Cutler Hammer, Div of Eaton Corp WMZS Catalog Page

UL 1077 DIN Rail Supplementary Protectors
WMZS Circuit Breakers
PRODUCT SELECTION
WMZS Product Selection — C Curve (5 – 10X I
Designed for inductive loads
Response time of instantaneous trip: 5 – 10X I
UL Recognized and CSA Certified as Supplementary Protectors
For international and domestic use (conform to IEC 60947-2)
n
current rating
n
Suitable for applications where medium levels of inrush current are expected. Instantaneous trip is 5 – 10X rating of device (I Applications include small transformers, lighting, pilot devices,
).
n
control circuits, and coils. Medium magnetic trip point.
C Curve (5 – 10X I Designed for Inductive Loads
1-Pole 2-Pole 3-Pole
Amperes
0.5 1 2
3 4 5
6 7 8
10 13 15
16 20 25
30 32 40
50 63
a
In North America, these switches are UL recognized and CSA certified as Supplementary Protection devices. Per the intent of NEC (National Electrical Code), Article 240, and CEC (Canadian Electrical Code), Part 1 C22.1, supplementary breakers cannot be used as a substitute for the branch circuit protective device. They can be used to provide overcurrent protection within an appliance or other electrical equipment where branch circuit overcurrent protection is already provided, or is not required.
Catalog Number Catalog Number Catalog Number
WMZS1C00 WMZS1C01 WMZS1C02
WMZS1C03 WMZS1C04 WMZS1C05
WMZS1C06 WMZS1C07 WMZS1C08
WMZS1C10 WMZS1C13 WMZS1C15
WMZS1C16 WMZS1C20 WMZS1C25
WMZS1C30 WMZS1C32 WMZS1C40
WMZS1C50 WMZS1C63
Current Rating) —
n
a
WMZS2C00 WMZS2C01 WMZS2C02
WMZS2C03 WMZS2C04 WMZS2C05
WMZS2C06 WMZS2C07 WMZS2C08
WMZS2C10 WMZS2C13 WMZS2C15
WMZS2C16 WMZS2C20 WMZS2C25
WMZS2C30 WMZS2C32 WMZS2C40
WMZS2C50 WMZS2C63
WMZS3C00 WMZS3C01 WMZS3C02
WMZS3C03 WMZS3C04 WMZS3C05
WMZS3C06 WMZS3C07 WMZS3C08
WMZS3C10 WMZS3C13 WMZS3C15
WMZS3C16 WMZS3C20 WMZS3C25
WMZS3C30 WMZS3C32 WMZS3C40
WMZS3C50 WMZS3C63
7200
3600
1200
600
300
120
t [sec]
0.5
0.2
0.1
0.05
0.02
0.01
0.005
0.002
0.001
0.0005
1.13
1.45
Specified non-tripping current
= 1.13 x IN for t > 1 h
I
NT
Specified tripping current
= 1.45 x IN for t < 1 h
I
T
60
30
10
5
2
1
1
1
1
2
3
4
B
C
I / I
a
2.55 IN: t = 1 – 60 s (I t = 1 – 120 s (I
b
Type B: 3 x IN: t > 0.1 s
c
Type B: 5 x IN: t < 0.1 s
d
Type C: 5 x IN: t > 0.1 s
e
Type C: 10 x IN: t < 0.1 s
f
Type D: 10 x IN: t > 0.1 s
g
Type D: 20 x IN: t < 0.1 s
5
6
D
1098765432
N
< 32A)
N
> 32A)
N
7
5040302015
Product Selection
For our complete product offering, see the Distribution Products Catalog (CA08101001E).
eaton corporation UL 1077 DIN Rail Supplementary Protectors