Cutler Hammer, Div of Eaton Corp WMZS Technical Specifications

UL 1077 DIN Rail Supplementary Protectors
WMZS Circuit Breakers
Technical Data
Description B Curve C Curve D Curve
Electrical
Standards IEC/EN 60947-2
Short-Circuit Trip Response 3 x 5 I
n
Supplementary Protectors — UL / CSA
Current Range 6 – 63A 0.5 – 63A 0.5 – 40A
Maximum Voltage Ratings — UL / CSA 1-Pole
2-, 3-Pole 2 Poles in Series
277 Vac 48 Vdc 480Y/277 Vac 125 Vdc
Thermal Tripping Characteristics Single-Pole Multi-Pole
1.35 x I
@ 40°C
n
1.45 x In @ 40°C
Short-Circuit Ratings (at Max. Voltage) 1-Pole 2-, 3-Pole 1-Pole 2 Poles in Series
10 kA (5 kA for 40–63A Device) 10 kA (5 kA for 40–63A Device) 10 kA @ 48 Vdc 10 kA @ 125 Vdc
Miniature Circuit Breaker — IEC
Current Range 6 – 63A 0.5 – 63A 0.5 – 40A
Maximum Voltage Ratings — IEC 60947-2 1-Pole
2-, 3-Pole
230 Vac 48 Vdc 230/400 Vac
Maximum Voltage Ratings — IEC 60898 1-Pole
2-, 3-Pole
240 Vac 48 Vdc 240/415 Vac
Thermal Tripping Characteristics Single-Pole Multi-pole
> 1 Hour @ 1.05 x I < 1 Hour @ 1.3 x I
n
n
Interrupt Ratings (at Max. Voltage) IEC 60947-2 IEC 60898 Operational Switching Capacity Max. Back-Up Fuse [gL/gG] Rated Impulse Withstand—U Rated Insulation Voltage—U
i
imp
15 kA 10 kA
7.5 kA 125A 4000 Vac 440 Vac
Environmental / General
Selectivity Class Lifespan (Operations) Shock (IEC 68-2-22) Operating Temperature Range Shipment & Short-Term Storage Housing Material
3 > 10000 (1 operation = ON/OFF) 10g–120 ms +23 – +104°F (-5 – +40°C)
-40 – +185°F (-40 – +85°C) Nylon
Mechanical
Standard Front Dimension Device Height Terminal Protection Mounting Width per Pole
Mounting Degree of Protection Terminals Top and Bottom Supply Connection
Terminal Capacity [mm
2
Torque Imperial Torque
]
80 mm Finger and Back-of-Hand Proof to IEC 536
17.7 mm
IEC/EN 60715 Top-Hat Rail IP20 Twin-Purpose Terminals Line or Load Side
1 x 25 (AWG 4 – 18) / 2 x 10 (AWG 8 – 18)
2.4 Nm 21 lb-in (AWG 18 – 12), 25 lb-in
(AWG 10 – 8), 36 lb-in (AWG 6 – 4) Thickness of Bus Bar Material Mounting Position
0.8 – 2 mm
As Required
5 x 10 I
n
277 Vac 48 Vdc 480Y/277 Vac 125 Vdc
1.35 x In @ 40°C
1.45 x In @ 40°C
10 kA (5 kA for 40–63A Device) 10 kA (5 kA for 40–63A Device) 10 kA @ 48 Vdc 10 kA @ 125 Vdc
230 Vac 48 Vdc 230/400 Vac
240 Vac 48 Vdc 240/415 Vac
> 1 Hour @ 1.05 x I < 1 Hour @ 1.3 x I
n
n
15 kA 10 kA
7.5 kA 125A 4000 Vac 440 Vac
3 > 10000 (1 operation = ON/OFF) 10g–120 ms +23 – +104°F (-5 – +40°C)
-40 – +185°F (-40 – +85°C) Nylon
80 mm Finger and Back-of-Hand Proof to IEC 536
17.7 mm
IEC/EN 60715 Top-Hat Rail IP20 Twin-Purpose Terminals Line or Load Side
1 x 25 (AWG 4 – 18) / 2 x 10 (AWG 8 – 18)
