UL 1077 DIN Rail Supplementary Protectors
WMZS Circuit Breakers
Product Overview
UL 1077 DIN Rail Supplementary Protectors
WMZS Circuit Breakers
PRODUCT OVERVIEW
Standard Features
WMZS breaker terminals provide finger and back-of-hand
protection to guard against accidental contact with live parts.
A color-coded red/green indicator provides immediate visual
indication of device status (green for OFF, red for ON) and
isolation function.
Product Overview
Eaton’s WMZS line of miniature circuit breakers includes a broad
range of devices defined as “supplementary protectors.” These
breakers comply with ULT 1077 and CSAT 22.2 No. 235 regulations defining supplementary overcurrent protection. In these
applications, branch circuit protection is not required, or is provided by a separate device like a fuse or molded case circuit breaker.
WMZS Supplementary Protectors are typically used for control
circuits, lighting, business equipment, appliances and a range of
other applications where “closer” protection is desired than that
offered by a branch circuit protection device.
All WMZS breakers also incorporate a “trip-free” mechanism.
This prevents the trip function from being defeated by holding
the operator in the ON position.
Worldwide Acceptance
WMZS Supplementary Protectors are UL Recognized for use
in the United States in accordance with NFPAT 70 (NECT). The
devices comply with UL 1077 and CSA 22.2 No. 235, meeting
the requirements for supplementary protectors. These devices
also comply with IEC 60947-2 and are CE marked.
Extensive Product Range
Eaton’s Supplementary Protectors are available in 1-, 2- and 3-pole
configurations and 20 different current ratings from 0.5A to 63A.
Three different trip characteristics, including B, C and D curves,
give you the ability to configure the exact protection scheme you
require. Devices can be used in applications up to 480 Vac and
48 Vdc with short-circuit ratings up to 10 kA.
Ease of Installation
All breakers mount on a standard 35 mm DIN rail. Each device
has box terminals that accept multiple conductors. Bus connectors and feeder terminals facilitate mounting and wiring of multiple
miniature circuit breaker arrays in control panel assemblies. Power
to the circuit breakers can also be fed from the line or load side.
2
EATON CORPORATION UL 1077 DIN Rail Supplementary Protectors

UL 1077 DIN Rail Supplementary Protectors
Discover These Advanced Features Three Tripping Curves to Choose
Eaton WMZS Supplementary Protectors are available with three
different tripping characteristics, including Type B, C and D.
Definitions for each trip curve are contained on the ordering pages
and can be used to determine the optimal characteristic for your
application. For example, low level short-circuit faults in control wiring, such as PLCs, are best protected by devices with Type B trip
characteristics (3 to 5X continuous rating of the device (I
Even though not required by NEC or CEC for Supplementary
Protectors, Eaton’s WMZS devices are current limiting, which
means they interrupt fault currents within one half cycle. Current
limiting devices offer superior protection by reducing peak letthrough current and energy.
7200
3600
1200
600
300
120
t [sec]
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.0005
2
1
60
30
10
5
2
1
1
Time-current characteristic acc. to UL 1077
a
conventional
non-tripping current
= 1.13 IN: t > 1 h
I
nt
b
conventional tripping
current
= 1.45 IN: t < 1 h
I
t
3
3
4
5
6
B
Breakers install on
standard DIN rail
Available in 1-, 2- and
3-pole models
Color-coded indicator
provides breaker status
for easy troubleshooting
Captive posidrive terminal
screws with finger and
back-of-hand protection
(IP20)
Trip-free design; breaker
cannot be defeated by
holding the handle in the
ON position
Breaker information
printed on the front of
the device for quick
identification
WMZS Circuit Breakers
PRODUCT OVERVIEW
).
n
c
C
I / I
2.55 IN:
t = 1 – 60 s (I
t = 1 – 120 s (I
d
Type B: 3 IN: t > 0.1 s
e
Type B: 5 IN: t < 0.1 s
f
Type C: 5 IN: t > 0.1 s
g
Type C: 10 IN: t < 0.1 s
h
Type D: 10 IN: t > 0.1 s
i
Type D: 20 IN: t < 0.1 s
7
8
D
1098765432
N
< 32A)
N
< 32A)
N
9
5040302015
Product Overview
Catalog Numbering System
Breaker Family
WMZS = Supplementary Protector
1 = 1-Pole
2 = 2-Pole
3 = 3-Pole
Number of Poles
WMZS 1 B 10
Protective Curve
B = B Curve (3–5X In)
C = C Curve (5–10X In)
D = D Curve (10–20X In)
Ampere Rating
00 = 0.5 Amps
01 = 1 Amps
02 = 2 Amps
03 = 3 Amps
04 = 4 Amps
05 = 5 Amps
06 = 6 Amps
EATON CORPORATION UL 1077 DIN Rail Supplementary Protectors
07 = 7 Amps
08 = 8 Amps
10 = 10 Amps
13 = 13 Amps
15 = 15 Amps
16 = 16 Amps
20 = 20 Amps
25 = 25 Amps
30 = 30 Amps
32 = 32 Amps
40 = 40 Amps
50 = 50 Amps
63 = 63 Amps
3