 150A
80 – 150A
80 – 150A
80 – 150A
80 – 150A
Frame F – G — Separate Mount
25 – 35
35 – 50
50 – 70
70 – 100
95 – 125
120 – 150
2 4 6 98 96
97 95
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
80 – 150A
80 – 150A
80 – 150A
80 – 150A
80 – 150A
80 – 150A
Frame L
50 – 70
70 – 100
95 – 125
120 – 160
160 – 220
200 – 250
For separate mounting, short circuit Type 1 rating is 500A and short circuit Type 2 rating is 400A.
1359795
2469896
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
185 – 250A
185 – 250A
185 – 250A
185 – 250A
185 – 250A
225 – 250A
Notes:
Short circuit protection: Observe the maximum permissible fuse of the contactor with
direct device mounting. See MN03402001E
for more information on overload relays for
Frame B – G.
Suitable for protection of EEx e-motors. EC
prototype test certificate available upon
request.
Observe manuals MN03402001E and
MN03407001E, see Table 34-129.
Trip Class: 10A
Short-Circuit Protection (A) Catalog
Fuse Maximum
Type 1
Coordination,
gG/gL
25
25
25
25
25
25
25
25
25
50
50
50
25
25
25
25
25
25
25
25
25
50
63
100
125
50
63
63
125
160
160
125
160
250
315
315
315
125
160
250
315
315
315
250
315
315
400
400
400
Type 2
Coordination,
gG/gL
0.5
1
2
4
4
6
10
16
20
25
25
25
0.5
1
2
4
4
6
10
16
20
25
35
35
63
25
35
50
63
80
100
100
125
160
200
250
250
100
125
160
200
250
250
160
200
250
250
315
315
February 2007
Circuit
Breaker
25
25
25
25
25
25
25
25
25
25
25
30
25
25
25
25
25
25
25
25
25
25
30
30
30
25
25
30
125
150
150
125
150
150
400
500
600
125
150
150
400
500
600
150
400
500
600
800
600
CEC/NEC
Fuse
3
3
3
3
3
6
6
15
20
35
45
45
3
3
3
3
3
6
6
15
20
25
25
25
25
25
25
25
125
150
200
125
200
200
400
400
600
125
200
200
400
400
600
200
400
400
600
800
700
Number
XTOBP16BC1
XTOBP24BC1
XTOBP40BC1
XTOBP60BC1
XTOB001BC1
XTOB1P6BC1
XTOB2P4BC1
XTOB004BC1
XTOB006BC1
XTOB010BC1
XTOB012BC1
XTOB016BC1
XTOBP16CC1
XTOBP24CC1
XTOBP40CC1
XTOBP60CC1
XTOB001CC1
XTOB1P6CC1
XTOB2P4CC1
XTOB004CC1
XTOB006CC1
XTOB010CC1
XTOB016CC1
XTOB024CC1
XTOB032CC1
XTOB010DC1
XTOB016DC1
XTOB024DC1
XTOB040DC1
XTOB057DC1
XTOB065DC1
XTOB035GC1
XTOB050GC1
XTOB070GC1
XTOB100GC1
XTOB125GC1
XTOB150GC1
XTOB035GC1S
XTOB050GC1S
XTOB070GC1S
XTOB100GC1S
XTOB125GC1S
XTOB150GC1S
XTOB070LC1
XTOB100LC1
XTOB125LC1
XTOB160LC1
XTOB220LC1
XTOB250LC1
Price
U.S. $
Technical Data . . . . . . . . . . . . . . . . . . Page 34-99
Dimensions . . . . . . . . . . . . . . . . . . . . . Page 34-101
Discount Symbol . . . . . . . . . . . . . . . . . 1CD7
For more information visit: www.eaton.com CA08102001E
February 2007
IEC Contactors & Starters
XT IEC Power Control
Overload Relays — XTOB, XTOT
34-97
Table 34-126. Current Transformer Operated Overload Relays
Overload
Releases, I
r
Contact
Sequence
Contact
Configuration
For Use
with
Contactor
Amp Range
Short-Circuit Protection (A) Catalog
Type 1
Coordination,
gG/gL
Frame M – N — Separate Mount
42 – 63
60 – 90
85 – 125
110 – 160
160 – 240
190 – 290
270 – 400
360 – 540
The main current parameters are defined by the main current wiring which is used.
420 – 630
9597
9698
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO-1NC
1NO1-NC
1NO-1NC
1NO-1NC
300 – 500A
300 – 500A
300 – 500A
300 – 500A
300 – 500A
300 – 500A
300 – 500A
500A
630A
—
—
—
—
—
—
—
—
—
Accessories
Table 34-127. DIN Rail or Panel Mount Adapter, Frame C – D
For Use
with…
XTOB…CC1 5 XTOBXDINC
XTOB…DC1 1 XTOBXDIND
Can be snap fitted on a top hat rail (DIN rail) to IEC/EN 60715 or can be screw fitted.
Pkg.
Qty.
Table 34-128. Terminal Shroud
For Use
with…
XTOB…LC1 XTOBXTSL
Catalog
Number
Catalog
Number
Price
U.S. $
Price
U.S. $
Type 2
Coordination,
gG/gL
—
—
—
—
—
—
—
—
—
Circuit
Breaker
150
250
500
600
600
600
1000
600
600
CEC/NEC
Fuse
200
250
400
600
700
700
1000
1000
1000
Number
XTOT063C3S
XTOT090C3S
XTOT125C3S
XTOT160C3S
XTOT240C3S
XTOT290C3S
XTOT400C3S
XTOT540C3S
XTOT630C3S
Price
U.S. $
34
For direct mounting of … Catalog
XTOB…LC1 to XTCE185L,
XTCE225L or XTCE250L
Number
XTOBXTSCL
Price
U.S. $
Table 34-129. Documentation — Manuals for
Overload Monitoring of EEX e-motors
Publication
Number
MN03402001E XTOB…BC1
MN03407001E XTOB…DC1
For Use
with…
XTOB…CC1
XTOB…GC1
CA08102001E For more information visit: www.eaton.com
Dimensions . . . . . . . . . . . . . . . . . . . . . Page 34-101
Discount Symbol . . . . . . . . . . . . . . . . 1CD7