2.4 Nm 21 lb-in (AWG 18 – 12), 25 lb-in (AWG 10 – 8), 36 lb-in (AWG 6 – 4)
0.8 – 2 mm As Required
10 x 20 I
277 Vac 48 Vdc 480Y/277 Vac 125 Vdc
1.35 x In @ 40°C
1.45 x In @ 40°C
5 kA 5 kA 10 kA @ 48 Vdc 10 kA @ 125 Vdc
230 Vac 48 Vdc 230/400 Vac
240 Vac 48 Vdc 240/415 Vac
> 1 Hour @ 1.05 x I < 1 Hour @ 1.3 x I
15 kA 10 kA
7.5 kA 125A 4000 Vac 440 Vac
3 > 10000 (1 operation = ON/OFF) 10g–120 ms +23 – +104°F (-5 – +40°C)
-40 – +185°F (-40 – +85°C) Nylon
80 mm Finger and Back-of-Hand Proof to IEC 536
17.7 mm
IEC/EN 60715 Top-Hat Rail IP20 Twin-Purpose Terminals Line or Load Side
1 x 25 (AWG 4 – 18) / 2 x 10 (AWG 8 – 18)
2.4 Nm 21 lb-in (AWG 18 – 12), 25 lb-in (AWG 10 – 8), 36 lb-in (AWG 6 – 4)
0.8 – 2 mm As Required
TECHNICAL DATA
n
n
n
Technical Data
eaton corporation UL 1077 DIN Rail Supplementary Protectors
11
UL 1077 DIN Rail Supplementary Protectors
WMZS Circuit Breakers
TECHNICAL DATA
Technical Data
Description
Electrical
Contact Function
Rated Operational Voltage U
n
Voltage Range WMZSST110 12 – 110 Vac
Voltage Range WMZSST415 110 – 415 Vac
Closing Threshold [x U
Tripping Threshold [x U
] 0.8
n
] 0.5
n
Rated Frequency ƒ 50/60 Hz 50/60 Hz 50/60 Hz
General Use (UL / CSA) AC—230/240 Vac DC—110/120 Vdc
Pilot Duty A600 / Q600
Conventional Free Air Thermal Current I
th
Rated Operational current AC-13 I AC-15 I DC-13 I
Rated Insulation Voltage U
Minimum Operating Voltage per Contract U
Rated Impulse Withstand Voltage (1.2/50μ) U
e
e
e
i
min
imp
Rated Conditional Short-Circuit Current with 6A Back-Up Fuse I
Max. Admissible Back-Up Fuse 4A gL
Mechanical
Standard Front Dimension 45 mm 45 mm 45 mm
Technical Data
Device Height 80 mm 80 mm 80 mm
Mounting Width 8.8 mm 17.6 mm 17.8 mm
Mounting On MCB IEC/EN 60715 Top-Hat Rail IEC/EN 60715 Top-Hat Rail
Degree of Protection Enclosed IP40 IP40 IP40
Terminal Protection Protection Against
Terminals Lift Terminals Twin-Purpose Terminals Twin-Purpose Terminals
Terminal Capacity Solid Flexible
Tightening Torque of Terminal Screws 0.8 – 1.0 Nm (7 – 9 lb-in) 2.4 Nm (21 lb-in) 0.8 Nm (7 lb-in)
WMZSAUX WMZSAUXTRIP WMZSST WMZSUVR
1A + 1B 2 C/O
— —
— —
250 Vac 115 Vac — WMZSUVR115
230 Vac — WMZSUVR230 400 Vac — WMZSUVR400
12 – 60 Vdc
110 – 230 Vdc
2 / 2A
0.5 / 0.5A
— —
— —
4A
3A (250 Vac) 2A (250 Vac)
0.5A (110 Vdc)
— — —
— — —
250 Vac
5 Vdc
2.5 kV
1 kA
SC
Electric Shock to IEC 536
0.5 – 2.5 mm
0.5 – 2.5 mm
2
2
Protection Against Electric Shock to IEC 536
1 – 2.5 mm 1 – 2.5 mm
2
2
Protection Against Electric Shock to IEC 536
2 x (1 – 2.5) mm 2 x (1 – 2.5) mm
2
2
12
eaton corporation UL 1077 DIN Rail Supplementary Protectors